HP and CU - Heat Pump Mini-Split Cutsheet.pdf
PDF 3 MB Posted
- Solicitation number
- 47PB5126R0008
- Issued by
- Not on record
About this file
This document is a submittal for HVAC equipment specifications for two projects at the 10199 Alburg Springs location, submitted on October 28, 2025, in the design stage.
The first project, the LAN Room, specifies a Mitsubishi Electric Trane HVAC system consisting of a PCA-AK24NL ceiling-suspended indoor unit (21,800 BTU/H rated capacity) paired with a PUZ-AH24NL heat pump outdoor unit (21,800 BTU/H rated heating capacity). Key specifications include SEER2 rating of 20.2, EER2 of 12, and HSPF2 of 9.3, with 208/230V single-phase 60Hz electrical service. The system features an inverter-driven compressor, low ambient cooling to 0°F, seacoast protection with blue fin coating, and pre-charged refrigerant for up to 165 feet of line length. The indoor unit offers multiple airflow settings, washable filter with status indicator, and multiple control options including comfort app and wireless controllers. Maximum piping length is 165 feet with maximum height difference of 100 feet.
The second project, the Inspection Booth, specifies a Mitsubishi Electric wall-mounted system with MSZ-GX24NL indoor unit (22,400 BTU/H rated cooling) and MUZ-GX24NLHZ inverter hyper-heat pump outdoor unit (22,400 BTU/H rated). This system delivers SEER2 of 21.5, EER2 of 13, and HSPF2 of 10, with Hyper-Heating INVERTER (H2i) technology providing 100% heating capacity down to 5°F with guaranteed heating to -22°F. The indoor unit features dual barrier coating for easier maintenance, econo cool mode, electrostatic enzyme filter, and multiple fan speed options. Both systems include detailed accessory options for remote controllers, condensate pumps, linesets, and optional components, with comprehensive dimension drawings provided for installation planning.
View the file
Other files
Show 40 more
Latest 50 of 56 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Contractor:
Engineer:
Architect:
Rep/Distributor:
Project Detail:
Customer:
Address:
City:
State:
Zip:
Submittal Date:
10/28/2025
Submitted By:
Name:
Company:
Email:
Phone:
Submittal Stage: Design Only
Submittal Project Name:
10199 Alburg Springs LAN Room (Revision 1)
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
PCA-AK24NL & PUZ-AH24NL
21,800 BTU/H CEILING-SUSPENDED INDOOR UNIT
21,800 BTU/H HEAT PUMP OUTDOOR UNIT
Indoor Unit� PCA-AK24NL
Outdoor Unit� PUZ-AH24NL
Job Name:
System Reference: Date:
INDOOR UNIT FEATURES
| • | Auto fan speed mode: Automatic adjustment of fan speed |
| • | Easy-to-clean, washable filter |
| • | Filter status indicator |
| • | Ideal PCA Spaces: Ideal for larger retail stores, classrooms, and restaurants |
| • | Knock-out for outside-air intake |
| • | Light commercial: Units with this icon are suitable for light commercial applications such as small offices, restaurants, and retail. |
| • | Multi-Airflow settings: Airflow settings for high and low ceiling applications |
| • | Multiple control options, including the comfort app for remote access, third-party interfaces, and both wired and wireless controllers |
| • | Suspends from ceiling for quick and easy installation |
| • | Up and down swing-mode: An indoor unit with this capability can move air up and down throughout the room like an oscillating fan using the horizontal |
vanes.
OUTDOOR UNIT FEATURES
• Blue Fin Coating: An anti-corrosion treatment applied to the aluminum fins of the heat exchanger of the outdoor unit to protect against corrosion caused by salt, sulfur, and other airborne contaminants, especially in coastal and industrial areas.
| • | Continuous operation: 24-hour continuous operation (cooling mode) |
| • | Fast restart |
| • | High pressure protection |
| • | High pressure/temperature protection |
| • | INVERTER-driven compressor: An inverter-driven compressor generates the precise capacity needed to maintain a temperature set point. |
| • | Low ambient cooling : Low ambient cooling down to 0°F providing 100% capacity |
| • | Pre-charged refrigerant: 12k -30k BTU/h come pre-charged for ease of installation. 24k – 30k BTU/h are pre-charged to maximum line length of 225 |
feet. 12k – 18k BTU/h are pre-charged for up to 165 feet of line length. For units with a capacity of 36,000 BTU/h and above, additional refrigerant charges will be required.
