R-P693_Drawings_Final_Vol14.5_20241007.pdf
PDF 21 MB Posted
- Solicitation number
- N6274225R1301
About this file
This file appears to be a comprehensive set of drawings (Volume 14.5) for solicitation N6274225R1301, which is for the construction of a Guam Defense Radar System Command Center and associated facilities at Joint Region Marianas, Guam.
The project, valued between $250-500 million, requires construction of a command center, power generation facility, switchgear building, fuel storage facility, and entry control facility. Key technical requirements include Risk Category IV seismic design with base isolation, 150-foot galvanized steel antenna tower, SSL-C security infrastructure, and complex control system integration. The contract includes five pre-priced options related to generators, fuel tanks, and uninterruptible power supply systems. The project has a 1,323-calendar-day completion period, with the RFP release scheduled for October 30, 2024. A pre-proposal site visit is scheduled for December 11, 2024, with base access request forms due by November 14, 2024. This unrestricted solicitation uses a best-value trade-off approach, with technical factors and past performance equally weighted and combined to be approximately equal to price.
View the file
Other files
Show 40 more
Latest 50 of 63 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
07-OCT-2024
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
10/17/2024
07-OCT-2024
Approved By
CAPT Troy Brown, JRM J4 via email
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
SEE SHEET 14ST-TS105
FOR CONTINUATION
SEE SHEET 14ST-TS105
FOR CONTINUATION
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
01. 4 x 4" SCHEDULE 80 PVC CONDUIT GOING TO COMMUNICATION MAINTENANCE HOLE
TMH-14ST5003.
02. 2 x 4" SCHEDULE 80 PVC CONDUIT GOING TO COMMUNICATION HAND HOLE TMH-14ST5301.
14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
SEE SHEET 14ST-TS108
FOR CONTINUATION
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
01. 4 x 4" SCHEDULE 80 PVC CONDUIT GOING TO COMMUNICATION MAINTENANCE HOLE
TMH-14ST5102.
02. 6 x 4" SCHEDULE 80 PVC GOING TO ANTENNA TOWER. SEE ROUTING DETAIL A1 ON SHEET
14CC-TX202.
03. 4 x 4" SCHEDULE 80 PVC CONDUIT GOING TO COMMUNICATION MAINTENANCE HOLE
TMH-14ST5003.
04. 2 x 4" SCHEDULE 80 PVC CONDUIT GOING TO COMMUNICATION HAND HOLE TMH-14ST5301.
14GI-T-001
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
14CC-T-401
A1
14CC-T-401
C1
J J
J J J J J J J J
TYP
TYP
14CC-T-407
A1
14CC-T-406
A1
J J
J J
J J J J J J J J J
TYP
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.
C. PENETRATIONS INTO (ROOMS 158, 130, AND 135) MUST BE FIRE RATED.
D. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE
ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50.
E. WALL MOUNT OUTLETS IN ROOMS 150 - 158 MUST BE SURFACE MOUNTED; NO IN-WALL
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
F. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
SPECIFICATIONS.
G. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.
01. 4" D x 12" W BELOW FLOOR BASKET TRAY LATERAL WITH DIVIDER CREATING 8" AND 4" WIDE
SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.
02. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE
SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.
03. ENSURE RAF TILES ARE ALIGNED BETWEEN ROOMS SO UNDER FLOOR SUPPORTS ALLOW
EFFICIENT ROUTING OF CABLE.
04. FIELD ROUTE BELOW FLOOR J-HOOK OR OTHER NON-CONTINUOUS SUPPORT FROM BASKET
TRAY TO OUTLETS; MAX SUPPORT SEPARATION OF 5'.
05. 2"D x 6"W BELOW FLOOR BASKET TRAY FOR BACKBONE AND MISC. FIBER.
06. 2"D x 6"W BELOW FLOOR BASKET TRAY FOR RED COPPER CABLE.
14GI-T-001
14CC-T-40114CC-T-4011114 111 14CC-T-40114CC-T-4011114 111
14CC-T-40714CC-T-4071114 7777
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
14CC-T-40614CC-T-4061114 6666
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
14CC-T-403
TYP
J J
J JJ
J J
J JJJ
TYP.
14CC-T-407
A1
J J
J
J J
14CC-TX204
A3
14CC-TX512
A1
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.
C. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE
RATED.
D. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE
ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50.
E. WALL MOUNT OUTLETS IN ROOMS 150 - 158 MUST BE SURFACE MOUNTED; NO IN-WALL
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
F. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
SPECIFICATIONS.
G. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.
01. 4"D x 18" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATEING 3 x 6" WIDE SECTIONS.
FOR UNCLASSIFIED, CLASSIFIED, AND AV CABLES RESPECTIVELY.
02. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE
SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.
03. ENSURE RAF TILES ARE ALIGNED BETWEEN ROOMS SO UNDER FLOOR SUPPORTS ALLOW
EFFICIENT ROUTING OF CABLE.
04. 2" D X 6" W BELOW FLOOR BASKET TRAY FOR BACKBONE AND MISC. FIBER.
05. FIELD ROUTE BELOW FLOOR J-HOOK OR OTHER NON-CONTINUOUS SUPPORT FROM BASKET
TRAY TO OUTLETS; MAX SUPPORT SEPARATION OF 5'.
06. 4" D x 18" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 3 X 6" WIDE SECTIONS
FOR AV AND CLASSIFIED VOICE.
07. 4" D X 12" W BELOW FLOOR BASKET TRAY.
08. 2" D X 12" W VERTICAL LADDER TRAY.
09. 2" D X 12" W OVERHEAD HORIZONTAL LADDER TRAY.
10. MMF DROPS AT THESE TWO LOCATIONS WILL HOME BACK TO THE BLACK CABINET (AA1) IN
ROOM 135.
11. MMF DROPS AT THESE TWO LOCATIONS WILL HOME BACK TO THE BLACK CABINET (A1) IN
ROOM 124.
14GI-T-001
14CC-T-40714CC-T-4071114 7777
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
14CC-TX51214CC-TX512414 22214
14CC-T-40314CC-T-4031114 3333
14CC-TX20414CC-TX2044 044414
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
14CC-T-401
A3
14CC-T-401
C3
14CC-T-406
A1
14CC-T-407
A1
XFMR-14CC61101AXFMR-14CC61101B
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.
C. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE
RATED.
D. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE
ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50.
E. WALL MOUNT OUTLETS IN ROOMS 150 - 158 MUST BE SURFACE MOUNTED; NO IN-WALL
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON
14CC-T-505.
F. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
SPECIFICATIONS.
G. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.
01. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE
SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY
02. 4" D x 18" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 3 X 6" WIDE SECTIONS
FOR AV AND CLASSIFIED VOICE.
03. ENSURE RAF TILES ARE ALIGNED BETWEEN ROOMS SO UNDER FLOOR SUPPORTS ALLOW
EFFICIENT ROUTING OF CABLE
04. 2" D X 6" W BELOW FLOOR BASKET TRAY FOR BACKBONE AND MISC. FIBER.
05. 4" D X 12" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 2 X 6" WIDE SECTIONS
FOR CLASSIFIED VOICE CABLE.
06. 6" D X 20" W BELOW FLOOR BASKET TRAY WITH DIVIDERS CREATING ONE 12" AND 2 X 4" W
SECTIONS FOR UNCLASSIFIED, CLASSIFIED, AND AV CABLES RESPECTIVELY.
07. FIELD ROUTE 1 1/4" CONDUIT IN SLAB TO EQUIPMENT SHOWN (XFMR-14CC61101A TPR-A AND
XFMR-14CC61101B TPR-B) TO STUB OUT UNDERNEATH RAF WHERE FIBER CAN BE PULLED TO
BASKET TRAY NOTED ON KEYNOTE 4.
14GI-T-001
1114CC-T-40114CC-T-4011114 111 14CC-T-40114CC-T-4011114 111
14CC-T-40714CC-T-4071114 7777
14CC-T-505
14CC-T-40614CC-T-4061114 6666
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
14CC-T-405
TYP
14CC-T-404
A1
14CC-T-402
A1
14CC-T-403
A1
14CC-T-407
A1
J J JJ
J
J
J
J J
J J
J
J J
J
J J
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.
C. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158,130, AND 135) MUST BE FIRE
RATED.
D. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE
ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50.
