EH - Electric Wall Heater Cutsheet.pdf

PDF 1 MB Posted

Attached to
Design Bid Build (DBB) Construction Requirement for Alburg Springs Land Port of Entry (LPOE), Alburg, Vermont
Solicitation number
47PB5126R0008
Issued by
Not on record

About this file

This document is an Owner's Manual and Installation Instructions for the Runtal Electric Wall Panel (EWP), a wall-mounted electric heating system available in 6 and 8 element configurations with widths of 24", 36", or 48".

The EWP must be installed horizontally and mounted on exterior walls, preferably under windows or near entry doors, with a minimum 2" clearance from the finished floor. Installation requires K12 wall mounting brackets positioned 4" to 6" from either end of the unit, with specific height calculations: for EWP6 models, brackets should be positioned 14" plus desired floor clearance; for EWP8 models, 19½" plus floor clearance. Electrical connections must be performed by a qualified electrician in accordance with the National Electric Code and local codes, using a 1" hub fitting and Romex clamp adapter at the junction box. The unit requires connection to a line voltage thermostat or low voltage thermostat with relay for temperature regulation, positioned away from heat sources, direct sunlight, and drafts at approximately 5 feet off the floor. Rigid conduit wall plates may be required in certain installations, with supply wires fed through the junction box and connected via wire nuts. The unit is secured to the wall using lockdown brackets at the bottom.

Maintenance is minimal and involves periodic vacuuming of the grille and occasional cleaning with a water-dampened cloth only; abrasive cleaners are prohibited. Power must be disconnected at the circuit breaker before cleaning or maintenance. The EWP includes a manual reset high-limit thermostat for overheating protection. The document provides electrical specifications for multiple installation configurations at 120V, 208V, and 240V with corresponding circuit breaker ratings, wire sizes, and maximum wattage capacities. Safety precautions include keeping combustible materials away from the unit, preventing air intake blockage, avoiding operation with malfunctions, and contacting licensed electricians for service issues.

View the file

Other files

File Type Posted
27. Amendment 47PB5126R0008 0008 2026 07 13.pdf PDF
3. Agreement Rev 2 2026 06 18.pdf PDF
25. Amendment 47PB5126R0008 0007 2026 06 18.pdf PDF
6. WD VT20250027 2026 05 18.pdf PDF
1. Solicitation Rev 1_2026 06 11.pdf PDF
2. SF1442 Rev 1 dated 2026 06 15.pdf PDF
3. Agreement Rev 1 2026 06 12.pdf PDF
21. Amendment 47PB5126R0008 0006 2026 06 15.pdf PDF
20. Amendment 47PB5126R0008 0005 2026 06 02.pdf PDF
19. Amendment 47PB5126R0008 0004 2026 05 29.pdf PDF
16. Alburg Springs - Port Signage SOW-ASR 01.pdf PDF
15. Amendment 47PB5126R0008 0003 2026 05 21.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes_Rev 1 Amendment 0002_ 2026 05 15.pdf PDF
14. Amendment 47PB5126R0008 0002 2026 05 15.pdf PDF
13. Amendment 47PB5126R0008 0001 2026 05 12.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
RP - Vertical Radiant Panel Cutsheet.pdf PDF
RG - Return Grille Cutsheet.pdf PDF
SG - Supply Grille Cutsheet.pdf PDF
ET - Expansion Tank Cutsheet.pdf PDF
FT - Fin Tube Cutsheet.pdf PDF
GFT - Glycol Feed Tank Cutsheet.pdf PDF
BT - Buffer Tank Cutsheet.pdf PDF
FB - Filter Box Cutsheet.pdf PDF
PUH - Propeller Unit Heater Cutsheet.pdf PDF
GI and GR - Gravity Intake and Relief Cutsheet.pdf PDF
DH - Duct Mounted Humidifier Cutsheet.pdf PDF
SG and EG - Security Grille Cutsheet.pdf PDF
BSF - Booth Supply Fan Cut Sheet.pdf PDF
RP - Horizontal Radiant Panel Cutsheet.pdf PDF
AS - Air Separator Cutsheet.pdf PDF
EHC - Electric Heating Coil Cutsheet.pdf PDF
2026-02-06 Review of Proposed Renovations - Historic Context (1).pdf PDF
4. GSA527-21a 2026 04 15.pdf PDF
FCU - Fan Coil Unit Cutsheet.pdf PDF
6. WD VT20250027 2026 04 15.pdf PDF
CP and GP - Pump Cutsheets.pdf PDF
3. Agreement 2026 04 15.pdf PDF
7. PBS PPQ 2026 04 15.pdf PDF
GSHP - Ground Source Heat Pump Cutsheet.pdf PDF
L - Louver Cutsheet.pdf PDF
HP and CU - Heat Pump Mini-Split Cutsheet.pdf PDF
8. Tips on Preparing a Subcontracting Plan 2026 04 15.pdf PDF
HUM - Steam Humidifier Cutsheet.pdf PDF
Alburg Springs VT LPOE Code Report - 20260206 (1).pdf PDF
9. Model Subcontracting Plan 2026 04 15.docx DOCX document
5. Proprietary Information Agreement 2026 04 15.docx DOCX document
EF - Exhaust Fan Cutsheet.pdf PDF
Show 40 more

