Am-0007.pdf
PDF 944 KB Posted
- Solicitation number
- N6274225R1301
About this file
This is Amendment 0007 to RFP N62742-25-R-1301 for the FY25 MCON P-693 PDI Guam Defense System Command Center project. The amendment updates multiple drawing sheets with new revisions dated 12/13/2024, including site layout plans, drainage details, utility details, command center floor plans, wall sections, plumbing plans, and mechanical schedules. It also adds a new section on mineral fiber blanket insulation and replaces existing sections on door hardware, HVAC instrumentation and control, utility monitoring and control systems, and concrete pavement. The amendment provides detailed hardware specifications for different door types, including hinges, locks, closers, strikes, and access control components. Special requirements are included for fire doors, security doors, and doors requiring specific access control. Hardware sets are defined for multiple door configurations throughout the facility with specific product requirements and operational descriptions for each set.
View the file
Other files
Show 40 more
Latest 50 of 63 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE
RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
1. CONTRACT ID CODE
2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
7. ADMINISTERED BY (If other than Item 6) CODE
STANDARD FORM 30 (REV. 11/2016)
Prescribed by GSA FAR (48 CFR) 53.243
FACILITY CODE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.
12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15C. DATE SIGNED
15A. NAME AND TITLE OF SIGNER (Type or print)
16C. DATE SIGNED
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
PAGE OF PAGES
6. ISSUED BY CODE
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)
CODE
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
Previous edition unusable
N62742-25-R-1301, FY25 MCON P-693 PDI: GUAM DEFENSE SYSTEM, COMMAND CENTER,
JOINT REGION MARIANAS, GUAM
Amendment No. 0007 is continued on page 2.
NAVFAC PACIFIC
CONSTR CONTRACTS BRANCH (CODE CON33)
258 MAKALAPA DR STE 100
JBPHH HI 96860-3134
N6274225R1301
1 4
12/16/2024
10/30/2024
RFP No. N6274225R1301
Amendment No. 0007
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SECTION 00 01 15.00 14 – LIST OF DRAWINGS
PARA 1.2 CONTRACT DRAWINGS: The following drawings, bearing revision date of 12/13/2024, supersede previously issued drawings bearing the same number and title. The revised drawings accompany this Amendment.
See Attachment (1).
NAVFAC
DWG NO.
SHEET NO.
REV
NO.
TITLE
17323245 14ST-CS105 1 SITE LAYOUT PLAN - PANEL B02
17323331 14ST-C-541 1 DRAINAGE DETAILS
17323332 14ST-C-542 1 DRAINAGE DETAILS
17323329 14ST-C-523 1 UTILITY DETAILS
17323726 14CC-A-111 1
COMMAND CENTER - FIRST FLOOR PLAN -
OVERALL
17323727 14CC-A-112 2 COMMAND CENTER - FIRST FLOOR PLAN - AREA A
17323728 14CC-A-113 1 COMMAND CENTER - FIRST FLOOR PLAN - AREA B
17323729 14CC-A-114 3 COMMAND CENTER - FIRST FLOOR PLAN - AREA C
17323730 14CC-A-115 1 COMMAND CENTER - FIRST FLOOR PLAN - AREA D
17323739 14CC-A-134 1
COMMAND CENTER - FIRST FLOOR REFLECTED
CEILING PLAN - AREA C
17323740 14CC-A-135 1
COMMAND CENTER - FIRST FLOOR REFLECTED
CEILING PLAN - AREA D
17323753 14CC-A-311 1 COMMAND CENTER - WALL SECTIONS
17323754 14CC-A-312 1 COMMAND CENTER - WALL SECTIONS
17323755 14CC-A-313 1 COMMAND CENTER - WALL SECTIONS
17323756 14CC-A-314 1 COMMAND CENTER - WALL SECTIONS
17323757 14CC-A-315 2 COMMAND CENTER - WALL SECTIONS
17323763 14CC-A-406 1
COMMAND CENTER - ENLARGED RESTROOM
PLAN
17323788 14CC-A-501 3 COMMAND CENTER - ARCH PARTITION TYPES
17323814 14CC-A-502 1 COMMAND CENTER - ARCH PARTITION TYPES
17323805 14CC-A-602 1 COMMAND CENTER - ROOM FINISH SCHEDULE
17323806 14CC-A-611 3 COMMAND CENTER - DOOR SCHEDULE
17323818 14CC-I-113 1
COMMAND CENTER - FIRST FLOOR FINISH PLAN -
AREA B
17323872 14CC-P-112 1
COMMAND CENTER - FIRST FLOOR PLUMBING
PLAN - AREA A
17323873 14CC-P-113 1
COMMAND CENTER - FIRST FLOOR PLUMBING
PLAN - AREA B
17323874 14CC-P-114 1
COMMAND CENTER - FIRST FLOOR PLUMBING
PLAN - AREA C
17323875 14CC-P-115 1
COMMAND CENTER - FIRST FLOOR PLUMBING
PLAN - AREA D
17323877 14CC-P-401 1 COMMAND CENTER - ENLARGED PLUMBING PLAN
17323890 14CC-P-911 1
COMMAND CENTER - PLUMBING DOMESTIC
WATER RISER DIAGRAM AREA - A
17323891 14CC-P-912 1
COMMAND CENTER - PLUMBING DOMESTIC
WATER RISER DIAGRAM AREA - B
NAVFAC
DWG NO.
SHEET NO.
REV
NO.