• Seacoast protection: Seacoast Protection, made standard in the 2022 production, features a robust anti-corrosion system with phosphate and acrylic-enamel coated external panels, epoxy resin-coated fan motor support and separator assembly valve beds, and Blue Fin treatment for the heat exchanger coil. These components are rated for 2,000 hours of durability under ASTM B117 testing standards, ensuring longevity in corrosive coastal environments.
• Superior energy and operational efficiency
Submittal Documents
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
SPECIFICATIONS: PCA-AK24NL & PUZ-AH24NL
Cooling at 95F1
Maximum Capacity Btu/h 24,000 Rated Capacity Btu/h 21,800 Minimum Capacity Btu/h 9,800 Maximum Power Input W 2,120 Rated Power Input W 1,810 Moisture Removal Pints/h 4 Sensible Heat Factor - 0.8 Power Factor [208V / 230V] % 95 / 95
Heating at 47F2
Maximum Capacity Btu/h 30,800 Rated Capacity Btu/h 28,000 Minimum Capacity Btu/h 8,300 Maximum Power Input W 2,760 Rated Power Input W 2,413 Power Factor [208V / 230V] % 96 / 96
Heating at 17F3
Maximum Capacity Btu/h 15,300 Rated Capacity Btu/h 15,300 Maximum Power Input W 1,610 Rated Power Input W 1,610
Heating at 5F4 Maximum Capacity Btu/h 11,600 Maximum Power Input W 1,660
Heating at -4F5 Maximum Capacity Btu/h 10,400
Efficiency
SEER2 20.2
EER21 12
HSPF2 [IV] 9.3
COP at 47°F2 3.4 COP at 17°F at Maximum Capacity3 2.7 COP at 5°F at Maximum Capacity4 2 COP at -4°F at Maximum Capacity5 1.92 ENERGY STAR® Certified Yes
Electrical
Voltage, Phase, Frequency V AC / V AC, ø, Hz 208 / 230, 1, 60 Guaranteed Voltage Range V AC 198 - 253 Voltage: Indoor - Outdoor, S1-S2 V AC 208/230 Voltage: Indoor - Outdoor, S2-S3 V DC 12-24 Short-circuit Current Rating [SCCR] kA 5 Recommended Fuse/Breaker Size (Outdoor) A 25 Recommended Wire Size [Indoor - Outdoor] AWG 14
Indoor Unit
Fan Motor Output W 95 Airflow Rate at Cooling, Dry CFM 495, 530, 565, 635 Airflow Rate at Cooling, Wet CFM 530, 565, 600, 670 Airflow Rate at Heating, Dry CFM 495, 530, 565, 635 Sound Pressure Level [Cooling] dB (A) 33, 35, 37, 40 Sound Pressure Level [Heating] dB (A) 33, 35, 37, 40 External Finish Color 6.4Y 8.9/0.4
Unit Dimensions (W x D x H) inch x inch x inch [mm x mm x mm] 50-3/8 x 26-3/4 x 9-1/16 [1,280 x 680 x 230]
Package Dimensions (W x D x H) inch x inch x inch [mm x mm x mm] 53-3/16 x 29-15/16 x 12-5/8 [1,350 x 760 x 320]
Unit Weight lbs [kg] 71 [32] Package Weight lbs [kg] 82 [37] Fan Motor Type DC Motor
IDU Operating Temp. Range Cooling Intake Air Temp [Maximum / Minimum] °FDB, °FWB / °FDB, °FWB 90, 73 / 66, 59
Heating Intake Air Temp [Maximum / Minimum] °FDB 82 / 50
NOTES
1Cooling at 95°F (Indoor: 80°F DB, 67°F WB // Outdoor: 95°F DB, 75°F WB) 2Heating at 47°F (Indoor: 70°F DB, 60°F WB // Outdoor: 47°F DB, 43°F WB) 3Heating at 17°F (Indoor: 70°F DB, 60°F WB // Outdoor: 17°F DB, 15°F WB) 4Heating at 5°F (Indoor: 70°F DB, 60°F WB // Outdoor: 5°F DB, 4°F WB) 5Heating at -4°F (Indoor: 70°F DB, 60°F WB // Outdoor: -4°F DB, -5°F WB) *Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):
• Wind baffles required to operate below 23°F DB in cooling mode.
• Heat pump system with wind baffle: 0°F - 115°F.
• Refer to wind baffle documentation for further information.
** Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
• System cuts out in heating mode and automatically restarts at these temperatures.
