R-P693_Drawings_Final_Vol14.5_20241007.pdf

PDF 21 MB Posted

Attached to
FY25 MCON P-693 PDI: GUAM DEFENSE SYSTEM, COMMAND CENTER, JOINT REGION MARIANAS, GUAM
Solicitation number
N6274225R1301
Issued by

About this file

This file appears to be a comprehensive set of drawings (Volume 14.5) for solicitation N6274225R1301, which is for the construction of a Guam Defense Radar System Command Center and associated facilities at Joint Region Marianas, Guam.

The project, valued between $250-500 million, requires construction of a command center, power generation facility, switchgear building, fuel storage facility, and entry control facility. Key technical requirements include Risk Category IV seismic design with base isolation, 150-foot galvanized steel antenna tower, SSL-C security infrastructure, and complex control system integration. The contract includes five pre-priced options related to generators, fuel tanks, and uninterruptible power supply systems. The project has a 1,323-calendar-day completion period, with the RFP release scheduled for October 30, 2024. A pre-proposal site visit is scheduled for December 11, 2024, with base access request forms due by November 14, 2024. This unrestricted solicitation uses a best-value trade-off approach, with technical factors and past performance equally weighted and combined to be approximately equal to price.

View the file

Other files

File Type Posted
25-1301 CmdCtrl Notice14.pdf PDF
Am-0011 Attachments 25-44.pdf PDF
Am-0011 Attachment 1_Revised Drawings dtd 1-28-2025.pdf PDF
Am-0011.pdf PDF
Am-0011 Attachments 2-24.pdf PDF
25-1301 CmdCtrl Notice13.pdf PDF
25-1301 CmdCtrl Notice12.pdf PDF
25-1301 CmdCtrl Notice11.pdf PDF
Am-0010 Attachment 2_Revised Drawings_Signed.pdf PDF
Am-0010.pdf PDF
25-1301 CmdCtrl Notice10.pdf PDF
25-1301 CmdCtrl Notice9.pdf PDF
Attachment 1_Revised Drawings_dtd 13 and 20 Dec 2024.pdf PDF
Am-0009.pdf PDF
Am-0008.pdf PDF
25-1301 CmdCtrl Notice8.pdf PDF
P693_Sign-in Sheets_Redacted.pdf PDF
Am-0007.pdf PDF
Am-0007 Attachment 1_Revised Drawings dtd 13 Dec 2024.pdf PDF
Am-0006 Attachment 1_Revised Drawings dtd 6 Dec 2024.pdf PDF
Am-0006.pdf PDF
25-1301 CmdCtrl Notice7.pdf PDF
Am-0005 Attachment 1_Revised Drawings dtd 11-22-2024.pdf PDF
Am-0005.pdf PDF
25-1301 CmdCtrl Notice6.pdf PDF
25-1301 CmdCtrl Notice5.pdf PDF
R-P693_Drawings_Final_Vol14.6_20241007.pdf PDF
R-P693_Drawings_Final_Vol14.8_20241007.pdf PDF
R-P693_Drawings_Final_Vol14.2_20241007.pdf PDF
R-P693_Drawings_Final_Vol14.1_20241007.pdf PDF
25-1301 CmdCtrl Notice4.pdf PDF
R-P693_Drawings_Final_Vol14.7_20241007.pdf PDF
R-P693_Drawings_Final_Vol14.4_20241007.pdf PDF
Am-0004 Attachment 1_Revised Drawings dtd 11-15-2024.pdf PDF
25-1301 CmdCtr Notice3.pdf PDF
Am-0004.pdf PDF
Am-0003.pdf PDF
Am-0003 Attachment 1_Revised Drawings dtd 11-8-2024.pdf PDF
25-1301 CmdCtrl Notice2.pdf PDF
Am-0002.pdf PDF
Am-0001.pdf PDF
25-1301 CmdCtrl Notice1.pdf PDF
P693_Drawings_Final_Vol14.2_20241007-Part3.pdf PDF
P693_Drawings_Final_Vol14.1_20241007-Part3.pdf PDF
P693_Drawings_Final_Vol14.2_20241007-Part2.pdf PDF
P693_Drawings_Final_Vol14.7_20241007.pdf PDF
P693_Drawings_Final_Vol14.3_20241007.pdf PDF
25-1301 P-693 RFP.pdf PDF
P693_Specs_Final_Vol02_20241007.pdf PDF
P693_Drawings_Final_Vol14.6_20241007.pdf PDF
Show 40 more

Latest 50 of 63 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

07-OCT-2024

Approved By

CAPT Troy Brown, JRM J4 via email

9/24/2024

10/17/2024

07-OCT-2024

Approved By

CAPT Troy Brown, JRM J4 via email

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

SEE SHEET 14ST-TS105

FOR CONTINUATION

SEE SHEET 14ST-TS105

FOR CONTINUATION

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

01. 4 x 4" SCHEDULE 80 PVC CONDUIT GOING TO COMMUNICATION MAINTENANCE HOLE

TMH-14ST5003.

02. 2 x 4" SCHEDULE 80 PVC CONDUIT GOING TO COMMUNICATION HAND HOLE TMH-14ST5301.

14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

SEE SHEET 14ST-TS108

FOR CONTINUATION

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

01. 4 x 4" SCHEDULE 80 PVC CONDUIT GOING TO COMMUNICATION MAINTENANCE HOLE

TMH-14ST5102.

02. 6 x 4" SCHEDULE 80 PVC GOING TO ANTENNA TOWER. SEE ROUTING DETAIL A1 ON SHEET

14CC-TX202.

03. 4 x 4" SCHEDULE 80 PVC CONDUIT GOING TO COMMUNICATION MAINTENANCE HOLE

TMH-14ST5003.

04. 2 x 4" SCHEDULE 80 PVC CONDUIT GOING TO COMMUNICATION HAND HOLE TMH-14ST5301.

14GI-T-001

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

14CC-T-401

A1

14CC-T-401

C1

J J

J J J J J J J J

TYP

TYP

14CC-T-407

A1

14CC-T-406

A1

J J

J J

J J J J J J J J J

TYP

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.

C. PENETRATIONS INTO (ROOMS 158, 130, AND 135) MUST BE FIRE RATED.

D. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE

ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50.

E. WALL MOUNT OUTLETS IN ROOMS 150 - 158 MUST BE SURFACE MOUNTED; NO IN-WALL

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

F. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

SPECIFICATIONS.

G. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.

01. 4" D x 12" W BELOW FLOOR BASKET TRAY LATERAL WITH DIVIDER CREATING 8" AND 4" WIDE

SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.

02. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE

SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.

03. ENSURE RAF TILES ARE ALIGNED BETWEEN ROOMS SO UNDER FLOOR SUPPORTS ALLOW

EFFICIENT ROUTING OF CABLE.

04. FIELD ROUTE BELOW FLOOR J-HOOK OR OTHER NON-CONTINUOUS SUPPORT FROM BASKET

TRAY TO OUTLETS; MAX SUPPORT SEPARATION OF 5'.

05. 2"D x 6"W BELOW FLOOR BASKET TRAY FOR BACKBONE AND MISC. FIBER.

06. 2"D x 6"W BELOW FLOOR BASKET TRAY FOR RED COPPER CABLE.

14GI-T-001

14CC-T-40114CC-T-4011114 111 14CC-T-40114CC-T-4011114 111

14CC-T-40714CC-T-4071114 7777

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

14CC-T-40614CC-T-4061114 6666

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

14CC-T-403

TYP

J J

J JJ

J J

J JJJ

TYP.

14CC-T-407

A1

J J

J

J J

14CC-TX204

A3

14CC-TX512

A1

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.

C. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE

RATED.

D. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE

ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50.

E. WALL MOUNT OUTLETS IN ROOMS 150 - 158 MUST BE SURFACE MOUNTED; NO IN-WALL

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

F. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

SPECIFICATIONS.

G. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.

01. 4"D x 18" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATEING 3 x 6" WIDE SECTIONS.

FOR UNCLASSIFIED, CLASSIFIED, AND AV CABLES RESPECTIVELY.

02. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE

SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.

03. ENSURE RAF TILES ARE ALIGNED BETWEEN ROOMS SO UNDER FLOOR SUPPORTS ALLOW

EFFICIENT ROUTING OF CABLE.

04. 2" D X 6" W BELOW FLOOR BASKET TRAY FOR BACKBONE AND MISC. FIBER.

05. FIELD ROUTE BELOW FLOOR J-HOOK OR OTHER NON-CONTINUOUS SUPPORT FROM BASKET

TRAY TO OUTLETS; MAX SUPPORT SEPARATION OF 5'.

06. 4" D x 18" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 3 X 6" WIDE SECTIONS

FOR AV AND CLASSIFIED VOICE.

07. 4" D X 12" W BELOW FLOOR BASKET TRAY.

08. 2" D X 12" W VERTICAL LADDER TRAY.