TITLE
17323892 14CC-P-913 1
COMMAND CENTER - PLUMBING DOMESTIC
WATER RISER DIAGRAM AREA - C
17323893 14CC-P-914 1
COMMAND CENTER - PLUMBING DOMESTIC
WATER RISER DIAGRAM AREA - D
17323918 14CC-M-707 1 COMMAND CENTER - MECHANICAL SCHEDULES
17324484 14PP-A-201 1 POWER PLANT - BUILDING ELEVATIONS
17324485 14PP-A-202 1 POWER PLANT - BUILDING ELEVATIONS
17324486 14PP-A-301 1 POWER PLANT - BUILDING SECTIONS
17324487 14PP-A-501 1 POWER PLANT - WALL SECTIONS
17324528 14PP-M-503 2 POWER PLANT - MECHANICAL DETAILS
17324586 14PP-EP651 1
POWER PLANT - ONE-LINE DIAGRAM – BREAKER
DETAILS
17324588 14PP-EP653 1
POWER PLANT - ONE-LINE DIAGRAM – BREAKER
DETAILS (SWGR A)
17324590 14PP-EP655 1
POWER PLANT - ONE-LINE DIAGRAM – BREAKER
DETAILS (SWGR B)
17324651 14PP-EI607 1
POWER PLANT - PCMS-14PP69201A - ENCLOSURE
BLOCK DIAGRAM
17324652 14PP-EI608 1
POWER PLANT - PCMS-14PP69201B - ENCLOSURE
BLOCK DIAGRAM
17324663 14PP-EI902 1 POWER PLANT - PCMS I/O LIST - SHEET 2
17324679 14PP-EI918 1 POWER PLANT - PCMS I/O LIST - SHEET 18
17324680 14PP-EI919 1 POWER PLANT - PCMS I/O LIST - SHEET 19
17324685 14PP-EI924 1 POWER PLANT - PCMS I/O LIST - SHEET 24
17324686 14PP-EI925 1 POWER PLANT - PCMS I/O LIST - SHEET 25
SECTION 07 21 16.00 14 – MINERAL FIBER BLANKET INSULATION
Add Section 07 21 16.00 14 – MINERAL FIBER BLANKET INSULATION (dtd 13DEC2024) in its entirety. This
Section accompanies this Amendment. See Attachment (2).
SECTION 08 71 00.00 14 – DOOR HARDWARE
Delete this Section in its entirety and replace with Section 08 71 00.00 14 – DOOR HARDWARE (dtd 13DEC2024).
The revised Section accompanies this Amendment. See Attachment (3).
SECTION 23 09 00.00 14 – INSTRUMENTATION AND CONTROL FOR HVAC
Delete this Section in its entirety and replace with SECTION 23 09 00.00 14 – INSTRUMENTATION AND
CONTROL FOR HVAC (dtd 13DEC2024). The revised Section accompanies this Amendment. See Attachment (4).
SECTION 25 10 10.00 14 – UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END
AND INTEGRATION
Delete this Section in its entirety and replace with SECTION 25 10 10.00 14 – UTILITY MONITORING AND
CONTROL SYSTEM (UMCS) FRONT END AND INTEGRATION (dtd 13DEC2024). The revised Section accompanies this Amendment. See Attachment (5).
SECTION 32 13 13.06 14 – PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SITE
FACILITIES
Delete this Section in its entirety and replace with SECTION 32 13 13.06 14 – PORTLAND CEMENT
CONCRETE PAVEMENT FOR ROADS AND SITE FACILITIES (dtd 13DEC2024). The revised Section accompanies this Amendment. See Attachment (6).
SECTION 32 15 00.00 14 – AGGREGATE SURFACING
Delete this Section in its entirety. This Section is no longer applicable to this project.
-- End of Amendment --
FY25 MDA Project 693 PDI: Guam Defense System, Command Center, 1812861 Andersen AFB, Guam
SECTION 07 21 16.00 14
MINERAL FIBER BLANKET INSULATION
08/23
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM C665 (2023) Standard Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing
ASTM C930 (2019) Standard Classification of Potential Health and Safety Concerns Associated with Thermal Insulation Materials and Accessories
ASTM D5359 (1998; R 2021) Standard Specification for Glass Cullet Recovered from Waste for Use in Manufacture of Glass Fiber
ASTM E84 (2023) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM E136 (2022) Standard Test Method for Assessing Combustibility of Materials Using a Vertical Tube Furnace at 750 Degrees C
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2017; Version 1.2) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 31 (2020; TIA 23-1) Standard for the Installation of Oil-Burning Equipment
NFPA 54 (2024) National Fuel Gas Code
NFPA 70 (2023; ERTA 4 2023; ERTA 5 2023; ERTA 6
2023) National Electrical Code
SECTION 07 21 16.00 14 Page 1
13 DECEMBER 2024
NFPA 211 (2019) Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
U.S. DEPARTMENT OF ENERGY (DOE)
Energy Star (1992; R 2006) Energy Star Energy Efficiency Labeling System (FEMP)
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.134 Respiratory Protection
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2022) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submittals not specifically identified with a building apply to all buildings and all miscellaneous site structures. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Blanket Insulation ; G
Recycled Content for Insulation Materials ; S
Energy Star Label for Insulation Materials ; S
Accessories
SD-07 Certificates
Indoor Air Quality for Adhesives ; S
SD-08 Manufacturer's Instructions
Insulation
1.3 CERTIFICATIONS
Submit required indoor air quality certifications and validations in one submittal package.
SECTION 07 21 16.00 14 Page 2
1.3.1 Insulation Products
Provide product certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification by other third-party programs. Provide current product certification from certification body.
1.3.2 Adhesives and Sealants
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party programs that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.4 DELIVERY, STORAGE, AND HANDLING
1.4.1 Delivery
Deliver materials to site in original sealed wrapping bearing manufacturer's name and brand designation, specification number, type, grade, R-value, and class. Store and handle to protect from damage. Do not allow insulation materials to become wet, soiled, crushed, or covered with ice or snow. Comply with manufacturer's recommendations for handling, storing, and protecting of materials before and during installation.
1.4.2 Storage
Inspect materials delivered to the site for damage; unload and store out of weather in manufacturer's original packaging. Store only in dry locations, not subject to open flames or sparks, and easily accessible for inspection and handling.
