SG - Supply Grille Cutsheet.pdf

PDF 222 KB Posted

Attached to
Design Bid Build (DBB) Construction Requirement for Alburg Springs Land Port of Entry (LPOE), Alburg, Vermont
Solicitation number
47PB5126R0008
Issued by
Not on record

About this file

This is a submittal sheet for the 600 Series Aluminum Louvered Face Supply Grille manufactured by Price Industries. The document provides comprehensive technical specifications and configuration options for HVAC supply grilles.

The 600 Series is available in two primary deflection configurations: Model 610 (Adjustable Single Deflection) and Model 620 (Adjustable Double Deflection), with blade orientation options of either parallel to the long dimension (L) or short dimension (S). Grille construction features aluminum louvers with panel options in either steel (3P, 916P, 17P, 15P) or aluminum (3PA, 916PA, 17PA, 15PA). Minimum grille size is 6" x 4" (152mm x 102mm), with maximum one-piece construction at 48" x 48" (1219mm x 1219mm). Available lay-in frame options include models F (1¼" flat frame), NF (¾" flat frame), and N (1" narrow frame) for 15/16" T-Bar ceiling systems, along with specialized panels for 9/16" flat T-Bar and 9/16" bolt slot configurations. Surface mount frames (F, N, D) accommodate duct mounting applications with specified dimensional parameters. Fastening options include countersunk screws (A), 2" drillpoint screws (AD2), concealed mounting brackets (C), or no screwholes (0). Optional accessories include VCS3 coated steel or VCS3AL aluminum opposed blade dampers, 18/16 mesh insect screens, and round neck adapters. Standard finish is B12 (Standard White), with custom colors and ARMSTRONG coordinated finishes available. Multi-section construction is available for installations exceeding 48" x 48" up to 144" x 96", utilizing aluminum duct mounting channels and mullions, with sections shipping loose for field installation.

View the file

Other files

File Type Posted
27. Amendment 47PB5126R0008 0008 2026 07 13.pdf PDF
3. Agreement Rev 2 2026 06 18.pdf PDF
25. Amendment 47PB5126R0008 0007 2026 06 18.pdf PDF
6. WD VT20250027 2026 05 18.pdf PDF
1. Solicitation Rev 1_2026 06 11.pdf PDF
2. SF1442 Rev 1 dated 2026 06 15.pdf PDF
3. Agreement Rev 1 2026 06 12.pdf PDF
21. Amendment 47PB5126R0008 0006 2026 06 15.pdf PDF
20. Amendment 47PB5126R0008 0005 2026 06 02.pdf PDF
19. Amendment 47PB5126R0008 0004 2026 05 29.pdf PDF
16. Alburg Springs - Port Signage SOW-ASR 01.pdf PDF
15. Amendment 47PB5126R0008 0003 2026 05 21.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes_Rev 1 Amendment 0002_ 2026 05 15.pdf PDF
14. Amendment 47PB5126R0008 0002 2026 05 15.pdf PDF
13. Amendment 47PB5126R0008 0001 2026 05 12.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
RP - Vertical Radiant Panel Cutsheet.pdf PDF
RG - Return Grille Cutsheet.pdf PDF
ET - Expansion Tank Cutsheet.pdf PDF
FT - Fin Tube Cutsheet.pdf PDF
GFT - Glycol Feed Tank Cutsheet.pdf PDF
BT - Buffer Tank Cutsheet.pdf PDF
FB - Filter Box Cutsheet.pdf PDF
PUH - Propeller Unit Heater Cutsheet.pdf PDF
GI and GR - Gravity Intake and Relief Cutsheet.pdf PDF
DH - Duct Mounted Humidifier Cutsheet.pdf PDF
SG and EG - Security Grille Cutsheet.pdf PDF
BSF - Booth Supply Fan Cut Sheet.pdf PDF
RP - Horizontal Radiant Panel Cutsheet.pdf PDF
AS - Air Separator Cutsheet.pdf PDF
EHC - Electric Heating Coil Cutsheet.pdf PDF
2026-02-06 Review of Proposed Renovations - Historic Context (1).pdf PDF
4. GSA527-21a 2026 04 15.pdf PDF
FCU - Fan Coil Unit Cutsheet.pdf PDF
6. WD VT20250027 2026 04 15.pdf PDF
CP and GP - Pump Cutsheets.pdf PDF
3. Agreement 2026 04 15.pdf PDF
EH - Electric Wall Heater Cutsheet.pdf PDF
7. PBS PPQ 2026 04 15.pdf PDF
GSHP - Ground Source Heat Pump Cutsheet.pdf PDF
L - Louver Cutsheet.pdf PDF
HP and CU - Heat Pump Mini-Split Cutsheet.pdf PDF
8. Tips on Preparing a Subcontracting Plan 2026 04 15.pdf PDF
HUM - Steam Humidifier Cutsheet.pdf PDF
Alburg Springs VT LPOE Code Report - 20260206 (1).pdf PDF
9. Model Subcontracting Plan 2026 04 15.docx DOCX document
5. Proprietary Information Agreement 2026 04 15.docx DOCX document
EF - Exhaust Fan Cutsheet.pdf PDF
Show 40 more