E. WALL MOUNT OUTLETS IN ROOMS 150 - 158 MUST BE SURFACE MOUNTED; NO IN-WALL
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
F. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
SPECIFICATIONS.
G. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.
01. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 16" AND 4" WIDE
SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.
02. 4" D x 18" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 3 X 6" WIDE SECTIONS
FOR AV AND CLASSIFIED VOICE CABLE.
03. ENSURE RAF TILES ARE ALIGNED BETWEEN ROOMS SO UNDER FLOOR SUPPORTS ALLOW
EFFICIENT ROUTING OF CABLE.
04. 4" D x 12" W BELOW FLOOR BASKET TRAY.
05. 2" D X 6" W BELOW FLOOR BASKET TRAY FOR BACKBONE AND MISC. FIBER.
06. 6" D X 20" W BELOW FLOOR BASKET TRAY WITH DIVIDERS CREATING ONE 12" AND 2 X 4" W
SECTIONS FOR UNCLASSIFIED, CLASSIFIED, AND AV CABLES RESPECTIVELY.
07. FOR UNCLASSIFIED, CLASSIFIED, AND AV CABLES RESPECTIVELY. FOR UNCLASSIFIED,
CLASSIFIED, AND AV CABLES RESPECTIVELY.
08. 4" D X 12" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 2 X 6" WIDE SECTIONS
FOR CLASSIFIED VOICE CABLE.
09. FIELD ROUTE BELOW FLOOR J-HOOK OR OTHER NON-CONTINUOUS SUPPORT FROM BASKET
TRAY TO OUTLETS; MAX SUPPORT SEPARATION OF 5'.
14GI-T-001
14CC-T-40214CC-T-4021114 2222
14CC-T-40414CC-T-4041114 4444
14CC-T-40514CC-T-4051114 5555
14CC-T-40714CC-T-4071114 7777
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
14CC-T-40314CC-T-4031114 3333
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
01. 3/4" AC RATED FIRE-RATED BACKBOARD PAINTED ON ALL SIDES WITH RETARDANT PAINT, FIRE-
RATING LABELS WILL BE LEFT UNPAINTED. COLOR TO MATCH THE WALL.
02. 12" VERTICAL ALUMINUM LADDER TRAY.
03. 20" W ALUMINUM LADDER TRAY.
04. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE
SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.
05. 2" D x 6" W BELOW FLOOR BASKET TRAY.
06. SECONDARY BONDING BUSBAR, MOUNTED 7' 6" AFF.
07. TELECOMMUNICATIONS CABINET, SEE SHEET 14CC-T-401 FOR ADDITIONAL DETAIL.
08. 12" W ALUMINUM LADDER TRAY.
09. IESS VERTICAL RACK (SECURITY). SEE DETAIL C3 ON SHEET 14CC-TY502.
14GI-T-001
14CC-T-401
14CC-TY502
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
RATING LABELS WILL BE LEFT UNPAINTED. COLOR TO MATCH THE WALL.
02. 12" VERTICAL ALUMINUM LADDER TRAY.
03. 12" W ALUMINUM LADDER TRAY
04. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH 3 DIVIDERS CREATING 8" AND 3 x 4" WIDE
SECTIONS FOR UNCLASSIFIED, CLASSIFIED SECRET, CLASSIFIED TS, AND AV CABLES.
05. 2" D x 6" W BELOW FLOOR BASKET TRAY.
06. SECONDARY BONDING BUSBAR, MOUNTED 7' 6" AFF.
07. TELECOMMUNICATIONS CABINET, SEE SHEET 14CC-T-401 FOR ADDITIONAL DETAIL.
08. 3 X 4" CONDUIT STUBBED 1"-3" AFF AND 3"-6" BELOW RAF. CONDUIT MUST BE IN GROMMETED
SLOT IN A RAF TILE.
09. ESS VERTICAL CABINETS. SEE SHEET 14CC-TY114.
14GI-T-001
14CC-T-401
14CC-TY114
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
TYP.
PTFE COATED STEEL TABLE ON
STRUT REFER TO 14CC-S-790
WIRE MESH SUPPORT GRIP
REFER TO 14CC-TX511
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
01. 3/4" AC RATED FIRE-RATED BACKBOARD PAINTED ON ALL SIDES WITH RETARDANT PAINT, FIRE-
RATING LABELS WILL BE LEFT UNPAINTED. COLOR TO MATCH THE WALL.
02. 24" W ALUMINUM LADDER TRAY, MOUNTED 10' AFF.
03. 30" VERTICAL ALUMINUM LADDER TRAY.
04. 4"D x 20"W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE
SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.
05. 10 x 4" SCHEDULE 40 PVC SLEEVES. SEE SHEETS 14CC-T-104 AND 14CC-T-105 FOR CONDUIT
ENTRY.
06. CABLE PORT ENTRY. SEE DETAIL A1 SHEET 14CC-TX505 FOR MORE INFORMATION.
07. PRIMARY BONDING BUSBAR, MOUNTED 7' 6" AFF.
08. SECONDARY BONDING BUSBAR, MOUNTED 7' 6" AFF.
09. 24" VERTICAL ALUMINUM LADDER TRAY.
10. 18" W ALUMINUM LADDER TRAY, MOUNTED 9' AFF.
11. 6 x 4" SCHEDULE 80 PVC GOING TO ANTENNA TOWER. SEE ROUTING DETAIL A1 ON SHEET
14CC-TX202.
12. SECONDARY BONDING BUSBAR, MOUNTED 18" AFF.
13. WALL MOUNTED 19U CLASSIFIED DISTRIBUTION RACK (24" W X 24" D X 36" H).
14. 12" W VERTICAL ALUMINUM LADDER TRAY.
15. 12" W OVERHEAD ALUMINUM LADDER TRAY.
16. 4" D x 12" W BELOW FLOOR BASKET TRAY.
17. RUNWAY DROP OUT, SEE DETAIL A1 SHEET 14CC-T-501 FOR MORE INFORMATION.
14GI-T-001
14CC-T-104 14CC-T-105
14CC-T-501
14CC-TX505
14CC-TX511
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
TYP
01. TWO POST CHANNEL RACK 84" H (MIN X 23.75" 2 x 40" D.
02. VERTICAL CABLE MANAGER 76.94" H X 12.20" W x 15.07" D.
03. VERTICAL ALUMINUM LADDER TRAY 2" H x 12" W.
04. 4" H x 20" W ALUMINUM LADDER TRAY.
05. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH 1 DIVIDER CREATING 16" AND 4" WIDE SECTIONS
FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.
06. SECONDARY BONDING BUSBAR. MOUNTED AT 7' 6" AFF.
07. ESS VERTICAL CABINETS. SEE SHEET 14CC-TY114.
08. 12" W ALUMINUM LADDER TRAY.
09. 2" D x 6" W BELOW FLOOR BASKET TRAY.
10. IESS VERTICAL RACK (SECURITY). SEE DETAIL C3 ON SHEET 14CC-TY502.
14GI-T-001
14CC-TY502
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
RATING LABELS WILL BE LEFT UNPAINTED. COLOR TO MATCH THE WALL.
02. 24" W ALUMINUM LADDER TRAY, MOUNTED 10' AFF.
03. 30" VERTICAL ALUMINUM LADDER TRAY.
04. 4"D X 20"W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE
SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.
05. 10 X 4" SCHEDULE 40 PVC SLEEVES. SEE SHEETS 14CC-T-104 AND 14CC-T-105 FOR CONDUIT
ENTRY.
06. CABLE PORT ENTRY. SEE DETAIL A1 SHEET 14CC-TX505 FOR MORE INFORMATION.
07. 24" VERTICAL ALUMINUM LADDER TRAY.
08. 18" W ALUMINUM LADDER TRAY, MOUNTED 9' AFF.
09. 4"H X 6"W THERMOPLASTIC FIBER TROUGH.
10. 6 X 4" SCHEDULE 80 PVC GOING TO ANTENNA TOWER. SEE ROUTING DETAIL A1 ON SHEET
14CC-TX202.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
14GI-T-001
14CC-T-104 14CC-T-105
14CC-TX505
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
TYP.
TYP.
01. 3/4" AC RATED FIRE-RATED BACKBOARD PAINTED ON ALL SIDES WITH RETARDANT PAINT, FIRE-
RATING LABELS WILL BE LEFT UNPAINTED. COLOR TO MATCH THE WALL.