09. 2" D X 12" W OVERHEAD HORIZONTAL LADDER TRAY.

10. MMF DROPS AT THESE TWO LOCATIONS WILL HOME BACK TO THE BLACK CABINET (AA1) IN

ROOM 135.

11. MMF DROPS AT THESE TWO LOCATIONS WILL HOME BACK TO THE BLACK CABINET (A1) IN

ROOM 124.

14GI-T-001

14CC-T-40714CC-T-4071114 7777

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

14CC-TX51214CC-TX512414 22214

14CC-T-40314CC-T-4031114 3333

14CC-TX20414CC-TX2044 044414

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

14CC-T-401

A3

14CC-T-401

C3

14CC-T-406

A1

14CC-T-407

A1

XFMR-14CC61101AXFMR-14CC61101B

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.

C. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE

RATED.

D. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE

ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50.

E. WALL MOUNT OUTLETS IN ROOMS 150 - 158 MUST BE SURFACE MOUNTED; NO IN-WALL

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON

14CC-T-505.

F. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

SPECIFICATIONS.

G. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.

01. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE

SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY

02. 4" D x 18" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 3 X 6" WIDE SECTIONS

FOR AV AND CLASSIFIED VOICE.

03. ENSURE RAF TILES ARE ALIGNED BETWEEN ROOMS SO UNDER FLOOR SUPPORTS ALLOW

EFFICIENT ROUTING OF CABLE

04. 2" D X 6" W BELOW FLOOR BASKET TRAY FOR BACKBONE AND MISC. FIBER.

05. 4" D X 12" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 2 X 6" WIDE SECTIONS

FOR CLASSIFIED VOICE CABLE.

06. 6" D X 20" W BELOW FLOOR BASKET TRAY WITH DIVIDERS CREATING ONE 12" AND 2 X 4" W

SECTIONS FOR UNCLASSIFIED, CLASSIFIED, AND AV CABLES RESPECTIVELY.

07. FIELD ROUTE 1 1/4" CONDUIT IN SLAB TO EQUIPMENT SHOWN (XFMR-14CC61101A TPR-A AND

XFMR-14CC61101B TPR-B) TO STUB OUT UNDERNEATH RAF WHERE FIBER CAN BE PULLED TO

BASKET TRAY NOTED ON KEYNOTE 4.

14GI-T-001

1114CC-T-40114CC-T-4011114 111 14CC-T-40114CC-T-4011114 111

14CC-T-40714CC-T-4071114 7777

14CC-T-505

14CC-T-40614CC-T-4061114 6666

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

14CC-T-405

TYP

14CC-T-404

A1

14CC-T-402

A1

14CC-T-403

A1

14CC-T-407

A1

J J JJ

J

J

J

J J

J J

J

J J

J

J J

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.

C. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158,130, AND 135) MUST BE FIRE

RATED.

D. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE

ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50.

E. WALL MOUNT OUTLETS IN ROOMS 150 - 158 MUST BE SURFACE MOUNTED; NO IN-WALL

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

F. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

SPECIFICATIONS.

G. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.

01. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 16" AND 4" WIDE

SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.

02. 4" D x 18" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 3 X 6" WIDE SECTIONS

FOR AV AND CLASSIFIED VOICE CABLE.

03. ENSURE RAF TILES ARE ALIGNED BETWEEN ROOMS SO UNDER FLOOR SUPPORTS ALLOW

EFFICIENT ROUTING OF CABLE.

04. 4" D x 12" W BELOW FLOOR BASKET TRAY.

05. 2" D X 6" W BELOW FLOOR BASKET TRAY FOR BACKBONE AND MISC. FIBER.

06. 6" D X 20" W BELOW FLOOR BASKET TRAY WITH DIVIDERS CREATING ONE 12" AND 2 X 4" W

SECTIONS FOR UNCLASSIFIED, CLASSIFIED, AND AV CABLES RESPECTIVELY.

07. FOR UNCLASSIFIED, CLASSIFIED, AND AV CABLES RESPECTIVELY. FOR UNCLASSIFIED,

CLASSIFIED, AND AV CABLES RESPECTIVELY.

08. 4" D X 12" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 2 X 6" WIDE SECTIONS

FOR CLASSIFIED VOICE CABLE.

09. FIELD ROUTE BELOW FLOOR J-HOOK OR OTHER NON-CONTINUOUS SUPPORT FROM BASKET

TRAY TO OUTLETS; MAX SUPPORT SEPARATION OF 5'.

14GI-T-001

14CC-T-40214CC-T-4021114 2222

14CC-T-40414CC-T-4041114 4444

14CC-T-40514CC-T-4051114 5555

14CC-T-40714CC-T-4071114 7777

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

14CC-T-40314CC-T-4031114 3333

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

01. 3/4" AC RATED FIRE-RATED BACKBOARD PAINTED ON ALL SIDES WITH RETARDANT PAINT, FIRE-

RATING LABELS WILL BE LEFT UNPAINTED. COLOR TO MATCH THE WALL.

02. 12" VERTICAL ALUMINUM LADDER TRAY.

03. 20" W ALUMINUM LADDER TRAY.

04. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE

SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.

05. 2" D x 6" W BELOW FLOOR BASKET TRAY.

06. SECONDARY BONDING BUSBAR, MOUNTED 7' 6" AFF.

07. TELECOMMUNICATIONS CABINET, SEE SHEET 14CC-T-401 FOR ADDITIONAL DETAIL.

08. 12" W ALUMINUM LADDER TRAY.

09. IESS VERTICAL RACK (SECURITY). SEE DETAIL C3 ON SHEET 14CC-TY502.

14GI-T-001

14CC-T-401

14CC-TY502

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

RATING LABELS WILL BE LEFT UNPAINTED. COLOR TO MATCH THE WALL.

02. 12" VERTICAL ALUMINUM LADDER TRAY.

03. 12" W ALUMINUM LADDER TRAY

04. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH 3 DIVIDERS CREATING 8" AND 3 x 4" WIDE

SECTIONS FOR UNCLASSIFIED, CLASSIFIED SECRET, CLASSIFIED TS, AND AV CABLES.

05. 2" D x 6" W BELOW FLOOR BASKET TRAY.

06. SECONDARY BONDING BUSBAR, MOUNTED 7' 6" AFF.

07. TELECOMMUNICATIONS CABINET, SEE SHEET 14CC-T-401 FOR ADDITIONAL DETAIL.

08. 3 X 4" CONDUIT STUBBED 1"-3" AFF AND 3"-6" BELOW RAF. CONDUIT MUST BE IN GROMMETED

SLOT IN A RAF TILE.

09. ESS VERTICAL CABINETS. SEE SHEET 14CC-TY114.

14GI-T-001

14CC-T-401

14CC-TY114

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

TYP.

PTFE COATED STEEL TABLE ON

STRUT REFER TO 14CC-S-790

WIRE MESH SUPPORT GRIP

REFER TO 14CC-TX511

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

01. 3/4" AC RATED FIRE-RATED BACKBOARD PAINTED ON ALL SIDES WITH RETARDANT PAINT, FIRE-

RATING LABELS WILL BE LEFT UNPAINTED. COLOR TO MATCH THE WALL.

02. 24" W ALUMINUM LADDER TRAY, MOUNTED 10' AFF.

03. 30" VERTICAL ALUMINUM LADDER TRAY.

04. 4"D x 20"W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE

SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.

05. 10 x 4" SCHEDULE 40 PVC SLEEVES. SEE SHEETS 14CC-T-104 AND 14CC-T-105 FOR CONDUIT

ENTRY.

06. CABLE PORT ENTRY. SEE DETAIL A1 SHEET 14CC-TX505 FOR MORE INFORMATION.

07. PRIMARY BONDING BUSBAR, MOUNTED 7' 6" AFF.

08. SECONDARY BONDING BUSBAR, MOUNTED 7' 6" AFF.

09. 24" VERTICAL ALUMINUM LADDER TRAY.

10. 18" W ALUMINUM LADDER TRAY, MOUNTED 9' AFF.

11. 6 x 4" SCHEDULE 80 PVC GOING TO ANTENNA TOWER. SEE ROUTING DETAIL A1 ON SHEET

14CC-TX202.

12. SECONDARY BONDING BUSBAR, MOUNTED 18" AFF.

13. WALL MOUNTED 19U CLASSIFIED DISTRIBUTION RACK (24" W X 24" D X 36" H).

14. 12" W VERTICAL ALUMINUM LADDER TRAY.

15. 12" W OVERHEAD ALUMINUM LADDER TRAY.

16. 4" D x 12" W BELOW FLOOR BASKET TRAY.

17. RUNWAY DROP OUT, SEE DETAIL A1 SHEET 14CC-T-501 FOR MORE INFORMATION.

14GI-T-001

14CC-T-104 14CC-T-105

14CC-T-501

14CC-TX505

14CC-TX511

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

TYP

01. TWO POST CHANNEL RACK 84" H (MIN X 23.75" 2 x 40" D.

02. VERTICAL CABLE MANAGER 76.94" H X 12.20" W x 15.07" D.

03. VERTICAL ALUMINUM LADDER TRAY 2" H x 12" W.

04. 4" H x 20" W ALUMINUM LADDER TRAY.

05. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH 1 DIVIDER CREATING 16" AND 4" WIDE SECTIONS

FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.

06. SECONDARY BONDING BUSBAR. MOUNTED AT 7' 6" AFF.

07. ESS VERTICAL CABINETS. SEE SHEET 14CC-TY114.

08. 12" W ALUMINUM LADDER TRAY.

09. 2" D x 6" W BELOW FLOOR BASKET TRAY.

10. IESS VERTICAL RACK (SECURITY). SEE DETAIL C3 ON SHEET 14CC-TY502.

14GI-T-001

14CC-TY502

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

RATING LABELS WILL BE LEFT UNPAINTED. COLOR TO MATCH THE WALL.

02. 24" W ALUMINUM LADDER TRAY, MOUNTED 10' AFF.

03. 30" VERTICAL ALUMINUM LADDER TRAY.

04. 4"D X 20"W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE

SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.

05. 10 X 4" SCHEDULE 40 PVC SLEEVES. SEE SHEETS 14CC-T-104 AND 14CC-T-105 FOR CONDUIT

ENTRY.

06. CABLE PORT ENTRY. SEE DETAIL A1 SHEET 14CC-TX505 FOR MORE INFORMATION.

07. 24" VERTICAL ALUMINUM LADDER TRAY.

08. 18" W ALUMINUM LADDER TRAY, MOUNTED 9' AFF.

09. 4"H X 6"W THERMOPLASTIC FIBER TROUGH.

10. 6 X 4" SCHEDULE 80 PVC GOING TO ANTENNA TOWER. SEE ROUTING DETAIL A1 ON SHEET

14CC-TX202.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

14GI-T-001

14CC-T-104 14CC-T-105

14CC-TX505

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

TYP.

TYP.

01. 3/4" AC RATED FIRE-RATED BACKBOARD PAINTED ON ALL SIDES WITH RETARDANT PAINT, FIRE-

RATING LABELS WILL BE LEFT UNPAINTED. COLOR TO MATCH THE WALL.

02. 30" VERTICAL ALUMINUM LADDER TRAY.

03. 24" VERTICAL ALUMINUM LADDER TRAY.

04. 18" W ALUMINUM LADDER TRAY, MOUNTED 9' AFF.

05. 24" W ALUMINUM LADDER TRAY, MOUNTED 10' AFF.

06. SECONDARY BONDING BUSBAR, MOUNTED 7' 6" AFF.

07. PRIMARY BONDING BUSBAR, MOUNTED 8' 6" AFF.

08. TELECOMMUNICATIONS CABINET, SEE SHEET 14CC-T-405 FOR ADDITIONAL DETAIL.

09. 10 x 4" SCHEDULE 40 PVC SLEEVES, SEE SHEET 14CC-T-203 FOR SLEEVE DETAIL.

10. 4" H x 6" W THERMOPLASTIC FIBER THROUGH.

11. CABLE PORT ENTRY. SEE DETAIL A1 SHEET 14CC-TX505 FOR MORE INFORMATION.

TYP.

14GI-T-001

14CC-T-203

14CC-T-405

14CC-TX505

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

RATING LABELS WILL BE LEFT UNPAINTED. COLOR TO MATCH THE WALL.

02. WALL MOUNTED 19U CLASSIFIED DISTRIBUTION RACK (24" W X 24" D X 36" H).

03. 12" W VERTICAL ALUMINUM LADDER TRAY.

04. 12" W OVERHEAD ALUMINUM LADDER TRAY.

05. 16" W OVERHEAD ALUMINUM LADDER TRAY.

06. SECONDARY BONDING BUSBAR.

14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

01. F/UTP CAT6A SHOULD BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURER

SPECIFICATIONS.

14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

01. F/UTP CAT6A SHOULD BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURER

SPECIFICATIONS.

14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

A2

A1 B1

B2A2

TYP

B3

B4 A4

A3

14CC-T-201

A1

14CC-T-201 C3

14CC-T-201

A3

14CC-T-201C1

A2A3A4A5A6A7A8A9A10

B6

A1

B7 B5 B4 B3 B2 B1B8B9

14CC-T-202

A1

14CC-T-202 C314CC-T-202C1

14CC-T-202

A3

BCS-14CC65011

B7 B6 B4B5 B3 B2 B1

A1A2A3A4A5A6A7A8A9A10

SPARE

B8B9

SPARE

BCS-14CC65011

A2

A1 B1

B2

A3

A4 B4

B3

SPARE

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. SEE SHEET 14CC-T-602 FOR TELECOMMUNICATIONS RACK IDENTIFICATION.

C. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.

D. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE

RATED. SEE DETAIL B3 SHEET 14CC-T-401.

E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE

ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50. SEE DETAIL B3 SHEET

14CC-T-401

F. WALL MOUNT OUTLETS IN ROOMS 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON

14CC-T-505.

G. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

SPECIFICATIONS.

01. 3/4" AC RATED FIRE-RATED BACKBOARD PAINTED ON ALL SIDES WITH RETARDANT PAINT, FIRE-

RATING LABELS WILL BE LEFT UNPAINTED. COLOR TO MATCH THE WALL.

02. TWO POST CHANNEL RACK 84" H MIN X 23.75" x 40" D. SEE DETAIL A3 SHEET 14CC-T-502.

03. VERTICAL CABLE MANAGER 76.94" H X 12.20" W x 15.07" D. SEE DETAIL C3 SHEET 14CC-T-502.

04. VERTICAL ALUMINUM LADDER TRAY 12" W.

05. 4" H x 20" W ALUMINUM LADDER TRAY.

06. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH 1 DIVIDER CREATING 16" AND 4" WIDE SECTIONS

FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.

07. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH 3 DIVIDERS CREATING 8" AND 3 x 4" WIDE

SECTIONS FOR UNCLASSIFIED, CLASSIFIED SECRET, CLASSIFIED TS, AND AV CABLES.

08. 3 x 4" CONDUIT STUBBED 1"-3" AFF AND 3"-6" BELOW RAF. CONDUIT MUST BE IN GROMMETED

SLOT IN A RAF TILE.

09. SECONDARY BONDING BUSBAR. MOUNTED AT 7' 6" AFF.

10. 12" W ALUMINUM LADDER TRAY.

11. 2" D x 6" W BELOW FLOOR BASKET TRAY.

14GI-T-001

14CC-T-201 14CC-T-201

14CC-T-201

14CC-T-201

14CC-T-202

14CC-T-20214CC-T-202

14CC-T-202

14CC-T-505

14CC-T-602

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

B. SEE SHEET 14CC-T-602 FOR TELECOMMUNICATIONS RACK IDENTIFICATION.

C. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.

D. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE

RATED.

E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE

ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50.

F. WALL MOUNT OUTLETS IN ROOMS 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

G. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

SPECIFICATIONS.

01. 12"W VERTICAL ALUMINUM LADDER TRAY.

02. 4" D x 12" W BELOW FLOOR BASKET TRAY.

14GI-T-001

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

14CC-T-602

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

14CC-T-203 A1

B. SEE SHEET 14CC-T-602 FOR TELECOMMUNICATIONS RACK IDENTIFICATION.

C. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.

D. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE

RATED. SEE DETAIL B3 SHEET 14CC-T-401.

E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE

ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50. SEE DETAIL B3 SHEET

14CC-T-401

F. WALL MOUNT OUTLETS IN ROOMS 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON

14CC-T-505.

G. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

SPECIFICATIONS.

01. 3/4" AC RATED FIRE-RATED BACKBOARD PAINTED ON ALL SIDES WITH RETARDANT PAINT.

COLOR TO MATCH THE WALL.

02. WALL MOUNTED 19U CLASSIFIED DISTRIBUTION RACK (24" W X 24" D X 36" H). SEE DETAIL C1

SHEET 14CC-T-502.

03. VERTICAL ALUMINUM LADDER TRAY 2" H x 12" W.

04. 4" D X 12" W OVERHEAD ALUMINUM LADDER TRAY.

05. 4" D X 16" W OVERHEAD ALUMINUM LADDER TRAY (PLAN WEST LADDER TRAY THAT RUNS PLAN

NORTH TO SOUTH).