Latest 50 of 56 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

3/4" (19mm)

APPROVED BY:

3/4/2025

Aluminum

Submittal Sheet

600 Series

Louvered Face Supply Grille

PROJECT:

269915

620-1-2

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

A

DRAWING NO:

ALL METRIC DIMENSIONS [ ] ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

ENGINEER:

SHEET 1 OF 5

DATE DRAWN:

REV© Copyright PRICE INDUSTRIES 2025 610-1-2

600 - Aluminum Louvered Face Supply Grille

Adjustable Single Deflection

□ 610

Front blades parallel to short dimension

□ S

620□

Adjustable Double Deflection

3/4" (19mm) 3/4" (19mm)

Front blades parallel to long dimension

□ L

SUPPLY

parallel to nominal size dimension larger than 24" (610mm)

• For supply grilles, visible mullions are included when blades are

MATERIAL:

֩• Grille: Aluminum construction

• Panel: Steel construction (3P, 916P, 17P and 15P)

Aluminum construction (3PA, 916PA, 17PA and 15PA)

NOTES:

BLADE ORIENTATION :

15/16" T-Bar 15/16" T-Bar

9/16"

15/16" T-Bar

9/16" T-Bar

Ceiling Module = Panel Size

Max. Grille Size = Ceiling Module - 4" (102mm)

Panel Face = Ceiling Module - 1" (25mm)

Max. Grille Size = Ceiling Module - 4" (102mm)

Ceiling Module = Panel Size

15/16" T-Bar

600 Series

Louvered Face Supply Grille

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

610-1-2

620-1-2

DRAWING NO:

ALL METRIC DIMENSIONS [ ] ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

© Copyright PRICE INDUSTRIES 2025 SHEET 2 OF 5

3/4/2025

DATE DRAWN:

REV

269915

APPROVED BY:

Aluminum

A

Submittal Sheet 600 - Aluminum Louvered Face Supply Grille

Overall = D + 1 3/4" (44mm)

Ceiling Module = D + 2" (51mm)

D = Nominal Duct

1 1/4" (32mm)

AVAILABLE SIZES :

֩• Minimum size: 6" x 4" (152mm x 102mm)

• Maximum size one piece construcition: 48" x 48" (1219mm x 1219mm)

• 3P, 3PA, 17P, 17PA, 916P, 916PA, 15P and 15PA Panels:

□ 12" x 12" (305mm x 305mm) Ceiling Module

□ 24" x 12" (610mm x 305mm) Ceiling Module

□ 24" x 24" (610mm x 610mm) Ceiling Module

□ 48" x 24" (1219mm x 610mm) Ceiling Module

• F and N frames available for surface mount applications in multiple sections with mullions and / or duct mounting channels - see page 5 for details

SURFACE MOUNT FRAMES:

□ F - 1 1/4" (32mm) Flat Frame for 15/16" T-Bar Lay-In

LAY-IN FRAMES:

□ NF - 3/4" (19mm) Flat Frame for 15/16" T-Bar Lay-In

□ 3P - Steel Panel for 15/16" T-Bar Lay-In

□ 3PA - Aluminum Panel for 15/16" T-Bar Lay-In

□ 916P - Steel Panel for 9/16" Flat T-Bar

□ 916PA - Aluminum Panel for 9/16" Flat T-Bar

□ 17P - Steel Panel for 9/16" Bolt Slot or Tegular T-Bar

□ 17PA - Aluminum Panel for 9/16" Bolt Slot or Tegular T-Bar

□ 15P - Steel Panel for 15/16" Tegular T-Bar

□ 15PA - Aluminum Panel for 15/16" Tegular T-Bar

Ceiling Module = D + 1" (25mm)

Overall = D + 23/32" (18mm)

D = Nominal Duct

3/4" (19mm)

Panel Face

= Ceiling Module- 5/8" (16mm)

Max. Grille Size =

Ceiling Module - 4" (102mm)

Ceiling Module = Panel Size

5/16"

Panel Overall = Ceiling Module - 1/4" (6mm)

Ceiling Module = Panel Size

Max. Grille Size

= Ceiling Module - 4" (102mm)

D = Nominal Duct

Overall = D + 1 1/4" (32mm)

□ N - 1" (25mm) Narrow Frame

1" (25mm)

Panel Overall = Ceiling Module - 1/8" (3mm)

Overall = D + 1 3/4" (44mm)

D = Nominal Duct

□ F - 1 1/4" (32mm) Flat Frame

1 1/4" (32mm)

Duct Size + 2 1/2" (64mm)

Duct Size + 3/16" (5mm)

Opening = Duct Size + 1/4" (6mm)

□ D - 3/8" (10mm) Flat Mounting Frame with 1 1/4" (32mm) Frame

3/8" (10mm)

Varies with duct diameter & nominal width

600 Series

Louvered Face Supply Grille

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

610-1-2

620-1-2

DRAWING NO:

ALL METRIC DIMENSIONS [ ] ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

© Copyright PRICE INDUSTRIES 2025 SHEET 3 OF 5

3/4/2025

DATE DRAWN:

REV

269915

APPROVED BY:

Aluminum

A

Submittal Sheet 600 - Aluminum Louvered Face Supply Grille

Nom. Length + 1 3/4" (44mm)

MATERIAL:

• Adapter Frame: Galvanized steel

FINISH:

• Adapter Frame: Mill finish

NOTES:

• Intended for use in spiral or round duct applications

• Available sizes:

Min.: 6" x 4" (152mm x 102mm)

Max.: 36" x 16" (914mm x 406mm)

• Available in 1" (25mm) increments

• Open cell foam insulation provides a tight seal around the grille opening in any round duct

• Fits 600 series grilles with "F" frame

• Grille comes fastened to spiral duct frame with 'A' countersunk screw mounting

SPIRAL DUCT FRAME:

Grille

Duct Adapter

Frame

Round or Spiral Duct

Nom. With + 1 3/4" (44mm)

Nom. Duct

Diameter

Min. Nom.

Grille Width

Min. Nom.

Grille Length

10'' (254mm) 4'' (102mm) 8'' (203mm)

12'' (305mm) 4'' (102mm) 9'' (229mm)

14'' (356mm) 4'' (102mm) 11'' (279mm)

16'' (406mm) 4'' (102mm) 12'' (305mm)

18'' (457mm) 4'' (102mm) 13'' (330mm)

20'' (508mm) 4'' (102mm) 14'' (356mm)

22'' (559mm) 4'' (102mm) 15'' (381mm)

24'' (610mm) 4'' (102mm) 16'' (406mm)

26'' (660mm) 4'' (102mm) 16'' (406mm)

28'' (711mm) 4'' (102mm) 16'' (406mm)

30'' (762mm) 4'' (102mm) 16'' (406mm)

32'' (813mm) 4'' (102mm) 16'' (406mm)

34'' (864mm) 4'' (102mm) 16'' (406mm)

36'' (914mm) 4'' (102mm) 16'' (406mm)

38'' (965mm) 4'' (102mm) 16'' (406mm)

40'' (1016mm) 4'' (102mm) 16'' (406mm)

42'' (1067mm) 12'' (305mm) 16'' (406mm)

48'' (1219mm) 12'' (305mm) 16'' (406mm)

600 Series

Louvered Face Supply Grille

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

610-1-2

620-1-2

DRAWING NO:

ALL METRIC DIMENSIONS [ ] ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

© Copyright PRICE INDUSTRIES 2025 SHEET 4 OF 5

3/4/2025

DATE DRAWN:

REV

269915

APPROVED BY:

Aluminum

A

Submittal Sheet 600 - Aluminum Louvered Face Supply Grille

Max. Size = 24" x 24" (610mm x 610mm)

NOTES:

• Type A and AD2 fastening - Countersunk screw holes for #8 screws located per factory standard (screws supplied)

• Grilles are ordered by nominal duct size, for module size details in lay-in applications see page 2

• Only one of options IS or SR may be selected and are not available with 'C' mounting

• C mounting - steel construction

• Factory tolerance 1/32" (1mm)

FASTENING:

□ A - Countersunk Screw □ C - Concealed Mounting Bracket □ 0 - No Screwholes

For lay-in applications or fastening by others

DAMPERS

□ VCS3 - Coated Steel Opposed Blade Damper

□ VCS3AL - Aluminum Opposed Blade Damper - Mill finish

□ SR - Round Neck Adaptor

Coated steel construction - Mill finish

FINISH:

Standard Finsih:

□ B12 - Standard White

Optional Finishes Available:

• Optional colors

• Custom colors

• ARMSTRONG coordinated finishes

See finishes brochure for additional information.

Contact your PRICE representative for leadtimes and pricing

□ IS - Insect Screen 18/16 Mesh

Not available with Opposed Blade Damper or SR

Maximum size 48" x 48" (1219mm x 1219mm)

□ AD2 - 2" (51mm) Drillpoint Screw

Scan for link to additional product information and installation instructions

Available on frames "F" and "N"

Round Inlet Nom. Size - 1/8" (3mm)

Nom. Size - 1/16" (2mm) (Inside)

2 5/16" (59mm)

1 1/2" (38mm)

H

H

610 1 1/4" (32mm)

620 2" (51mm)

600 Series

Louvered Face Supply Grille

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

610-1-2

620-1-2

DRAWING NO:

ALL METRIC DIMENSIONS [ ] ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

© Copyright PRICE INDUSTRIES 2025 SHEET 5 OF 5

3/4/2025

DATE DRAWN:

REV

269915

APPROVED BY:

Aluminum

A

Submittal Sheet 600 - Aluminum Louvered Face Supply Grille

One dimension over 48" (1219mm)

Sizes up to 144" x 48" (3658mm x 1219mm)

Three Sections with Mullions

A A

One dimension over 48" (1219mm)

Sizes up to 96" x 48" (2438mm x 1219mm)

Two Sections with Mullion

AA

Both dimensions over 48" (1219mm)

Up to 144" x 96" (3658mm x 2438mm)

Mullions and Two Mounting Channels

A

A

B B

NOTES:

• Sections ship loose for field installation

• Duct mounting channels provided in aluminum

(Other materials available as special order)

Multi-Section Construction - Surface Mount, Sizes over 48" x 48" (1219mm x 1219mm)

Both dimensions over 48" (1219mm)

Up to 96" x 96" (2438mm x 2438mm)

Mullions and Mounting Channel

A

A

BB

SECTION A-A

3/4" (19mm)

SECTION B-B

Mounting

Channel

1/4" (6mm) for F frame 3/4" (19mm) for N frame

2" (51mm)

Ends of mounting channel fasten to opening with screws

(by others) to divide opening

File details come from the government source that posted it. Updated .