This is a product specification and submittal document for the DriSteem Ultra-Sorb Model MP steam dispersion panel, a humidification device used in HVAC applications.

The Ultra-Sorb Model MP is a customizable steam dispersion panel available in sizes ranging from 12" to 144" in both width and height (in 1" increments), with unit widths from 15" to 147" and heights from 19.375" to 151.375". The panel features Type 304 stainless steel construction and can be configured with either 1.5" or 2.0" diameter dispersion tubes. For evaporative steam applications, the unit delivers 700 lbs/hr capacity, while pressurized steam (2-50 psi) achieves 2,720 lbs/hr capacity. Individual tube capacities range from 40-43 lbs/hr for 1.5" tubes and 77-80 lbs/hr for 2.0" tubes, with insulated options available for improved efficiency. The humidifier accepts multiple steam inlet configurations including 1" or 2" NPT couplings for pressurized steam, 1.5" or 2" NPT couplings for evaporative steam, and 3" or 4" flange connections, with metric BSPT and hose connection options also available. The unit includes a ¾" NPT drain port and mounting flanges designed for vertical installation with horizontal airflow. Panels exceeding 98" in height are shipped unassembled and include Type 304 stainless steel components, connection hardware, tube grommets, and for boiler steam applications, float and thermostatic traps, inlet strainers, and control valves. Installation requires 100% airflow passage through the unit with sealed openings, minimum water seals (10" for pressurized, 5" for non-pressurized applications), and proper condensate drainage with air gap provisions.

View the file

Other files

File Type Posted
27. Amendment 47PB5126R0008 0008 2026 07 13.pdf PDF
3. Agreement Rev 2 2026 06 18.pdf PDF
25. Amendment 47PB5126R0008 0007 2026 06 18.pdf PDF
6. WD VT20250027 2026 05 18.pdf PDF
1. Solicitation Rev 1_2026 06 11.pdf PDF
2. SF1442 Rev 1 dated 2026 06 15.pdf PDF
3. Agreement Rev 1 2026 06 12.pdf PDF
21. Amendment 47PB5126R0008 0006 2026 06 15.pdf PDF
20. Amendment 47PB5126R0008 0005 2026 06 02.pdf PDF
19. Amendment 47PB5126R0008 0004 2026 05 29.pdf PDF
16. Alburg Springs - Port Signage SOW-ASR 01.pdf PDF
15. Amendment 47PB5126R0008 0003 2026 05 21.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes_Rev 1 Amendment 0002_ 2026 05 15.pdf PDF
14. Amendment 47PB5126R0008 0002 2026 05 15.pdf PDF
13. Amendment 47PB5126R0008 0001 2026 05 12.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
RP - Vertical Radiant Panel Cutsheet.pdf PDF
RG - Return Grille Cutsheet.pdf PDF
SG - Supply Grille Cutsheet.pdf PDF
ET - Expansion Tank Cutsheet.pdf PDF
FT - Fin Tube Cutsheet.pdf PDF
GFT - Glycol Feed Tank Cutsheet.pdf PDF
BT - Buffer Tank Cutsheet.pdf PDF
FB - Filter Box Cutsheet.pdf PDF
PUH - Propeller Unit Heater Cutsheet.pdf PDF
GI and GR - Gravity Intake and Relief Cutsheet.pdf PDF
SG and EG - Security Grille Cutsheet.pdf PDF
BSF - Booth Supply Fan Cut Sheet.pdf PDF
RP - Horizontal Radiant Panel Cutsheet.pdf PDF
AS - Air Separator Cutsheet.pdf PDF
EHC - Electric Heating Coil Cutsheet.pdf PDF
2026-02-06 Review of Proposed Renovations - Historic Context (1).pdf PDF
4. GSA527-21a 2026 04 15.pdf PDF
FCU - Fan Coil Unit Cutsheet.pdf PDF
6. WD VT20250027 2026 04 15.pdf PDF
CP and GP - Pump Cutsheets.pdf PDF
3. Agreement 2026 04 15.pdf PDF
EH - Electric Wall Heater Cutsheet.pdf PDF
7. PBS PPQ 2026 04 15.pdf PDF
GSHP - Ground Source Heat Pump Cutsheet.pdf PDF
L - Louver Cutsheet.pdf PDF
HP and CU - Heat Pump Mini-Split Cutsheet.pdf PDF
8. Tips on Preparing a Subcontracting Plan 2026 04 15.pdf PDF
HUM - Steam Humidifier Cutsheet.pdf PDF
Alburg Springs VT LPOE Code Report - 20260206 (1).pdf PDF
9. Model Subcontracting Plan 2026 04 15.docx DOCX document
5. Proprietary Information Agreement 2026 04 15.docx DOCX document
EF - Exhaust Fan Cutsheet.pdf PDF
Show 40 more