02. 30" VERTICAL ALUMINUM LADDER TRAY.
03. 24" VERTICAL ALUMINUM LADDER TRAY.
04. 18" W ALUMINUM LADDER TRAY, MOUNTED 9' AFF.
05. 24" W ALUMINUM LADDER TRAY, MOUNTED 10' AFF.
06. SECONDARY BONDING BUSBAR, MOUNTED 7' 6" AFF.
07. PRIMARY BONDING BUSBAR, MOUNTED 8' 6" AFF.
08. TELECOMMUNICATIONS CABINET, SEE SHEET 14CC-T-405 FOR ADDITIONAL DETAIL.
09. 10 x 4" SCHEDULE 40 PVC SLEEVES, SEE SHEET 14CC-T-203 FOR SLEEVE DETAIL.
10. 4" H x 6" W THERMOPLASTIC FIBER THROUGH.
11. CABLE PORT ENTRY. SEE DETAIL A1 SHEET 14CC-TX505 FOR MORE INFORMATION.
TYP.
14GI-T-001
14CC-T-203
14CC-T-405
14CC-TX505
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
RATING LABELS WILL BE LEFT UNPAINTED. COLOR TO MATCH THE WALL.
02. WALL MOUNTED 19U CLASSIFIED DISTRIBUTION RACK (24" W X 24" D X 36" H).
03. 12" W VERTICAL ALUMINUM LADDER TRAY.
04. 12" W OVERHEAD ALUMINUM LADDER TRAY.
05. 16" W OVERHEAD ALUMINUM LADDER TRAY.
06. SECONDARY BONDING BUSBAR.
14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
01. F/UTP CAT6A SHOULD BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURER
SPECIFICATIONS.
14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
01. F/UTP CAT6A SHOULD BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURER
SPECIFICATIONS.
14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
A2
A1 B1
B2A2
TYP
B3
B4 A4
A3
14CC-T-201
A1
14CC-T-201 C3
14CC-T-201
A3
14CC-T-201C1
A2A3A4A5A6A7A8A9A10
B6
A1
B7 B5 B4 B3 B2 B1B8B9
14CC-T-202
A1
14CC-T-202 C314CC-T-202C1
14CC-T-202
A3
BCS-14CC65011
B7 B6 B4B5 B3 B2 B1
A1A2A3A4A5A6A7A8A9A10
SPARE
B8B9
SPARE
BCS-14CC65011
A2
A1 B1
B2
A3
A4 B4
B3
SPARE
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. SEE SHEET 14CC-T-602 FOR TELECOMMUNICATIONS RACK IDENTIFICATION.
C. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.
D. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE
RATED. SEE DETAIL B3 SHEET 14CC-T-401.
E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE
ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50. SEE DETAIL B3 SHEET
14CC-T-401
F. WALL MOUNT OUTLETS IN ROOMS 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON
14CC-T-505.
G. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
SPECIFICATIONS.
01. 3/4" AC RATED FIRE-RATED BACKBOARD PAINTED ON ALL SIDES WITH RETARDANT PAINT, FIRE-
RATING LABELS WILL BE LEFT UNPAINTED. COLOR TO MATCH THE WALL.
02. TWO POST CHANNEL RACK 84" H MIN X 23.75" x 40" D. SEE DETAIL A3 SHEET 14CC-T-502.
03. VERTICAL CABLE MANAGER 76.94" H X 12.20" W x 15.07" D. SEE DETAIL C3 SHEET 14CC-T-502.
04. VERTICAL ALUMINUM LADDER TRAY 12" W.
05. 4" H x 20" W ALUMINUM LADDER TRAY.
06. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH 1 DIVIDER CREATING 16" AND 4" WIDE SECTIONS
FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.
07. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH 3 DIVIDERS CREATING 8" AND 3 x 4" WIDE
SECTIONS FOR UNCLASSIFIED, CLASSIFIED SECRET, CLASSIFIED TS, AND AV CABLES.
08. 3 x 4" CONDUIT STUBBED 1"-3" AFF AND 3"-6" BELOW RAF. CONDUIT MUST BE IN GROMMETED
SLOT IN A RAF TILE.
09. SECONDARY BONDING BUSBAR. MOUNTED AT 7' 6" AFF.
10. 12" W ALUMINUM LADDER TRAY.
11. 2" D x 6" W BELOW FLOOR BASKET TRAY.
14GI-T-001
14CC-T-201 14CC-T-201
14CC-T-201
14CC-T-201
14CC-T-202
14CC-T-20214CC-T-202
14CC-T-202
14CC-T-505
14CC-T-602
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
B. SEE SHEET 14CC-T-602 FOR TELECOMMUNICATIONS RACK IDENTIFICATION.
C. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.
D. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE
RATED.
E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE
ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50.
F. WALL MOUNT OUTLETS IN ROOMS 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
G. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
SPECIFICATIONS.
01. 12"W VERTICAL ALUMINUM LADDER TRAY.
02. 4" D x 12" W BELOW FLOOR BASKET TRAY.
14GI-T-001
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
14CC-T-602
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
14CC-T-203 A1
B. SEE SHEET 14CC-T-602 FOR TELECOMMUNICATIONS RACK IDENTIFICATION.
C. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.
D. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE
RATED. SEE DETAIL B3 SHEET 14CC-T-401.
E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE
ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50. SEE DETAIL B3 SHEET
14CC-T-401
F. WALL MOUNT OUTLETS IN ROOMS 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON
14CC-T-505.
G. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
SPECIFICATIONS.
01. 3/4" AC RATED FIRE-RATED BACKBOARD PAINTED ON ALL SIDES WITH RETARDANT PAINT.
COLOR TO MATCH THE WALL.
02. WALL MOUNTED 19U CLASSIFIED DISTRIBUTION RACK (24" W X 24" D X 36" H). SEE DETAIL C1
SHEET 14CC-T-502.
03. VERTICAL ALUMINUM LADDER TRAY 2" H x 12" W.
04. 4" D X 12" W OVERHEAD ALUMINUM LADDER TRAY.
05. 4" D X 16" W OVERHEAD ALUMINUM LADDER TRAY (PLAN WEST LADDER TRAY THAT RUNS PLAN
NORTH TO SOUTH).
06. SECONDARY BONDING BUSBAR. SEE DETAIL C1 SHEET 14CC-EG501.
14GI-T-001
14CC-T-203
14CC-T-401
14CC-T-401
14CC-T-505
14CC-T-602
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
AE1
AE2
AE3
AE4
AE5
AE6
AE7
AE9
AB1
AB2
AB3
AB4
AB5
AB6
AB7
AB8
AD1
AD2
AD3
AA4
AA5
AA6
AA7
AA8
AA9
AA3
AA2
AA1
AC2
AC3
AC4
AC5
BE1
BE2
BE3
BE4
BE5
BE6
BD1
BD2
BD3
BD4
BD5
BD7
BD8
BD9
BD10
BD11
BD12
BC1
BC2
BC3
BC4
BC5
BC6
BC7
BC8
BC9
BB1
BB2
BB3
BB4
BB5
BB6
BB7
BB8
BB9
BB10
BB11
BB12
BA1
BA2
BA3
BA4
BA5
BA6
BA7
BA8
BA9
BD6
BC10
BC11
BC12
AD4
AD6
AD7
AD5
AD8
AD9
AD10
AD11
AE10
AE11
AB9
AB10
AB11
BE7
BE8
BE9
BE10
BE11
BE12
SPARE
AC6
AC7
AC8
AC9
AC1
SPARE
SPARE
BA10
SPARE
AE8
SPARE
SPARE
SPARE
SPARE
BA11
SPARE
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. SEE SHEET 14CC-T-602 FOR TELECOMMUNICATIONS RACK IDENTIFICATION.
C. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.
D. PENETRATIONS INTO TELECOMMUICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE
RATED.
E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE
ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50.
F. WALL MOUNT OUTLETS IN ROOMS 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
G. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
SPECIFICATIONS.
01. 3/4" AC RATED FIRE-RATED BACKBOARD PAINTED ON ALL SIDES WITH RETARDANT PAINT.
COLOR TO MATCH THE WALL.
02. 4"D x 20"W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE
SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.
03. 2" D x 6"W BELOW FLOOR BASKET TRAY.
04. 4" D x 12" BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 2 x 6" WIDE SECTIONS FOR
CLASSIFIED VOICE CABLE.