06. SECONDARY BONDING BUSBAR. SEE DETAIL C1 SHEET 14CC-EG501.

14GI-T-001

14CC-T-203

14CC-T-401

14CC-T-401

14CC-T-505

14CC-T-602

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

AE1

AE2

AE3

AE4

AE5

AE6

AE7

AE9

AB1

AB2

AB3

AB4

AB5

AB6

AB7

AB8

AD1

AD2

AD3

AA4

AA5

AA6

AA7

AA8

AA9

AA3

AA2

AA1

AC2

AC3

AC4

AC5

BE1

BE2

BE3

BE4

BE5

BE6

BD1

BD2

BD3

BD4

BD5

BD7

BD8

BD9

BD10

BD11

BD12

BC1

BC2

BC3

BC4

BC5

BC6

BC7

BC8

BC9

BB1

BB2

BB3

BB4

BB5

BB6

BB7

BB8

BB9

BB10

BB11

BB12

BA1

BA2

BA3

BA4

BA5

BA6

BA7

BA8

BA9

BD6

BC10

BC11

BC12

AD4

AD6

AD7

AD5

AD8

AD9

AD10

AD11

AE10

AE11

AB9

AB10

AB11

BE7

BE8

BE9

BE10

BE11

BE12

SPARE

AC6

AC7

AC8

AC9

AC1

SPARE

SPARE

BA10

SPARE

AE8

SPARE

SPARE

SPARE

SPARE

BA11

SPARE

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. SEE SHEET 14CC-T-602 FOR TELECOMMUNICATIONS RACK IDENTIFICATION.

C. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.

D. PENETRATIONS INTO TELECOMMUICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE

RATED.

E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE

ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50.

F. WALL MOUNT OUTLETS IN ROOMS 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

G. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

SPECIFICATIONS.

01. 3/4" AC RATED FIRE-RATED BACKBOARD PAINTED ON ALL SIDES WITH RETARDANT PAINT.

COLOR TO MATCH THE WALL.

02. 4"D x 20"W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE

SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.

03. 2" D x 6"W BELOW FLOOR BASKET TRAY.

04. 4" D x 12" BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 2 x 6" WIDE SECTIONS FOR

CLASSIFIED VOICE CABLE.

05. 10 x 4" SCHEDULE 40 PVC SLEEVES. SEE SHEETS 14CC-T-104 AND 14CC-T-105 FOR CONDUIT

ENTRY.

14GI-T-001

14CC-T-104 14CC-T-105

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

14CC-T-602

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

AE1

AE3

AE2

AE4

AE5

AE6

AE7

AE9

AB1

AB3

AB2

AB4

AB5

AB6

AB7

AB8

AD1

AD2

AD3

AA4

AA5

AA6

AA7

AA8

AA9

AC2

AC3

AC4

AC5

BE1

BE2

BE3

BE4

BE5

BE6

BD1

BD2

BD3

BD4

BD5

BD7

BD8

BD9

BD10

BD11

BD12

BC1

BC2

BC3

BC4

BC5

BC6

BC7

BC8

BC9

BB1

BB3

BB2

BB4

BB5

BB6

BB7

BB8

BB9

BB10

BB11

BB12

BA1

BA2

BA3

BA4

BA5

BA6

BA7

BA8

BA9

BD6

AA1

AA2

AA3

TYP.

TYP.

TYP.

TYP.

AD4

AD6

AD7

AD9

AD8

AD10

AD11

AC1

AC9

AC8

AC7

AC6

AB9

AB10

AB11

BC10

BC11

BC12

BA10

BE7

BE9

BE8

BE10

BE11

BE12

AE10

AE11

AE8

SPARE

SPARE

SPARE

SPARESPARE

SPARE

SPARE

SPARE

SPARE

14CC-T-203

C1

14CC-T-203 C3

TYP.

TYP.

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. SEE SHEET 14CC-T-602 FOR TELECOMMUNICATIONS RACK IDENTIFICATION.

C. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.

D. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE

RATED. SEE DETAIL B3 SHEET 14CC-T-401.

E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE

ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50. SEE DETAIL B3 SHEET

14CC-T-401.

F. WALL MOUNT OUTLETS IN ROOMS 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

G. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

SPECIFICATIONS.

01. 3/4" AC RATED FIRE-RATED BACKBOARD PAINTED ON ALL SIDES WITH RETARDANT PAINT.

COLOR TO MATCH THE WALL.

02. TWO POST CHANNEL RACK 84"H (MIN) x 23.75" W x 40" D. SEE DETAIL A3 SHEET 14CC-T-502

03. VERTICAL CABLE MANAGER 76.94" H x 12.20" W x 15.07" D. SEE DETAIL C3 SHEET 14CC-T-502

04. VERTICAL CABLE MANAGER 76.94" H x 16.25" W x 15.07" D. SEE DETAIL A1 SHEET 14CC-T-502

05. 18" ALUMINUM LADDER TRAY.

06. 30" W VERTICAL LADDER TRAY.

07. 4" H x 6" W THERMOPLASTIC FIBER TROUGH.

08. OVERHEAD FIRE PENETRATION FOR ROUTING FIBER BETWEEN OVERHEAD LADDER TRAY IN

ROOM 135 TO ROOM 130.

14GI-T-001

14CC-T-203

14CC-T-203

14CC-T-401

14CC-T-401

14CC-T-502

14CC-T-502

14CC-T-502

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

14CC-T-602

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

BCS-14CC65011

JJJJJJJ

J J

TYP

J

14CC-T-401

C3

14CC-T-401

A3

TYPTYP

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. SEE SHEET 14CC-T-602 FOR TELECOMMUNICATIONS RACK IDENTIFICATION.

C. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.

D. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE

RATED. SEE DETAIL B3 SHEET 14CC-T-401.

E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUSTE BE

ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50. SEE DETAIL B3 SHEET

14CC-T-401.

F. WALL MOUNT OUTLETS IN ROOM 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON

14CC-T-505.

G. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

SPECIFICATIONS.

H. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.

01. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH 3 DIVIDERS CREATING 8" AND 3 x 4" WIDE

SECTIONS FOR UNCLASSIFIED, CLASSIFIED SECRET, CLASSIFIED TS, AND AV CABLES.

02. FIELD ROUTE BELOW FLOOR J-HOOK OR OTHER NON-CONTINUOUS SUPPORT FROM BASKET

TRAY TO OUTLETS; MAX SUPPORT SEPARATION OF 5'.

03. 2" D x 12" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 2 x 6" WIDE SECTIONS

FOR CLASSIFIED VOICE CABLE.

04. RF PENETRATION SEE DETAIL C1 ON SHEET 14CC-T-504.

14GI-T-001

14CC-T-4011114 111

14CC-T-4011114 111

14CC-T-401

14CC-T-401

14CC-T-504

14CC-T-505

14CC-T-602

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

CP CP

TYP

CP

J J

J J

J J

J J

J J

J J

J J

TYP

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. SEE SHEET 14CC-T-602 FOR TELECOMMUNICATIONS RACK IDENTIFICATION.

C. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.

D. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE

RATED. SEE DETAIL B3 SHEET 14CC-T-401.

E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE

ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50. SEE DETAIL B3 SHEET

14CC-T-401.

F. WALL MOUNT OUTLETS IN ROOMS 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON

14CC-T-505.

G. ALL SHIELDED CABLE MUST BE ROUNDED IN ACCORDANCE WITH CABLE MANUFACTURES

SPECIFICATIONS.

H. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.

01. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH ONE DIVIDER CREATING 16" AND 4" WIDE

SECTIONS FOR UNCLASSIFIED AND CLASSIFIED CABLES RESPECTIVELY.

02. FIELD ROUTE BELOW FLOOR J-HOOK OR OTHER NON-CONTINUOUS SUPPORT FROM BASKET

TRAY TO OUTLETS; MAX SUPPORT SEPARATION OF 5'.

03. 4" D x 18" W BELOW FLOOR BASKET TRAY LATERAL WITH DIVIDER CREATING 3 X 6" WIDE

SECTIONS FOR AV AND CLASSIFIED VOICE.

04. 2"D x 6"W BELOW FLOOR BASKET TRAY.

05. RAISED ACCESS FLOOR CP WITH 24 PORT (8P8C) CPP.

06. RAISED ACCESS FLOOR CP WITH 24 PORT DUPLEX LC MMF FOP.

07. RAISED ACCESS FLOOR CP WITH 24 PORT (8P8C) PATCH PANEL WITH GROUNDING FOR F/UTP

CABLE. 10 PAIRS OF 22 AWG SINGLE PAIR SHOULD ALSO BE PULLED TO THIS CP WITH

SERVICE LOOP FOR TERMINATION LATER BY OTHERS.

14GI-T-001

14CC-T-401

14CC-T-401

14CC-T-505

14CC-T-602

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

BOND EACH SECTION OF THE CABLE RUNWAY WITH 5/8" BONDING

CONDUCTOR TYPICAL FOR EACH SECTION OF RUNWAYBONDING CABLE RUNWAY

TO BONDING BUSBAR

TEBC

STAND OFF BRACKET TO

MAINTAIN BONDING/

COMMUNICATIONS CABLE

SEPARATION

EQUIPMENT RACK

VERTICAL MANAGEMENT

RBB, ONE PER CABINET/RACK

RBB

5/8" BONDING CONDUCTOR

RUNWAY RADIUS DROP,

CROSS MEMBER

RUNWAY

RUNWAY MOVABLE

CROSS MEMBER

MANUFACTURERS

SUGGESTED BONDING CLAMP

BONDING JUMPER 5/8" JACKETED

COPPER CONDUCTOR

1. REMOVE PAINT AT BOLTED BOND ATTACHMENT LOCATIONS AS NEEDED TO

ENSURE PROPER CONNECTION.