Latest 50 of 56 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Thank you for purchasing the Runtal Electric Wall Panel. We are very proud of our workmanship and quality, and we are certain that you will be thoroughly satisfied with your new Runtal Electric Wall Panel. We urge you to contact your local Runtal representative if you have comments or questions.

This manual is intended to show installation and care for your Runtal Electric Wall Panel. The electrical wiring connections must be made by a qualified professional electrician. Wiring procedures and connections must be in accordance with the National Electric Code (NEC) and local codes.

Owner’s Manual & Installation Instructions

1. �Runtal Electric Wall Panel must be properly installed before it is used.

2. �Runtal Electric Wall Panel must be connected to a switching device, thermostat / relay switch, etc.

3. �The heating element and high-limit thermostat should not be tampered with.

4. �Individual thermostats used in conjunction with the EWP will determine operational use.

Runtal North America, Inc. US Tel: 800-526-2621 s Canadian Tel: 888-829- 4901 s www.runtalnorthamerica.com

Contents:

1 Electric Wall Panel (EWP) 1 Mounting Hardware Package 1 Owner’s Manual

Tools Required:

Screw Drivers Electric Drill

Correct Orientation Incorrect Orientations

Operating Instructions

Electric Wall Panel

Proper installation requires the Runtal Electric Wall Panel to be in the horizontal position as shown. No other orientations are acceptable.

The Electric Wall Panel must be installed in a horizontal orientation as shown below.

IMPORTANT INSTRUCTIONS READ & SAVE THESE INSTRUCTIONS

L

8 Element Wall Panel Front View

EWP 8 EWP 6

Top

Bottom

8 & 6 Element Wall Panel Side View 6 Element Wall Panel Back View

23⁄8”

23⁄8” L

171⁄4”

231⁄8”

L = 24”, 36”, 48”

Mounting & Installation Overview: The EWP is designed for a very quick and easy wall mounting installation.

Simply choose an appropriate location, attach wall brackets to the wall, make the electrical connection, hang the unit on the wall and screw in the lockdowns. Please note that all installations of the Runtal EWP should be in accordance with local building and electrical codes and performed by a licensed installer.

Locating the EWP: The Runtal Electric Wall Panel (EWP) is intended to be permanently wall mounted in a horizontal position (please see the drawing for correct orientation).

It is recommended that the EWP be mounted no less than 2” above the finished floor.

Inspect the desired location for the EWP and insure that there is sufficient room for the unit and that there are no obstacles that might hinder wall mounting.

The EWP is designed so that the wall brackets K12 may be placed on the wall at stud locations. It is recommended that the wall hangers be installed roughly 4” to 6” from either end of the radiator.

Determine how much clearance between the floor and the bottom of the EWP is desired (to give you the height you need to place the wall brackets). Mark this location.

For Model EWP6: The top of the wall brackets should be 14” plus the floor clearance distance.

Example: If you would like to have 2” clearance from the floor, the top of the K12 mounting bracket should be on the wall 16” above the floor (14” for the unit and 2” for clearance).

For Model EWP8: The top of the wall brackets should be 19½” plus the floor clearance distance.

Example: If you would like to have 2” clearance from the floor, the top of the K12 mounting bracket should be on the wall 21½” above the floor (19½” for the unit and 2” for clearance).

Determine how far apart to hang the (K12) mounting brackets.

This measurement depends upon the width of the radiator to be installed as noted above.

Mark this location.

Example: A 24” wide EWP should have the mounting brackets a minimum of 12” apart and a maximum of 16” apart (4” to 6” in from either side) Using the appropriate fastener(s), firmly attach the K12 mounting brackets to the Wall in the desired locations.

Hang the EWP on the Wall brackets to insure the location is acceptable and that the wall brackets are solidly installed. If the location is acceptable remove the radiator and set aside on the wrapping foam to protect the finish.

Runtal North America, Inc. US Tel: 800-526-2621 s Canadian Tel: 888-829- 4901 s www.runtalnorthamerica.com

Mo u n t i n g EWP Step 1

IMPORTANT INSTRUCTIONS READ & SAVE THESE INSTRUCTIONS

17½”

Floor

Example

Model EWP6 (back view)

14”

K12 K12

2” Minimum Clearance

4” to 6” 4” to 6”

24”

Top

Bottom

Wiring and Locating EWP Step 2

�Please be sure to follow all applicable building and electrical codes. It is recommended that the installation be performed by a licensed electrician. The electrical supply must be from the wall at the rear of the radiator.

