APPENDIX_D_Air Leakage Rate by Fan Pressurization.xlsx
XLSX spreadsheet 59 KB Posted
- Solicitation number
- N4008526R0004
About this file
This file is a data sheet appendix documenting air leakage rate testing results conducted using ASTM E 779-10 blower door pressure testing methodology for a building envelope at an unspecified facility. The testing was performed for an Army building using trailer-mounted fan equipment, with testing data collected across 10 pressure measurement points during both positive and negative pressure tests, supplemented by 12 pre-test and 12 post-test bias pressure data points. Test conditions included indoor and outdoor temperatures of 75.2°F and 62.6°F respectively, with an average wind speed of 5.0 mph from the west, and an envelope surface area of 80,000 square feet at an elevation of 760 feet above sea level.
The test results demonstrate compliance with specified acceptance criteria. The combined positive and negative pressure test yielded an envelope leakage rate of 0.208 cfm/ft² at 75 Pa with an upper 95% confidence limit of 0.223 cfm/ft², both satisfactory results below the 0.25 cfm/ft² maximum allowable leakage rate threshold. The pressure exponent (n) of 0.714 fell within the acceptable range of 0.45 to 0.8, and the data correlation coefficient squared of 0.9980 exceeded the required 0.98 minimum. All data quality checks passed, including the required number of pre-test bias, test, and post-test bias pressure data points. The effective leakage area calculated at 75 Pa was 12.6 square feet with an absolute leakage volume of 16,634 cfm at that pressure differential.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Data_Sheet
| U.S. Army Corps of Engineers |
| Air Leakage Rate by Fan Pressurization |
| Using ASTM E 779-10 |
| Building Name | Test Date | |||
| Building Address | ||||
| Prime Contractor | ||||
| Contract No. | ||||
| Pressure Testing Agency | ||||
| Testing Agency Address | ||||
| Testing Agency Contact | Phone | |||
| Lead On-Site Personnel | Phone | |||
| Witness Name | Organization | Telephone |
Building / Test Comments
| What method is used for this pressure test? | Blower Door | Pressure Test Requirements | Army | Navy | AF | This Test | |||||
| Trailer Mounted Fan | 1 | Equipment type | Number of Pre Test Bias Pressure Data Points | 12 | 12 | 12 | 12 | ||||
| Building Air Handling System | Number of Pressure Test Data Points | 10 | 10 | 10 | 10 | ||||||
| Number of Post-test Bias Pressure Data Points | 12 | 12 | 12 | 12 | |||||||
| Is this an Air Force, Army or Navy Building? | Army | Maximum Allowable Bias Pressure (Pa) | NA | NA | NA | NA | |||||
| Navy | 3 | DoD Branch | Minumum Test Pressure (Pa) - Double Sided | 40 | 40 | 25 | 25 | ||||
| Air Force | Minumum Test Pressure (Pa) - Single sided | 50 | 50 | 25 | 25 | ||||||
| Lowest Allowable Maximum Test Pressure (Pa) | 75 | 75 | 50 | 50 | |||||||
| Note: Performing a two-sided test is highly recommended for increased result accuracy. | Test Pressure Range (Pa) | 25 | 25 | 25 | 25 | ||||||
| Data Correlation Coefficient | 0.98 | 0.98 | 0.98 | 0.98 | |||||||