2. BONDING JUMPER TO BE FROM SAME MANUFACTURER AS CABLE / LADDER

TRAY TO MAINTAIN UL OR BRITISH STANDARD DETAILS.

GROUND LUG WALL

GROUNDING WIRE

GROUNDING LUG

CABLE TRAY

FIRE RATED PATHWAYS THRU-WALL FOR ACCESS TO CABLE

TRAY. ALL FIRE STOPS MUST BE FIRE PROOFED AS REQUIRED

BY ALL APPLICABLE CODES. REFER TO PLAN SHEETS OR

RISER DIAGRAMS FOR FIRE STOP REQUIREMENTS. FIRE

STOPS MUST BE SIZED TO MEET SAME CABLE FILL AS TRAY

SYSTEM.

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. REMOVE PAINT AT BOLTED BOND ATTACHMENT LOCATIONS AS NEEDED TO ENSURE PROPER

CONNECTION.

C. BONDING JUMPER TO BE FROM SAME MANUFACTURER AS CABLE LADDER TRAY TO MAINTAIN

UL STANDARD DETAILS.

14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

86" 84"

16" 23.75"

30"

40"

TOP VIEW

SIDE VIEW FRONT VIEW

3" DIA (2-1/2" CONDUIT)

KNOCKOUTS. 2 PLACES.

1.1" DIA (3/4" CONDUIT)

KNOCKOUTS. 2 PLACES.

9"W x 2.2"D KNOCKOUT

15.07" 16.25"

76.94"

15.07" 12.20"

76.94"

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. REMOVE PAINT AT BOLTED BOND ATTACHMENT LOCATIONS AS NEEDED TO ENSURE PROPER

CONNECTION.

C. BONDING JUMPER TO BE FROM SAME MANUFACTURER AS CABLE LADDER TRAY TO MAINTAIN

UL STANDARD DETAILS.

14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

15-1/8"

11-3/16"

6"

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

1-1/8" - 18 THD

STAINLESS STEEL

PLATE

1-5/32"

SECURE PLATE

TO FRAME, TYP.

FRAME

CONDUCTIVE TAPE

FOIL RF

SHEILDING, TYP.

TIGHTEN TO

MFR SPECIFIED

TORQUE RATING

CENTER WAVEGUIDE

IN STEEL PLATE

UNSECURED SIDE SECURED SIDE

GYPSUM WALLBOARDGYPSUM WALLBOARD

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. PREPARE THE STAINLESS STEEL PLATE BY BORING 1-5/32" DIAMETER MOUNTING HOLES IN THE

SPECIFIED LOCATIONS. ANY ADJACENT HOLES MUST BE NO CLOSER THAN 2".

C. CLEAN AND DE-BURR THE AREA AROUND THE MOUNTING HOLES.

D. INSERT THE BUSHING THROUGH THE MOUNTING HOLE, AND PLACE THE MOUNTING NUTS ON

EACH SIDE OF THE STAINLESS STEEL PLATE. CENTER THE BUSHING IN THE PLATE BY HOLDING

THE NUT AND ROTATING THE BUSHING UNTIL THERE ARE EQUAL THREADS ON BOTH SIDES.

E. TIGHTEN ONE OF THE MOUNTING NUTS TO MANUFACTURER SPECIFIED MAXIMUM TORQUE.

F. MOUNT PLATE TO WOOD FRAME.

G. OVERLAP STEEL PLATE WITH EXISTING RF SHIELDING, AND COVER SEEMS OF PLATE/WALL

WITH CONDUCTIVE TAPE.

01. STAINLESS STEEL PLATE SHOWN ON ACCOMPANYING DETAILS C3 AND A3

14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

1-1/4" EMT CONDUIT

THREADED TYPE STEEL

CONNECTOR BELOW JUNCTION BOX

CAT6 UTP PLENUM CABLES

6- PORT SINGLE GANG IVORY FACEPLATE

CATEGORY 6A

MODULAR JACK

SINGLE GANG PLASTER RING

PULL STRING 200LB TEST

4 11/16"H x 4 11/16"W x 2 1/8"D (MIN)

OUTLET BOX

LC-UPC MODULAR JACK OM4 MMF CABLE

W T

1 1/4" EMT CONDUIT

THREADED TYPE

STEEL CONNECTOR

PULL STRING

200 LB TEST

SINGLE GANG

PLASTER RING

CATEGORY 6A

MODULAR JACK

OM4 MMF CABLE

4 - PORT SINGLE

GANG WHITE FACEPLATE

BLANK LEER

LC-UPC MODULAR JACK

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

CAT6 UTP PLENUM CABLES

6- PORT SINGLE GANG IVORY FACEPLATE

CATEGORY 6A

MODULAR JACK

LC-UPC MODULAR JACK

OM4 MMF CABLE

CAT6 UTP PLENUM CABLES

6- PORT SINGLE GANG IVORY FACEPLATE

CAT6A MODULAR

JACK

LC-UPC MODULAR JACK

OM4 MMF CABLE

DB

CAT6A F/UTP

PLENUM CABLES

CAT6A SHIELDED

MODULAR JACK

BLANK

T

DR T

2 PORT SINGLE GANG

IVORY FACEPLATE

DB

DB

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

CAT6A UTP PLENUM CABLES

6- PORT SINGLE GANG IVORY FACEPLATE

CAT6A MODULAR

JACK

LC-UPC MODULAR JACK

OM4 MMF CABLE

DB

DR

DB

DR

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. CATEGORY 6A 8P8C DATA JACKS MUST BE TERMINATED T568A.

C. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE

RATED.

D. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE

ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50.

E. WALL MOUNT OUTLETS IN ROOMS 150-158 MUST BE SURFACE MOUNTED; NO IN-WALL

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

F. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTUERS

SPECIFICATIONS.

G. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.

14GI-T-001

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTUERS

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

RACK A1

SMF FOP

MMF FOP

CPP

RACK B1

SMF FOP

MMF FOP

RACK A1

SMF FOP

CPP

TE

SMF FOP

MMF FOP

RACK AA1-AA2

SMF FOP

MMF FOP

CPP

CABINET AB6

GFGI PP

RACK BA1-BA2

SMF FOP

MMF FOP

CPP

CABINET BA7

GFGI PP

24 SMF

144 MMF

144 SMF

48 SMF

48 SMF

48 SMF

CAT6A

UTP

OM4 MMF

OM4 MMF

CAT6A UTP

OM4 MMF

CAT6A UTP

22 AWG SINGLE

PAIR

OM4 MMF

CAT6A F/UTP

22 AWG SINGLE

PAIR

24 UTP

CAT6A 48 MMF

24 MMF

24 F/UTP

CAT6A

RACK B1

MMF FOP

CPP

GFGI PP

CAT6A F/UTP

SINGLE PAIR 22

AWG COPPER

OM4 MMF

GFGI PP

SINGLE PAIR 22

AWG COPPER

GFGI PP

GFGI PP

SINGLE PAIR 22

AWG COPPER

SINGLE PAIR 22

AWG COPPER

TYP

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. ALL INSIDE PLANT TELECOMMUNICATION CABLING IS REQUIRED TO BE PLENUM RATED.

C. CATEGORY 6A 8P8C DATA JACKS MUST BE ERMINATED T568A.

D. PENETRATIONS INTO TELECOMMUNICATION SPACES (ROOMS 158, 130, AND 135) MUST BE FIRE

RATED.

E. PENETRATIONS INTO ALL ROOMS, EXCEPT ROOMS SPECIFIED IN NOTE C, MUST BE

F. ACOUSTICAL PENETRATIONS WITH A MINIMUM STC RATING OF 50

G. WALL MOUNT OUTLETS IN ROOMS 150 - 158 MUST BE SURFACE MOUNTED; NO IN-WALL

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

H. ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

SPECIFICATIONS.

I. SEE SHEET 14CC-IF108 FOR EXACT FLOOR BOX LOCATIONS WITH FURNITURE.

J. SEE SHEET 14CC-T-221 AND 14CC-T-222 FOR RACK ELEVATIONS.

01. 3 x PLENUM UTP CAT6A, ROUTED THROUGH 1 1/4" CONDUIT TO WALL BOX OR J-HOOK UNDER

RAF TO FLOOR BOX.

02. SIX (6) STRAND PLENUM OM4 MMF, ROUTED THROUGH 1 1/4" CONDUIT TO WALL BOX OR J-HOOK

UNDER RAF TO FLOOR BOX.

03. 2" D x 6" W UNDERFLOOR BASKET TRAY. USED FOR BUILDING BACKBONE CABLING AND SPECIAL

DISTRIBUTION TO RM 107.