For ease of installation it is recommended that the supply wire coming from the wall be long enough and flexible enough to allow the electrification of the unit while placed face down on the floor (protected to insure the finish on the front of the unit is not damaged) near its wall hung location.

Mark a vertical line where the center of the radiator will be located.

Measure down from the top of the wall bracket 12½” for a EWP-6 to determine the point to drill a 2” hole in the wall for the electrical supply wires.

Measure down from the top of the wall bracket 183/8” for a EWP-8 to determine the point to drill a 2” hole in the wall for the electrical supply wires.

Step 4 Run Supply Wires

Step 3 Prepare the EWP for Wall Hanging and Electrification

Runtal North America, Inc. US Tel: 800-526-2621 s Canadian Tel: 888-829- 4901 s www.runtalnorthamerica.com

Thermostat: A line voltage thermostat or a low voltage thermostat with a relay is recommended for room temperature regulation, and for switching off the Electric Wall Panel when not in use. Thermostat and /or relay are by others, and is not supplied with the Runtal Electric Wall Panel.

Note: Thermostat location recommendations

Locate the thermostat away from the heater and other appliances that give off heat.
Locate the thermostat where it will not be in direct sunlight.
Locate the thermostat on an inside wall away from drafts.
Do not exceed the electrical rating of the thermostat ,relay or other switching device.
Most thermostats are mounted about 5 feet off the floor. Check with your local code officer, as ADA
regulations may apply.

Location: For best results locate the Electric Wall Panel on a outside wall, under a window or near an entry door.

Voltage: It is important that you verify the electrical supply voltage is the same as the Electric Wall Panel.

Connecting a 240 volt Electric Wall Panel to a 120 volt supply will decrease the heaters output:

connecting a Electric Wall Panel to a higher voltage may damage the heater and void the warranty.

Warning: Do not install heaters against combustible low density cellulose fiberboard surfaces.

Keep drapes 2 inches away from the Electric Wall Panel. Do not install Electric Wall Panel heater below an electrical convenience receptacle. To reduce the risk of fire, do not store or use gasoline or other flammable vapors and liquids in the vicinity of the heater. Only install as illustrated in this manual.

Name Plate Location: (UL Label) The name plate is located on the right side of the radiator.

IMPORTANT INSTRUCTIONS READ & SAVE THESE INSTRUCTIONS

Factory Wiring Diagram

Central Supply

L2

L1

Temperature High Limit

Step 6 Hang the Electrified Unit on the Wall

Floor

W al l

Wall Mounting Bracket K12

Mounting Screw

Mounting Screw and Cap

Add Decorative Screw Cap Before Attaching Bracket to Wall.

Lockdown Bracket

1” Hub Fitting A

Lift the EWP onto the Wall Brackets while inserting the wiring into the wall.

Locate the Lockdown Brackets on the bottom of the radiator and put a mounting screw (with screw cap) through each one into the wall.

Note: The Runtal EWP is equipped with a manual reset High-Limit Thermostat to insure against overheating. Should the radiator stop working for any reason, Runtal recommends that the power to the unit be shut off at the source (circuit breaker) and a licensed electri-cian be contacted for service.

IMPORTANT INSTRUCTIONS READ & SAVE THESE INSTRUCTIONS

Locking Down Wall Panel

Runtal North America, Inc. US Tel: 800-526-2621 s Canadian Tel: 888-829- 4901 s www.runtalnorthamerica.com

Step 5 Attach the Electrical Supply to the Unit

Remove the flat square cover from the junction box and discard. Remove the junction box Cover B and install the 1” hub Fitting A to the junction box.

Next install the Romex clamp adapter to the 1” hub fitting.

Locate the supply wire coming out of the wall and feed it through the restraint into the junction box. Allow as much wire as needed to make the connection to the radiator heater wires.

Secure the supply wire by tightening the screws on the wire restraint.

Use wire nuts to connect the green supply wire to the green grounding wire in the junction box and one of the heater wires to each of the supply wires. Make sure that all wiring connections are secure inside the junction box and replace the bottom junction box cover.

The unit is now ready for wall hanging

Cover B

Green

Hub Fitting A

Black

White

Line in

Thermostat

Romex /

Arm or ed C able Wire

Mounting Instructions for Rigid Conduit, where Required.

Secure the Rigid Conduit Wall Plate (illustration A) and connections in selected wall location, allow six (6”) inches of supply wire (illustration B) to estab-lish a connection to the radiators junction box. The radiator must be centered with the Rigid Conduit Wall Plate and the wall plate aligned with the back portion of the radiator’s electrical junction box, this will allow for access of the supply wires. Lift the EWP onto the Wall Brackets to hang while ensuring the rigid conduit from the mounted wall plate is inserted into the back of the radiator’s junction box, the wires are then fed through the bottom of the junction box and connected to the appropriate connections locat-ed in the junction box. Use wire nuts to connect the green wire to the green grounding wire in the junc-tion box and one of the heater wires to each of the supply wires. Make sure all wiring connections are secure inside the junction box, replace the bottom cover and affix the bottom cover with the provided screws. The electrified radiator unit is now ready to be securely mounted for wall hanging. The radiator must be secured to the wall at the bottom portion of the radiator with provided Lockdown Brackets.

Runtal North America, Inc. US Tel: 800-526-2621 s Canadian Tel: 888-829- 4901 s www.runtalnorthamerica.com

IMPORTANT INSTRUCTIONS READ & SAVE THESE INSTRUCTIONS

Illustration A

Conduit Nipple

Locknut

PVC Connector

Wall Plate

Assembled Rigid Conduit Wall Plate

Green

W hite

Black

Illustration B

Runtal North America, Inc. US Tel: 800-526-2621 s Canadian Tel: 888-829- 4901 s www.runtalnorthamerica.com

Operation & Maintenance Ma i n t e n a n c e & Cl e a n i n g

Your Runtal Electric Wall Panel (EWP) has been designed to require the absolute minimum maintenance and care under normal use. However, care should be taken when cleaning the surface of the panel. Periodically vacuum across the top of the grille to remove dust from the grille. A slight odor may be noticeable during initial operation and will dissipate within a few hours.

The EWP’s powder coated finish provides an elegant yet durable finish to a welded steel product.

Occasional cleaning of this finish is best done with a water dampened cloth. Under no circumstances should abrasive cleaner be used. Before cleaning make sure the power has been turned off at the circuit breaker panel, and the heating element is cool. Be sure to restore power when cleaning and maintenance is complete.

All other servicing should be performed by qualified service personnel.

For installation of multiple electric wall panel radiators, the following chart should be used.

The chart indicates supply voltage, circuit breaker rating, minimum wire size, and maximum total wattage of electric radiators on the circuit.

Ma x i m u m Wat tag e o n a C i r c u i t

Voltage A.C.Circuit Breaker SizeMaximum WattageMinimum
Wire Size
12015 Amp144014/2 with Ground
12020 Amp192012/2 with Ground
12030 Amp288010/2 with Ground
20815 Amp249614/2 with Ground
20820 Amp332812/2 with Ground
20830 Amp499210/2 with Ground
24015 Amp288014/2 with Ground
24020 Amp384012/2 with Ground
24030 Amp576010/2 with Ground

IMPORTANT INSTRUCTIONS READ & SAVE THESE INSTRUCTIONS

Runtal North America, Inc. US Tel: 800-526-2621 s Canadian Tel: 888-829- 4901 s www.runtalnorthamerica.com

IMPORTANT INSTRUCTIONS READ & SAVE THESE INSTRUCTIONS

When using electrical appliances, basic precautions should always be followed to reduce the risk of fire, electric shock, and injury to persons, including the following:

1. �Read all instructions before using this heater.

2. �A heater has hot and arcing or sparking parts inside. Do not use it in areas where gasoline, paint, or flammable liquids are used or stored.

3. �This heater is hot when in use. To avoid burns, do not let bare skin touch hot surfaces. Keep combustible materials, such as furniture, pillows, bedding, papers, clothes, and curtains away from heater.

4. �To prevent a possible fire, do not block air intakes or exhaust in any manner. Do not use on soft surfaces, like a bed, where openings may become clogged.

5. �Do not insert or allow foreign objects to enter any ventilation or exhaust opening as this may cause an electrical shock or fire, or damage the heater. Never tamper with the EWP or any of its components.

6. �Use heater only as described in this manual. Any other use not recommended by the manufacturer may cause fire, electric shock, or injury to persons.

7. �Extreme caution is necessary when any heater is used by or near children or persons which may require supervision and whenever the heater is left operating and unattended

8. �Do not operate any heater after it malfunctions. Disconnect power at service panel and have the heater inspected by a reputable electrician before reusing.

9. �Do not use outdoors.

10. �The EWP should not be in direct contact with water.

11. �To disconnect heater, turn controls to off, and turn off power to the heater circuit at main disconnect panel ( or operate internal disconnect switch if provided).

12. �The Runtal EWP is equipped with a manual reset High-Limit Thermostat to insure against overheating. Should the radiator stop working for any reason, Runtal recommends that the power to the unit be shut off at the source (circuit breaker) and a licensed electrician be contacted for service.

13. SAVE THESE INSTRUCTIONS

Important Instructions

Runtal North America, Inc.

PO Box 8278, Ward Hill, MA 01835 (Haverhill) Tel: 800-526-2621 s In Canada: 888 829-4901 www.runtalnorthamerica.com