05. 10 x 4" SCHEDULE 40 PVC SLEEVES. SEE SHEETS 14CC-T-104 AND 14CC-T-105 FOR CONDUIT
ENTRY.
14GI-T-001
14CC-T-104 14CC-T-105
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
14CC-T-602
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
AE1
AE3
AE2
AE4
AE5
AE6
AE7
AE9
AB1
AB3
AB2
AB4
AB5
AB6
AB7
AB8
AD1
AD2
AD3
AA4
AA5
AA6
AA7
AA8
AA9
AC2
AC3
AC4
AC5
BE1
BE2
BE3
BE4
BE5
BE6
BD1
BD2
BD3
BD4
BD5
BD7
BD8
BD9
BD10
BD11
BD12
BC1
BC2
BC3
BC4
BC5
BC6
BC7
BC8
BC9
BB1
BB3
BB2
BB4
BB5
BB6
BB7
BB8
BB9
BB10
BB11
BB12
BA1
BA2
BA3
BA4
BA5
BA6
BA7
BA8
BA9
BD6
AA1
AA2
AA3
TYP.
TYP.
TYP.
TYP.
AD4
AD6
AD7
AD9
AD8
AD10
AD11
AC1
AC9
AC8
AC7
AC6
AB9
AB10
AB11
BC10
BC11
BC12
BA10
BE7
BE9
BE8
BE10
BE11
BE12
AE10
AE11
AE8
SPARE
SPARE
SPARE
SPARESPARE
SPARE
SPARE
SPARE
SPARE
14CC-T-203
C1
14CC-T-203 C3
TYP.
TYP.
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. SEE SHEET 14CC-T-602 FOR TELECOMMUNICATIONS RACK IDENTIFICATION.
C. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.
D. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE
RATED. SEE DETAIL B3 SHEET 14CC-T-401.
E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE
ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50. SEE DETAIL B3 SHEET
14CC-T-401.
F. WALL MOUNT OUTLETS IN ROOMS 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
G. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
SPECIFICATIONS.
01. 3/4" AC RATED FIRE-RATED BACKBOARD PAINTED ON ALL SIDES WITH RETARDANT PAINT.
COLOR TO MATCH THE WALL.
02. TWO POST CHANNEL RACK 84"H (MIN) x 23.75" W x 40" D. SEE DETAIL A3 SHEET 14CC-T-502
03. VERTICAL CABLE MANAGER 76.94" H x 12.20" W x 15.07" D. SEE DETAIL C3 SHEET 14CC-T-502
04. VERTICAL CABLE MANAGER 76.94" H x 16.25" W x 15.07" D. SEE DETAIL A1 SHEET 14CC-T-502
05. 18" ALUMINUM LADDER TRAY.
06. 30" W VERTICAL LADDER TRAY.
07. 4" H x 6" W THERMOPLASTIC FIBER TROUGH.
08. OVERHEAD FIRE PENETRATION FOR ROUTING FIBER BETWEEN OVERHEAD LADDER TRAY IN
ROOM 135 TO ROOM 130.
14GI-T-001
14CC-T-203
14CC-T-203
14CC-T-401
14CC-T-401
14CC-T-502
14CC-T-502
14CC-T-502
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
14CC-T-602
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
BCS-14CC65011
JJJJJJJ
J J
TYP
J
14CC-T-401
C3
14CC-T-401
A3
TYPTYP
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. SEE SHEET 14CC-T-602 FOR TELECOMMUNICATIONS RACK IDENTIFICATION.
C. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.
D. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE
RATED. SEE DETAIL B3 SHEET 14CC-T-401.
E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUSTE BE
ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50. SEE DETAIL B3 SHEET
14CC-T-401.
F. WALL MOUNT OUTLETS IN ROOM 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON
14CC-T-505.
G. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
SPECIFICATIONS.
H. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.
01. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH 3 DIVIDERS CREATING 8" AND 3 x 4" WIDE
SECTIONS FOR UNCLASSIFIED, CLASSIFIED SECRET, CLASSIFIED TS, AND AV CABLES.
02. FIELD ROUTE BELOW FLOOR J-HOOK OR OTHER NON-CONTINUOUS SUPPORT FROM BASKET
TRAY TO OUTLETS; MAX SUPPORT SEPARATION OF 5'.
03. 2" D x 12" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 2 x 6" WIDE SECTIONS
FOR CLASSIFIED VOICE CABLE.
04. RF PENETRATION SEE DETAIL C1 ON SHEET 14CC-T-504.
14GI-T-001
14CC-T-4011114 111
14CC-T-4011114 111
14CC-T-401
14CC-T-401
14CC-T-504
14CC-T-505
14CC-T-602
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
CP CP
TYP
CP
J J
J J
J J
J J
J J
J J
J J
TYP
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. SEE SHEET 14CC-T-602 FOR TELECOMMUNICATIONS RACK IDENTIFICATION.
C. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.
D. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE
RATED. SEE DETAIL B3 SHEET 14CC-T-401.
E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE
ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50. SEE DETAIL B3 SHEET
14CC-T-401.
F. WALL MOUNT OUTLETS IN ROOMS 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON
14CC-T-505.
G. ALL SHIELDED CABLE MUST BE ROUNDED IN ACCORDANCE WITH CABLE MANUFACTURES
SPECIFICATIONS.
H. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.
01. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE
SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.
02. FIELD ROUTE BELOW FLOOR J-HOOK OR OTHER NON-CONTINUOUS SUPPORT FROM BASKET
TRAY TO OUTLETS; MAX SUPPORT SEPARATION OF 5'.
03. 4" D x 18" W BELOW FLOOR BASKET TRAY LATERAL WITH DIVIDER CREATING 3 X 6" WIDE
SECTIONS FOR AV AND CLASSIFIED VOICE.
04. 2"D x 6"W BELOW FLOOR BASKET TRAY.
05. RAISED ACCESS FLOOR CP WITH 24 PORT (8P8C) CPP.
06. RAISED ACCESS FLOOR CP WITH 24 PORT DUPLEX LC MMF FOP.
07. RAISED ACCESS FLOOR CP WITH 24 PORT (8P8C) PATCH PANEL WITH GROUNDING FOR F/UTP
CABLE. 10 PAIRS OF 22 AWG SINGLE PAIR SHOULD ALSO BE PULLED TO THIS CP WITH
SERVICE LOOP FOR TERMINATION LATER BY OTHERS.
14GI-T-001
14CC-T-401
14CC-T-401
14CC-T-505
14CC-T-602
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
BOND EACH SECTION OF THE CABLE RUNWAY WITH 5/8" BONDING
CONDUCTOR TYPICAL FOR EACH SECTION OF RUNWAYBONDING CABLE RUNWAY
TO BONDING BUSBAR
TEBC
STAND OFF BRACKET TO
MAINTAIN BONDING/
COMMUNICATIONS CABLE
SEPARATION
EQUIPMENT RACK
VERTICAL MANAGEMENT
RBB, ONE PER CABINET/RACK
RBB
5/8" BONDING CONDUCTOR
RUNWAY RADIUS DROP,
CROSS MEMBER
RUNWAY
RUNWAY MOVABLE
CROSS MEMBER
MANUFACTURERS
SUGGESTED BONDING CLAMP
BONDING JUMPER 5/8" JACKETED
COPPER CONDUCTOR
1. REMOVE PAINT AT BOLTED BOND ATTACHMENT LOCATIONS AS NEEDED TO
ENSURE PROPER CONNECTION.
2. BONDING JUMPER TO BE FROM SAME MANUFACTURER AS CABLE / LADDER
TRAY TO MAINTAIN UL OR BRITISH STANDARD DETAILS.
GROUND LUG WALL
GROUNDING WIRE
GROUNDING LUG
CABLE TRAY
FIRE RATED PATHWAYS THRU-WALL FOR ACCESS TO CABLE
TRAY. ALL FIRE STOPS MUST BE FIRE PROOFED AS REQUIRED
BY ALL APPLICABLE CODES. REFER TO PLAN SHEETS OR
RISER DIAGRAMS FOR FIRE STOP REQUIREMENTS. FIRE
STOPS MUST BE SIZED TO MEET SAME CABLE FILL AS TRAY
SYSTEM.
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. REMOVE PAINT AT BOLTED BOND ATTACHMENT LOCATIONS AS NEEDED TO ENSURE PROPER
CONNECTION.