SPECIFICATIONS: PCA-AK24NL & PUZ-AH24NL
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Outdoor Unit
MCA A 22
MOCP A 37
Fan Motor Output W 74 Airflow Rate Cooling CFM 1,940 Airflow Rate Heating CFM 1,940 Defrost Method Reverse Cycle Coating on Heat Exchanger (Bluefin, Sea Coast) Yes, Yes Sound Pressure Level, Cooling1 dB (A) 49 Sound Pressure Level, Heating2 dB (A) 52 Compressor Type Twin Rotary Compressor Model SRB172FQHMC-L1 Compressor Oil [Type // Charge] Type // oz RM68EH // 23 External Finish Color Munsell 3Y 7.8/1.1 Base Pan Heater Optional
Unit Dimensions (W x D x H) inch x inch x inch [mm x mm x mm] 37-13/32 x 14 x 37-1/8 [950 x 355 x 943]
Package Dimensions (W x D x H) inch x inch x inch [mm x mm x mm] 41-15/16 x 17-3/4 x 42-1/2 [1,065 x 450 x 1,079]
Unit Weight lbs [kg] 155 [70] Package Weight lbs [kg] 179 [81]
ODU Operating Temp. Range
Cooling Intake Air Temp [Maximum / Minimum*] °FDB 115 / 23
Heating Intake Air Temp [Maximum / Minimum] °FDB, °FWB / °FDB, °FWB 70, 59 / -4, -4
Heating Thermal Lock-out / Re-start Temperatures** °FDB -13 / -4
Refrigerant
Type R454B Pre-Charged Refrigerant Amount lbs, oz 7, 11 Maximum Pre-Charged Piping Length ft [m] 165 [50] Additional Refrigerant Charge Per Additional Piping Length oz/ft 0
Piping
Gas Pipe Size O.D. [Flared] inch [mm] 5/8 [15.88] Liquid Pipe Size O.D. [Flared] inch [mm] 3/8 [9.52] Maximum Piping Length ft [m] 165 [50] Maximum Height Difference ft [m] 100 [30] Maximum Number of Bends 15
NOTES
1Cooling at 95°F (Indoor: 80°F DB, 67°F WB // Outdoor: 95°F DB, 75°F WB) 2Heating at 47°F (Indoor: 70°F DB, 60°F WB // Outdoor: 47°F DB, 43°F WB) 3Heating at 17°F (Indoor: 70°F DB, 60°F WB // Outdoor: 17°F DB, 15°F WB) 4Heating at 5°F (Indoor: 70°F DB, 60°F WB // Outdoor: 5°F DB, 4°F WB) 5Heating at -4°F (Indoor: 70°F DB, 60°F WB // Outdoor: -4°F DB, -5°F WB) *Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):
• Wind baffles required to operate below 23°F DB in cooling mode.
• Heat pump system with wind baffle: 0°F - 115°F.
• Refer to wind baffle documentation for further information.
** Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
INDOOR UNIT ACCESSORIES: PCA-AK24NL
Control Interface
Airzone Wired Blueface Controller Black AZZBSBLUEZEROCN Airzone Wired Blueface Controller White AZZBSBLUEZEROCB Airzone Wireless Lite Controller Black AZZBSLITERN Airzone Wireless Lite Controller White AZZBSLITERB Airzone Wireless Think Controller Black AZZBSTHINKRN Airzone Wireless Think Controller White AZZBSTHINKRB IT Extender for kumo station PAC-WHS01IE-E kumo station for the Comfort app PAC-WHS01HC-E Operation and Error Status Output Adapter 1 PAC-SF40RM-E Procon BACnet and Modbus Interface PAC-UKPRC001-CN-1 Thermostat Interface for 3rd Party Thermostats PAC-US445CN-1 Wireless Interface Adapter for the Comfort app PAC-USWHS002-WF-2
Condensate
Blue Diamond Advanced Mini Condensate Pump w Reservoir Sensor 208230V recommended X87-721 Blue Diamond MaxiBlue Advanced Mini Condensate Pump w Reservoir Sensor 110V up to 48000 BTUH recommended X87-711 Blue Diamond MegaBlue Advanced Condensate Pump w Reservoir Sensor X87-835 Blue Diamond Sensor Extension Cable 15 Ft C13-103 Refco Condensate Pump 100-240 VAC up to 120000 BTUH COMBI
Wired Remote Controller
Deluxe Wired MA Remote Controller 1 PAR-42MAAUB Simple Direct Wired Remote Controller PAC-SDW01RC-1 Simple MA Remote Controller 1 PAC-YT53CRAU-J Touch MA Wired Remote Controller 1 PAR-CT01MAU-SB
Lineset