| What type of test is being performed? | Positive & Negative - Two Sided | Acceptable Leakage Rate (cfm/ft2) | 0.25 | 0.25 | 0.4 | 0.4 | |||||
| Positive - Single Sided | 1 | Test Type | Maximum Bias Pressure (Pa) - % of Min Test Two sided | 30% | 30% | 30% | 30% | ||||
| Negative - Single Sided | Maximum Bias Pressure (Pa) - % of Min Test One sided | 30% | 30% | 30% | 30% | ||||||
| Allowable 95% Confidence Interval (CI) | 0.02 | 0.02 | 0.02 | 0.02 | |||||||
| Building Data | |||||||||||
| Elevation Above Sea Level (ft) | 760 | Building Envelope Pressure (Pa) | 75 | ||||||||
| Envelope Surface Area (ft2) | 80,000 | Acceptable Leakage Rate (cfm/ft2) | 0.25 |
| Test Conditions | |||||
| Indoor Temperature (oF) | Outdoor Temperature (oF) | Average Wind Speed (MPH) | 5.0 | ||
| Pre Test | 75.2 | Pre Test | 62.6 | Prevailing Wind Direction | W |
| Post Test | 75.2 | Post Test | 62.6 | Average Bias Pressure (Pa) | -0.3 |
| Average | 75.2 | Average | 62.6 |
| Pre Test Bias Pressure Test Points | ||||||||||||||||||||
| Pressure (Pa) | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | ||||||||
| -0.4 | -0.4 | -0.4 | -0.4 | -0.4 | -0.4 | -0.4 | -0.4 | -0.4 | -0.4 | -0.4 | -0.4 | |||||||||
| Post Test Bias Pressure Test Points | ||||||||||||||||||||
| Pressure (Pa) | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | ||||||||
| -0.2 | -0.2 | -0.2 | -0.2 | -0.2 | -0.2 | -0.2 | -0.2 | -0.2 | -0.2 | -0.2 | -0.2 | |||||||||
| CALCULATION TABLES | ||||||||||||||||||||
| Positive Pressure Test Data | Enter all pressure data as positve values. | |||||||||||||||||||
| Pressure (Pa) | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | Positive Pressure Test | |||||||
| 40.9 | 45.1 | 50.5 | 55.6 | 61.7 | 65.1 | 67.7 | 71.1 | 74.3 | 81.6 | Bias & Temp -Corrected | ||||||||||
| Fan 1 | 11,022 | 12,230 | 13,144 | 14,022 | 15,054 | 15,596 | 16,002 | 16,541 | 17,022 | 18,207 | Pressure | Leakage | ρo= | 0.07517 | ||||||
| Fan 2 | (Pa) | (cfm) | Ln(ΔP) | Ln(Q) | ρin = | 0.07218 | ||||||||||||||
| Fan 3 | 1 | 41.2 | 11382.8 | 3.71844 | 9.33986 | ρout = | 0.07392 | |||||||||||||
| Fan 4 | 2 | 45.4 | 12630.3 | 3.81551 | 9.44386 | µo = | 0.04389 | |||||||||||||
| Fan 5 | 3 | 50.8 | 13574.2 | 3.92790 | 9.51593 | µin = | 0.04435 | |||||||||||||
| Fan 6 | 4 | 55.9 | 14481.0 | 4.02356 | 9.58059 | µout = | 0.04354 | |||||||||||||
| Fan 7 | 5 | 62.0 | 15546.8 | 4.12713 | 9.65161 | C = | 847.7 | |||||||||||||
| Fan 8 | 6 | 65.4 | 16106.5 | 4.18052 | 9.68698 | N= | 10 | |||||||||||||
| Fan 9 | 7 | 68.0 | 16525.8 | 4.21951 | 9.71268 | |||||||||||||||
| Fan 10 | 8 | 71.4 | 17082.4 | 4.26830 | 9.74581 | S2ln(dP) = | 0.050016 | |||||||||||||
| Fan 11 | 9 | 74.6 | 17579.2 | 4.31214 | 9.77447 | S2ln(Q) = | 0.024884 | |||||||||||||
| Fan 12 | 10 | 81.9 | 18803.0 | 4.40550 | 9.84177 | Sln(dP)ln(Q) = | 0.035218 | |||||||||||||
| Gauge (cfm) | 11022 | 12230 | 13144 | 14022 | 15054 | 15596 | 16002 | 16541 | 17022 | 18207 | 0 | 0 | 11 | 0.3 | 0.0 | NA | NA | Sn = | 0.065811 | |
| Actual (cfm) |
g6mdxkgc: Actual Airflow at site conditions (elevation and temperature)
| 11115 | 12333 | 13255 | 14140 | 15181 | 15727 | 16137 | 16680 | 17165 | 18360 | 0 | 0 | 12 | 0.3 | 0.0 | NA | NA | Sln(Q)(ln(dPr)) = | 0.020003 | |||
