BSF - Booth Supply Fan Cut Sheet.pdf
PDF 429 KB Posted
- Solicitation number
- 47PB5126R0008
- Issued by
- Not on record
About this file
This is a product specification cut sheet for the Greenheck CSP-A390-VG inline cabinet fan. The document is marked "Not for Submittal" and was generated on December 5, 2025, for Mark BSF-1.
The CSP-A390-VG is an inline cabinet fan featuring corrosion-resistant galvanized steel construction with sound-absorbing insulation, a double inlet forward curved wheel, and a spring-loaded back draft damper. Selected options include a Vari-Green EC motor with 0-10 VDC input signal, wiring harness, UL/cUL 507 listing, wall louvered discharge, a single pole rocker function switch, vibration isolation kit, and aluminum wheel material. The unit is Energy Star certified. Performance specifications include a requested and actual volume of 200 CFM, total external static pressure of 0.5 inches water gauge, fan speed of 1170 RPM, and noise level of 1.3 Sones. The motor operates at 230V/60Hz/1 phase with 0.04 kW input power and 0.9 FLA. Weight without accessories is 24 pounds and with accessories is 32 pounds. The unit dimensions measure 15.5 x 12.875 x 11.875 inches. AMCA certification confirms air performance ratings comply with AMCA Publication 211 and are based on installation type D (ducted inlet, ducted outlet) with performance ratings including backdraft damper effects. Ratings are calculated for 10 feet of insulated duct.
View the file
Other files
Show 40 more
Latest 50 of 56 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Model: CSP-A390-VG Inline Cabinet Fan Standard Construction Features:
- Corrosion resistant galvanized steel scroll and housing - Sound absorbing insulation - Rectangular inlet and outlet duct collar - Outlet with integral spring loaded back draft damper - Double inlet forward curved wheel - Plug type disconnect - Adjustable mounting brackets - Field rotatable discharge Selected Options & Accessories:
Motor - Vari-Green EC motor 0-10 VDC Input Signal Wiring Harness, Shipped Loose (PN: 385822) UL/cUL 507 Listed - Electric Fan Wall Louvered Discharge, (PN: WL-18X6) Shipped Loose 1 Function Switch, Single Pole Rocker (PN: 872243), Shipped Loose Isolation Kit, (PN: VI KIT-SP/CSP), Shipped Loose Adjustable easy installation mounting bracket Energy Star Certified Aluminum Wheel Material
MOUNTING
BRACKET
AIR FLOW
1/4 in. threaded rod (field provided)
Vibration Isolators (from manufacturer)
11.25 8 10
12.875
11.875 1 1
15.5
6.75
Dimensional Quantity 1
Weight w/o Acc's (lb) 24 Weight w/ Acc's (lb) 32
Performance Requested Volume (CFM) 200
Actual Volume (CFM) 200
Total External SP (in. wg) 0.5
Fan RPM 1170
* FLA (A) 0.9
Elevation (ft) 62
Airstream Temp.(F) 0
Air Density (lb/ft3) 0.086
Sones 1.3
Motor Motor Mounted Yes
** FEP Input Power (kW) 0.04
Voltage/Cycle/Phase 230/60/1 Enclosure TEAO
Control Input Voltage 6.4 Notes:
All dimensions shown are in units of in.
*FLA is approximate and will vary slightly with the motor.
Sones - calculated using AMCA 301 at 5 ft ** Wattage is approximate and may vary between motors.
Cut Sheet - Not for Submittal 12/05/2025Printed Date:
BSF-1Mark:
CSP-A390-VGModel:
Generated by: sheckman@rfsengineering.comCAPS 4.48.1062 Page 1 of 3 C:\Users\smh1028\OneDrive - RFS Engineering\Documents\CAPS\Jobs\10199.gfcj
CSP-A390-VG Min/Max Fan Curve
Performance Requested
Volume
(CFM)
Actual Volume
(CFM)
Total External SP (in. wg)
Fan
RPM
Operating Power (hp)
200 200 0.5 1170 0.06
Cut Sheet - Not for Submittal 12/05/2025Printed Date:
BSF-1Mark:
CSP-A390-VGModel:
Generated by: sheckman@rfsengineering.comCAPS 4.48.1062 Page 2 of 3
AMCA
AMCA Licensed for Air Performance. Power rating (BHP/kW) does not include transmission losses.
Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings seal applies to air performance ratings only. Performance certified is for installation type D: Ducted inlet, Ducted outlet. Performance ratings include the effects of a backdraft damper. Speed (RPM) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are for loudness values in spherical sones at 5 ft. (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type D: ducted inlet spherical sone levels. Ratings do not include the effects of duct end correction. Ratings are based on 10 ft. of insulated duct.
Cut Sheet - Not for Submittal 12/05/2025Printed Date:
BSF-1Mark:
CSP-A390-VGModel:
Generated by: sheckman@rfsengineering.comCAPS 4.48.1062 Page 3 of 3