10 x 3/8 x 10 x 5/8 Lineset Twin-Tube Insulation MPLS385812T-10 100 x 3/8 x 100 x 5/8 Lineset Twin-Tube Insulation MPLS385812T-100 15 x 3/8 x 15 x 5/8 Lineset Twin-Tube Insulation MPLS385812T-15 30 x 3/8 x 30 x 5/8 Lineset Twin-Tube Insulation MPLS385812T-30 50 x 3/8 x 50 x 5/8 Lineset Twin-Tube Insulation MPLS385812T-50 65 x 3/8 x 65 x 5/8 Lineset Twin-Tube Insulation MPLS385812T-65
Power Supplies & Auxiliary Components
3-Pin Wiring Harness PAC-715AD 5-Pin Wiring Harness PAC-725AD
Wireless Remote Controller
Lockdown Bracket for Wireless Handheld Remote Controllers RCMKP1CB RedLINK Wireless Remote Controller MHK2 Universal Wireless MA Handheld Remote Controller PAR-FL32MA-E Universal Wireless Receiver for PAR-FL32MA-E PAR-FA32MA-W Wireless Handheld Controller kit with Receiver and i-See Sensor for Ceiling Suspended Models PAR-SA92MW-E Wireless Handheld Controller kit with Receiver for PCA models PAR-SL93B-E
Disconnect Switch 30A600VUL fits 2 X 4 utility box - Black TAZ-MS303 30A600VUL fits 2 X 4 utility box - White TAZ-MS303W
Remote Sensor
Flush Mount Remote Temperature Sensor for SEZ SLZ SVZ and all P-Series models PAC-USSEN002-FM-1 Wall Mount Remote Temperature Sensor PAC-SE41TS-E Wireless temperature and humidity sensor for the Comfort app PAC-USWHS003-TH-1
Power Supplies and Auxiliary Components Backup Heat Relay Kit Adapter for CN24 or CN152 Connector CN24RELAY-KIT-CM3
Filter 65 Medium Efficiency Filter MERV 8 PAC-SH89KF-E
NOTES
1Unable to use with Wireless Remote Controller
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
OUTDOOR UNIT ACCESSORIES: PUZ-AH24NL
Mini-Split Wire
14 Gauge 4 wire Armored MiniSplit Cable250 ft roll SW144-250 14 Gauge 4 wire Armored MiniSplit Cable50 ft roll SW144-50 14 Gauge 4 wire MiniSplit Cable250 ft roll S144-250 14 Gauge 4 wire MiniSplit Cable50 ft roll S144-50
Stand
18 Single Fan Stand QSMS1801M 24 Single Fan Stand QSMS2401M Condenser Wall Bracket QSWB2000M-1 Condenser Wall Bracket - Stainless Steel Finish QSWBSS Outdoor Unit 3-14 inch Mounting Base Pair - Plastic DSD-400P Outdoor Unit Stand 12 High QSMS1201M
Power Supplies & Auxiliary Components
3-Pin Wiring Harness PAC-715AD 5-Pin Wiring Harness PAC-725AD
Wind Baffle
Front Wind Baffle WB-PA5 Rear Wind Baffle WB-RE5 Side Advanced Wind Baffle WB-SD5
M-NET Converter M-Net Interface for P-Series PAC-SJ95MA-E Air Outlet Guide Air Outlet Guide 1 Piece PAC-SG59SG-E Mounting Pad Condensing Unit Mounting Pad 24 x 42 x 3 ULTRILITE2 Hail Guards Hail Guard HG-A6 Drain Socket Drain Socket PAC-SG61DS-E
Control/Service Tool ControlService Tool PAC-SK52ST M- & P-Series Maintenance Tool Cable Set M21EC0397
Optional Defrost Heater Optional Defrost Heater PAC-SK62BH-E Centralized Drain Pan Centralized Drain Pan PAC-SG64DP-E Snow/Rain Diverter SnowRain Diverter SRD-4
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Wh en dr ain so cke t is i nst alle d
3( 9-
3/
Dr ai na ge
W he n dr ai n so ck et is in st al le d
6(
9-
/1 6) i-se e s ens or liqu id Φ
9.5 2(Φ
3/8 ga s Φ
.88
(Φ 5/8
Dra ina ge
(4 6-
3/
2( 1/
2( 1/
(5 0-
3/ 8)
(1
-7 /8
8(
5/
(4 7-
3/
(3
-3 /8
2( 7-
3/
680(26-3/4)
476(18-3/4)57(2-1/4)
230(9-1/16)
195(7-11/16)
88(3-7/16)
84(3-5/16)
80(3-1/8)
680(26-3/4)
320(12-5/8)
(4 8-
/1
6) (S us pe ns io n bo lt pi tc h)
18(11/16)
0(
5- 1/
2)
(2 -7
/1 6)
150(5-7/8)
236(9-5/16)
0(
7- 7/
8)
6(
9-
/1 6)
(2
(3
/8
5( 3/
7(
-1
/4
(3
-3 /8
(3
-3 /8
(1
-1 /2
(2
-1 5/
) W he n el ec tri ca l b ox is pu lle d do wn
2( 1/
0(
-1
/4
1(1/16)
190(7-1/12)
37(1-7/16)
8(
5- 7/
126(4-15/16)
In c ase of the re ar pip e a rra nge me nt, ma ke sur e to rem ove the sh ade d p ort ion s fr om the ind epe nde nt p iec e.
