About this file

This is a product specification document for the Greenheck IDHE Series electric duct heater. The IDHE is the industry's first and only electric duct heater approved by UL for multiple mounting positions, allowing the control cabinet to be installed on either side of a horizontal duct or in any orientation on a vertical duct. The heater features UL 1996 certification, 50/60 Hz compatibility, zero clearance rating, hinged control cabinet cover, power and control terminal boards, automatic reset thermal safety switch, and heavy gauge G60 construction. The absolute maximum capacity is 478.8 kW, with individual maximum capacities dependent on voltage/phase, control type, and heater dimensions.

Standard construction specifications include universal airflow direction, magnetic contactor, universal control box offset, 24 Vac control voltage, standard 80/20 element wire, SCR or Vernier SCR heater control stages, slip-in or flange heater types, galvanized steel material, and unfused control transformer. Optional features include airflow switches, disconnect switches with door interlock, duct thermostats, dust-tight boxes, fan interlock, pilot lights, power fusing (required at 48 amps or larger), recesses for insulated ducts, room thermostats, stainless steel hardware, time delay relays, and vapor barriers. Available voltage/phase options are 120/1 (standard) and 208/1, 208/3, 240/1, 240/3, 277/1, 480/1, and 480/3 (optional). Size limitations range from 8 x 8 inches minimum to 120 x 144 inches maximum (consulting factory required for heights exceeding 90 inches). Air flow requirements specify a maximum inlet air temperature of 110°F and maximum heater capacity of 30 kW per square foot of duct cross section, with minimum air velocity determined by provided charts correlating inlet air temperature and CFM to kW minimum.

View the file

Other files

File Type Posted
27. Amendment 47PB5126R0008 0008 2026 07 13.pdf PDF
3. Agreement Rev 2 2026 06 18.pdf PDF
25. Amendment 47PB5126R0008 0007 2026 06 18.pdf PDF
6. WD VT20250027 2026 05 18.pdf PDF
1. Solicitation Rev 1_2026 06 11.pdf PDF
2. SF1442 Rev 1 dated 2026 06 15.pdf PDF
3. Agreement Rev 1 2026 06 12.pdf PDF
21. Amendment 47PB5126R0008 0006 2026 06 15.pdf PDF
20. Amendment 47PB5126R0008 0005 2026 06 02.pdf PDF
19. Amendment 47PB5126R0008 0004 2026 05 29.pdf PDF
16. Alburg Springs - Port Signage SOW-ASR 01.pdf PDF
15. Amendment 47PB5126R0008 0003 2026 05 21.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes_Rev 1 Amendment 0002_ 2026 05 15.pdf PDF
14. Amendment 47PB5126R0008 0002 2026 05 15.pdf PDF
13. Amendment 47PB5126R0008 0001 2026 05 12.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
RP - Vertical Radiant Panel Cutsheet.pdf PDF
RG - Return Grille Cutsheet.pdf PDF
SG - Supply Grille Cutsheet.pdf PDF
ET - Expansion Tank Cutsheet.pdf PDF
FT - Fin Tube Cutsheet.pdf PDF
GFT - Glycol Feed Tank Cutsheet.pdf PDF
BT - Buffer Tank Cutsheet.pdf PDF
FB - Filter Box Cutsheet.pdf PDF
PUH - Propeller Unit Heater Cutsheet.pdf PDF
GI and GR - Gravity Intake and Relief Cutsheet.pdf PDF
DH - Duct Mounted Humidifier Cutsheet.pdf PDF
SG and EG - Security Grille Cutsheet.pdf PDF
BSF - Booth Supply Fan Cut Sheet.pdf PDF
RP - Horizontal Radiant Panel Cutsheet.pdf PDF
AS - Air Separator Cutsheet.pdf PDF
2026-02-06 Review of Proposed Renovations - Historic Context (1).pdf PDF
4. GSA527-21a 2026 04 15.pdf PDF
FCU - Fan Coil Unit Cutsheet.pdf PDF
6. WD VT20250027 2026 04 15.pdf PDF
CP and GP - Pump Cutsheets.pdf PDF
3. Agreement 2026 04 15.pdf PDF
EH - Electric Wall Heater Cutsheet.pdf PDF
7. PBS PPQ 2026 04 15.pdf PDF
GSHP - Ground Source Heat Pump Cutsheet.pdf PDF
L - Louver Cutsheet.pdf PDF
HP and CU - Heat Pump Mini-Split Cutsheet.pdf PDF
8. Tips on Preparing a Subcontracting Plan 2026 04 15.pdf PDF
HUM - Steam Humidifier Cutsheet.pdf PDF
Alburg Springs VT LPOE Code Report - 20260206 (1).pdf PDF
9. Model Subcontracting Plan 2026 04 15.docx DOCX document
5. Proprietary Information Agreement 2026 04 15.docx DOCX document
EF - Exhaust Fan Cutsheet.pdf PDF
Show 40 more