| T = | 2.306004 | ||||||||||||||||||||
| Positive Pressure Test - Data Quality Check | Iln(Q)(ln(dP)) = | 0.046126 | |||||||||||||||||||
| Number of Pre Test Bias Pressure Data Points | 12 | PASS | 12 Points Required | ||||||||||||||||||
| Number of Pressure Test Data Points | 10 | PASS | 10 Points Required | ||||||||||||||||||
| Number of Post Test Bias Pressure Data Points | 12 | PASS | 12 Points Required | ||||||||||||||||||
| Maximum Bias Pressure (Pa) | 0.4 | PASS | For a two-sided test, the maximum allowable bias pressure is 30 percent of the lowest pressure data point - 12.27 Pa | ||||||||||||||||||
| Minumum Test Pressure (Pa) | 40.9 | PASS | For an Air Force, single sided, test the lowest allowable data point pressure is 25 Pa | ||||||||||||||||||
| Lowest Allowable Maximum Pressure | |||||||||||||||||||||
| Data Point (Pa) | 81.6 | PASS | The lowest allowable maximum pressure data point is 50 Pa | ||||||||||||||||||
| Test Pressure Range (Pa) | 40.7 | PASS | Must be > 25 Pa | ||||||||||||||||||
| Data Correlation Coefficient (r) Squared | 0.9965 | PASS | Must be > 0.98 |
| Negative Pressure Test Data | Enter all pressure data as positve values. | Combined Positive and Negative Tests | |||||||||||||||||||||
| Pressure (Pa) | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | Negative Pressure Test | ||||||||||
| 42.2 | 46.9 | 50.8 | 54.7 | 59.3 | 64.4 | 68.7 | 72.5 | 77.4 | 82.1 | Bias & Temp -Corrected | Combined Positive and Negative Tests | ρo= | 0.07517 | ||||||||||
| Fan 1 | 10,424 | 11,242 | 12,076 | 12,452 | 13,229 | 14,106 | 14,837 | 15,397 | 16,166 | 17,067 | Pressure | Leakage | ρo= | 0.07517 | ρ = | 0.07305 | |||||||
| Fan 2 | (Pa) | (cfm) | Ln(ΔP) | Ln(Q) | ρin = | 0.07218 | µo = | 0.04389 | |||||||||||||||
| Fan 3 | 1 | 41.9 | 10387.3 | 3.73529 | 9.24834 | ρout = | 0.07392 | µ = | 0.04395 | ||||||||||||||
| Fan 4 | 2 | 46.6 | 11202.4 | 3.84160 | 9.32388 | µo = | 0.04389 | C = | 763.7 | ||||||||||||||
| Fan 5 | 3 | 50.5 | 12033.5 | 3.92197 | 9.39545 | µin = | 0.04435 | n= | 0.71513 | ||||||||||||||
| Fan 6 | 4 | 54.4 | 12408.2 | 3.99636 | 9.42611 | µout = | 0.04354 | N= | 20 | ||||||||||||||
| Fan 7 | 5 | 59.0 | 13182.4 | 4.07754 | 9.48664 | C = | 691.9 | S2ln(dP) = | 0.04722 | ||||||||||||||
| Fan 8 | 6 | 64.1 | 14056.3 | 4.16044 | 9.55083 | N= | 10 | Sn = | 0.066835 | ||||||||||||||
| Fan 9 | 7 | 68.4 | 14784.8 | 4.22537 | 9.60135 | Sln(Q)(ln(dPr)) = | 0.034279 | ||||||||||||||||
| Fan 10 | 8 | 72.2 | 15342.8 | 4.27944 | 9.63840 | S2ln(dP) = | 0.049660 | T = | 2.100922 | ||||||||||||||
| Fan 11 | 9 | 77.1 | 16109.1 | 4.34510 | 9.68714 | S2ln(Q) = | 0.026136 | Iln(Q)(ln(dP)) = | 0.072017 | ||||||||||||||
| Fan 12 | 10 | 81.8 | 17006.9 | 4.40428 | 9.74137 | Sln(dP)ln(Q) = | 0.035991 | ||||||||||||||||
| Gauge (cfm) | 10,424 | 11,242 | 12,076 | 12,452 | 13,229 | 14,106 | 14,837 | 15,397 | 16,166 | 17,067 | 0 | 0 | 11 | -0.3 | 0.0 | NA | NA | Sn = | 0.051310 | ||||
| Actual (cfm) |
g6mdxkgc: Actual Airflow at site conditions (elevation and temperature) g6mdxkgc: Actual Airflow at site conditions (elevation and temperature)
| 10,638 | 11,473 | 12,324 | 12,707 | 13,500 | 14,395 | 15,141 | 15,713 | 16,497 | 17,417 | 0 | 0 | 12 | -0.3 | 0.0 | NA | NA | SLn(Q)(ln(dPr)) = | 0.015609 | |||