Th en put the ind epe nde nt p iec e b ack in init ial pos itio n.( Th e h eat ex cha nge r m igh t be clo gge d b eca use of dus t)
Ce ilin g
El ec tri ca l b ox
[F
RO
NT
V
IE
W
(1
1/
121(4-3/4)
Φ125(Φ4-15/16)
190(7-1/2)
76(3) 124(4-7/8)
1(
-1
/8
46(1-13/16)
3(
9- 3/
NO
TE
1.
Us e M or
W 3/8 sc rew fo r a nc ho r b olt
DE
FR
OS
T/S
TA
ND
BY
lam p
Em er ge nc y o pe ra tio n sw itc h <
Co oli ng
Re cei ver Op era tion lam p
Em er ge nc y o pe ra tio n sw itc h <
He ati ng
In ca se of w ire les s r em ote co ntr oll er an d i
-se e s en so r(O pti on al
Pa rts
Kn oc ko ut ho le for up pe r d rai n p ipe ar ran ge me nt
Kn oc ko ut ho le for fre sh ai r in tak e Φ
0(Φ 3-1
5/1 6)
Kn oc ko ut ho le for w irin g a rra ng em en t Φ
(Φ 7/8
Ac ce ss ory ...D rai n s oc ke t (2 6(1
)I.D
876321 4 5
Dr ain ag e p ipe co nn ec tio n(2
6(1 )I.D
Dr ain ag e p ipe co nn ec tio n(f or the le ft a rra ng em en t)
Kn oc ko ut ho le for le ft d rai n-p ipi ng ar ran ge me nt
Re frig era nt-pip e c on ne cti on
(ga s p ipe si de /fla red co nn ec tio n)
Re frig era nt-pip e c on ne cti on
(liq uid pi pe si de
/fla red co nn ec tio n)
El ec tri ca l b ox
Ai r o ut le t In cas e o f w irel ess rem ote co ntro ller and i-s ee sen sor
(Op tion al P arts
9/16
254(10)
0(
7- 1/
0° 8
Ai r i nt ak e
INDOOR UNIT DIMENSIONS: PCA-AK24NL
METUS_2025-02_PROPIN
1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 https://mitsubishicomfort.com
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
OUTDOOR UNIT DIMENSIONS: PUZ-AH24NL
Job Name: Location: Date:
Purchaser: Engineer:
Submitted to: For Reference Approval Construction System Designation: Schedule No.:
M- and P-SERIES
Specifications are subject to change without notice.
© 2013 Mitsubishi Electric US, Inc.
