DH - Duct Mounted Humidifier Cutsheet.pdf
PDF 157 KB Posted
- Solicitation number
- 47PB5126R0008
- Issued by
- Not on record
About this file
This is a product specification and submittal document for the DriSteem Ultra-Sorb Model MP steam dispersion panel, a humidification device used in HVAC applications.
The Ultra-Sorb Model MP is a customizable steam dispersion panel available in sizes ranging from 12" to 144" in both width and height (in 1" increments), with unit widths from 15" to 147" and heights from 19.375" to 151.375". The panel features Type 304 stainless steel construction and can be configured with either 1.5" or 2.0" diameter dispersion tubes. For evaporative steam applications, the unit delivers 700 lbs/hr capacity, while pressurized steam (2-50 psi) achieves 2,720 lbs/hr capacity. Individual tube capacities range from 40-43 lbs/hr for 1.5" tubes and 77-80 lbs/hr for 2.0" tubes, with insulated options available for improved efficiency. The humidifier accepts multiple steam inlet configurations including 1" or 2" NPT couplings for pressurized steam, 1.5" or 2" NPT couplings for evaporative steam, and 3" or 4" flange connections, with metric BSPT and hose connection options also available. The unit includes a ¾" NPT drain port and mounting flanges designed for vertical installation with horizontal airflow. Panels exceeding 98" in height are shipped unassembled and include Type 304 stainless steel components, connection hardware, tube grommets, and for boiler steam applications, float and thermostatic traps, inlet strainers, and control valves. Installation requires 100% airflow passage through the unit with sealed openings, minimum water seals (10" for pressurized, 5" for non-pressurized applications), and proper condensate drainage with air gap provisions.
View the file
Other files
Show 40 more
Latest 50 of 56 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRISTEEM ULTRA-SORB MODEL MP SUBMITTAL • PAGE 1 OF 5REV. 0319
Ultra-sorb Model MP steam dispersion panel mechanical specifications
FIGURE 1-1: ULTRA-SORB MODEL MP DIMENSIONS
OM-7915_mp
Top view
Elevation view
Blank side view
Header
Connections side view
A
A’
B’
C D
B
F
E
G
H
J
All except with 4" NPT steam inlet
4" NPT
steam inlet
G
H
Note:
See Table page 2-1: Ultra-sorb MP dimensions
DRISTEEM ULTRA-SORB MODEL MP SUBMITTAL • PAGE 2 OF 5REV. 0319
Table 2-1:
Ultra-sorb Model MP dimensions
Dimension Inches (mm)
A Unit width 15" (380 mm) min, 147" (3735 mm) max, in ½" (13 mm) increments
A' Face width 12" (305 mm) min, 144" (3660 mm) max, in ½" (13 mm) increments
B Unit height* 19.375" (492 mm) min, 151.375" (3845 mm) max, in ½" (13 mm) increments
B' Face height 12" (305 mm) min, 144" (3660 mm) max, in ½" (13 mm) increments
C Frame depth 7.2" (183 mm) 2.3" (58 mm) for side drain port (H) when 4" coupling (DN100) steam inlet
D Frame enclosure 1.5" (38 mm)
E Header enclosure 5.85" (149 mm)
F Mounting flange 1.5" (38 mm)
G �Humidification steam inlet
| • | �1" or 2" NPT coupling, for pressurized steam |
| • | 1½" or 2" NPT coupling, for evaporative steam |
| • | 3" or 4" flange, for evaporative steam |
| • | DN25 or DN50 BSPT nipple, for pressurized steam |
| • | DN50, DN80, or DN100 BSPT nipple, for evaporative steam |
| • | 1½" or 2" (DN40 or DN50) hose, for evaporative steam |
H �Drain port (internal thread) ¾" NPT (DN20) coupling
J Overall width
| • | �1" NPT coupling, dimension A + 1/8"; |
| • | �1½" NPT coupling, dimension A + ½"; |
| • | 2" NPT coupling, dimension A + 1" |
| • | 3" and 4" flange connection, dimension A + 6.5" |
| • | DN25, DN50, DN80 BSP nipple, dimension A + 38 mm |
| • | DN100 BSP nipple, dimension A + 64 mm |
| • | 1½" or 2" (DN40 or DN50) hose connection, dimension A + ½" (dimension A + 13 mm) |
* �Panels with unit height more than 120" (3048 mm) have two-piece side flanges and are shipped with brackets for easy field assembly. Panels with unit height more than 98" (2490 mm) are shipped unassembled.
DRISTEEM ULTRA-SORB MODEL MP SUBMITTAL • PAGE 3 OF 5REV. 0319
Ultra-sorb Model MP connections, capacities, and dispersion tube detail
Table 3-2:
Ultra-sorb Model MP tube capacity*
Tubes lbs/hr kg/hr
1.5" Uninsulated 40 18.1
Insulated 43 19.5
2.0" Uninsulated 77 34.9
Insulated 80 36.3
* If face height (B') is <17" (432 mm), consult DriSteem or see DriCalc for the correct calculation.