C. BONDING JUMPER TO BE FROM SAME MANUFACTURER AS CABLE LADDER TRAY TO MAINTAIN
UL STANDARD DETAILS.
14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
86" 84"
16" 23.75"
30"
40"
TOP VIEW
SIDE VIEW FRONT VIEW
3" DIA (2-1/2" CONDUIT)
KNOCKOUTS. 2 PLACES.
1.1" DIA (3/4" CONDUIT)
KNOCKOUTS. 2 PLACES.
9"W x 2.2"D KNOCKOUT
15.07" 16.25"
76.94"
15.07" 12.20"
76.94"
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. REMOVE PAINT AT BOLTED BOND ATTACHMENT LOCATIONS AS NEEDED TO ENSURE PROPER
CONNECTION.
C. BONDING JUMPER TO BE FROM SAME MANUFACTURER AS CABLE LADDER TRAY TO MAINTAIN
UL STANDARD DETAILS.
14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
15-1/8"
11-3/16"
6"
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
1-1/8" - 18 THD
STAINLESS STEEL
PLATE
1-5/32"
SECURE PLATE
TO FRAME, TYP.
FRAME
CONDUCTIVE TAPE
FOIL RF
SHEILDING, TYP.
TIGHTEN TO
MFR SPECIFIED
TORQUE RATING
CENTER WAVEGUIDE
IN STEEL PLATE
UNSECURED SIDE SECURED SIDE
GYPSUM WALLBOARDGYPSUM WALLBOARD
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. PREPARE THE STAINLESS STEEL PLATE BY BORING 1-5/32" DIAMETER MOUNTING HOLES IN THE
SPECIFIED LOCATIONS. ANY ADJACENT HOLES MUST BE NO CLOSER THAN 2".
C. CLEAN AND DE-BURR THE AREA AROUND THE MOUNTING HOLES.
D. INSERT THE BUSHING THROUGH THE MOUNTING HOLE, AND PLACE THE MOUNTING NUTS ON
EACH SIDE OF THE STAINLESS STEEL PLATE. CENTER THE BUSHING IN THE PLATE BY HOLDING
THE NUT AND ROTATING THE BUSHING UNTIL THERE ARE EQUAL THREADS ON BOTH SIDES.
E. TIGHTEN ONE OF THE MOUNTING NUTS TO MANUFACTURER SPECIFIED MAXIMUM TORQUE.
F. MOUNT PLATE TO WOOD FRAME.
G. OVERLAP STEEL PLATE WITH EXISTING RF SHIELDING, AND COVER SEEMS OF PLATE/WALL
WITH CONDUCTIVE TAPE.
01. STAINLESS STEEL PLATE SHOWN ON ACCOMPANYING DETAILS C3 AND A3
14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
1-1/4" EMT CONDUIT
THREADED TYPE STEEL
CONNECTOR BELOW JUNCTION BOX
CAT6 UTP PLENUM CABLES
6- PORT SINGLE GANG IVORY FACEPLATE
CATEGORY 6A
MODULAR JACK
SINGLE GANG PLASTER RING
PULL STRING 200LB TEST
4 11/16"H x 4 11/16"W x 2 1/8"D (MIN)
OUTLET BOX
LC-UPC MODULAR JACK OM4 MMF CABLE
W T
1 1/4" EMT CONDUIT
THREADED TYPE
STEEL CONNECTOR
PULL STRING
200 LB TEST
SINGLE GANG
PLASTER RING
CATEGORY 6A
MODULAR JACK
OM4 MMF CABLE
4 - PORT SINGLE
GANG WHITE FACEPLATE
BLANK LEER
LC-UPC MODULAR JACK
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
CAT6 UTP PLENUM CABLES
6- PORT SINGLE GANG IVORY FACEPLATE
CATEGORY 6A
MODULAR JACK
LC-UPC MODULAR JACK
OM4 MMF CABLE
CAT6 UTP PLENUM CABLES
6- PORT SINGLE GANG IVORY FACEPLATE
CAT6A MODULAR
JACK
LC-UPC MODULAR JACK
OM4 MMF CABLE
DB
CAT6A F/UTP
PLENUM CABLES
CAT6A SHIELDED
MODULAR JACK
BLANK
T
DR T
2 PORT SINGLE GANG
IVORY FACEPLATE
DB
DB
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
CAT6A UTP PLENUM CABLES
6- PORT SINGLE GANG IVORY FACEPLATE
CAT6A MODULAR
JACK
LC-UPC MODULAR JACK
OM4 MMF CABLE
DB
DR
DB
DR
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.
C. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE
RATED.
D. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE
ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50.
E. WALL MOUNT OUTLETS IN ROOMS 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
F. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTUERS
SPECIFICATIONS.
G. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.
14GI-T-001
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTUERS
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
RACK A1
SMF FOP
MMF FOP
CPP
RACK B1
SMF FOP
MMF FOP
RACK A1
SMF FOP
CPP
TE
SMF FOP
MMF FOP
RACK AA1-AA2
SMF FOP
MMF FOP
CPP
CABINET AB6
GFGI PP
RACK BA1-BA2
SMF FOP
MMF FOP
CPP
CABINET BA7
GFGI PP
24 SMF
144 MMF
144 SMF
48 SMF
48 SMF
48 SMF
CAT6A
UTP
OM4 MMF
OM4 MMF
CAT6A UTP
OM4 MMF
CAT6A UTP
22 AWG SINGLE
PAIR
OM4 MMF
CAT6A F/UTP
22 AWG SINGLE
PAIR
24 UTP
CAT6A 48 MMF
24 MMF
24 F/UTP
CAT6A
RACK B1
MMF FOP
CPP
GFGI PP
CAT6A F/UTP
SINGLE PAIR 22
AWG COPPER
OM4 MMF
GFGI PP
SINGLE PAIR 22
AWG COPPER
GFGI PP
GFGI PP
SINGLE PAIR 22
AWG COPPER
SINGLE PAIR 22
AWG COPPER
TYP
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. ALL INSIDE PLANT TELECOMMUNICATION CABLING IS REQUIRED TO BE PLENUM RATED.
C. CATEGORY 6A 8P8C DATA JACKS MUST BE ERMINATED T568A.
D. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE
RATED.
E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE
F. ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50
G. WALL MOUNT OUTLETS IN ROOMS 150 - 158 MUST BE SURFACE MOUNTED; NO IN-WALL
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
H. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
SPECIFICATIONS.
I. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.
J. SEE SHEET 14CC-T-221 AND 14CC-T-222 FOR RACK ELEVATIONS.
01. 3 x PLENUM UTP CAT6A, ROUTED THROUGH 1 1/4" CONDUIT TO WALL BOX OR J-HOOK UNDER
RAF TO FLOOR BOX.
02. SIX (6) STRAND PLENUM OM4 MMF, ROUTED THROUGH 1 1/4" CONDUIT TO WALL BOX OR J-HOOK
UNDER RAF TO FLOOR BOX.
03. 2" D x 6" W UNDERFLOOR BASKET TRAY. USED FOR BUILDING BACKBONE CABLING AND SPECIAL
DISTRIBUTION TO RM 107.
04. 4" D x 20" W UNDERFLOOR BASKET TRAY. USED FOR HORIZONTAL DISTRIBUTION FROM ROOM 124.
05. 6" D x 20" W UNDERFLOOR BASKET TRAY. USED FOR HORIZONTAL DISTRIBUTION FROM ROOM
135. ALSO HAS CHANNEL FOR AV BACKBONE CABLE, SEE TA SHEETS FOR AV RISER.
06. 4" D x 12" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 2 X 6" WIDE SECTIONS FOR
CLASSIFIED VOICE CABLE FROM ROOM 135.
07. 2" D X 6" W UNDERFLOOR BASKET TRAY. USED FOR HORIZONTAL DISTRIBUTION OF CLASSIFIED
COPPER FROM ROOM 124.
08. GFGI PATCH PANELS ARE INSTALLED AT A LATER DATE BY OTHERS. SINGLE PAIR 22 AWG
COPPER WIRE (SEE SPEC AND LEGEND) PLLED TO THE RACK SHOULD HAVE SERVICE LOOP
PLUS 25FT OF SPARE CABLE FOR INSTALLATION BY OTHERS.