1.5 SAFETY PRECAUTIONS
1.5.1 Respirators
Provide installers with dust/mist respirators, training in their use, and protective clothing, all approved by National Institute for Occupational Safety and Health (NIOSH)/Mine Safety and Health Administration (MSHA) in accordance with 29 CFR 1910.134 .
1.5.2 Other Safety Concerns
Consider other safety concerns and measures as outlined in ASTM C930.
PART 2 PRODUCTS
2.1 BLANKET INSULATION
ASTM C665, Type I, blankets without membrane coverings and II, blankets with non-reflecting coverings; Class A, membrane-faced surface with a flame spread of 25 or less, except a flame spread rating of 25 or less and a smoke developed rating of 150 or less when tested in accordance with
ASTM E84.
SECTION 07 21 16.00 14 Page 3
Provide insulation with R-Value as indicated on drawings
2.1.1 Recycled Materials
Provide insulation materials containing the following minimum percentage of recycled material content by weight:
a. Fiberglass: 20 percent glass cullet complying with ASTM D5359
b. Mineral wool: 75 percent recovered materials content from slag
Provide data identifying percentage of recycled content for insulation materials .
2.1.2 Energy Star
Provide insulation materials that are Energy Star labeled. Provide data identifying Energy Star label for insulation materials .
2.1.3 Prohibited Materials
Do not provide asbestos-containing materials.
2.1.4 Reduced Volatile Organic Compounds (VOC) for Insulation Materials
Provide certification of indoor air quality for insulation materials .
2.2 BLOCKING
Wood, metal, unfaced mineral fiber blankets in accordance with ASTM C665, Type I, or other approved materials. Use only non-combustible materials meeting the requirements of ASTM E136 for blocking around chimneys and heat producing devices.
2.3 ACCESSORIES
2.3.1 Adhesive
As recommended by the insulation manufacturer. Provide non-aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) that meet either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168 . Provide aerosol adhesives used on the interior of the building that meet either emissions requirements of CDPH SECTION 01350 (use the office or classroom requirements, regardless of space type) or VOC content requirements of GS-36. Provide certification or validation of indoor air quality for adhesives .
2.3.2 Mechanical Fasteners
Corrosion resistant fasteners as recommended by the insulation manufacturer.
2.3.3 Wire Mesh
Corrosion resistant and as recommended by the insulation manufacturer.
SECTION 07 21 16.00 14 Page 4
PART 3 EXECUTION
3.1 EXISTING CONDITIONS
Before installing insulation, ensure that surfaces that will be in contact with the insulation are dry and free of projections which could cause voids, compressed insulation, or punctured vapor retarders. If moisture or other conditions are found that do not allow the workmanlike installation of the insulation, do not proceed but notify Contracting Officer of such conditions.
3.2 PREPARATION
3.2.1 Blocking at Attic Vents and Access Doors
Prior to installation of insulation, install permanent blocking to prevent insulation from slipping over, clogging, or restricting air flow through soffit vents at eaves.
3.2.2 Blocking Around Heat Producing Devices
Install non-combustible blocking around heat producing devices to provide the following clearances:
a. Recessed lighting fixtures, including wiring compartments, ballasts, and other heat producing devices, unless these are certified by the manufacturer for installation surrounded by insulation: 3 inches from outside face of fixtures and devices or as required by NFPA 70 and, if insulation is to be placed above fixture or device, 24 inches above fixture.
b. Masonry chimneys or masonry enclosing a flue: 2 inches from outside face of masonry. Masonry chimneys for medium and high heat operating appliances: Minimum clearances required by NFPA 211 .
c. Vents and vent connectors used for venting the products of combustion, flues, and chimneys other than masonry chimneys: Minimum clearances as required by NFPA 211 .
d. Gas Fired Appliances: Clearances as required in NFPA 54 .
e. Oil Fired Appliances: Clearances as required in NFPA 31 .
Blocking around flues and chimneys is not required when insulation blanket, including any attached vapor retarder, passes ASTM E136, in addition to meeting other requirements stipulated in Part 2. Blocking is also not required if the chimneys are certified by the manufacturer for use in contact with insulating materials.
3.3 INSTALLATION
3.3.1 Insulation
Install and handle insulation in accordance with manufacturer's instructions. Keep material dry and free of extraneous materials. Any materials that show visual evidence of biological growth due to presence of moisture must not be installed on the building project. Ensure personal protective clothing and respiratory equipment is used as required. Observe safe work practices.
SECTION 07 21 16.00 14 Page 5
3.3.1.1 Electrical wiring
Do not install insulation in a manner that would sandwich electrical conductors, that are not installed in conduit, between two layers of insulation.
3.3.1.2 Continuity of Insulation
Install blanket insulation to butt tightly against adjoining blankets and to studs, rafters, joists, sill plates, headers and any obstructions.
Where insulation required is thicker than depth of joist, provide full width blankets to cover across top of joists. Provide continuity and integrity of insulation at corners, wall to ceiling joints, roof, and floor. Avoid creating thermal bridges.
3.3.1.3 Installation at Bridging and Cross Bracing
Insulate at bridging and cross bracing by splitting blanket vertically at center and packing one half into each opening. Butt insulation at bridging and cross bracing; fill in bridged area with loose or scrap insulation.
3.3.1.4 Insulation without Affixed Vapor Retarder
Provide snug friction fit to hold insulation in place. Stuff pieces of insulation into cracks between trusses, joists, studs and other framing, such as at attic access doors, door and window heads, jambs, and sills, band joists, and headers.
3.3.1.5 Sizing of Blankets
Provide only full width blankets when insulating between trusses, joists, or studs. Size width of blankets for a snug fit where trusses, joists or studs are irregularly spaced.
3.3.1.6 Special Requirements for Ceilings
Place insulation under electrical wiring occurring across joists. Pack insulation into narrowly spaced framing. Do not block flow of air through soffit vents.
3.3.1.7 Special Requirements for Floors
Hold insulation in place with corrosion resistant wire mesh, wire fasteners, or wire lacing.