04. 4" D x 20" W UNDERFLOOR BASKET TRAY. USED FOR HORIZONTAL DISTRIBUTION FROM ROOM 124.

05. 6" D x 20" W UNDERFLOOR BASKET TRAY. USED FOR HORIZONTAL DISTRIBUTION FROM ROOM

135. ALSO HAS CHANNEL FOR AV BACKBONE CABLE, SEE TA SHEETS FOR AV RISER.

06. 4" D x 12" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 2 X 6" WIDE SECTIONS FOR

CLASSIFIED VOICE CABLE FROM ROOM 135.

07. 2" D X 6" W UNDERFLOOR BASKET TRAY. USED FOR HORIZONTAL DISTRIBUTION OF CLASSIFIED

COPPER FROM ROOM 124.

08. GFGI PATCH PANELS ARE INSTALLED AT A LATER DATE BY OTHERS. SINGLE PAIR 22 AWG

COPPER WIRE (SEE SPEC AND LEGEND) PLLED TO THE RACK SHOULD HAVE SERVICE LOOP

PLUS 25FT OF SPARE CABLE FOR INSTALLATION BY OTHERS.

09. 2" D x 12" W BELOW FLOOR BASKET TRAY WITH DIVIDER CREATING 2 x 6" WIDE SECTIONS FOR

CLASSIFIED VOICE CABLE FROM ROOM 158.

10. 4" D x 20" W BELOW FLOOR BASKET TRAY WITH 3 DIVIDERS CREATING 8" AND 3 x 4" WIDE

SECTIONS FROM UNCLASSIFIED, CLASSIFIED SECRET, CLASSIFIED TS, AND AV CABLES FROM

ROOM 158.

11. OVERHEAD LADDER TRAY, PATH BETWWEN ROOM 130 AND 135.

14GI-T-001

14CC-T-222

CONDUIT/J-BOX. ALL OTHER SPACES WILL HAVE IN-WALL CONDUIT/J-BOX AS SHOWN ON 14CC- T-505.

ALL SHIELDED CABLE MUST BE GROUNDED IN ACCORDANCE WITH CABLE MANUFACTURERS

14CC-T-221

10/04/2024

10/04/2024

10/04/2024

10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

PBB

SBB

SBB

SBB

RM 130

RM 124

RM 158

RM 135

TO MGB IN A RM 144

SEE SHEET 14CC-EG601 FOR RISER CONTINUATION

SBB RM 132

SBB

SBB

SBB

SUS-GB

RM 103

RM 105

RM 135

PBB

#6 (MIN.)

#6 (MIN.)

#6 (MIN.)

#6 (MIN.)

#6 (MIN.)

#6 (MIN.)

#6 (MIN.) METALLIC WALL CONDUIT STUB OUTS AND FIRESTOPPING

BUILDING STEEL

LADDER RACK

DEDICATED COMM ROOM PANELBOARD

METALLIC FLOOR CONDUIT STUB UPS AND FIRESTOPPING

UNDERFLOOR TRAY

RACK MOUNTED GROUNDING BUSBAR (TYPICAL FOR EACH RACK)TO MGB IN RM 144

SEE SHEET 14CC-EG601 FOR RISER CONTINUATION

RM 135

SBB

#6 (MIN.)

#6 (MIN.)

#6 (MIN.)

#6 (MIN.)

#6 (MIN.)

#6 (MIN.)

#6 (MIN.) METALLIC WALL CONDUIT STUB OUTS AND FIRESTOPPING

BUILDING STEEL

LADDER RACK (IF APPLICABLE)

UNDERFLOOR TRAY (IF APPLICABLE)

DEDICATED COMM ROOM PANELBOARD

METALLIC FLOOR CONDUIT STUB UPS AND FIRESTOPPING

RACK MOUNTED GROUNDING BUSBAR (TYPICAL FOR EACH RACK)TO PBB IN RM 135

SEE SHEET 14PP-T-603/C1 FOR RISER

CONTINUATION

RM 124 / RM 158 / RM 130 / RM 132 / RM 105 / RM 103

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

01. TELECOMMUNICATIONS BONDING BACKBONE, SIZE BONDING CONDUCTOR IN ACCORDANCE

WITH TIA-607-D.

02. TELECOMMUNICATIONS BONDING CONDUCTOR, SIZE BONDING CONDUCTOR IN ACCORDANCE

WITH TIA-607-D.

14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

14CC-TX401

14CC-TX506

A1

14CC-TX402

A1

14CC-TX204

A3

14CC-TX512

A1

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001

14CC-TX40114CC-TX4011144 0111

14CC-TX40214CC-TX4021144 0222

4CC-TX506414CC-TX50614CC-TX506144111114 0666

14CC-TX51214CC-TX5124 22214

04TX20404441414CC-14

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

(TY

P.)

SATCOM ANTENA MOUNT, TYP.

SEE SHEET 14CC-TX503/504 FOR MORE INFORMATION.

RF CABLE HATCH

(TYP)

CATWALK

(TYP)

14CC-TX204

A3

14CC-TX512

A1

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001

14CC-TX503/

14CC-TX51214CC-TX51222214

14CC-TX20414CC-TX20411414 0444

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

SATCOM ANTENNA MOUNT, TYP.

SEE SHEET 14CC-TX503/504 FOR MORE INFORMATION.

CATWALK

(TYP)

ROOF ACCESS

STAIRS

RF CABLE HATCH

(TYP)

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001

14CC-TX503/

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

ROOFTOP CATWALK (TYP.)

VERTICAL CABLE TRAY

14CC-TX203

A3

14CC-TX204

A1

14CC-TX506

A1

RF CABLING HATCH

OPS FLOOR

ACCESS STAIRS

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

SATCOM ANTENNA MOUNT, TYP.

SEE SHEET 14CC-TX503/504 FOR MORE INFORMATION.

14GI-T-001

14CC-TX503/

14CC-TX50614CC-TX506066614

14CC-TX20314CC-TX203033314

14CC-TX20414CC-TX2041144 0444

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

TOWER

1/2" SUPERFLEX

COAXIAL CABLE

RACK, TYP.

4" CONDUIT

PTFE COATED STEEL TABLE ON

STRUT REFER TO 14CC-S-790

GROUND BAR.

REFER TO EG115

CONNECTOR

TRANSITION

CABLE ENTRY

PORTRADIO

INSTALLATION OF COAX SHOULD NOT EXCEED

MANUFACTURER RECOMMENDED BEND RADIUS.

3' ADDITIONAL SLACK ON SUPPORT

TABLE REFER TO 14CC-TX401

WIRE MESH SUPPORT GRIP

REFER TO 14CC-TX511

REFER TO

14CC-TX511

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

01. WORK TO BE EXECUTED BY OTHERS.

14GI-T-001

14CC-TX40114CC-TX401

14CC-TX511111

14CC-TX511

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

10' X 9' PTFE COATED SUPPORT

TABLE ON STRUT - REFER TO

14CC-S-790.

3' ADDITIONAL SLACK ON SUPPORT

TABLE. REFER TO 14CC-TX401.

WIRE MESH SUPPORT GRIP

REFER TO 14CC-TX511

6'-4" VERTICAL CONDUIT

COAXIAL CABLE

6'-4" VERTICAL CONDUIT

SATCOM ANTENNA MOUNT, TYP.

VERTICAL CABLE TRAY.

SEE SHEET TO 14CC-TX503/504

FOR MORE INFORMATION.

CABLE PORT ENTRY. SEE SHEET

14CC-TX505 FOR MORE

INFORMATION.

VERTICAL CABLE TRAY. SEE

SHEET 14CC5-TX506 FOR MORE

INFORMATION.

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

01. WORK TO BE EXECUTED BY OTHERS.

14GI-T-001

14CC-TX401

14CC-TX503/

14CC-TX505

14CC-TX511

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

VERTICAL CABLE TRAY.

SEE SHEET 14CC-TX507

FOR MORE INFORMATION.

VERTICAL CABLE TRAY. SEE SHEET

14CC-TX512 FOR MORE INFORMATION.

CABLE PORT ENTRY. SEE SHEET 14CC-

TX505 FOR MORE INFORMATION

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.14GI-T-001

CABLE PORT ENTRY. SEE SHEET 14CC-

TX505 FOR MORE INFORMATION14CC-TX512

14CC-TX507

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

14CC-TX203 A1 14CC-TX203

3 1

10'X9' PTFE COATED STEEL TABLE

ON STRUT SEE 14CC-S-790.

3' OF SLACK LAID ON

TABLE

14CC-TX506

A1

TOWER

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

01. WORK TO BE EXECUTED BY OTHERS.

14GI-T-001

14CC-TX50614CC-TX5064 066614

14CC-TX203 4CC-TX2034CC-TX2034 033341

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

B. PENETRATIONS BETWEEN ROOMS 103, 104, AND 105 MUST BE ACOUSTICAL PENETRATIONS

WITH A MINIMUM STC RATING OF 50.