09. 2" D x 12" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 2 x 6" WIDE SECTIONS FOR
CLASSIFIED VOICE CABLE FROM ROOM 158.
10. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH 3 DIVIDERS CREATING 8" AND 3 x 4" WIDE
SECTIONS FROM UNCLASSIFIED, CLASSIFIED SECRET, CLASSIFIED TS, AND AV CABLES FROM
ROOM 158.
11. OVERHEAD LADDER TRAY, PATH BETWWEN ROOM 130 AND 135.
14GI-T-001
14CC-T-222
CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.
ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS
14CC-T-221
10/04/2024
10/04/2024
10/04/2024
10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
PBB
SBB
SBB
SBB
RM 130
RM 124
RM 158
RM 135
TO MGB IN A RM 144
SEE SHEET 14CC-EG601 FOR RISER CONTINUATION
SBB RM 132
SBB
SBB
SBB
SUS-GB
RM 103
RM 105
RM 135
PBB
#6 (MIN.)
#6 (MIN.)
#6 (MIN.)
#6 (MIN.)
#6 (MIN.)
#6 (MIN.)
#6 (MIN.) METALLIC WALL CONDUIT STUB OUTS AND FIRESTOPPING
BUILDING STEEL
LADDER RACK
DEDICATED COMM ROOM PANELBOARD
METALLIC FLOOR CONDUIT STUB UPS AND FIRESTOPPING
UNDERFLOOR TRAY
RACK MOUNTED GROUNDING BUSBAR (TYPICAL FOR EACH RACK)TO MGB IN RM 144
SEE SHEET 14CC-EG601 FOR RISER CONTINUATION
RM 135
SBB
#6 (MIN.)
#6 (MIN.)
#6 (MIN.)
#6 (MIN.)
#6 (MIN.)
#6 (MIN.)
#6 (MIN.) METALLIC WALL CONDUIT STUB OUTS AND FIRESTOPPING
BUILDING STEEL
LADDER RACK (IF APPLICABLE)
UNDERFLOOR TRAY (IF APPLICABLE)
DEDICATED COMM ROOM PANELBOARD
METALLIC FLOOR CONDUIT STUB UPS AND FIRESTOPPING
RACK MOUNTED GROUNDING BUSBAR (TYPICAL FOR EACH RACK)TO PBB IN RM 135
SEE SHEET 14PP-T-603/C1 FOR RISER
CONTINUATION
RM 124 / RM 158 / RM 130 / RM 132 / RM 105 / RM 103
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
01. TELECOMMUNICATIONS BONDING BACKBONE, SIZE BONDING CONDUCTOR IN ACCORDANCE
WITH TIA-607-D.
02. TELECOMMUNICATIONS BONDING CONDUCTOR, SIZE BONDING CONDUCTOR IN ACCORDANCE
WITH TIA-607-D.
14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
14CC-TX401
14CC-TX506
A1
14CC-TX402
A1
14CC-TX204
A3
14CC-TX512
A1
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001
14CC-TX40114CC-TX4011144 0111
14CC-TX40214CC-TX4021144 0222
4CC-TX506414CC-TX50614CC-TX506144111114 0666
14CC-TX51214CC-TX5124 22214
04TX20404441414CC-14
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
(TY
P.)
SATCOM ANTENA MOUNT, TYP.
SEE SHEET 14CC-TX503/504 FOR MORE INFORMATION.
RF CABLE HATCH
(TYP)
CATWALK
(TYP)
14CC-TX204
A3
14CC-TX512
A1
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001
14CC-TX503/
14CC-TX51214CC-TX51222214
14CC-TX20414CC-TX20411414 0444
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
SATCOM ANTENNA MOUNT, TYP.
SEE SHEET 14CC-TX503/504 FOR MORE INFORMATION.
CATWALK
(TYP)
ROOF ACCESS
STAIRS
RF CABLE HATCH
(TYP)
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001
14CC-TX503/
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
ROOFTOP CATWALK (TYP.)
VERTICAL CABLE TRAY
14CC-TX203
A3
14CC-TX204
A1
14CC-TX506
A1
RF CABLING HATCH
OPS FLOOR
ACCESS STAIRS
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
SATCOM ANTENNA MOUNT, TYP.
SEE SHEET 14CC-TX503/504 FOR MORE INFORMATION.
14GI-T-001
14CC-TX503/
14CC-TX50614CC-TX506066614
14CC-TX20314CC-TX203033314
14CC-TX20414CC-TX2041144 0444
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
TOWER
1/2" SUPERFLEX
COAXIAL CABLE
RACK, TYP.
4" CONDUIT
PTFE COATED STEEL TABLE ON
STRUT REFER TO 14CC-S-790
GROUND BAR.
REFER TO EG115
CONNECTOR
TRANSITION
CABLE ENTRY
PORTRADIO
INSTALLATION OF COAX SHOULD NOT EXCEED
MANUFACTURER RECOMMENDED BEND RADIUS.
3' ADDITIONAL SLACK ON SUPPORT
TABLE REFER TO 14CC-TX401
WIRE MESH SUPPORT GRIP
REFER TO 14CC-TX511
REFER TO
14CC-TX511
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
01. WORK TO BE EXECUTED BY OTHERS.
14GI-T-001
14CC-TX40114CC-TX401
14CC-TX511111
14CC-TX511
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
10' X 9' PTFE COATED SUPPORT
TABLE ON STRUT - REFER TO
14CC-S-790.
3' ADDITIONAL SLACK ON SUPPORT
TABLE. REFER TO 14CC-TX401.
WIRE MESH SUPPORT GRIP
REFER TO 14CC-TX511
6'-4" VERTICAL CONDUIT
COAXIAL CABLE
6'-4" VERTICAL CONDUIT
SATCOM ANTENNA MOUNT, TYP.
VERTICAL CABLE TRAY.
SEE SHEET TO 14CC-TX503/504
FOR MORE INFORMATION.
CABLE PORT ENTRY. SEE SHEET
14CC-TX505 FOR MORE
INFORMATION.
VERTICAL CABLE TRAY. SEE
SHEET 14CC5-TX506 FOR MORE
INFORMATION.
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
01. WORK TO BE EXECUTED BY OTHERS.
14GI-T-001
14CC-TX401
14CC-TX503/
14CC-TX505
14CC-TX511
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
VERTICAL CABLE TRAY.
SEE SHEET 14CC-TX507
FOR MORE INFORMATION.
VERTICAL CABLE TRAY. SEE SHEET
14CC-TX512 FOR MORE INFORMATION.
CABLE PORT ENTRY. SEE SHEET 14CC-
TX505 FOR MORE INFORMATION
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001
CABLE PORT ENTRY. SEE SHEET 14CC-
TX505 FOR MORE INFORMATION14CC-TX512
14CC-TX507
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
14CC-TX203 A1 14CC-TX203
3 1
10'X9' PTFE COATED STEEL TABLE
ON STRUT SEE 14CC-S-790.
3' OF SLACK LAID ON
TABLE
14CC-TX506
A1
TOWER
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
01. WORK TO BE EXECUTED BY OTHERS.
14GI-T-001
14CC-TX50614CC-TX5064 066614
14CC-TX203 4CC-TX2034CC-TX2034 033341
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
B. PENETRATIONS BETWEEN ROOMS 103, 104, AND 105 MUST BE ACOUSTICAL PENETRATIONS
WITH A MINIMUM STC RATING OF 50.
01. 2"D X 6"W HORIZONTAL BASKET TRAY ABOVE DROP CEILING.
02. CABLE TRAY MUST BE GROUNDED PER MANUFACTURER RECOMMENDATIONS AND AS SHOWN
IN 14CC-T501.