3.3.1.8 Access Panels and Doors
Affix blanket insulation to access panels greater than one square foot and access doors in insulated floors and ceilings. Use insulation with same R-Value as that for floor or ceiling.
-- End of Section --
SECTION 07 21 16.00 14 Page 6
SECTION 08 71 00.00 14
DOOR HARDWARE
02/16, CHG 4: 02/22
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM B117 (2019) Standard Practice for Operating Salt Spray (Fog) Apparatus
ASTM E283 (2019) Standard Test Method for Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen
ASTM F883 (2013; R 2022) Standard Performance Specification for Padlocks
STEEL DECK INSTITUTE (SDI)
ANSI/SDI A250.6 Reinforcing Standard Steel Doors and Frames
BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)
ANSI/BHMA A156.1 (2021) Butts and Hinges
ANSI/BHMA A156.2 (2022) Bored and Preassembled Locks and Latches
ANSI/BHMA A156.3 (2020) Exit Devices
ANSI/BHMA A156.4 (2013) Door Controls - Closers
ANSI/BHMA A156.5 (2020) Cylinder and Input Devices for Locks
ANSI/BHMA A156.6 (2021) Architectural Door Trim
ANSI/BHMA A156.7 (2016) Template Hinge Dimensions
ANSI/BHMA A156.8 (2021) Door Controls - Overhead Stops and Holders
ANSI/BHMA A156.10 (2017) Power Operated Pedestrian Doors
ANSI/BHMA A156.13 (2022) Mortise Locks & Latches Series 1000
ANSI/BHMA A156.14 (2013) Sliding and Folding Door Hardware
ANSI/BHMA A156.15 (2021) Release Devices Closer Holder, SECTION 08 71 00.00 14 Page 1
Electromagnetic and Electromechanical
ANSI/BHMA A156.16 (2023) Auxiliary Hardware
ANSI/BHMA A156.17 (2019) Self Closing Hinges & Pivots
ANSI/BHMA A156.18 (2020) Materials and Finishes
ANSI/BHMA A156.19 (2013) Power Assist & Low Energy Power Operated Doors
ANSI/BHMA A156.21 (2019) Thresholds
ANSI/BHMA A156.22 (2021) Gasketing
ANSI/BHMA A156.24 (2012) Delayed Egress Locking Systems
ANSI/BHMA A156.25 (2013) Electrified Locking Devices
ANSI/BHMA A156.26 (2012) Continuous Hinges
ANSI/BHMA A156.27 (2011) Power and Manual Operated Revolving Pedestrian Doors
ANSI/BHMA A156.28 2023 Recommended Practices for Mechanical Keying Systems
ANSI/BHMA A156.29 (2012) Exit Locks, Exit Alarms, Alarms for Exit Devices
ANSI/BHMA A156.30 (2014) High Security Cylinders
ANSI/BHMA A156.31 (2013) Electric Strikes and Frame Mounted Actuators
ANSI/BHMA A156.36 (2010) Auxiliary Locks
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023; ERTA 7 2023; TIA 23-15) National Electrical Code
NFPA 72 (2022; ERTA 22-1) National Fire Alarm and Signaling Code
NFPA 80 (2022) Standard for Fire Doors and Other Opening Protectives
NFPA 101 (2021; TIA 21-1) Life Safety Code
NFPA 105 (2022) Standard for Smoke Door Assemblies and Other Opening Protectives
NFPA 252 (2022) Standard Methods of Fire Tests of Door Assemblies
STEEL DOOR INSTITUTE (SDI/DOOR)
SDI/DOOR A250.8 (2023) Specifications for Standard Steel
SECTION 08 71 00.00 14 Page 2
Doors and Frames
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
UNDERWRITERS LABORATORIES (UL)
UL 294 (2023) UL Standard for Safety Access Control System Units
UL 1784 Standard for Air Leakage Tests of Door Assemblies
UL Bld Mat Dir (updated continuously online) Building Materials Directory
1.2 DEFINITIONS
The following acronyms are used: "AC" is the Access Control Point, "CC" is the Command Center, "PP" is the Power Plant, "ST" is Site, and "UL" is the Fuel Unloading and all other miscellaneous site structures not otherwise listed.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submittals not specifically identified with a building apply to all buildings and all miscellaneous site structures. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Manufacturer's Detail Drawings for CC ; G Manufacturer's Detail Drawings for PP ; G
Verification of Existing Conditions for CC ; G Verification of Existing Conditions for PP ; G
Hardware Schedule for CC ; G Hardware Schedule for PP Items, Data Package 1; G
Keying System for CC ; G Keying System for PP ; G
SD-03 Product Data
Hardware Items for CC ; G Hardware Items for PP ; G
Fire Department Knoxbox ; G
SD-08 Manufacturer's Instructions
SECTION 08 71 00.00 14 Page 3
Installation
SD-10 Operation and Maintenance Data
Hardware Schedule for CC Items, Data Package 1; G Hardware Schedule for PP Items, Data Package 1; G
SD-11 Closeout Submittals
Key Bitting
1.4 SHOP DRAWINGS
Submit Manufacturer's Detail Drawings for CC and Manufacturer's Detail Drawings for PP indicating all hardware assembly components and interface with adjacent construction. Indicate power components and wiring coordination for electrified hardware. Base shop drawings on verified field measurements and include Verification of Existing Conditions for CC and Verification of Existing Conditions for PP .
1.5 PRODUCT DATA
Indicate fire-ratings at applicable components. Provide documentation of ABA/ADA accessibility compliance of applicable components, as required by 36 CFR 1191 Appendix D - Technical.
