APPENDIX_D_Air Leakage Rate by Fan Pressurization.xlsx

XLSX spreadsheet 59 KB Posted

Attached to
Design-Bid-Build, P1102 Weapons Magazine and Ordnance Operations Facility, Naval Submarine Base New London, Groton, Connecticut
Solicitation number
N4008526R0004
Issued by

About this file

This file is a data sheet appendix documenting air leakage rate testing results conducted using ASTM E 779-10 blower door pressure testing methodology for a building envelope at an unspecified facility. The testing was performed for an Army building using trailer-mounted fan equipment, with testing data collected across 10 pressure measurement points during both positive and negative pressure tests, supplemented by 12 pre-test and 12 post-test bias pressure data points. Test conditions included indoor and outdoor temperatures of 75.2°F and 62.6°F respectively, with an average wind speed of 5.0 mph from the west, and an envelope surface area of 80,000 square feet at an elevation of 760 feet above sea level.

The test results demonstrate compliance with specified acceptance criteria. The combined positive and negative pressure test yielded an envelope leakage rate of 0.208 cfm/ft² at 75 Pa with an upper 95% confidence limit of 0.223 cfm/ft², both satisfactory results below the 0.25 cfm/ft² maximum allowable leakage rate threshold. The pressure exponent (n) of 0.714 fell within the acceptable range of 0.45 to 0.8, and the data correlation coefficient squared of 0.9980 exceeded the required 0.98 minimum. All data quality checks passed, including the required number of pre-test bias, test, and post-test bias pressure data points. The effective leakage area calculated at 75 Pa was 12.6 square feet with an absolute leakage volume of 16,634 cfm at that pressure differential.

View the file

Other files

File Type Posted
Amend 0014 Spec 1667770.pdf PDF
N4008526R00040014 SF 30.pdf PDF
N4008526R00040013 SF 30.pdf PDF
N4008526R00040012 SF 30.pdf PDF
N4008526R00040011 SF 30.pdf PDF
N4008526R00040010 SF 30.pdf PDF
ATTACHMENT H - Price Proposal Form REV4.docx DOCX document
ATTACHMENT T - P1102_PROD.xlsx XLSX spreadsheet
1667770spc07.28.26_rev.pdf PDF
Revised Attachment H Price Proposal Form REV2.docx DOCX document
P1102_Amend 0007_Drawings3of3.pdf PDF
P-1102_Amend 0007_Drawings2of3.pdf PDF
ATTACHMENT R - Geo Inv Analytical Rep.pdf PDF
ATTACHMENT Q - NRZ_Checklist-POAM_Items.pdf PDF
JA ML-26-16 P1102 Interior Finishes_Redacted.pdf PDF
JA ML-26-15 P1102 Stormwater_Redacted.pdf PDF
JA ML-26-13 P1102 Fire Alarm_Redacted.pdf PDF
JA ML-26-12 P1102 ESS_Redacted.pdf PDF
ATTACHMENT N - NDDB Determination Renewal 16JAN2026.pdf PDF
ATTACHMENT L - Explosive Safety-HERO training.pptx PPTX presentation
P-1102_Amend 0006_Drawings_rev.pdf PDF
ATTACHMENT O - MK48 STORAGE FACILITY.pdf PDF
ATTACHMENT M - Permits Record of Decision (PROD).pdf PDF
N4008526R00040005 SF 30.pdf PDF
Attachment G- Small Business Subcontracting Plan (SBSP) Rev.pdf PDF
Amendment 0004 PPIs.pdf PDF
Attachment K - P1102 Site Visit Log.pdf PDF
Amendment 0002 PPIs.pdf PDF
N4008526R00040002 SF 30.pdf PDF
Attachment I - Site Visit Map.pdf PDF
N4008526R00040001 SF 30.pdf PDF
Solicitation - N4008526R0004.pdf PDF
Attachment B - PIEE Vendor Access Instructions.pdf PDF
Attachment E - Historical Small Business Utilization.pdf PDF
Attachment F - Small Business Participation Commitment.pdf PDF
FINAL DESIGN_1667770dwg1of2Sentry.pdf PDF
FINAL DESIGN_1667770dwg1of1TypeG.pdf PDF
FINAL DESIGN_1667770dwg1of1TypeH.pdf PDF
Attachment D - Past Performance Questionnaire.pdf PDF
FINAL DESIGN_1667770dwg2of3Operations.pdf PDF
FINAL DESIGN_1667770dwg2of2Sentry.pdf PDF
FINAL DESIGN_1667770dwg2of4Site.pdf PDF
FINAL DESIGN_1667770dwg3of4Site.pdf PDF
P-1102_1667770spc1of3.pdf.pdf PDF
P-1102_1667770spc3of3.pdf.pdf PDF
Attachment C - Construction Experience Project Data.pdf PDF
Attachment G - Individual Small Business Subcontracting Plan.pdf PDF
FINAL DESIGN_1667770dwg1of3Operations.pdf PDF
FINAL DESIGN_1667770dwg1of4Site.pdf PDF
FINAL DESIGN_1667770dwg4of4Site.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Data_Sheet