Latest 50 of 56 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

The IDHE series is the industry’s first and only electric duct heater approved by UL for multiple mounting positions. This allows the control cabinet to be installed on either side of a horizontal duct or in any orientation on a vertical duct. The control cabinet is offset from the heating elements similar to traditional heaters.

However, the IDHE affords the installer the flexibility to position the offset on the left or right as preferred.

The IDHE has the following standard features:

• UL 1996 certified
• 50/60 Hz compatibility
• Zero clearance rating
• Hinged control cabinet cover
• Power and control terminal boards
• Automatic reset thermal safety switch for
primary over temperature protection
• Heavy gauge G60 construction

Individual maximum capacities are dependent on voltage/phase, control type, and heater dimensions.

Absolute maximum capacity: 478.8 kW

* The Greenheck model IDHE duct heater is universally configured to allow airflow in either direction in all mounting orientations.

Options available:

• Airflow switch (adjustable or fixed set point)

• Disconnect switch with door interlock

• Duct thermostat (available with SCR control)

• Dust tight box with gasketed door

• Fan interlock

• Pilot light

• Power fusing required when 48 amps or larger

• Recess for internally insulated ducts

• Room thermostat

• Stainless steel hardware

• Time delay relay - delay heater or delay stages

• Vapor barrier

* �Vernier SCR is required in heaters greater than 48 amps to comply with NEC requirements.

** �Slip in heaters are 1⁄8 in. (3 mm) undersized for the width and 1⁄4 in.

(6 mm) undersized for the height.

W x H Minimum Size Maximum Size

Inches 8 x 8 120 x 144* mm 203 x 203 3048 x 3658

* Consult factory for heights larger than 90 in. ( 2286mm)

Size Limitations

Standard Optional

Airflow Direction Universal -

Contactor Magnetic -

Control Box Offset Universal -

Control Voltage 24 Vac -

Element Wire Standard 80/20

Heater Control Stage SCR, Vernier SCR*

Heater Type Slip in** Flange

Heater Voltage/ Phase

120/1 208/1, 208/3, 240/1, 240/3, 277/1, 480/1, 480/3

Material Galvanized Steel -

Recess (in.) None 1, 2, 3

Control Transformer

Unfused Fused, None

Deration (kW) None .035, .025

Construction

IDHE

Duct Heater

Application

IDHE October 2025

IDHE: Air Flow Requirements Minimum Air Velocity: See charts below

Maximum Inlet Air Temp: 110°F

Maximum Heater KW: 30 KW per Square Foot of Duct Cross Section

IDHE October 2025

Document Links

TRIFOLDINSTALLATION

SPECIFICATIONS

SELECTION GUIDE

WARRANTY

IDHE

Duct Heater

Copyright ® 2025 Greenheck Fan Corporation

IDHE, R11, October 2025

Greenheck Fan Corporation reserves the right to make product changes without notice https://content.greenheck.com/public/DAMProd/Original/10011/DuctHeater_quadfold.pdf https://content.greenheck.com/public/DAMProd/Original/10001/478052ductheaters_iom.pdf https://content.greenheck.com/public/DAMProd/Original/10010/IDHBIDHE_spec.rtf https://content.greenheck.com/public/DAMProd/Original/10002/InteractiveDamperSelectionGuide.pdf https://content.greenheck.com/public/DAMProd/Original/10002/ductheater_warranty.pdf

File details come from the government source that posted it. Updated .