1.6 HARDWARE SCHEDULE FOR CC AND HARDWARE SCHEDULE FOR PP
Provide Hardware Item List and Hardware Schedule containing the following information, and additional information as needed to identify the complete make up of each hardware set and its application to each opening:
1.6.1 Hardware Item List:
a. Hardware Type
b. Item Number
c. Quantity
d. Size(s)
e. Reference Publication / Type Number
f. Manufacturer's Name / Catalog Number
g. Key Control Symbols
h. UL Mark (If fire rated and listed)
i. BHMA Finish(es)
j. Remarks
1.6.2 Hardware Schedule
a. Hardware Set Number
SECTION 08 71 00.00 14 Page 4
b. Opening Number(s)
c. Opening Description (single/double leaf, hand, size, door/frame material)
d. Fire Rating
e. Sound Rating
f. Hardware Items
g. Quantity
h. Size
i. BHMA Finish
j. Remarks
In addition, submit hardware schedule data package 1 in accordance with Section 01 78 23.00 14 OPERATION AND MAINTENANCE DATA.
1.7 KEY BITTING CHART REQUIREMENTS
1.7.1 Requirements
Submit key bitting charts to the Contracting Officer prior to completion of the work. Include:
a. Complete listing of all keys (e.g. AA1 and AA2).
b. Complete listing of all key cuts (AA1-123456, AA2-123458).
c. Tabulation showing which key fits which door.
d. Copy of floor plan showing doors and door numbers.
e. Listing of 20 percent more key cuts than are presently required in each master system.
1.8 QUALITY ASSURANCE
1.8.1 Hardware Manufacturers and Modifications
Provide, as far as feasible, locks, hinges, pivots, and closers of one lock, hinge, pivot, or closer manufacturer's make. Modify hardware as necessary to provide features indicated or specified.
1.8.2 Key Shop Drawings Coordination Meeting
Prior to the submission of the key shop drawing, the Contracting Officer, Contractor, Door Hardware Subcontractor, using Activity and Base Locksmith must meet to discuss and coordinate key requirements for the facility.
1.8.3 Pre-Installation Meetings
1.8.3.1 Keying Conference
Incorporate keying conference decisions into final keying schedule after
SECTION 08 71 00.00 14 Page 5 reviewing door hardware keying system including:
a. Function of building, flow of traffic, purpose of each area, degree of security required, and plans for future expansion.
b. Preliminary key system schematic diagram.
c. Requirements for key control system.
d. Requirements for access control.
e. Address for delivery of keys.
1.8.3.2 Pre-installation Conference
a. Review and finalize construction schedule and verify availability of materials, Installer's personnel, equipment, and facilities needed to make progress and avoid delays.
b. Inspect and discuss preparatory work performed by other trades.
c. Inspect and discuss electrical roughing-in for electrified door hardware.
d. Review sequence of operation for each type of electrified door hardware.
e. Review required testing, inspecting, and certifying procedures.
f. Review questions or concerns related to proper installation and adjustment of door hardware.
1.8.3.3 Electrified Hardware Coordination Conference
Prior to ordering electrified hardware, schedule and hold meeting to coordinate door hardware with security, electrical, doors and frames, and other related suppliers.
1.9 COORDINATION
Coordinate layout and installation of floor-recessed door hardware with floor construction. Cast anchoring inserts into concrete.
Installation Templates: Distribute for doors, frames, and other work specified to be factory or shop prepared. Check Shop Drawings of other work to confirm that adequate provisions are made for locating and installing door hardware to comply with indicated requirements.
Electrical System Roughing-In: Coordinate layout and installation of electrified door hardware with connections to power supplies and building safety and security systems.
1.10 WARRANTY
Manufacturer's standard form in which manufacturer agrees to repair or replace components of door hardware that fail in materials or workmanship within published warranty period.
Warranty does not cover damage or faulty operation due to improper
SECTION 08 71 00.00 14 Page 6 installation, improper use or abuse.
Warranty Period: Beginning from date of Substantial Completion, for durations indicated in manufacturer's published listings.
a. Mechanical Warranty
1. Locks: 3 years
2. Exit Devices: 3 years
3. Closers: 2 years
b. Electrical Warranty
1. Locks: 1 year
2. Exit Devices: 1 year
3. Closers: 2 years
1.11 DELIVERY, STORAGE, AND HANDLING
Deliver hardware in original individual containers, complete with necessary appurtenances including fasteners and instructions. Mark each individual container with item number as shown on hardware schedule.
Deliver permanent keys and removable cores to the Contracting Officer, either directly or by certified mail. Deliver construction master keys with the locks.
PART 2 PRODUCTS
2.1 TEMPLATE HARDWARE
Hardware applied to metal or to prefinished doors must be manufactured using a template. Provide templates to door and frame manufacturers in accordance with ANSI/BHMA A156.7 for template hinges. Coordinate hardware items to prevent interference with other hardware.
2.2 HARDWARE FOR FIRE DOORS AND EXIT DOORS
Provide all hardware necessary to meet the requirements of NFPA 72 for door alarms, NFPA 80 for fire doors, NFPA 101 for exit doors, NFPA 252 for fire tests of door assemblies, ABA/ADA accessibility requirements, and all other requirements indicated, even if such hardware is not specifically mentioned in paragraph HARDWARE SCHEDULE. Provide Underwriters Laboratories, Inc. labels for such hardware in accordance with UL Bld Mat Dir or equivalent labels in accordance with another testing laboratory approved in writing by the Contracting Officer.
2.3 HARDWARE ITEMS FOR CC AND HARDWARE ITEMS FOR PP
Clearly and permanently mark with the manufacturer's name or trademark, hinges, pivots, locks, latches, exit devices, bolts and closers where the identifying mark is visible after the item is installed. For closers with covers, the name or trademark may be beneath the cover. Coordinate electrified door hardware components with corresponding components specified in Division 28 ELECTRONIC SECURITY SYSTEMS (ESS).