U.S. Army Corps of Engineers
Air Leakage Rate by Fan Pressurization
Using ASTM E 779-10
Building NameTest Date
Building Address
Prime Contractor
Contract No.
Pressure Testing Agency
Testing Agency Address
Testing Agency ContactPhone
Lead On-Site PersonnelPhone
Witness NameOrganizationTelephoneEmail

Building / Test Comments

What method is used for this pressure test?Blower DoorPressure Test RequirementsArmyNavyAFThis Test
Trailer Mounted Fan1Equipment typeNumber of Pre Test Bias Pressure Data Points12121212
Building Air Handling SystemNumber of Pressure Test Data Points10101010
Number of Post-test Bias Pressure Data Points12121212
Is this an Air Force, Army or Navy Building?ArmyMaximum Allowable Bias Pressure (Pa)NANANANA
Navy3DoD BranchMinumum Test Pressure (Pa) - Double Sided40402525
Air ForceMinumum Test Pressure (Pa) - Single sided50502525
Lowest Allowable Maximum Test Pressure (Pa)75755050
Note: Performing a two-sided test is highly recommended for increased result accuracy.Test Pressure Range (Pa)25252525
Data Correlation Coefficient0.980.980.980.98
What type of test is being performed?Positive & Negative - Two SidedAcceptable Leakage Rate (cfm/ft2)0.250.250.40.4
Positive - Single Sided1Test TypeMaximum Bias Pressure (Pa) - % of Min Test Two sided30%30%30%30%
Negative - Single SidedMaximum Bias Pressure (Pa) - % of Min Test One sided30%30%30%30%
Allowable 95% Confidence Interval (CI)0.020.020.020.02
Building Data
Elevation Above Sea Level (ft)760Building Envelope Pressure (Pa)75
Envelope Surface Area (ft2)80,000Acceptable Leakage Rate (cfm/ft2)0.25
Test Conditions
Indoor Temperature (oF)Outdoor Temperature (oF)Average Wind Speed (MPH)5.0
Pre Test75.2Pre Test62.6Prevailing Wind DirectionW
Post Test75.2Post Test62.6Average Bias Pressure (Pa)-0.3
Average75.2Average62.6
Pre Test Bias Pressure Test Points
Pressure (Pa)123456789101112
-0.4-0.4-0.4-0.4-0.4-0.4-0.4-0.4-0.4-0.4-0.4-0.4
Post Test Bias Pressure Test Points
Pressure (Pa)123456789101112
-0.2-0.2-0.2-0.2-0.2-0.2-0.2-0.2-0.2-0.2-0.2-0.2
CALCULATION TABLES
Positive Pressure Test DataEnter all pressure data as positve values.
Pressure (Pa)123456789101112Positive Pressure Test
40.945.150.555.661.765.167.771.174.381.6Bias & Temp -Corrected
Fan 111,02212,23013,14414,02215,05415,59616,00216,54117,02218,207PressureLeakageρo=0.07517
Fan 2(Pa)(cfm)Ln(ΔP)Ln(Q)ρin =0.07218
Fan 3141.211382.83.718449.33986ρout =0.07392
Fan 4245.412630.33.815519.44386µo =0.04389
Fan 5350.813574.23.927909.51593µin =0.04435
Fan 6455.914481.04.023569.58059µout =0.04354
Fan 7562.015546.84.127139.65161C =847.7
Fan 8665.416106.54.180529.68698N=10
Fan 9768.016525.84.219519.71268
Fan 10871.417082.44.268309.74581S2ln(dP) =0.050016
Fan 11974.617579.24.312149.77447S2ln(Q) =0.024884
Fan 121081.918803.04.405509.84177Sln(dP)ln(Q) =0.035218
Gauge (cfm)1102212230131441402215054155961600216541170221820700110.30.0NANASn =0.065811
Actual (cfm)

g6mdxkgc: Actual Airflow at site conditions (elevation and temperature)