| T = | 2.306004 | ||||||||||||||||||||
| Negative Pressure Test - Data Quality Check | Iln(Q)(ln(dP)) = | 0.035995 | |||||||||||||||||||
| Number of Pre Test Bias Pressure Data Points | 12 | PASS | 12 Points Required | ||||||||||||||||||
| Number of Pressure Test Data Points | 10 | PASS | 10 Points Required | ||||||||||||||||||
| Number of Post Test Bias Pressure Data Points | 12 | PASS | 12 Points Required | ||||||||||||||||||
| Maximum Bias Pressure (Pa) | 0.4 | PASS | For a two-sided test, the maximum allowable bias pressure is 30 percent of the lowest pressure data point - 12.66 Pa. | ||||||||||||||||||
| Minumum Test Pressure Data Point (Pa) | 42.2 | PASS | For a two-sided test, the lowest allowable data point pressure is 25 Pa | ||||||||||||||||||
| Lowest Allowable Maximum Pressure | |||||||||||||||||||||
| Data Point (Pa) | 82.1 | PASS | The lowest allowable maximum pressure data point is 50 Pa | ||||||||||||||||||
| Test Pressure Range (Pa) | 39.9 | PASS | Must be > 25 Pa | ||||||||||||||||||
| Data Correlation Coefficient (r) Squared | 0.9980 | PASS | Must be > 0.98 |
| Calculated Values | Positive | ||
| Test | Negative | ||
| Test | Pos & Neg Test |
| Effective Leakage Area (AL) @ 75 Pa (ft2) | 13.4 | 11.9 | 12.6 |
| Pressure Exponent, n | 0.704 | 0.725 | 0.714 |
| Air Leakage Coefficient - CCorr (cfm/Pan) | 841.2 | 686.2 | 763.7 |
| Leakage Rates @ 75 Pa (Q75) (cfm) | |||
| Envelope Leakage Rate | 17586 | 15682 | 16634 |
| Upper 95% Confidence Leakage Rate | 18416 | 16257 | 17831 |
| Lower 95% Confidence Leakage Rate | 16793 | 15128 | 15466 |
| Leakage per square foot of envelope area @ 75 Pa (cfm/ft2) | |||
| Leakage per Sq. Ft. of Envelope | 0.220 | 0.196 | 0.208 |
| Upper 95% Confidence Limit | 0.230 | 0.203 | 0.223 |
| Lower 95% Confidence Limit | 0.210 | 0.189 | 0.193 |
| 95% Confidence Interval (CI) | 0.010 | 0.007 | 0.015 |
| Pressure Test Results | Positive | ||
| Test | Negative | ||
| Test | Pos & Neg Test |
| 0.45 < Exponent (n) < 0.8 | PASS | PASS | NA |
| Envelope Leakage Rate < 0.25 cfm/sq ft | PASS | PASS | PASS |
| Upper 95% Confidence Limit < 0.27 cfm/sq ft | PASS | PASS | NA |
| The envelope leakage rate is less than 0.25 cfm/sq ft and |
the 95% confidence interval is less than 0.02
OR
The envelope leakage rate is less than 0.25 cfm/sq ft, the 95% confidence interval is greater than 0.02 and the leakage rate plus the 95% confidence interval is less than 0.25 cfm/sq ft. PASS PASS NA
| Pressure | Leakage |
| (Pa) | (cfm) |
| 75 | 20,000 |
| Positive Test Correction Factor | 1.0084 | ||||||||||
| Pressure | Flow | ||||||||||
| 40.9 | 11114.8 | 3.7111 | 9.3160 | ||||||||
| 45.1 | 12333.0 | 3.8089 | 9.4200 | ||||||||
| 50.5 | 13254.7 | 3.9220 | 9.4921 | P | This area is used for calculating the combined slope and interceprt for the actual fan flow and uncorrected data and plotting the combined trendline | ||||||
| 55.6 | 14140.1 | 4.0182 | 9.5568 | O | |||||||
| 61.7 | 15180.8 | 4.1223 | 9.6278 | S | |||||||
| 65.1 | 15727.3 | 4.1759 | 9.6632 | I | |||||||
| 67.7 | 16136.7 | 4.2151 | 9.6889 | T | |||||||
| 71.1 | 16680.3 | 4.2641 | 9.7220 | I | |||||||
| 74.3 | 17165.3 | 4.3081 | 9.7506 | V | |||||||
| 81.6 | 18360.3 | 4.4018 | 9.8179 | E | Uncorrected Data Set Slope and Intercept | ||||||
| NA | NA | NA | NA | Combined | Positive | Negative | |||||
| NA | NA | NA | NA | n = | 0.714 | n = | 0.700 | n = | 0.728 | ||
| 42.2 | 10637.7 | 3.7424 | 9.2722 | C = | 769.296 | C = | 843.4 | C = | 695.2 | ||
| 46.9 | 11472.5 | 3.8480 | 9.3477 | ||||||||
| 50.8 | 12323.6 | 3.9279 | 9.4193 | N | Combined | ||||||
| 54.7 | 12707.3 | 4.0019 | 9.4499 | E | Trendline | ||||||
| 59.3 | 13500.2 | 4.0826 | 9.5105 | G | P | Q | |||||
| 64.4 | 14395.2 | 4.1651 | 9.5747 | A | 35.0 | 9756 | |||||
| 68.7 | 15141.2 | 4.2297 | 9.6252 | T | 100.0 | 20654 | |||||
| 72.5 | 15712.7 | 4.2836 | 9.6622 | I | 20 | 20 | |||||
| 77.4 | 16497.5 | 4.3490 | 9.7110 | V | |||||||
| 82.1 | 17416.9 | 4.4079 | 9.7652 | E | 75 | Pa | |||||
| NA | NA | NA | NA | Line | |||||||
| NA | NA | NA | NA | 75 | 100.0 | ||||||
| Pressure | Flow | 75 | 20654.4 | ||||||||
| Negative Test Correction Factor | 1.0205 |
Page &P
Corrected Data - Pressure vs Leakage Rate
40.9 45.1 50.5 55.6 61.7 65.099999999999994 67.7 71.099999999999994 74.3 81.599999999999994 11114.802001924616 12332.973007034843 13254.668618517251 14140.061120575845 15180.750257391866 15727.313738161522 16136.732138885656 16680.270360536659 17165.320239227072 18360.29759109431 0.01 0.01 42.2 46.9 50.8 54.7 59.3 64.400000000000006 68.7 72.5 77.400000000000006 82.1 10637.732772228455 11472.504971737559 12323.605233828745 12707.314704507746 13500.246243650254 14395.228173930795 15141.216533149809 15712.698723522788 16497.466231374252 17416.940255527923 0.01 0.01 35 100 9755.9157166952737 20654.422448034849 75 20000 Actual Fan Flow Leakage Rate (cfm)
Differential Pressure (Pa)
Input Data - Pressure vs Leakage Rate
42.2 46.9 50.8 54.7 59.3 64.400000000000006 68.7 72.5 77.400000000000006 82.1 10637.732772228455 11472.504971737559 12323.605233828745 12707.314704507746 13500.246243650254 14395.228173930795 15141.216533149809 15712.698723522788 16497.466231374252 17416.940255527923 0.01 0.01 40.9 45.1 50.5 55.6 61.7 65.099999999999994 67.7 71.099999999999994 74.3 81.599999999999994 11114.802001924616 12332.973007034843 13254.668618517251 14140.061120575845 15180.750257391866 15727.313738161522 16136.732138885656 16680.270360536659 17165.320239227072 18360.29759109431 0.01 0.01 Actual Fan Flow Leakage Rate (cfm)
Differential Pressure (Pa)
Sheet1_(2)
| x | y | Calculated | Percent |
| N-2 | T | T | Error |
| 3 | 3.182 | 3.179 | 0.10% |
| 4 | 2.776 | 2.785 | -0.34% |
| 5 | 2.571 | 2.566 | 0.21% |
| 6 | 2.447 | 2.441 | 0.23% |
| 7 | 2.365 | 2.365 | -0.00% |
| 8 | 2.306 | 2.310 | -0.19% |
| 9 | 2.262 | 2.266 | -0.17% |
| 10 | 2.228 | 2.228 | -0.02% |
| 11 | 2.201 | 2.198 | 0.14% |
| 12 | 2.179 | 2.175 | 0.18% |
| 13 | 2.160 | 2.159 | 0.04% |
| 14 | 2.145 | 2.147 | -0.10% |
| 15 | 2.131 | 2.135 | -0.19% |
| 16 | 2.120 | 2.120 | -0.02% |
| 17 | 2.110 | 2.105 | 0.22% |
| 18 | 2.101 | 2.103 | -0.09% |
| 6 | 0.0000019405797 | ||
| 5 | -0.0001377612 | ||
| 4 | 0.0039821644 | ||
| 3 | -0.06015926 | ||
| 2 | 0.50554573 | ||
| 1 | -2.3022682 | ||
| C | 6.8696373 |