SECTION 08 71 00.00 14 Page 7
2.3.1 Hinges
Provide in accordance with ANSI/BHMA A156.1 . Provide hinges that are 4-1/2 by 4-1/2 inch unless otherwise indicated. Construct loose pin hinges for interior doors and reverse-bevel exterior doors so that pins are non-removable when door is closed. Other anti-friction bearing hinges may be provided in lieu of ball bearing hinges.
a. Provide five knuckle, ball bearing hinges.
b. 1-3/4 inch thick doors, up to and including 36 inches wide:
1. Exterior: Standard weight, bronze or stainless steel, 4-1/2 inches high.
2. Interior: Standard weight, steel, 4-1/2 inches high.
c. 1-3/4 inch thick doors over 36 inches wide:
1. Exterior: Heavy weight, bronze/stainless steel, 5 inches high.
2. Interior: Heavy weight, steel, 5 inches high.
d. 2 inches or thicker doors:
1. Exterior: Heavy weight, bronze or stainless steel, 5 inches high.
2. Interior: Heavy weight, steel, 5 inches high.
e. Adjust hinge width for door, frame, and wall conditions to allow proper degree of opening.
f. Provide three hinges per door leaf for doors 90 inches or less in height, and one additional hinge for each 30 inches of additional door height.
g. Where new hinges are specified for existing doors or existing frames, provide new hinges of identical size to hinge preparation present in existing door or existing frame.
h. Hinge Pins: Except as otherwise indicated, provide hinge pins as follows:
1. Steel Hinges: Steel pins
2. Non-Ferrous Hinges: Stainless steel pins
3. Out-Swinging Exterior Doors: Non-removable pins
4. Out-Swinging Interior Lockable Doors: Non-removable pins
5. Interior Non-lockable Doors: Non-rising pins
i. Provide hinges with electrified options as scheduled in the hardware sets. Provide with number and gage of wires enough to accommodate electric function of specified hardware. Locate electric hinge at second hinge from bottom or nearest to electrified locking component.
Provide mortar guard for each electrified hinge specified.
SECTION 08 71 00.00 14 Page 8
2.3.1.1 Protection Devices
Provide full height hand and finger protection device at the hinge-side area opening of doors and gates. Provide hinge-side protection devices on both sides of doors and gates, covering hinges and space between door and frame when doors are in the open position. The installed device must push hand and fingers out of the opening and away from a crushing hazard.
2.3.2 Continuous Hinges
Where continuous hinges are required, provide in accordance with
ANSI/BHMA A156.26 .
a. Provide aluminum geared continuous hinges conforming to ANSI/BHMA A156.26 , Grade 1.
b. Provide aluminum geared continuous hinges, where specified in the hardware sets, fabricated from 6063-T6 aluminum.
c. Provide split nylon bearings at each hinge knuckle for quiet, smooth, self-lubricating operation.
d. Provide hinges capable of supporting door weights up to 450 pounds, and successfully tested for 1,500,000 cycles.
e. On fire-rated doors, provide aluminum geared continuous hinges classified for use on rated doors by testing agency acceptable to authority having jurisdiction.
f. Provide aluminum geared continuous hinges with electrified option scheduled in the hardware sets. Provide with number and gage of wires enough to accommodate electric function of specified hardware.
g. Provide hinges 1 inch shorter in length than nominal height of door, unless otherwise noted or door details require shorter length and with symmetrical hole pattern.
2.3.3 Pivots
Provide in accordance with ANSI/BHMA A156.17 .
2.3.4 Spring Hinges
Provide in accordance with ANSI/BHMA A156.17 .
a. Provide 3 knuckle, steel based, spring full mortise hinges.
b. Adjust hinge width for door, frame, and wall conditions to allow proper degree of opening.
c. Provide two spring hinges and one bearing hinge per door leaf for doors 90 inches or less in height. Do not use spring hinges on doors 96 inches and greater in height.
d. Where new hinges are specified for existing doors or existing frames, provide new hinges of identical size to hinge preparation present in existing door or existing frame.
SECTION 08 71 00.00 14 Page 9
2.3.5 Locks and Latches
a. At exterior locations provide locksets of full stainless steel type 302 or 304 construction including fronts, strike, escutcheons, knobs, bolts and all interior working parts. Marine Grade I, fully non-ferrous.
b. In non-air-conditioned interior environments or humid interior environments, provide interior locksets on the same Marine Grade I, fully non-ferrous as exterior locksets.
2.3.5.1 Mortise Locks and Latches
Provide in accordance with ANSI/BHMA A156.13 , Series 1000, Operational Grade 1, Security Grade 2. Provide knobs and roses of mortise locks with screwless shanks and no exposed screws.
a. Provide mortise locks conforming to ANSI/BHMA A156.13 Series 1000, Grade 1, and UL Listed for 3-hour fire doors.
b. Indicators: Where specified, provide indicator window measuring a minimum 2-inch x 1/2 inch with 180-degree visibility. Provide messages color-coded with full text and/or symbols, as scheduled, for easy visibility.
c. Provide locks manufactured from heavy gauge steel, containing components of steel with a zinc dichromate plating for corrosion resistance.
d. Provide lock case that is multi-function and field reversible for handing without opening case. Cylinders: Refer to "KEYING" article, herein.
e. Provide locks with standard 2-3/4 inches backset with full 3/4 inch throw stainless steel mechanical anti-friction latchbolt. Provide deadbolt with full 1-inch throw, constructed of stainless steel.
f. Provide standard ASA strikes unless extended lip strikes are necessary to protect trim.
g. Provide electrified options as scheduled in the hardware sets. Where scheduled, provide switches and sensors integrated into the locks and latches. Provide motor based electrified locksets that comply with the following requirements:
1. Universal input voltage - single chassis accepts 12 or 24VDC to allow for changes in the field without changing lock chassis.
2. Fail Safe/Fail Secure - changing mode between electrically locked (fail safe) and electrically unlocked (fail secure) is field selectable without opening the lock case
3. Low maximum current draw - maximum 0.4 amps to allow for multiple locks on a single power supply.
4. Low holding current - maximum 0.01 amps to produce minimal heat, eliminate "hot levers" in electrically locked applications, and to provide reliable operation in wood doors that provide minimal ventilation and air flow.