01. 2"D X 6"W HORIZONTAL BASKET TRAY ABOVE DROP CEILING.

02. CABLE TRAY MUST BE GROUNDED PER MANUFACTURER RECOMMENDATIONS AND AS SHOWN

IN 14CC-T501.

03. CABLE PORT ENTRY. SEE SHEET 14CC-TX505 FOR MORE INFORMATION

14GI-T-001

14CC-TX505

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

20'

40'

60'

80'

100'

120'

140'

160'

TOP OF NEW TOWER

ELEVATION 150'-0" +/- AGL

PROPOSED AIR TERMINAL (SEE GENERAL SHEET NOTE D)

TIP ELEVATION 160'-0" +/- AGL

PROPOSED L-864/L-865 TOP OF TOWER BEACON (SEE GENERAL SHEET NOTE C)

TIP ELEVATION PER TOWER MANUFACTURER

MOUNT ELEVATION 150'-0" +/- AGL

BEACON ELEVATION 153'-0" +/- AGL

A3

14CC-TX501

PROPOSED INTERMIEDIATE L-810 MARKERS

(SEE GENERAL SHEET NOTE E)

SEE SHEET 14CC-S-792 FOR

FOUNDATION DETAILS

TOP OF TOWER L-864/L-865 BEACON

(SEE GENERAL SHEET NOTE C)

AIR TERMINAL (SEE

GENERAL SHEET NOTE D)

L-810 MARKER LIGHTS (SEE

GENERAL SHEET NOTE E)

MARKER INTERFACE ENCLOSURE

(OPTIONAL DEPENDENT UPON MFR)

L864/L-865 BEACON

(SEE GENERAL SHEET NOTE C)

PROPOSED AIR TERMINAL

(SEE GENERAL SHEET NOTE D)

L-810 MARKERS PLACED AT 75' (MAY BE INSTALLED HIGHER

IF SURROUDNING OBJECTS WOULD OBSCURE LIGHTS), TYP.

(SEE GENERAL SHEET NOTE E)

TO SITE

POWER

PHOTODIODE

GROUND

CONTROL UNIT

GPS ANTENNA

(OPTIONAL)

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. PROPOSED TOWER IS DESIGNED AND FABRICATED BY TOWER MANUFACTURER. CONTRACTOR

MUST REFER TO TOWER MANUFACTURER DESIGN PACKAGE FOR MORE DETAILS.

C. TOP OF TOWER BEACON MUST BE FAA CERTIFIED L-864/L-865 DUAL RED/WHITE MEDIUM

INTENSITY FLASHING BEACON AND IS TO BE MOUNTED TO TOP OF TOWER LEG PER TOWER

MANUFACTURER USING THE SUPPLIED BEACON MOUNT. SELECTED TOWER LEG MUST HAVE

THE TOWER MANUFACTURER SUPPLIED CLIMBING PATH AND SAFETY CLIMB CABLE INSTALLED

TO PERMIT EASE OF ACCESS.

D. PROPOSED AIR TERMINAL MUST BE INSTALLED AT THE TOP OF A TOWER LEG NOT SHARED BY

THE TOP OF TOWER BEACON. ATTACH TO TOWER PER TOWER MANUFACTURER.

E. THREE INTERMEDIATE L-810 MARKERS LOCATED APPROXIMATELY AT MIDPOINT OF TOWER,

ONE PER TOWER LEG. MUST FLASH IN UNISON WITH L-864/L-865 TOP OF TOWER BEACON.

F. TOWER MANUFACTURER IS TO ASSUME THAT TOWER PAINTING IN ACCORDANCE WITH FAA

ADVISORY CIRCULAR 70/7460-1M IS REQUIRED.

14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

WAVEGUIDE LADDER ROUTED TO

TOP OF TOWER

WAVEGUIDE LADDER ROUTED TO TOP OF TOWER,

ADJUST OFFSET ALONG TOWER FACES TO ALIGN

WITH ROUTING OF CABLES FROM THE COMMAND

CENTER

EXAMPLE CABLING, RECOMMENDED

ATTACHMENT TO WAVEGUIDE LADDER

ARE STAINLESS STEEL SNAP-IN

HANGERS AT 3FT SPACING.

INTERIOR CLIMBING LADDER

( SEE GENERAL SHEET NOTE D)

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. PROPOSED TOWER IS DESIGNED AND FABRICATED BY TOWER MANUFACTURER. CONTRACTOR

MUST REFER TO TOWER MANUFACTURER DESIGN PACKAGE FOR MORE DETAILS.

C. WORK TO BE DONE BY OTHERS.

D. INTERIOR CLIMBING LADDER TO BE ATTACHED TO TOWER PER TOWER MANUFACTURER.

LOCATION OF CLIMBING LADDER MAY BE INSTALLED OFFSET FROM ANY TOWER LEG TO BEST

ACCOMODATE FUTURE INSTALLATION OF CABLING.

E. FOR TOWER GROUNDING DETAILS, REFER TO SHEET 14CC-EG504

14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

5/8" DIA. HEAVY HEX HEADED ANCHOR BOLT,

STAINLESS STEEL, MINIMUM 6" CONCRETE

EMBEDMENT WITH MINIMUM 2-1/2" THREADED

PROJECTION

CONCRETE RING BEAM

SURFACE MOUNTED PLATE

HSS ARMS (TYP 2)

SATCOM ANTENNA TO BE

PROVIDED BY THE CUSTOMER

U-BOLT

(TYP 4)

SS HSS4-1/2" x 3/8"

U-BOLT

ATTACHMENT

PLATE (TYP 2)

TYP 2 PLCS5/16

TYP 2 PLCS

U-BOLT

ATTACHMENT

PLATE (TYP 2)

HSS ROUND TUBE

CONCRETE RING BEAM

SURFACE MOUNTED PLATE

HSS ARMS (TYP 2)

U-BOLT

(TYP 4)

5/16

(1/4) (1/4) 2

SS SHEAR STOP

PL2" x 2" x 1/4"

SS TEMPLATE PL12" x 17-1/4" x 1/4"

(SEE GENERAL SHEET NOTE D)

(SE

E G

EN

ER

AL

SH

EE

T N

OT

E C

(SEE GENERAL

SHEET NOTE C)

CAST-IN-PLACE

HEADED ANCHORS

(TYP 6)

#6 HORIZONTAL BARS

#4 @ 6" STIRRUPS

4 - #8#4 U BAR @ 8" OCTEMPLATE PLATE

#4 U BAR @ 8" OC

#6 @ 8" OC MAX

#4 U BAR

#4 STIRRUP

(4) - #8, TOP AND

BOTTOM, NOT

FULLY SHOWN

#6 @ 8" OC MAX

COMPOSITE SLAB

REINF REFER TO

OTHER DETAILS

RING BEAM EDGE

(WHERE APPLICABLE)

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. ALL METAL IS STAINLESS STEEL UNLESS NOTED OTHERWISE.

C. MINIMUM DISTANCES FROM EDGE OF SURFACE MOUNTED PLATE TO ANY EDGE OF THE

CONCRETE RING BEAM MUST BE HORIZONTALLY 11-1/2" AND VERTICALLY 6".

D. DIMENSIONS AND LAYOUT OF ANCHOR BOLT HOLES IN TEMPLATE PLATE TO MATCH SURFACE

MOUNTED PLATE AS SHOWN ON SHEET 14CC-TX504. PLATE THICKNESS MUST BE 1/4".

ADDITIONAL HOLES IN TEMPLATE PLATE MAY BE DRILLED TO ACCOMODATE ASSEMBLY OF

RING BEAM'S REBAR CAGE.

14GI-T-001

14CC-TX504

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

SS HSS4" x 4" x 1/2"

HSS ARM DETAIL

U-BOLT CONNECTION PLATE DETAIL

11/16" DIA. BOLT HOLES

(TYP 4)

HSS ARMS WELDED TO

CENTER OF U-BOLT

CONNECTION PLATE

SS PL7-1/2" x 7-1/2" x 5/8"

SURFACE MOUNTED PLATE DETAIL

SS PL1'-0" x 1'-5 1/4" x 1"

11/16" DIA. (TYPE 6 PLCS) SS HEAVY HEX NUT FOR 5/8" BOLT

SS COMPRESSIBLE-WASHER-TYPE DIRECT TENSION INDICATOR

(SEE STRUCTURAL STEEL CONNECTION NOTES ON SHEET 14CC-S-006)

SS FLAT WASHER FOR 5/8" BOLT

5/8" DIA. SS U-BOLT

U-BOLT DETAIL

HEAVY HEX STUDDED ANCHOR

MINIMUM THREADED PROJECTION

SURFACE OF CONCRETE RING BEAM

CONCRETE

EMBEDMENT

SS HEAVY HEX HEADED

ANCHOR BOLT

TEMPLATE PLATE

SS HEAVY HEX NUT FOR 5/8" BOLT

SS FLAT WASHER FOR 5/8" BOLT

SS HEAVY HEX NUT FOR 5/8" BOLT

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. ALL METAL IS STAINLESS STEEL UNLESS NOTED OTHERWISE.