03. CABLE PORT ENTRY. SEE SHEET 14CC-TX505 FOR MORE INFORMATION
14GI-T-001
14CC-TX505
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
20'
40'
60'
80'
100'
120'
140'
160'
TOP OF NEW TOWER
ELEVATION 150'-0" +/- AGL
PROPOSED AIR TERMINAL (SEE GENERAL SHEET NOTE D)
TIP ELEVATION 160'-0" +/- AGL
PROPOSED L-864/L-865 TOP OF TOWER BEACON (SEE GENERAL SHEET NOTE C)
TIP ELEVATION PER TOWER MANUFACTURER
MOUNT ELEVATION 150'-0" +/- AGL
BEACON ELEVATION 153'-0" +/- AGL
A3
14CC-TX501
PROPOSED INTERMIEDIATE L-810 MARKERS
(SEE GENERAL SHEET NOTE E)
SEE SHEET 14CC-S-792 FOR
FOUNDATION DETAILS
TOP OF TOWER L-864/L-865 BEACON
(SEE GENERAL SHEET NOTE C)
AIR TERMINAL (SEE
GENERAL SHEET NOTE D)
L-810 MARKER LIGHTS (SEE
GENERAL SHEET NOTE E)
MARKER INTERFACE ENCLOSURE
(OPTIONAL DEPENDENT UPON MFR)
L864/L-865 BEACON
(SEE GENERAL SHEET NOTE C)
PROPOSED AIR TERMINAL
(SEE GENERAL SHEET NOTE D)
L-810 MARKERS PLACED AT 75' (MAY BE INSTALLED HIGHER
IF SURROUDNING OBJECTS WOULD OBSCURE LIGHTS), TYP.
(SEE GENERAL SHEET NOTE E)
TO SITE
POWER
PHOTODIODE
GROUND
CONTROL UNIT
GPS ANTENNA
(OPTIONAL)
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. PROPOSED TOWER IS DESIGNED AND FABRICATED BY TOWER MANUFACTURER. CONTRACTOR
MUST REFER TO TOWER MANUFACTURER DESIGN PACKAGE FOR MORE DETAILS.
C. TOP OF TOWER BEACON MUST BE FAA CERTIFIED L-864/L-865 DUAL RED/WHITE MEDIUM
INTENSITY FLASHING BEACON AND IS TO BE MOUNTED TO TOP OF TOWER LEG PER TOWER
MANUFACTURER USING THE SUPPLIED BEACON MOUNT. SELECTED TOWER LEG MUST HAVE
THE TOWER MANUFACTURER SUPPLIED CLIMBING PATH AND SAFETY CLIMB CABLE INSTALLED
TO PERMIT EASE OF ACCESS.
D. PROPOSED AIR TERMINAL MUST BE INSTALLED AT THE TOP OF A TOWER LEG NOT SHARED BY
THE TOP OF TOWER BEACON. ATTACH TO TOWER PER TOWER MANUFACTURER.
E. THREE INTERMEDIATE L-810 MARKERS LOCATED APPROXIMATELY AT MIDPOINT OF TOWER,
ONE PER TOWER LEG. MUST FLASH IN UNISON WITH L-864/L-865 TOP OF TOWER BEACON.
F. TOWER MANUFACTURER IS TO ASSUME THAT TOWER PAINTING IN ACCORDANCE WITH FAA
ADVISORY CIRCULAR 70/7460-1M IS REQUIRED.
14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
WAVEGUIDE LADDER ROUTED TO
TOP OF TOWER
WAVEGUIDE LADDER ROUTED TO TOP OF TOWER,
ADJUST OFFSET ALONG TOWER FACES TO ALIGN
WITH ROUTING OF CABLES FROM THE COMMAND
CENTER
EXAMPLE CABLING, RECOMMENDED
ATTACHMENT TO WAVEGUIDE LADDER
ARE STAINLESS STEEL SNAP-IN
HANGERS AT 3FT SPACING.
INTERIOR CLIMBING LADDER
( SEE GENERAL SHEET NOTE D)
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. PROPOSED TOWER IS DESIGNED AND FABRICATED BY TOWER MANUFACTURER. CONTRACTOR
MUST REFER TO TOWER MANUFACTURER DESIGN PACKAGE FOR MORE DETAILS.
C. WORK TO BE DONE BY OTHERS.
D. INTERIOR CLIMBING LADDER TO BE ATTACHED TO TOWER PER TOWER MANUFACTURER.
LOCATION OF CLIMBING LADDER MAY BE INSTALLED OFFSET FROM ANY TOWER LEG TO BEST
ACCOMODATE FUTURE INSTALLATION OF CABLING.
E. FOR TOWER GROUNDING DETAILS, REFER TO SHEET 14CC-EG504
14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
5/8" DIA. HEAVY HEX HEADED ANCHOR BOLT,
STAINLESS STEEL, MINIMUM 6" CONCRETE
EMBEDMENT WITH MINIMUM 2-1/2" THREADED
PROJECTION
CONCRETE RING BEAM
SURFACE MOUNTED PLATE
HSS ARMS (TYP 2)
SATCOM ANTENNA TO BE
PROVIDED BY THE CUSTOMER
U-BOLT
(TYP 4)
SS HSS4-1/2" x 3/8"
U-BOLT
ATTACHMENT
PLATE (TYP 2)
TYP 2 PLCS5/16
TYP 2 PLCS
U-BOLT
ATTACHMENT
PLATE (TYP 2)
HSS ROUND TUBE
CONCRETE RING BEAM
SURFACE MOUNTED PLATE
HSS ARMS (TYP 2)
U-BOLT
(TYP 4)
5/16
(1/4) (1/4) 2
SS SHEAR STOP
PL2" x 2" x 1/4"
SS TEMPLATE PL12" x 17-1/4" x 1/4"
(SEE GENERAL SHEET NOTE D)
(SE
E G
EN
ER
AL
SH
EE
T N
OT
E C
(SEE GENERAL
SHEET NOTE C)
CAST-IN-PLACE
HEADED ANCHORS
(TYP 6)
#6 HORIZONTAL BARS
#4 @ 6" STIRRUPS
4 - #8#4 U BAR @ 8" OCTEMPLATE PLATE
#4 U BAR @ 8" OC
#6 @ 8" OC MAX
#4 U BAR
#4 STIRRUP
(4) - #8, TOP AND
BOTTOM, NOT
FULLY SHOWN
#6 @ 8" OC MAX
COMPOSITE SLAB
REINF REFER TO
OTHER DETAILS
RING BEAM EDGE
(WHERE APPLICABLE)
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. ALL METAL IS STAINLESS STEEL UNLESS NOTED OTHERWISE.
C. MINIMUM DISTANCES FROM EDGE OF SURFACE MOUNTED PLATE TO ANY EDGE OF THE
CONCRETE RING BEAM MUST BE HORIZONTALLY 11-1/2" AND VERTICALLY 6".
D. DIMENSIONS AND LAYOUT OF ANCHOR BOLT HOLES IN TEMPLATE PLATE TO MATCH SURFACE
MOUNTED PLATE AS SHOWN ON SHEET 14CC-TX504. PLATE THICKNESS MUST BE 1/4".
ADDITIONAL HOLES IN TEMPLATE PLATE MAY BE DRILLED TO ACCOMODATE ASSEMBLY OF
RING BEAM'S REBAR CAGE.
14GI-T-001
14CC-TX504
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
SS HSS4" x 4" x 1/2"
HSS ARM DETAIL
U-BOLT CONNECTION PLATE DETAIL
11/16" DIA. BOLT HOLES
(TYP 4)
HSS ARMS WELDED TO
CENTER OF U-BOLT
CONNECTION PLATE
SS PL7-1/2" x 7-1/2" x 5/8"
SURFACE MOUNTED PLATE DETAIL
SS PL1'-0" x 1'-5 1/4" x 1"
11/16" DIA. (TYPE 6 PLCS) SS HEAVY HEX NUT FOR 5/8" BOLT
SS COMPRESSIBLE-WASHER-TYPE DIRECT TENSION INDICATOR
(SEE STRUCTURAL STEEL CONNECTION NOTES ON SHEET 14CC-S-006)
SS FLAT WASHER FOR 5/8" BOLT
5/8" DIA. SS U-BOLT
U-BOLT DETAIL
HEAVY HEX STUDDED ANCHOR
MINIMUM THREADED PROJECTION
SURFACE OF CONCRETE RING BEAM
CONCRETE
EMBEDMENT
SS HEAVY HEX HEADED
ANCHOR BOLT
TEMPLATE PLATE
SS HEAVY HEX NUT FOR 5/8" BOLT
SS FLAT WASHER FOR 5/8" BOLT
SS HEAVY HEX NUT FOR 5/8" BOLT
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. ALL METAL IS STAINLESS STEEL UNLESS NOTED OTHERWISE.
C. MINIMUM DISTANCES FROM EDGE OF SURFACE MOUNTED PLATE TO ANY EDGE OF THE
CONCRETE RING BEAM MUST BE HORIZONTALLY 11-1/2" AND VERTICALLY 6".