1111512333132551414015181157271613716680171651836000120.30.0NANASln(Q)(ln(dPr)) =0.020003
T =2.306004
Positive Pressure Test - Data Quality CheckIln(Q)(ln(dP)) =0.046126
Number of Pre Test Bias Pressure Data Points12PASS12 Points Required
Number of Pressure Test Data Points10PASS10 Points Required
Number of Post Test Bias Pressure Data Points12PASS12 Points Required
Maximum Bias Pressure (Pa)0.4PASSFor a two-sided test, the maximum allowable bias pressure is 30 percent of the lowest pressure data point - 12.27 Pa
Minumum Test Pressure (Pa)40.9PASSFor an Air Force, single sided, test the lowest allowable data point pressure is 25 Pa
Lowest Allowable Maximum Pressure
Data Point (Pa)81.6PASSThe lowest allowable maximum pressure data point is 50 Pa
Test Pressure Range (Pa)40.7PASSMust be > 25 Pa
Data Correlation Coefficient (r) Squared0.9965PASSMust be > 0.98
Negative Pressure Test DataEnter all pressure data as positve values.Combined Positive and Negative Tests
Pressure (Pa)123456789101112Negative Pressure Test
42.246.950.854.759.364.468.772.577.482.1Bias & Temp -CorrectedCombined Positive and Negative Testsρo=0.07517
Fan 110,42411,24212,07612,45213,22914,10614,83715,39716,16617,067PressureLeakageρo=0.07517ρ =0.07305
Fan 2(Pa)(cfm)Ln(ΔP)Ln(Q)ρin =0.07218µo =0.04389
Fan 3141.910387.33.735299.24834ρout =0.07392µ =0.04395
Fan 4246.611202.43.841609.32388µo =0.04389C =763.7
Fan 5350.512033.53.921979.39545µin =0.04435n=0.71513
Fan 6454.412408.23.996369.42611µout =0.04354N=20
Fan 7559.013182.44.077549.48664C =691.9S2ln(dP) =0.04722
Fan 8664.114056.34.160449.55083N=10Sn =0.066835
Fan 9768.414784.84.225379.60135Sln(Q)(ln(dPr)) =0.034279
Fan 10872.215342.84.279449.63840S2ln(dP) =0.049660T =2.100922
Fan 11977.116109.14.345109.68714S2ln(Q) =0.026136Iln(Q)(ln(dP)) =0.072017
Fan 121081.817006.94.404289.74137Sln(dP)ln(Q) =0.035991
Gauge (cfm)10,42411,24212,07612,45213,22914,10614,83715,39716,16617,0670011-0.30.0NANASn =0.051310
Actual (cfm)

g6mdxkgc: Actual Airflow at site conditions (elevation and temperature) g6mdxkgc: Actual Airflow at site conditions (elevation and temperature)

10,63811,47312,32412,70713,50014,39515,14115,71316,49717,4170012-0.30.0NANASLn(Q)(ln(dPr)) =0.015609
T =2.306004
Negative Pressure Test - Data Quality CheckIln(Q)(ln(dP)) =0.035995
Number of Pre Test Bias Pressure Data Points12PASS12 Points Required
Number of Pressure Test Data Points10PASS10 Points Required
Number of Post Test Bias Pressure Data Points12PASS12 Points Required
Maximum Bias Pressure (Pa)0.4PASSFor a two-sided test, the maximum allowable bias pressure is 30 percent of the lowest pressure data point - 12.66 Pa.
Minumum Test Pressure Data Point (Pa)42.2PASSFor a two-sided test, the lowest allowable data point pressure is 25 Pa
Lowest Allowable Maximum Pressure
Data Point (Pa)82.1PASSThe lowest allowable maximum pressure data point is 50 Pa
Test Pressure Range (Pa)39.9PASSMust be > 25 Pa
Data Correlation Coefficient (r) Squared0.9980PASSMust be > 0.98
Calculated ValuesPositive
TestNegative
TestPos & Neg Test
Effective Leakage Area (AL) @ 75 Pa (ft2)13.411.912.6
Pressure Exponent, n0.7040.7250.714
Air Leakage Coefficient - CCorr (cfm/Pan)841.2686.2763.7
Leakage Rates @ 75 Pa (Q75) (cfm)
Envelope Leakage Rate175861568216634
Upper 95% Confidence Leakage Rate184161625717831
Lower 95% Confidence Leakage Rate167931512815466
Leakage per square foot of envelope area @ 75 Pa (cfm/ft2)
Leakage per Sq. Ft. of Envelope0.2200.1960.208
Upper 95% Confidence Limit0.2300.2030.223
Lower 95% Confidence Limit0.2100.1890.193
95% Confidence Interval (CI)0.0100.0070.015
Pressure Test ResultsPositive
TestNegative
TestPos & Neg Test
0.45 < Exponent (n) < 0.8PASSPASSNA
Envelope Leakage Rate < 0.25 cfm/sq ftPASSPASSPASS
Upper 95% Confidence Limit < 0.27 cfm/sq ftPASSPASSNA
The envelope leakage rate is less than 0.25 cfm/sq ft and

the 95% confidence interval is less than 0.02

OR

The envelope leakage rate is less than 0.25 cfm/sq ft, the 95% confidence interval is greater than 0.02 and the leakage rate plus the 95% confidence interval is less than 0.25 cfm/sq ft. PASS PASS NA