Latest 50 of 56 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRISTEEM ULTRA-SORB MODEL MP SUBMITTAL • PAGE 1 OF 5REV. 0319

Ultra-sorb Model MP steam dispersion panel mechanical specifications

FIGURE 1-1: ULTRA-SORB MODEL MP DIMENSIONS

OM-7915_mp

Top view

Elevation view

Blank side view

Header

Connections side view

A

A’

B’

C D

B

F

E

G

H

J

All except with 4" NPT steam inlet

4" NPT

steam inlet

G

H

Note:

See Table page 2-1: Ultra-sorb MP dimensions

DRISTEEM ULTRA-SORB MODEL MP SUBMITTAL • PAGE 2 OF 5REV. 0319

Table 2-1:

Ultra-sorb Model MP dimensions

Dimension Inches (mm)

A Unit width 15" (380 mm) min, 147" (3735 mm) max, in ½" (13 mm) increments

A' Face width 12" (305 mm) min, 144" (3660 mm) max, in ½" (13 mm) increments

B Unit height* 19.375" (492 mm) min, 151.375" (3845 mm) max, in ½" (13 mm) increments

B' Face height 12" (305 mm) min, 144" (3660 mm) max, in ½" (13 mm) increments

C Frame depth 7.2" (183 mm) 2.3" (58 mm) for side drain port (H) when 4" coupling (DN100) steam inlet

D Frame enclosure 1.5" (38 mm)

E Header enclosure 5.85" (149 mm)

F Mounting flange 1.5" (38 mm)

G �Humidification steam inlet

•�1" or 2" NPT coupling, for pressurized steam
•1½" or 2" NPT coupling, for evaporative steam
•3" or 4" flange, for evaporative steam
•DN25 or DN50 BSPT nipple, for pressurized steam
•DN50, DN80, or DN100 BSPT nipple, for evaporative steam
•1½" or 2" (DN40 or DN50) hose, for evaporative steam

H �Drain port (internal thread) ¾" NPT (DN20) coupling

J Overall width

•�1" NPT coupling, dimension A + 1/8";
•�1½" NPT coupling, dimension A + ½";
•2" NPT coupling, dimension A + 1"
•3" and 4" flange connection, dimension A + 6.5"
•DN25, DN50, DN80 BSP nipple, dimension A + 38 mm
•DN100 BSP nipple, dimension A + 64 mm
•1½" or 2" (DN40 or DN50) hose connection, dimension A + ½" (dimension A + 13 mm)

* �Panels with unit height more than 120" (3048 mm) have two-piece side flanges and are shipped with brackets for easy field assembly. Panels with unit height more than 98" (2490 mm) are shipped unassembled.

DRISTEEM ULTRA-SORB MODEL MP SUBMITTAL • PAGE 3 OF 5REV. 0319

Ultra-sorb Model MP connections, capacities, and dispersion tube detail

Table 3-2:

Ultra-sorb Model MP tube capacity*

Tubes lbs/hr kg/hr

1.5" Uninsulated 40 18.1

Insulated 43 19.5

2.0" Uninsulated 77 34.9

Insulated 80 36.3

* If face height (B') is <17" (432 mm), consult DriSteem or see DriCalc for the correct calculation.

Table 3-1:

Ultra-sorb Model MP unit capacity Evaporative steam Pressurized steam (2-50 psi) lbs/hr kg/hr lbs/hr kg/hr

700 318 2720 1235

OM-7841

Steam inlet location

Grommet

1½” (Typ)

¾” Offset (Typ)

1½ or 2" Dia.

dispersion tube

OM-7842

Orifice tubelet

Airflow

¾" (DN20) threaded condensate drain outlet

FIGURE 3-1: ULTRA-SORB MODEL MP STEAM INLET AND CONDENSATE

OUTLET POSITIONS

FIGURE 3-2: DISPERSION TUBE DETAIL

Steam supply header separator

Tubelets

Dispersion tubes

Dispersion tube insulation

OM-7843

Steam

FIGURE 3-4: INSULATED TUBE DETAIL

(HIGH-EFFICIENCY TUBE OPTION)

Grommet

DRISTEEM ULTRA-SORB MODEL MP SUBMITTAL • PAGE 4 OF 5REV. 0319

Ultra-sorb Model MP mounting - pressurized steam application

Notes:

1. Locate drain air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.

2. Dashed lines indicate provided by installer.

3. Steam supply line to unit and piping are not included.

4. Mount the Ultra-sorb Model MP vertically (for horizontal airflow only).

5. For pressurized steam applications provide a 10" (255 mm) minimum water seal.

6. Locate drain air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.

7. When mounting an Ultra-sorb in a duct, headers and flanges are mounted outside the duct.

8. 100% of the airflow must pass through the Ultra-sorb, which means that any openings surrounding it must be sealed. The blanked-off area below the Ultra-sorb provides clearance height for water seals, and condensate piping connections.