D. DIMENSIONS AND LAYOUT OF ANCHOR BOLT HOLES IN TEMPLATE PLATE TO MATCH SURFACE
MOUNTED PLATE AS SHOWN ON SHEET 14CC-TX504. PLATE THICKNESS MUST BE 1/4".
ADDITIONAL HOLES IN TEMPLATE PLATE MAY BE DRILLED TO ACCOMODATE ASSEMBLY OF
RING BEAM'S REBAR CAGE.
14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
SCREW
FINISHING WASHER
DRILL PILOT HOLES FOR
MOUNTING SCREWS
USE MANUFACTURER RECOMMENDED
SEALANT AROUND EDGES
BUILDING
EXTERIOR WALL
ENTRY PANELS EXTERIOR
WALL OF BUILDING
3X4 CABLE ENTRY PORT
BOOT ASSEMBLY AND
CABLE INSTALLATION
TO BE DONE BY
OTHERS
MAXIMUM FOUR (4) 7/8"
CABLES PER 4" ENTRY
SCREW
FINISHING WASHER DRILL PILOT HOLES FOR
MOUNTING SCREWS
USE MANUFACTURER RECOMMENDED
SEALANT AROUND EDGES
BUILDING
EXTERIOR WALL
ENTRY PANELS EXTERIOR
WALL OF BUILDING
1X1 CABLE ENTRY PORT
BOOT ASSEMBLY AND
CABLE INSTALLATION
TO BE DONE BY
OTHERS
BOOT ASSEMBLY FOR
SINGLE 7/8" CABLE
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. LOCATE, PREPARE EXISTING OPENING AND INSTALL A NEW 24 HOLE ENTRY PORT PANEL AT
EXISTING SHELTER. INSTALL AND WEATHERPROOF PORT IN ACCORDANCE WITH
MANUFACTURER'S ASSEMBLY GUIDE.
C. PRIOR TO INSTALLING THE ENTRY PORT PANEL, THE CONTRACTOR MUST ENSURE THAT THE
LOCATION WILL NOT INTERFERE WITH ANY EQUIPMENT/ MATERIAL INSIDE THE SHELTER.
D. DO NOT COVER ANY EQUIPMENT WITH PLASTIC.
E. DO NOT ALLOW ANY OUTSIDE DEBRIS OR WATER TO ENTER THE SHELTER WHILE INSTALLING
THE NEW ENTRY PORT.
F. REMOVE ALL DUST AND DEBRIS, ETC. FROM THE SHELTER WHEN CONTRACTOR IS
COMPLETED.
G. IF A SHUT-DOWN OF THE EQUIPMENT OCCURS DUE TO A SUBCONTRACTOR ERROR AND NOT
FOLLOWING PROCEDURE, THE SUBCONTRACTOR WILL BE HELD RESPONSIBLE.
H. PROPOSED ENTRY PORT PANEL MUST BE GROUNDED TO PROPOSED MAIN GROUND BUS BAR.
14GI-T-001
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
MI
N.
(SE
E G
EN
ER
AL
SH
EE
T N
OT
E C
CABLE TRAY ATTACHMENT BRACKET
(REFER TO SHEET 14CC-TX508)
VERTICAL CABLE TRAY (SEE
GENERAL SHEET NOTE C)
1" MINIMUM FROM
BOTTOM OF CABLE
TRAYS TO CABLE
ENTRY PORTS.
(TYP.)
STAINLESS STEEL STRAPPING WITH BAND
CLAMP (TYP, SEE GENERAL SHEET NOTE D)
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. ALL METAL IS STAINLESS STEEL UNLESS NOTED OTHERWISE.
C. CABLE TRAY REQUIREMENTS:
a. CABLE TRAY MUST BE STAINLESS STEEL TYPE 316 WITH A MINIMUM MATERIAL THICKNESS
OF 18 GAUGE.
b. CABLE TRAY MUST BE A MINIMUM OF 24 INCHES WIDE WITH A MINIMUM 4 INCH LOADING
DEPTH.
c. CABLE TRAY RUNGS MUST BE SPACED AT 6 INCHES ON CENTER.
d. CABLE TRAY MUST BE SUFFICIENT TO SUPPORT A MINIMUM OF (15) 7/8-INCH NOMINAL
CABLES WITH 1.102 INCH OUTSIDE DIAMETER AND WEIGHING 0.302 POUNDS PER FOOT.
e. CABLE TRAY RUNGS MUST HAVE MANUFACTURED SLOTS TO ACCOMMODATE
ATTACHMENT OF CABLES WITH STAINLESS STEEL BANDING. SLOTS MUST BE 3/4-INCH BY
7/16-INCH AND SPACED AT 1 INCH ON CENTER OR APPROVED ALTERNATIVE. QUANTITY OF
SLOTS MUST BE SUFFICIENT TO ACCOMMODATE ATTACHMENT OF AT LEAST (15) 7/8-INCH
NOMINAL CABLES.
f. FULLY LOADED CABLE TRAY MUST BE SUFFICIENT TO WITHSTAND 229.4 POUNDS PER
SQUARE FOOT POSITIVE WIND PRESSURE, 243.6 POUNDS PER SQUARE FOOT NEGATIVE
PRESSURE, AND 252.42 POUNDS PER SQUARE FOOT LATERAL WIND PRESSURE.
g. FULLY LOADED CABLE TRAY MUST BE SUFFICIENT TO WITHSTAND SEISMIC FORCES EQUAL
TO 0.50 TIMES GRAVITY LOAD LATERALLY AND 1.74 TIMES GRAVITY LOAD VERTICALLY.
h. CABLE TRAY SPANS MUST BE 4 FEET MAXIMUM UNLESS OTHERWISE REQUIRED BY CABLE
TRAY SUPPLIER. CABLE TRAY SUPPLIER MAY EXTRAPOLATE FROM EXISTING 3RD PARTY
TESTING DATA TO DERIVE EQUIVALENT ALLOWABLE SPAN LOADS FOR 4-FOOT SPANS.
D. FOR ROUTING AND ATTACHING CABLES LARGER THAN 1 INCH IN DIAMETER, CABLE LOCATIONS
WILL NEED TO BE SHIFTED OFF-CENTER AS SHOWN AND EVERY THIRD CABLE LOCATION
OMITTED. 1/2-INCH WIDE STAINLESS STEEL BANDING WITH A MINIMUM BREAKING STRENGTH OF
1,000 POUNDS IS RECOMMENDED.
14GI-T-001
14CC-TX508
10/04/2024
10/04/2024
10/04/2024 10/04/2024
9/24/2024
Approved By
CAPT Troy Brown, JRM J4
(SE
E G
EN
ER
AL
SH
EE
T N
OT
E C
CABLE TRAY ATTACHMENT BRACKET
(REFER TO SHEET 14CC-TX508)
VERTICAL CABLE TRAY (SEE
GENERAL SHEET NOTE C)
WALKING PLATFORM
STAINLESS STEEL STRAPPING WITH BAND
CLAMP (TYP, SEE GENERAL SHEET NOTE D)
A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.
B. ALL METAL IS STAINLESS STEEL UNLESS NOTED OTHERWISE.
C. CABLE TRAY REQUIREMENTS:
a. CABLE TRAY MUST BE STAINLESS STEEL TYPE 316 WITH A MINIMUM MATERIAL THICKNESS
OF 18 GAUGE.
b. CABLE TRAY MUST BE A MINIMUM OF 24 INCHES WIDE WITH A MINIMUM 4 INCH LOADING
DEPTH.
c. CABLE TRAY RUNGS MUST BE SPACED AT 6 INCHES ON CENTER.
d. CABLE TRAY MUST BE SUFFICIENT TO SUPPORT A MINIMUM OF (15) 7/8-INCH NOMINAL
CABLES WITH 1.102 INCH OUTSIDE DIAMETER AND WEIGHING 0.302 POUNDS PER FOOT.
e. CABLE TRAY RUNGS MUST HAVE MANUFACTURED SLOTS TO ACCOMMODATE
ATTACHMENT OF CABLES WITH STAINLESS STEEL BANDING. SLOTS MUST BE 3/4-INCH BY
7/16-INCH AND SPACED AT 1 INCH ON CENTER OR APPROVED ALTERNATIVE. QUANTITY OF
SLOTS MUST BE SUFFICIENT TO…
This is the start of the file's text. The full file is on GovTribe.