PressureLeakage
(Pa)(cfm)
7520,000
Positive Test Correction Factor1.0084
PressureFlow
40.911114.83.71119.3160
45.112333.03.80899.4200
50.513254.73.92209.4921PThis area is used for calculating the combined slope and interceprt for the actual fan flow and uncorrected data and plotting the combined trendline
55.614140.14.01829.5568O
61.715180.84.12239.6278S
65.115727.34.17599.6632I
67.716136.74.21519.6889T
71.116680.34.26419.7220I
74.317165.34.30819.7506V
81.618360.34.40189.8179EUncorrected Data Set Slope and Intercept
NANANANACombinedPositiveNegative
NANANANAn =0.714n =0.700n =0.728
42.210637.73.74249.2722C =769.296C =843.4C =695.2
46.911472.53.84809.3477
50.812323.63.92799.4193NCombined
54.712707.34.00199.4499ETrendline
59.313500.24.08269.5105GPQ
64.414395.24.16519.5747A35.09756
68.715141.24.22979.6252T100.020654
72.515712.74.28369.6622I2020
77.416497.54.34909.7110V
82.117416.94.40799.7652E75Pa
NANANANALine
NANANANA75100.0
PressureFlow7520654.4
Negative Test Correction Factor1.0205

Page &P

Corrected Data - Pressure vs Leakage Rate

40.9 45.1 50.5 55.6 61.7 65.099999999999994 67.7 71.099999999999994 74.3 81.599999999999994 11114.802001924616 12332.973007034843 13254.668618517251 14140.061120575845 15180.750257391866 15727.313738161522 16136.732138885656 16680.270360536659 17165.320239227072 18360.29759109431 0.01 0.01 42.2 46.9 50.8 54.7 59.3 64.400000000000006 68.7 72.5 77.400000000000006 82.1 10637.732772228455 11472.504971737559 12323.605233828745 12707.314704507746 13500.246243650254 14395.228173930795 15141.216533149809 15712.698723522788 16497.466231374252 17416.940255527923 0.01 0.01 35 100 9755.9157166952737 20654.422448034849 75 20000 Actual Fan Flow Leakage Rate (cfm)

Differential Pressure (Pa)

Input Data - Pressure vs Leakage Rate

42.2 46.9 50.8 54.7 59.3 64.400000000000006 68.7 72.5 77.400000000000006 82.1 10637.732772228455 11472.504971737559 12323.605233828745 12707.314704507746 13500.246243650254 14395.228173930795 15141.216533149809 15712.698723522788 16497.466231374252 17416.940255527923 0.01 0.01 40.9 45.1 50.5 55.6 61.7 65.099999999999994 67.7 71.099999999999994 74.3 81.599999999999994 11114.802001924616 12332.973007034843 13254.668618517251 14140.061120575845 15180.750257391866 15727.313738161522 16136.732138885656 16680.270360536659 17165.320239227072 18360.29759109431 0.01 0.01 Actual Fan Flow Leakage Rate (cfm)

Differential Pressure (Pa)

Sheet1_(2)

xyCalculatedPercent
N-2TTError
33.1823.1790.10%
42.7762.785-0.34%
52.5712.5660.21%
62.4472.4410.23%
72.3652.365-0.00%
82.3062.310-0.19%
92.2622.266-0.17%
102.2282.228-0.02%
112.2012.1980.14%
122.1792.1750.18%
132.1602.1590.04%
142.1452.147-0.10%
152.1312.135-0.19%
162.1202.120-0.02%
172.1102.1050.22%
182.1012.103-0.09%
60.0000019405797
5-0.0001377612
40.0039821644
3-0.06015926
20.50554573
1-2.3022682
C6.8696373

Confidence Limit T 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 3.1819999999999999 2.7759999999999998 2.5710000000000002 2.4470000000000001 2.3650000000000002 2.306 2.262 2.2280000000000002 2.2010000000000001 2.1789999999999998 2.16 2.145 2.1309999999999998 2.12 2.11 2.101 Two-Sided Confidence Limit - T

N-2 (No. Points minus 2)

File details come from the government source that posted it. Updated .