SECTION 08 71 00.00 14 Page 10
5. Connections - provide quick-connect Molex system standard.
h. Lever Trim: Solid brass, bronze, or stainless steel, cast or forged in design specified, with wrought roses and external lever spring cages. Provide thru-bolted levers with 2-piece spindles.
1. Lever Design: 06A
2.3.5.2 Bored Locks and Latches
Provide in accordance with ANSI/BHMA A156.2 , Series 4000, Grade 1.
2.3.5.3 Auxiliary Locks
Provide in accordance with ANSI/BHMA A156.36 , Grade 1.
2.3.6 Exit Devices
Provide in accordance with ANSI/BHMA A156.3 , Grade 1. Provide adjustable strikes for rim type and vertical rod devices. Provide open back strikes for pairs of doors with mortise and vertical rod devices. Provide touch bars in lieu of conventional crossbars and arms. Provide escutcheons not less than 7 by 2-1/4 inch .
Use stainless steel or bronze base metal with plated finishes. Also include stainless steel fasteners and screws.
a. Cylinders: Refer to "KEYING" article, herein.
b. Provide grooved touchpad type exit devices, fabricated of brass, bronze, stainless steel, or aluminum, plated to standard architectural finishes to match balance of door hardware.
c. Touchpad must extend a minimum of one half of door width. No plastic inserts are allowed in touchpads.
d. Provide exit devices with deadlatching feature for security and for future addition of alarm kits and/or other electrified requirements.
e. Provide exit devices with weather resistant components that can withstand harsh conditions of various climates and corrosive cleaners used in outdoor pool environments.
f. Provide flush end caps for exit devices.
g. Provide exit devices with manufacturer's approved strikes.
h. Provide exit devices cut to door width and height. Install exit devices at height recommended by exit device manufacturer, allowable by governing building codes, and approved by Architect.
i. Mount mechanism case flush on face of doors or provide spacers to fill gaps behind devices. Where glass trim or molding projects off face of door, provide glass bead kits.
j. Provide cylinder or hex-key dogging as specified at non fire-rated openings.
SECTION 08 71 00.00 14 Page 11
k. Removable Mullions: 2 inches x 3 inches steel tube. Where scheduled as keyed removable mullion, provide type that can be removed by use of a keyed cylinder, which is self-locking when re-installed.
l. Provide factory drilled weep holes for exit devices used in full exterior application, highly corrosive areas, and where noted in hardware sets.
m. Provide electrified options as scheduled.
n. Top latch mounting: double- or single-tab mount for steel doors, face mount for aluminum doors eliminating requirement of tabs, and double tab mount for wood doors.
o. Provide exit devices with optional trim designs to match other lever and pull designs used on the project.
2.3.7 Exit Locks With Alarm
Provide in accordance with ANSI/BHMA A156.3 and ANSI/BHMA A156.29 , Type E0431 (with full width horizontal actuating bar) for single doors; Type E0431 (with actuating bar) or E0471 (with actuating bar and top and bottom bolts, both leaves active) for pairs of doors, unless otherwise specified. Provide terminals for connection to remote indicating panel.
Provide outside control key. Provide door alarms integrated with the fire alarm system in accordance with NFPA 72 .
2.3.8 Cylinders and Cores
Provide cylinders and cores for new locks, including locks provided under other sections of this specification. Provide cylinders and cores with six pin tumblers. Provide cylinders from the products of one manufacturer, and provide cores from the products of one manufacturer.
Rim cylinders, mortise cylinders, and knobs of bored locksets have interchangeable cores which are removable by special control keys. Stamp each interchangeable core with a key control symbol in a concealed place on the core.
a. Provide cylinders/cores compliant with ANSI/BHMA A156.5 ; latest revision; cylinder face finished to match lockset; manufacturer's series as indicated. Refer to "KEYING" article, herein.
b. Provide cylinders in the below-listed configuration(s), distributed throughout the Project as indicated.
1. Patented Restricted: cylinder with interchangeable core with patented, restricted keyway.
c. Patent Protection: Cylinders/cores requiring use of restricted, patented keys, patent protected.
d. Nickel silver bottom pins.
2.3.8.1 High Security Cylinders
Provide in accordance with ANSI/BHMA A156.30 , security level A for all high security cylinder components.
SECTION 08 71 00.00 14 Page 12
2.3.9 Push Button Mechanisms
Provide in accordance with ANSI/BHMA A156.5 , Grade 1.
2.3.10 Electrified Hardware
Comply with the requirements of NFPA 70 for wiring of electrified hardware.
2.3.10.1 Electric Strikes and Frame Mounted Actuators
Provide in accordance with ANSI/BHMA A156.31 , Grade 1. Provide electric strikes and actuators as required to meet operational requirements.
Provide electric strikes that remain secure during power failure. Provide a separate power supply for electric strikes, other locking devices and ancillary parts. Provide strikes and actuators with a minimum opening force of 2300 pounds .
Provide facility interface devices that use direct current (dc) power to energize the solenoids. Provide electric strikes and actuators that incorporate end-of-line resistors to facilitate line supervision by the system. If not incorporated into the electric strike or local controller, provide metal oxide resistors (MOVs) to protect the controller from reverse current surges.
a. Provide power supplies approved by manufacturer of supplied electrified hardware.
b. Provide appropriate quantity of power supplies necessary for proper operation of electrified locking components as recommended by manufacturer of electrified locking components with consideration for each electrified component using power supply, location of power supply, and approved wiring diagrams. Locate power supplies as directed by Architect.
c. Provide regulated and filtered 24 VDC power supply, and UL Class 2 listed.
d. Provide power supplies with the following features:
1. 12/24 VDC Output, field selectable.