9. �Due to the pressure drop across the valve, the steam pressure at the header traps is minimal. Condensate must be drained.

10. Dispersion tubes are available at : 3" (76 mm), 4" (102 mm; for 2" diameter only), 6" (152 mm), 9" (228 mm), 12" (305 mm) centers.

11. �Ultra-sorb humidifiers will be assembled, crated, and shipped intact in all sizes up to 98" (2490 mm) tall. Ultra-sorb can be shipped unassembled, by request, requiring field assembly.

12. Sizes are 12" to 144" (305 mm to 3658 mm) x 12" to 144" (305 mm to 3658 mm) in 1" (25 mm) increments.

Each Ultra-sorb humidifier is furnished with:

1. Type 304 stainless steel header/separator and dispersion tubes when shipped unassembled.

2. Hardware for connection of dispersion tubes to header when shipped unassembled.

3. Tube grommets for connection when shipped unassembled.

Each Ultra-sorb humidifier used with boiler steam is also furnished with:

1. One 3/4" NPT float and thermostatic trap (≤15 psi steam source) or an inverted bucket trap for steam main drip leg use (>15 psi).

2. Inlet "Y" strainer.

3. Normally closed steam valve with stainless steel parabolic plug and seat.

Install strainer within 3' (1 m) of Ultra-sorb

Face width

Water seal (see Note 5)

Condensate header

1½" (38 mm) flange

AHU width

Face height

AHU/

Overall height

¾" (DN20) pipe thread

Valve

Open drain 1" (25 mm) air gap (see Note 1)

Tubelets perpendicular to airflow

OM-7839

FIGURE 4-1: MOUNTING ULTRA-SORB MODEL MP (PRESSURIZED STEAM APPLICATION SHOWN)

≥ 2" (51 mm)

Blanked-off area

DRISTEEM ULTRA-SORB MODEL MP SUBMITTAL • PAGE 5 OF 5REV. 0319

Ultra-sorb Model MP mounting - nonpressurized steam application

Water seal (see Note 4)

Typical evaporative humidifier

Depending on humidification load, interconnecting piping may be hose, tubing, or hard pipe

Face width

Blanked-off area

Position tubelets perpendicular to airflow

Insulate tubing and hard pipe to reduce steam loss

≥ 2" (51 mm)

1½" (38 mm) flange

AHU width

Face height AHU/Overall height

¾" (DN20) pipe thread

*Pitch 1/8"/ft (1%)

90˚ long sweep or two 45˚ elbows

Notes:

1. Locate drain air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.

2. When mounting an Ultra-sorb in a duct, headers and flanges are mounted outside the duct.

3. Mount the Ultra-sorb Model MP vertically (for horizontal airflow only).

4. For non-pressurized steam, provide a 5" (127 mm) minimum water seal with a 2" (51 mm) minimum drop from the header connection.

5. 100% of the airflow must pass through the Ultra-sorb, which means that any openings surrounding it must be sealed. The blanked-off area below the Ultra-sorb provides clearance height for water seals and condensate piping connections.

6. Condensate must be drained.

7. Dispersion tubes are available at: 3" (76 mm), 4" (102 mm; for 2" diameter only), 6" (152 mm), 9" (228 mm), 12" (305 mm) centers.

8. �Ultra-sorb humidifiers will be assembled, crated, and shipped intact in all sizes up to 98" (2490 mm) wide. Ultra-sorb can be shipped unassembled, by request, requiring field assembly.

9. Sizes are 12" to 144" (305 mm to 3658 mm) x 12" to 144" (305 mm to 3658 mm) in 1" (25 mm) increments.

Each Ultra-sorb humidifier is furnished with:

1.Type 304 stainless steel header/separator and dispersion tubes when shipped unassembled.
2.Hardware for connection of dispersion tubes to header when shipped unassembled.
3.Tube grommets for connection when shipped unassembled.

*For electrode type humidifiers pitch towards Ultra-sorb MP steam dispersion panel.

OM-7840

Open drain 1" (25 mm) air gap:

(see Note 1)

FIGURE 5-1: MOUNTING ULTRA-SORB MODEL MP (NONPRESSURIZED STEAM APPLICATION SHOWN)

Condensate header