Table 3-1:
Ultra-sorb Model MP unit capacity Evaporative steam Pressurized steam (2-50 psi) lbs/hr kg/hr lbs/hr kg/hr
700 318 2720 1235
OM-7841
Steam inlet location
Grommet
1½” (Typ)
¾” Offset (Typ)
1½ or 2" Dia.
dispersion tube
OM-7842
Orifice tubelet
Airflow
¾" (DN20) threaded condensate drain outlet
FIGURE 3-1: ULTRA-SORB MODEL MP STEAM INLET AND CONDENSATE
OUTLET POSITIONS
FIGURE 3-2: DISPERSION TUBE DETAIL
Steam supply header separator
Tubelets
Dispersion tubes
Dispersion tube insulation
OM-7843
Steam
FIGURE 3-4: INSULATED TUBE DETAIL
(HIGH-EFFICIENCY TUBE OPTION)
Grommet
DRISTEEM ULTRA-SORB MODEL MP SUBMITTAL • PAGE 4 OF 5REV. 0319
Ultra-sorb Model MP mounting - pressurized steam application
Notes:
1. Locate drain air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.
2. Dashed lines indicate provided by installer.
3. Steam supply line to unit and piping are not included.
4. Mount the Ultra-sorb Model MP vertically (for horizontal airflow only).
5. For pressurized steam applications provide a 10" (255 mm) minimum water seal.
6. Locate drain air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.
7. When mounting an Ultra-sorb in a duct, headers and flanges are mounted outside the duct.
8. 100% of the airflow must pass through the Ultra-sorb, which means that any openings surrounding it must be sealed. The blanked-off area below the Ultra-sorb provides clearance height for water seals, and condensate piping connections.
9. �Due to the pressure drop across the valve, the steam pressure at the header traps is minimal. Condensate must be drained.
10. Dispersion tubes are available at : 3" (76 mm), 4" (102 mm; for 2" diameter only), 6" (152 mm), 9" (228 mm), 12" (305 mm) centers.
11. �Ultra-sorb humidifiers will be assembled, crated, and shipped intact in all sizes up to 98" (2490 mm) tall. Ultra-sorb can be shipped unassembled, by request, requiring field assembly.
12. Sizes are 12" to 144" (305 mm to 3658 mm) x 12" to 144" (305 mm to 3658 mm) in 1" (25 mm) increments.
Each Ultra-sorb humidifier is furnished with:
1. Type 304 stainless steel header/separator and dispersion tubes when shipped unassembled.
2. Hardware for connection of dispersion tubes to header when shipped unassembled.
3. Tube grommets for connection when shipped unassembled.
Each Ultra-sorb humidifier used with boiler steam is also furnished with:
1. One 3/4" NPT float and thermostatic trap (≤15 psi steam source) or an inverted bucket trap for steam main drip leg use (>15 psi).
2. Inlet "Y" strainer.
3. Normally closed steam valve with stainless steel parabolic plug and seat.
Install strainer within 3' (1 m) of Ultra-sorb
Face width
Water seal (see Note 5)
Condensate header
1½" (38 mm) flange
AHU width
Face height
AHU/
Overall height
¾" (DN20) pipe thread
Valve
Open drain 1" (25 mm) air gap (see Note 1)
Tubelets perpendicular to airflow
OM-7839
FIGURE 4-1: MOUNTING ULTRA-SORB MODEL MP (PRESSURIZED STEAM APPLICATION SHOWN)
≥ 2" (51 mm)
Blanked-off area
DRISTEEM ULTRA-SORB MODEL MP SUBMITTAL • PAGE 5 OF 5REV. 0319
Ultra-sorb Model MP mounting - nonpressurized steam application
Water seal (see Note 4)
Typical evaporative humidifier
Depending on humidification load, interconnecting piping may be hose, tubing, or hard pipe
Face width
Blanked-off area
Position tubelets perpendicular to airflow
Insulate tubing and hard pipe to reduce steam loss
≥ 2" (51 mm)
1½" (38 mm) flange
AHU width
Face height AHU/Overall height
¾" (DN20) pipe thread
*Pitch 1/8"/ft (1%)
90˚ long sweep or two 45˚ elbows
Notes:
1. Locate drain air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.
2. When mounting an Ultra-sorb in a duct, headers and flanges are mounted outside the duct.
3. Mount the Ultra-sorb Model MP vertically (for horizontal airflow only).
4. For non-pressurized steam, provide a 5" (127 mm) minimum water seal with a 2" (51 mm) minimum drop from the header connection.
5. 100% of the airflow must pass through the Ultra-sorb, which means that any openings surrounding it must be sealed. The blanked-off area below the Ultra-sorb provides clearance height for water seals and condensate piping connections.
6. Condensate must be drained.
7. Dispersion tubes are available at: 3" (76 mm), 4" (102 mm; for 2" diameter only), 6" (152 mm), 9" (228 mm), 12" (305 mm) centers.
8. �Ultra-sorb humidifiers will be assembled, crated, and shipped intact in all sizes up to 98" (2490 mm) wide. Ultra-sorb can be shipped unassembled, by request, requiring field assembly.
9. Sizes are 12" to 144" (305 mm to 3658 mm) x 12" to 144" (305 mm to 3658 mm) in 1" (25 mm) increments.
Each Ultra-sorb humidifier is furnished with:
| 1. | Type 304 stainless steel header/separator and dispersion tubes when shipped unassembled. |
| 2. | Hardware for connection of dispersion tubes to header when shipped unassembled. |
| 3. | Tube grommets for connection when shipped unassembled. |
*For electrode type humidifiers pitch towards Ultra-sorb MP steam dispersion panel.
OM-7840
Open drain 1" (25 mm) air gap:
(see Note 1)
FIGURE 5-1: MOUNTING ULTRA-SORB MODEL MP (NONPRESSURIZED STEAM APPLICATION SHOWN)
Condensate header
File details come from the government source that posted it. Updated .