2. Class 2 Rated power limited output.
3. Universal 120-240 VAC input.
4. Low voltage DC, regulated and filtered.
5. Polarized connector for distribution boards.
6. Fused primary input.
7. AC input and DC output monitoring circuit w/LED indicators.
8. Cover mounted AC Input indication.
9. Tested and certified to meet UL 294 .
10. NEMA 1 enclosure.
SECTION 08 71 00.00 14 Page 13
11. Hinged cover w/lock down screws.
12. High voltage protective cover.
2.3.10.1.1 Solenoid
Provide actuating solenoid for strikes and actuators that are rated for continuous duty, cannot dissipate more than 12 Watts and must operate on 12 or 24 Volts dc. Inrush current cannot exceed 1 ampere and the holding current cannot be greater than 500 milliamperes. Actuating solenoid must move from fully secure to fully open positions in less than 500 milliseconds.
2.3.10.1.2 Signal Switches
Provide strikes and actuators with signal switches to indicate to the system when the bolt is not engaged or the strike mechanism is unlocked.
Signal switches must report a forced entry to the system.
2.3.10.1.3 Tamper Resistance
Provide strike guards that prevent tampering with the latch bolt of the locking hardware or the latch bolt keeper of the electric strike. Strike guards to bolt through the door using tamper resistant screws. Provide strike guards made of 1/8 inch thick brass and that are 11-1/14 inch high by 1-5/8 inch wide , with a minimum 5/32 inch wide offset.
2.3.10.1.4 Coordination
Provide electric strikes and actuators of a size, weight and profile compatible with each specified door frame. Field verify installation clearances prior to procurement.
a. Where pairs of doors are equipped with automatic flush bolts, an astragal, or other hardware that requires synchronized closing of the doors, provide bar-type coordinating device, surface applied to underside of stop at frame head.
b. Provide filler bar of correct length for unit to span entire width of opening, and appropriate brackets for parallel arm door closers, surface vertical rod exit device strikes, or other stop mounted hardware. Factory-prepared coordinators for vertical rod devices as specified.
2.3.10.1.5 Mounting Method
Provide electric strikes and actuators suitable for use with single and double doors, with mortise or rim type hardware specified, and for right or left hand mounting as specified. In double door installations, locate the lock in the active leaf and monitor the fixed leaf.
2.3.10.2 Electrified Mortise Locks
Provide in accordance with ANSI/BHMA A156.25 , Grade 1. Provide electrified mortise locks that remain secure during power failure.
Provide facility interface devices that use dc power to energize solenoids. Provide solenoids, resisters, and signal switches in accordance with paragraph ELECTRIC STRIKES AND FRAME MOUNTED ACTUATORS.
SECTION 08 71 00.00 14 Page 14
2.3.10.2.1 Power Transfer Hinges
Provide power transfer hinges with each electrified lock that route power and monitoring signals from the lockset to the door frame. Coordinate power transfer hinges with door frames.
a. Provide power transfer with electrified options as scheduled in the hardware sets. Provide with number and gage of wires enough to accommodate electric function of specified hardware.
b. Locate electric power transfer per manufacturer's template and UL requirements, unless interference with operation of door or other hardware items.
2.3.10.3 Power Operated Pedestrian Door Hardware
Provide in accordance with ANSI/BHMA A156.10 , Grade 1.
2.3.10.4 Release Devices
In accordance with ANSI/BHMA A156.15 , Grade 1.
2.3.10.4.1 Closer Holders
Provide floor, door, header mounted closer holder devices connected by integral releasing to fire smoke detecting devices.
2.3.10.4.2 Release Devices
Provide wall mounted free swinging release devices connected to fire smoke detecting devices.
2.3.10.5 Power Assist and Low Energy Power Operated Doors
Provide in accordance with ANSI/BHMA A156.19 , Grade 1.
2.3.10.6 Delayed Egress Locking System
Provide in accordance with ANSI/BHMA A156.24 , Grade 1.
2.3.10.7 Power and Manual Operated Revolving Pedestrian Doors
Provide in accordance with ANSI/BHMA A156.27 , Grade 1.
2.3.11 Keying System for CC and Keying System for PP
Provide a grand master keying system Provide a construction master keying system construction interchangeable cores. Provide key cabinet as specified.
a. Scheduled System:
1. New factory registered system:
a) Provide a factory registered keying system, complying with guidelines in ANSI/BHMA A156.28 , incorporating decisions made at keying conference.
b. Requirements:
SECTION 08 71 00.00 14 Page 15
1. Construction Keying:
a) Replaceable Construction Cores.
1) Provide temporary construction cores replaceable by permanent cores, furnished in accordance with the following requirements.
i) 3 construction control keys.
ii) 12 construction change (day) keys.
2) Owner/Tenant or Owner/Tenant's Representative will replace temporary construction cores with permanent cores.
2. Permanent Keying:
a) Provide permanent cylinders/cores keyed by the manufacturer according to the following key system.
1) Master Keying system as directed by the Owner/Tenant.
b) Forward bitting list and keys separately from cylinders, by means as directed by Owner/Tenant. Failure to comply with forwarding requirements will be cause for replacement of cylinders/cores involved at no additional cost to Owner/Tenant.
c) Provide keys with the following features:
1) Material: Nickel silver; minimum thickness of 0.107-inch .
2) Patent Protection: Keys and blanks protected by one or more utility patent(s).
3) Geographically Exclusive: Where High Security or Security cylinders/cores are indicated, provide nationwide, geographically exclusive key system complying with the following restrictions.
d) Identification:
1) Mark permanent cylinders/cores and keys with applicable blind code for identification. Do not provide blind code marks with actual key cuts.
2) Identification stamping provisions must be approved by the Architect and Owner/Tenant.
3) Stamp cylinders/cores and keys with Owner/Tenant's unique key system facility code as established by the manufacturer; key symbol and embossed or stamped with "DO NOT DUPLICATE" along with the "PATENTED" or patent number to enforce the patent protection.
4) Failure to comply with stamping…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .