HUM - Steam Humidifier Cutsheet.pdf

PDF 674 KB Posted

Attached to
Design Bid Build (DBB) Construction Requirement for Alburg Springs Land Port of Entry (LPOE), Alburg, Vermont
Solicitation number
47PB5126R0008
Issued by
Not on record

About this file

This is a product submittal document for the DriSteem RTS Humidifier RX Series, an electric resistive steam humidifier designed for commercial and industrial building environments. The document provides comprehensive technical specifications, dimensions, weights, electrical requirements, and installation guidance for the product line.

The RTS RX Series includes models ranging from 6 lbs/hr to 324 lbs/hr steam capacity across single-stage, two-stage, three-stage, and four-stage configurations. Electrical specifications are provided for multiple voltage options including 120V, 208V, 240V, 277V, 380V, 480V, and 600V in both single-phase and three-phase configurations, with power requirements ranging from 2 kW to 108 kW depending on model selection. All units operate at 50/60 Hz and feature a standard 5kA Short Circuit Current Rating with optional 100kA rating available. The humidifier uses resistive heating elements to boil water into steam, automatically determines drain rates based on water quality, and includes integrated drain water tempering as standard. Indoor and outdoor enclosure options are available, with detailed dimensional specifications provided for both configurations. For space distribution, two Space Distribution Unit (SDU) models are offered: the SDU-I-RX with 30 lbs/hr capacity and the SDU-E-RX with 126 lbs/hr capacity, both with specific rise, spread, and throw distance requirements to prevent condensation on surrounding surfaces depending on ambient relative humidity conditions.

View the file

Other files

File Type Posted
27. Amendment 47PB5126R0008 0008 2026 07 13.pdf PDF
3. Agreement Rev 2 2026 06 18.pdf PDF
25. Amendment 47PB5126R0008 0007 2026 06 18.pdf PDF
6. WD VT20250027 2026 05 18.pdf PDF
1. Solicitation Rev 1_2026 06 11.pdf PDF
2. SF1442 Rev 1 dated 2026 06 15.pdf PDF
3. Agreement Rev 1 2026 06 12.pdf PDF
21. Amendment 47PB5126R0008 0006 2026 06 15.pdf PDF
20. Amendment 47PB5126R0008 0005 2026 06 02.pdf PDF
19. Amendment 47PB5126R0008 0004 2026 05 29.pdf PDF
16. Alburg Springs - Port Signage SOW-ASR 01.pdf PDF
15. Amendment 47PB5126R0008 0003 2026 05 21.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes_Rev 1 Amendment 0002_ 2026 05 15.pdf PDF
14. Amendment 47PB5126R0008 0002 2026 05 15.pdf PDF
13. Amendment 47PB5126R0008 0001 2026 05 12.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
RP - Vertical Radiant Panel Cutsheet.pdf PDF
RG - Return Grille Cutsheet.pdf PDF
SG - Supply Grille Cutsheet.pdf PDF
ET - Expansion Tank Cutsheet.pdf PDF
FT - Fin Tube Cutsheet.pdf PDF
GFT - Glycol Feed Tank Cutsheet.pdf PDF
BT - Buffer Tank Cutsheet.pdf PDF
FB - Filter Box Cutsheet.pdf PDF
PUH - Propeller Unit Heater Cutsheet.pdf PDF
GI and GR - Gravity Intake and Relief Cutsheet.pdf PDF
DH - Duct Mounted Humidifier Cutsheet.pdf PDF
SG and EG - Security Grille Cutsheet.pdf PDF
BSF - Booth Supply Fan Cut Sheet.pdf PDF
RP - Horizontal Radiant Panel Cutsheet.pdf PDF
AS - Air Separator Cutsheet.pdf PDF
EHC - Electric Heating Coil Cutsheet.pdf PDF
2026-02-06 Review of Proposed Renovations - Historic Context (1).pdf PDF
4. GSA527-21a 2026 04 15.pdf PDF
FCU - Fan Coil Unit Cutsheet.pdf PDF
6. WD VT20250027 2026 04 15.pdf PDF
CP and GP - Pump Cutsheets.pdf PDF
3. Agreement 2026 04 15.pdf PDF
EH - Electric Wall Heater Cutsheet.pdf PDF
7. PBS PPQ 2026 04 15.pdf PDF
GSHP - Ground Source Heat Pump Cutsheet.pdf PDF
L - Louver Cutsheet.pdf PDF
HP and CU - Heat Pump Mini-Split Cutsheet.pdf PDF
8. Tips on Preparing a Subcontracting Plan 2026 04 15.pdf PDF
Alburg Springs VT LPOE Code Report - 20260206 (1).pdf PDF
9. Model Subcontracting Plan 2026 04 15.docx DOCX document
5. Proprietary Information Agreement 2026 04 15.docx DOCX document
EF - Exhaust Fan Cutsheet.pdf PDF
Show 40 more

Latest 50 of 56 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 1 OF 16REV. 07/25

RTS® Humidifier RX Series

ELECTRIC RESISTIVE HUMIDIFIER

From providing comfort humidity to meeting the strictest clean-room requirements, the RTS electric humidifier is designed to meet the humidification demands of any building environment. The RTS humidifier RX series is an electric humidifier that uses resistive heating elements to boil water into steam. While RO/DI water will grant you the best accuracy with the RTS, any water type can be used. Drain rates are automatically determined per the quality of your water, and integrated drain water tempering is standard on every unit.

FIGURE 1-1: RTS HUMIDIFIER

OM-8040

Water level control

Steam outlet

Fill valve

P-trap

Skimmer

Heaters

Vapor-logic controller touchscreen display

Drain valve

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 2 OF 16REV. 07/25

Models, capacities, and electrical specifications

Table 2-1:

RTS humidifier capacities, electrical specifications

RTS

model

Maximum steam capacity Power Stages

Total max current draw (amps)

Single-phase Three-phase lbs/hr kg/h kW Contactors 120V 208V 240V 277V 480V 600V 208V 240V 380V 480V 600V

RX-6-1 6 2.7 2 1 16.7 9.6 8.3 21.7 4.2 3.3 — — — — —

RX-12-1 12 5.4 4 1 33.3 19.2 16.7 21.7 8.3 6.7 16.7 14.4 9.10 7.2 5.8

RX-18-1 18 8.2 6 1 — 28.9 25 21.7 12.5 10 16.7 14.4 9.10 7.2 5.8

RX-24-1 24 10.9 8 1 — 38.5 33.3 43.3 16.7 13.3 25 21.7 13.70 10.8 8.7

RX-30-1 30 13.6 10 1 — — 41.7 43.3 20.8 16.7 33.3 28.9 18.20 14.4 11.6

RX-36-1 36 16.3 12 1 — — — 43.3 25 20 33.3 28.9 18.20 14.4 11.6

RX-42-1 42 19.0 14 1 — — — — 29.2 23.3 41.6 36.1 22.80 18 14.4

RX-48-1 48 21.8 16 1 — — — — 33.3 26.7 — 43.3 27.40 21.7 17.3

RX-63-1 63 28.6 21 1 — — — — 43.8 35 — — 34.2 27.1 21.7

RX-75-1 75 34.0 25 1 — — — — — 45 — — 41 32.5 26

RX-30-2 30 13.6 10 2 — 57.7 — — — — — — — — —

RX-36-2 36 16.3 12 2 — 57.7 50 — — — — — — — —

RX-48-2 48 21.8 16 2 — 76.9 66.7 86.6 — — 50 — — — —

RX-63-2 63 28.6 21 2 — — 91.7 86.6 — — 66.6 57.7 — — —

RX-75-2 75 34.0 25 2 — — — — 54.2 — 83.2 72.2 — — —

RX-90-2 90 40.8 30 2 — — — — 62.5 50 — 86.6 54.7 43.3 34.6

RX-102-2 102 46.3 34 2 — — — — 70.8 56.7 — 86.6 54.7 43.3 34.6

RX-126-2 126 57.1 42 2 — — — — 87.5 70 — — 68.4 54.1 43.3

RX-144-2 144 65.3 48 2 — — — — — 80 — — 82 65 52

RX-162-2 162 73.5 54 2 — — — — — 90 — — 82 65 52

•All RTS humidifier models operate at 50/60 Hz.
•For wire sizing, the highest leg draw is shown due to current imbalance.
•See Table 70-1 for heaters.
•Maximum amps is determined based on the heaters used by each model. Some voltage/kW combinations show higher amperage values than

what the unit capacity will allow.

• The standard Short Circuit Current Rating (SCCR) for the RTS humidifier is 5kA. A 100kA rating is available as an option.

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 3 OF 16REV. 07/25

Models, capacities, and electrical specifications (continued)

Table 3-1:

RTS humidifier capacities, electrical specifications (continued)

RTS model

Maximum steam capacity Power Stages

Total max current draw (amps)

Single-phase Three-phase lbs/hr kg/h kW Contactors 120V 208V 240V 277V 480V 600V 208V 240V 380V 480V 600V

RX-63-3 63 28.6 21 3 — 115.4 — — — — — — — — —

RX-75-3 75 34.0 25 3 — 129.8 112.5 130 — — — — — — —

RX-90-3 90 40.8 30 3 — — 125 130 — — 99.9 — — — —

RX-102-3 102 46.3 34 3 — — — 130 — — 99.9 — — — —

RX-126-3 126 57.1 42 3 — — — — — — 124.9 108.3 — — —

RX-144-3 144 65.3 48 3 — — — — 100 — — 129.9 — — —

RX-162-3 162 73.5 54 3 — — — — 112.5 — — 129.9 — — —

RX-189-3 189 85.7 63 3 — — — — 137.5 110 — — 102.6 81.2 65

RX-216-3 216 98.0 72 3 — — — — — 120 — — 123.1 97.4 77.9

RX-243-3 243 110.2 81 3 — — — — — 135 — — 123.1 97.4 77.9

RX-102-4 102 46.3 34 4 — 173.1 150 — — — — — — — —

RX-126-4 126 57.1 42 4 — — 183.3 173.3 — — — — — — —

RX-144-4 144 65.3 48 4 — — — 173.3 — — 133.2 — — — —

RX-162-4 162 73.5 54 4 — — — — — — 166.5 — — — —

RX-216-4 216 98.0 72 4 — — — — 150 — — 173.2 — — —

RX-264-4 264 119.7 88 4 — — — — 183.3 146.7 — — 164.1 129.9 103.9

RX-288-4 288 130.6 96 4 — — — — — 160 — — 164.1 129.9 103.9

RX-324-4 324 146.9 108 4 — — — — — 180 — — 164.1 129.9 103.9

•All RTS humidifier models operate at 50/60 Hz.
•For wire sizing, the highest leg draw is shown due to current imbalance.
•See Table 70-1 for heaters.
•Maximum amps is determined based on the heaters used by each model. Some voltage/kW combinations show higher amperage values than

what the unit capacity will allow.

• The standard Short Circuit Current Rating (SCCR) for the RTS humidifier is 5kA. A 100kA rating is available as an option.

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 4 OF 16REV. 07/25

Indoor and no enclosure dimensions (RX-XX-1 and RX-XX-2)

OM-8076

Top view

Back viewFront view

Bottom view

M Door access

Electrical knockout

Touch screen

Steam outlet

Mounting holes (4)

E

C

A Q

R

B

D

Probe

K

F H

LN

J & G

0.75” (DN 20) NPT/BSP fill 1” (DN25) NPT/BSP drain

FIGURE 4-1: RTS HUMIDIFIER DIMENSIONS

See Table 5-1 for dimension.

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 5 OF 16REV. 07/25

Indoor and no enclosure dimensions (RX-XX-1 and RX-XX-2)

Table 5-1:

Indoor unit dimensions

Description

RX-XX-1 RX-XX-2

inches mm inches mm

A Overall length 24.8 629 26.1 663

B Overall width 16.4 416 21.0 533

C Overall height 24.9 632 31.4 798

D Steam outlet

11.3 286 11.9 301

E 2.8 70 3.3 83

F Supply water

1.6 41 3.0 76

G 2.6 66 1.6 41

H Drain water

4.0 102 3.0 76

J 2.6 66 4.0 102

K Electrical knockout (Control)

8.8 224 2.8 71

L 9.1 231 10.1 256

M Electrical knockout (Power)

2.8 71 8.8 224

N 9.6 244 9.4 239

Q Mounting holes

16.0 406 16.0 406

R 21.3 541 28.0 711

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 6 OF 16REV. 07/25

Indoor and no enclosure dimensions (RX-XX-3 and RX-XX-4)

FIGURE 6-1: RTS HUMIDIFIER DIMENSIONS

Table 6-1:

Indoor unit dimensions

Description

RX-XX-3 & RX-XX-4

inches mm

A Overall length 37.4 950

B Overall width 21.6 549

C Overall height 41.3 1049

D Steam outlet

5.3 135

E 5.9 150

F Supply water

5.7 145

G 4.3 109

H Drain water

4.7 119

J 7.2 183

K Electrical knockout

8.3 211

L 4.2 107

M Steam outlet (flange connection only) 3.5 89

OM-8077

Top view

Back viewFront view

L

Touch screen keypad

Steam outlet E

C

A

B

D

Fill

H

G

K

Side view

Door access

F

J

Electrical knockout

Drain

Probe

M

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 7 OF 16REV. 07/25

Weights:RX-XX-1 and RX-XX-2

Table 7-1:

RTS humidifier (RX-XX-1 and RX-XX-2) weights

RTS

model

Indoor Enclosure Outdoor Enclosure No Enclosure

Dry Weight* (Empty) Operating Weight Dry Weight*

(Empty) Operating Weight Dry Weight* (Empty) Operating Weight lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg

RX-6-1 92.9 42.2 137.1 62.3 357.7 162.6 401.5 182.5 91.3 41.5 135.5 61.6

RX-12-1 94.1 42.8 138.3 62.9 358.5 163.0 402.7 183.0 92.5 42.0 136.7 62.1

RX-18-1 95.3 43.3 139.5 63.4 359.7 163.5 403.9 183.6 93.7 42.6 137.9 62.7

RX-24-1 95.3 43.3 139.5 63.4 359.7 163.5 403.9 183.6 93.7 42.6 137.9 62.7

RX-30-1 95.3 43.3 139.5 63.4 359.7 163.5 403.9 183.6 93.7 42.6 137.9 62.7

RX-36-1 95.3 43.3 139.5 63.4 359.7 163.5 403.9 183.6 93.7 42.6 137.9 62.7

RX-42-1 95.7 43.5 139.9 63.6 360.1 163.7 404.3 183.8 94.1 42.8 138.3 62.9

RX-48-1 96.1 43.7 140.3 63.8 360.5 163.9 404.7 184.0 94.5 43.0 138.7 63.0

RX-63-1 97.0 44.1 141.2 64.2 361.4 164.3 405.6 184.4 95.4 43.4 139.6 63.5

RX-75-1 98.0 44.5 142.2 64.6 362.4 164.7 406.6 184.8 96.4 43.8 140.6 63.9

RX-30-2 132.6 60.3 246.9 112.2 397.6 180.7 511.9 232.7 131.6 59.8 245.9 111.8

RX-36-2 132.6 60.3 246.9 112.2 397.6 180.7 511.9 232.7 131.6 59.8 245.9 111.8

RX-48-2 136.6 62.1 250.9 114.0 401.6 182.5 515.9 234.5 135.6 61.6 249.9 113.6

RX-63-2 136.6 62.1 250.9 114.0 401.6 182.5 515.9 234.5 135.6 61.6 249.9 113.6

RX-75-2 140.6 63.9 254.9 115.8 405.6 184.4 519.9 236.3 139.6 63.5 253.9 115.4

RX-90-2 138.2 62.8 252.5 114.8 403.2 183.3 517.5 235.2 137.2 62.4 251.5 114.3

RX-102-2 139.0 63.2 253.3 115.1 404.0 183.6 518.3 235.6 138.0 62.7 252.3 114.7

RX-126-2 140.0 63.6 254.3 115.6 405.0 184.1 519.3 236.0 139.0 63.2 253.3 115.1

RX-144-2 141.0 64.1 255.3 116.0 406.0 184.5 520.3 236.5 140.0 63.6 254.3 115.6

RX-162-2 142.0 64.5 256.3 116.5 407.0 185.0 521.3 236.9 141.0 64.1 255.3 116.0

* Add approximately 46 lbs (21 kg) for packaging material for shipping weight.

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 8 OF 16REV. 07/25

Weights: RX-XX-3 and RX-XX-4

Table 8-1:

RTS humidifier (RX-XX-3 and RX-XX-4) weights

RTS model

Indoor Enclosure Outdoor Enclosure No Enclosure

Dry Weight* Operating Weight Dry Weight* Operating Weight Dry Weight* Operating Weight lbs kg lbs kg lbs kg lbs kg lbs kg lbs kg

RX-63-3 193.5 88.0 450.4 204.7 476.3 216.5 733.1 333.2 166.0 75.5 422.9 192.2

RX-75-3 192.6 87.5 449.5 204.3 475.4 216.1 732.2 332.8 165.1 75.0 422.0 191.8

RX-90-3 197.1 89.6 454.0 206.4 479.9 218.1 736.7 334.9 169.6 77.1 426.5 193.9

RX-102-3 197.1 89.6 454.0 206.4 479.9 218.1 736.7 334.9 169.6 77.1 426.5 193.9

RX-126-3 198.3 90.1 455.2 206.9 481.1 218.7 737.9 335.4 170.8 77.6 427.7 194.4

RX-144-3 199.5 90.7 456.4 207.4 482.3 219.2 739.1 336.0 172.0 78.2 428.9 194.9

RX-162-3 200.7 91.2 457.6 208.0 483.5 219.8 740.3 336.5 173.2 78.7 430.1 195.5

RX-189-3 202.5 92.0 459.4 208.8 485.3 220.6 741.8 337.2 175.0 79.5 431.9 196.3

RX-216-3 203.7 92.6 460.6 209.4 486.5 221.1 743.3 337.9 176.2 80.1 433.1 196.9

RX-243-3 205.2 93.3 462.1 210.0 488.0 221.8 744.8 338.6 177.7 80.8 434.6 197.5

RX-102-4 196.2 89.2 453.1 205.9 479.0 217.7 735.8 334.5 168.7 76.7 425.6 193.4

RX-126-4 201.0 91.4 457.9 208.1 483.8 219.9 740.6 336.6 173.5 78.9 430.4 195.6

RX-144-4 202.2 91.9 459.1 208.7 483.4 219.7 741.8 337.2 174.7 79.4 431.6 196.2

RX-162-4 203.8 92.6 460.7 209.4 486.6 221.2 743.4 337.9 176.3 80.1 433.2 196.9

RX-216-4 207.0 94.1 463.9 210.9 489.8 222.6 746.6 339.4 179.5 81.6 436.4 198.4

RX-264-4 209.4 95.2 466.3 211.9 492.2 223.7 749.0 340.5 181.9 82.7 438.8 199.4

RX-288-4 211.0 95.9 467.9 212.7 493.8 224.4 750.6 341.2 183.5 83.4 440.4 200.2

RX-324-4 213.0 96.8 469.9 213.6 495.8 225.3 752.6 342.1 185.5 84.3 442.4 201.1

* Add approximately 46 lbs (21 kg) for packaging material for shipping weight.

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 9 OF 16REV. 07/25

Location and clearance recommendations (Indoor and no enclosure)

FIGURE 9-1: RX SERIES CLEARANCE RECOMMENDATIONS FOR -1 AND -2 MODELS (INDOOR AND NO ENCLOSURE UNITS)

Top: 12"(305 mm)

Right side:

6" (152 mm)*

Supporting wall

Front electrical controls:

36" (915 mm)

Floor: 12"(305 mm) Plumbing connections

Left side: 2" (51 mm)

Secured to supporting wall

To dispersion assembly

OM-8041

Maintain these clearances for service and maintenance.

* � If there is more space available, increase the clearance on this side of the unit. Infrequent access may be required to the hoses behind the electrical cabinet.

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 10 OF 16REV. 07/25

Location and clearance recommendations (Indoor and no enclosure)

Table 10-1:

Floor stand weights and height (for indoor enclosures)

Part number Unit size

Weight configuration Height

Assembled Shipping inches mm lbs kg lbs kg

600935 -2 stage 26.8 12.2 30.8 14.0

19.25 489

600670 -3 & -4 stage 35.1 16.0 41.1 18.7

FIGURE 10-1: RX SERIES CLEARANCE RECOMMENDATIONS FOR -3 AND -4 MODELS (INDOOR AND NO ENCLOSURE UNITS)

Top: 12"(305 mm)

Right side:

24" (610 mm) Plumbing connections

Front:

36" (915 mm) Electrical controls

Left side: 2" (51 mm)

To dispersion assembly

OM-8078

Maintain these clearances for service and maintenance.

Back side: 2" (51 mm)

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 11 OF 16REV. 07/25

Outdoor enclosure: Dimensions

Table 11-1:

Outdoor unit amps (all models)

Full Load Amps (Heater Package)

Full Load Amps (No Heater Package)

120V 60 Hz

230V 50Hz

120V 60Hz

230V 50Hz

7.0 3.7 0.3 0.2

Table 11-1:

Outdoor enclosure dimensions

Description RX-XX-1 RX-XX-2 RX-XX-3 and RX-XX-4 inches mm inches mm inches mm

A Overall length 53.6 1361 53.6 1361 62.8 1595

B Overall width 32.8 833 32.8 833 32.8 833

C Overall height 62.0 1575 62.0 1575 62.0 1575

D Steam outlet (external)

55.0 1397 55.0 1397 55.0 1397

E 19.5 495 18.9 480 11.1 282

F Steam outlet (internal)

5.6 142 6.1 155 8.6 218

G 6.7 170 6.7 170 6.2 157

H Pipe chase position

4.4 112 4.4 112 4.4 112

J 4.4 112 4.4 112 4.4 112

K Pipe chase dimensions

14.0 356 14.0 356 14.0 356

L 7.0 178 7.0 178 7.0 178

FIGURE 11-1: OUTDOOR ENCLOSURE DIMENSIONS

OM-8093

E

G

K

H

F

B

J

Exit for steam outlet (through pipe chase)

Pipe chase

Ventilation fan

Heater

Control cabinet

RTS

humidifier

Ventilation fan

Access panel door

Exit for steam outlet

Airflow

Airflow

Access panel door

L

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 12 OF 16REV. 07/25

Outdoor enclosure: Clearances

Top: 6" (152 mm)

Right side electrical controls:

30" (76 mm)

Front 36" (915 mm)

• External steam outlet:

(16" (406 mm)

• Internal steam outlet:

(6" (152 mm)

Left side: 6" (152 mm)

OM-8097

FIGURE 12-1: RTS SERIES CLEARANCE RECOMMENDATIONS

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 13 OF 16REV. 07/25

3/8" typical clearance

Unit base Weather stripping Wood nailer (by installer)Insulation and cant (by installer)

B D

A C

1"x 2" (25 mm x 50 mm) wood nailer

3" (76 mm) typical

Cross section view

DM-7496

Table 13-1:

Outdoor enclosure curb dimensions

Outdoor enclosure model A B C D inches mm inches mm inches mm inches mm

RX-XX-1 and RX-XX-2 47.63 1209.8 45.48 1155.2 26.73 678.9 24.73 628.1

RX-XX-3 and RX-XX-4 56.73 1440.9 54.58 1386.3 26.73 678.9 24.73 628.1

Outdoor enclosure curb details and dimensions

FIGURE 13-1: RX SERIES OUTDOOR ENCLOSURE CURB DETAILS AND DIMENSIONS

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 14 OF 16REV. 07/25

RTS Humidifier: Dispersion

INSTALLING SPACE DISTRIBUTION UNITS (SDU)

Provide at least 6" (150 mm) clearance on each side of the SDU.

Field wiring is required to connect the SDU fan and airflow proving switch terminals to RTS electrical panel terminals. Refer to the external connections diagram in the package shipped with your unit.

Important: Maximum ambient RH must not exceed 45% for the SDU-I to operate properly.

Table 14-1:

SDU specifications

SDU model Maximum capacity Shipping weight Amps at

120V (50/60 Hz)

Horsepower cfm m3/s dB* lbs/hr kg/h lbs kg

SDU-I-RX 30 13.6 67 30.4 3.20 1/5 760 0.36 58

SDU-E-RX 126 57 61 27.7 2.07 1/8 545 0.26 64

* Measurement taken 6.5' (2 m) in front of SDU cabinet.

RX-XX-3 and RX-XX-4 models cannot be used with an SDU.

SDU's ship separate from the RX humidifier.

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 15 OF 16REV. 07/25

FIGURE 15-1: SDU-I-RX MECHANICAL DETAIL

Front view Side view

OM-8110

FIGURE 15-2: SDU-E-RX MECHANICAL DETAIL

Front view Side view

OM-8111

Back view

Back view

BA

FD

16.0" (406.4 mm)

Air intake vent

E

Humidifier air discharge vent Mounting holes (2)

3.13” (80 mm)

A

F D

16.0" (406.4 mm)

3.13” (80 mm)

Mounting holes (2)

B

Steam outlet

C

Table 15-1:

SDU dimension

SDU model A B C D E F in mm in mm in mm in mm in mm in mm

SDU-I-RX 24.7 627 16.0 406 17.9 455 11.4 290 2.8 70 Ø1.5 Ø38

SDU-E-RX 24.7 627 16.0 406 16.1 409 11.4 290 2.8 70 Ø1.5

or Ø2*

Ø38 or Ø51*

* 1.5" (38 mm) or 2" (51 mm) up to 75 lbs/hr. 2" (51 mm) only greater than 75 lbs/hr.

C

E

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 16 OF 16REV. 07/25

As steam is discharged from the SDU-E, it quickly cools and turns to a visible fog that is lighter than air. As this fog is carried away from the SDU-E by the airstream, it tends to rise toward the ceiling. If this fog contacts solid surfaces (columns, beams, ceiling, pipes, etc.) before it disappears, it could collect and drip as water. The greater the space relative humidity, the more the fog will rise, throw and spread.

Table 16-1 lists the minimum rise, throw and spread non-wetting distances for SDU-E at 40%, 50% and 60% RH in the space. Surfaces cooler than ambient temperature, or objects located within this minimum dimension, can cause condensation and dripping. To avoid steam impingement on surrounding areas, observe the minimum non-wetting distances in Table 16-1.

The SDU-E contains a blower (120 V, single-phase, 60 Hz) and an airflow proving switch (field-wired to the humidifier electrical panel). A wiring diagram of the SDU-E is included with the unit.

On a call for humidity, the humidifier begins producing steam, and the start relay energizes the SDU-E blower. When the call for humidity is satisfied, the Vapor-logic controller keeps the blower running to disperse residual moisture using a time delay.

Steam outlet

Throw

Air intake grille

OM-8114

Rise

FIGURE 16-1: SDU-E RISE, SPREAD, AND

THROW

Spread

DRISTEEM RTS HUMIDIFIER SUBMITTAL • PAGE 17 OF 16REV. 07/25

Table 17-1:

SDU-E-RX minimum nonwetting distances kW of

RTS

Maximum steam capacity

40% RH @ 70 °F (21 °C) 50% RH @ 70 °F (21 °C) 60% RH @ 70 °F (21 °C)

Rise Spread Throw Rise Spread Throw Rise Spread Throw lbs/hr kg/h ft m ft m ft m ft m ft m ft m ft m ft m ft m

2 6 2.7 1.0 0.3 1.0 0.3 5.0 1.5 1.5 0.5 1.5 0.5 6.5 2.0 2.5 0.8 2.5 0.8 7.5 2.3

4 12 5.4 1.0 0.3 1.0 0.3 5.0 1.5 1.5 0.5 1.5 0.5 6.5 2.0 2.5 0.8 2.5 0.8 7.5 2.3

6 18 8.2 1.0 0.3 1.0 0.3 5.0 1.5 1.5 0.5 1.5 0.5 6.5 2.0 2.5 0.8 2.5 0.8 7.5 2.3

8 24 10.9 1.0 0.3 1.0 0.3 5.5 1.7 1.5 0.5 1.5 0.5 6.5 2.0 2.5 0.8 2.5 0.8 7.5 2.3

10 30 13.6 1.5 0.5 1.5 0.5 6.0 1.8 2.0 0.6 2.0 0.6 7.0 2.1 3.0 1.0 3.0 1.0 8.0 2.5

12 36 16.3 1.5 0.5 1.5 0.5 6.0 1.8 2.0 0.6 2.0 0.6 7.0 2.1 3.0 1.0 3.0 1.0 8.0 2.5

14 42 19.1 2.0 0.6 2.0 0.6 7.0 2.1 2.0 0.6 2.0 0.6 7.0 2.1 3.0 1.0 3.0 1.0 9.0 2.7

16 48 21.8 2.0 0.6 2.0 0.6 7.0 2.1 2.0 0.6 2.0 0.6 7.0 2.1 3.0 1.0 3.0 1.0 9.0 2.7

21 63 28.6 2.0 0.6 2.0 0.6 7.5 2.3 2.5 0.8 2.5 0.8 10.0 3.0 3.0 1.0 3.0 1.0 12.0 3.7

25 75 34.0 2.0 0.6 2.0 0.6 8.0 2.5 2.5 0.8 2.5 0.8 10.5 3.2 3.5 1.1 3.5 1.1 12.5 3.8

30 90 40.9 2.0 0.6 2.0 0.6 8.0 2.5 2.5 0.8 2.5 0.8 10.5 3.2 3.5 1.1 3.5 1.1 12.5 3.8

34 102 46.3 2.0 0.6 2.0 0.6 8.0 2.5 2.5 0.8 2.5 0.8 10.5 3.2 3.5 1.1 3.5 1.1 12.5 3.8

42 126 57.1 2.5 0.6 2.5 0.6 8.5 2.5 3.0 0.8 3.0 0.8 11 3.2 4.0 1.1 4.0 1.1 13 3.8

Notes:

• Surfaces or objects directly in the path of steam discharge may cause condensation and dripping.

• To avoid steam impingement on surrounding areas, observe the minimum nonwetting dimensions in this table.

• Rise: The minimum nonwetting height above the steam outlet of the SDU-E-RX.

• Spread: The minimum nonwetting width from the steam outlet of the SDU-E-RX. Spread dimensions greater than 3 ft (1 m) may require additional side clearance.

• Throw: The minimum nonwetting horizontal distance from the steam outlet of the SDU-E-RX.