C. MINIMUM DISTANCES FROM EDGE OF SURFACE MOUNTED PLATE TO ANY EDGE OF THE

CONCRETE RING BEAM MUST BE HORIZONTALLY 11-1/2" AND VERTICALLY 6".

D. DIMENSIONS AND LAYOUT OF ANCHOR BOLT HOLES IN TEMPLATE PLATE TO MATCH SURFACE

MOUNTED PLATE AS SHOWN ON SHEET 14CC-TX504. PLATE THICKNESS MUST BE 1/4".

ADDITIONAL HOLES IN TEMPLATE PLATE MAY BE DRILLED TO ACCOMODATE ASSEMBLY OF

RING BEAM'S REBAR CAGE.

14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

SCREW

FINISHING WASHER

DRILL PILOT HOLES FOR

MOUNTING SCREWS

USE MANUFACTURER RECOMMENDED

SEALANT AROUND EDGES

BUILDING

EXTERIOR WALL

ENTRY PANELS EXTERIOR

WALL OF BUILDING

3X4 CABLE ENTRY PORT

BOOT ASSEMBLY AND

CABLE INSTALLATION

TO BE DONE BY

OTHERS

MAXIMUM FOUR (4) 7/8"

CABLES PER 4" ENTRY

SCREW

FINISHING WASHER DRILL PILOT HOLES FOR

MOUNTING SCREWS

USE MANUFACTURER RECOMMENDED

SEALANT AROUND EDGES

BUILDING

EXTERIOR WALL

ENTRY PANELS EXTERIOR

WALL OF BUILDING

1X1 CABLE ENTRY PORT

BOOT ASSEMBLY AND

CABLE INSTALLATION

TO BE DONE BY

OTHERS

BOOT ASSEMBLY FOR

SINGLE 7/8" CABLE

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. LOCATE, PREPARE EXISTING OPENING AND INSTALL A NEW 24 HOLE ENTRY PORT PANEL AT

EXISTING SHELTER. INSTALL AND WEATHERPROOF PORT IN ACCORDANCE WITH

MANUFACTURER'S ASSEMBLY GUIDE.

C. PRIOR TO INSTALLING THE ENTRY PORT PANEL, THE CONTRACTOR MUST ENSURE THAT THE

LOCATION WILL NOT INTERFERE WITH ANY EQUIPMENT/ MATERIAL INSIDE THE SHELTER.

D. DO NOT COVER ANY EQUIPMENT WITH PLASTIC.

E. DO NOT ALLOW ANY OUTSIDE DEBRIS OR WATER TO ENTER THE SHELTER WHILE INSTALLING

THE NEW ENTRY PORT.

F. REMOVE ALL DUST AND DEBRIS, ETC. FROM THE SHELTER WHEN CONTRACTOR IS

COMPLETED.

G. IF A SHUT-DOWN OF THE EQUIPMENT OCCURS DUE TO A SUBCONTRACTOR ERROR AND NOT

FOLLOWING PROCEDURE, THE SUBCONTRACTOR WILL BE HELD RESPONSIBLE.

H. PROPOSED ENTRY PORT PANEL MUST BE GROUNDED TO PROPOSED MAIN GROUND BUS BAR.

14GI-T-001

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

MI

N.

(SE

E G

EN

ER

AL

SH

EE

T N

OT

E C

CABLE TRAY ATTACHMENT BRACKET

(REFER TO SHEET 14CC-TX508)

VERTICAL CABLE TRAY (SEE

GENERAL SHEET NOTE C)

1" MINIMUM FROM

BOTTOM OF CABLE

TRAYS TO CABLE

ENTRY PORTS.

(TYP.)

STAINLESS STEEL STRAPPING WITH BAND

CLAMP (TYP, SEE GENERAL SHEET NOTE D)

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. ALL METAL IS STAINLESS STEEL UNLESS NOTED OTHERWISE.

C. CABLE TRAY REQUIREMENTS:

a. CABLE TRAY MUST BE STAINLESS STEEL TYPE 316 WITH A MINIMUM MATERIAL THICKNESS

OF 18 GAUGE.

b. CABLE TRAY MUST BE A MINIMUM OF 24 INCHES WIDE WITH A MINIMUM 4 INCH LOADING

DEPTH.

c. CABLE TRAY RUNGS MUST BE SPACED AT 6 INCHES ON CENTER.

d. CABLE TRAY MUST BE SUFFICIENT TO SUPPORT A MINIMUM OF (15) 7/8-INCH NOMINAL

CABLES WITH 1.102 INCH OUTSIDE DIAMETER AND WEIGHING 0.302 POUNDS PER FOOT.

e. CABLE TRAY RUNGS MUST HAVE MANUFACTURED SLOTS TO ACCOMMODATE

ATTACHMENT OF CABLES WITH STAINLESS STEEL BANDING. SLOTS MUST BE 3/4-INCH BY

7/16-INCH AND SPACED AT 1 INCH ON CENTER OR APPROVED ALTERNATIVE. QUANTITY OF

SLOTS MUST BE SUFFICIENT TO ACCOMMODATE ATTACHMENT OF AT LEAST (15) 7/8-INCH

NOMINAL CABLES.

f. FULLY LOADED CABLE TRAY MUST BE SUFFICIENT TO WITHSTAND 229.4 POUNDS PER

SQUARE FOOT POSITIVE WIND PRESSURE, 243.6 POUNDS PER SQUARE FOOT NEGATIVE

PRESSURE, AND 252.42 POUNDS PER SQUARE FOOT LATERAL WIND PRESSURE.

g. FULLY LOADED CABLE TRAY MUST BE SUFFICIENT TO WITHSTAND SEISMIC FORCES EQUAL

TO 0.50 TIMES GRAVITY LOAD LATERALLY AND 1.74 TIMES GRAVITY LOAD VERTICALLY.

h. CABLE TRAY SPANS MUST BE 4 FEET MAXIMUM UNLESS OTHERWISE REQUIRED BY CABLE

TRAY SUPPLIER. CABLE TRAY SUPPLIER MAY EXTRAPOLATE FROM EXISTING 3RD PARTY

TESTING DATA TO DERIVE EQUIVALENT ALLOWABLE SPAN LOADS FOR 4-FOOT SPANS.

D. FOR ROUTING AND ATTACHING CABLES LARGER THAN 1 INCH IN DIAMETER, CABLE LOCATIONS

WILL NEED TO BE SHIFTED OFF-CENTER AS SHOWN AND EVERY THIRD CABLE LOCATION

OMITTED. 1/2-INCH WIDE STAINLESS STEEL BANDING WITH A MINIMUM BREAKING STRENGTH OF

1,000 POUNDS IS RECOMMENDED.

14GI-T-001

14CC-TX508

10/04/2024

10/04/2024

10/04/2024 10/04/2024

9/24/2024

Approved By

CAPT Troy Brown, JRM J4

(SE

E G

EN

ER

AL

SH

EE

T N

OT

E C

CABLE TRAY ATTACHMENT BRACKET

(REFER TO SHEET 14CC-TX508)

VERTICAL CABLE TRAY (SEE

GENERAL SHEET NOTE C)

WALKING PLATFORM

STAINLESS STEEL STRAPPING WITH BAND

CLAMP (TYP, SEE GENERAL SHEET NOTE D)

A. SEE SHEET 14GI-T-001 FOR GENERAL NOTES, AND LEGENDS.

B. ALL METAL IS STAINLESS STEEL UNLESS NOTED OTHERWISE.

C. CABLE TRAY REQUIREMENTS:

a. CABLE TRAY MUST BE STAINLESS STEEL TYPE 316 WITH A MINIMUM MATERIAL THICKNESS

OF 18 GAUGE.

b. CABLE TRAY MUST BE A MINIMUM OF 24 INCHES WIDE WITH A MINIMUM 4 INCH LOADING

DEPTH.

c. CABLE TRAY RUNGS MUST BE SPACED AT 6 INCHES ON CENTER.

d. CABLE TRAY MUST BE SUFFICIENT TO SUPPORT A MINIMUM OF (15) 7/8-INCH NOMINAL

CABLES WITH 1.102 INCH OUTSIDE DIAMETER AND WEIGHING 0.302 POUNDS PER FOOT.

e. CABLE TRAY RUNGS MUST HAVE MANUFACTURED SLOTS TO ACCOMMODATE

ATTACHMENT OF CABLES WITH STAINLESS STEEL BANDING. SLOTS MUST BE 3/4-INCH BY

7/16-INCH AND SPACED AT 1 INCH ON CENTER OR APPROVED ALTERNATIVE. QUANTITY OF

SLOTS MUST BE SUFFICIENT TO…