Model: PAR-31MAA
BACKLIT MA REMOTE CONTROLLER (PAR-31MAA)
SPECIFICATIONS
| • | Controls group operation for up to 16 indoor units in a single group |
| • | Features selectable multi-lingual LCD (English, Spanish, and |
French)
| • | Supports both Fahrenheit and Celsius |
| • | User functions allow user to set |
- On/Off
- Operation modes cool, heat, dry, fan
- Set temperature
- Fan speed setting
- Airflow direction
• Timer Operation:
- Weekly Timer: On/Off/Temperature setting up to 8 times per day of the week in 1-minute increments
- Simple Timer: On and Off time can be set once within 72-hour period in 1-hour increments
- Auto-off Timer: Turns indoor unit Off based on countdown time up to 4-hours in 30-minute increments
• Room Temperature: Displays room temperature sensed either at the indoor unit (default) or at the remote controller
• Set Temperature Range Limit: From the Backlit MA Controller, the allowable set temperature range can be reduced for cool and heat modes
| • | Special Function Rotation/Backup (Lead/Lag for P-Series) |
| • | Static pressure setting (model dependent) |
| • | Fan speed setting for use with supplemental heating function |
(model dependent)
| • | Set P-Series twinning function |
| • | Function Lock Out: Prohibits all functions or all functions except |
On/Off from the backlit MA controller
| • | Addressing: No addressing required |
| • | Wiring: connects using two-wire, stranded, non-polar control wire to |
indoor unit connection terminal or control adapter (MAC-333IF for M-Series) requires crossover wiring for indoor unit grouping
• Dimensions: 4-3/4 x 3/4 x 4-3/4" (120 x 19 x 120 mm)
Job Name: Location: Date:
Purchaser: Engineer:
Submitted to: For Reference Approval Construction System Designation: Schedule No.:
M- and P-SERIES
Specifications are subject to change without notice.
© 2013 Mitsubishi Electric US, Inc.
Model: PAR-31MAA
BACKLIT MA REMOTE CONTROLLER (PAR-31MAA)
SPECIFICATIONS
• Controls group operation for up to 16 indoor units in a single group
• Features selectable multi-lingual LCD (English, Spanish, and
French)
• Supports both Fahrenheit and Celsius
• User functions allow user to set
- On/Off
- Operation modes cool, heat, dry, fan
- Set temperature
- Fan speed setting
- Airflow direction
• Timer Operation:
- Weekly Timer: On/Off/Temperature setting up to 8 times per day of the week in 1-minute increments
- Simple Timer: On and Off time can be set once within 72-hour period in 1-hour increments
- Auto-off Timer: Turns indoor unit Off based on countdown time up to 4-hours in 30-minute increments
• Room Temperature: Displays room temperature sensed either at the indoor unit (default) or at the remote controller
• Set Temperature Range Limit: From the Backlit MA Controller, the allowable set temperature range can be reduced for cool and heat modes
• Special Function Rotation/Backup (Lead/Lag for P-Series)
• SEZ Static Pressure Setting
• Supplemental heat function enable/disable
• Set P-Series twinning function
• Function Lock Out: Prohibits all functions or all functions except
On/Off from the backlit MA controller
• Addressing: No addressing required
• Wiring: connects using two-wire, stranded, non-polar control wire to indoor unit connection terminal or control adapter (MAC-333IF for M-Series) requires crossover wiring for indoor unit grouping
• Dimensions: 4-3/4 x 3/4 x 4-3/4" (120 x 19 x 120 mm)
2. Local remote controller A3 Rev.
CONTROLLER 3 - 4
C on tr ol le r
2. Local remote controller2-1. MA remote controller [PAR-31MAA]
1. Operation/Display Functions
Item Description Setting Display
ON/OFF
Operation mode switching
Room temp.
setting *3
Fan speed setting
Switches between ON and OFF.
Switches among Cool/Dry/Fan/Auto/Heat.
The temperature can be set within the following range.
Cool/Dry : 19°C - 30°C (14°C - 30°C) / 67°F - 87°F (57°F - 87°F) Heat : 17°C - 28°C (17°C - 28°C) / 63°F - 83°F (63°F - 83°F) Auto : 19°C - 28°C (17°C - 28°C) / 67°F - 83°F (63°F - 83°F) ( ) For PEFY/PFFY by setting DipSW 7-1 to ON and limits to NI6H fan speed only.
Changes fan speed.
* Available fan speeds vary depending on the model.
Air flow direction setting
Changes airflow direction.
* Available airflow directions vary depending on the model.
Louver setting Switches between louver ON/OFF.
Ventilation equipment control
Interlocked setting and interlocked operation setting with the City Multi LOSSNAY units can be made.
The Stop/Low/High settings of the ventilation equipment can be controlled.
Auto descending panel *1
Raises and lowers the automatic elevating panel.
backlight Pressing any button turns the backlight on and it will stay lit for a certain period of time depending on the screen.
Main display mode setting
The Main display can be displayed in two different modes:
"Full" and "Basic."
Clock *2 Date (year/month/day) and time (hour/minute) can be set.
The set time as well as the day of the week will be displayed on the Main display.
It is also possible to set not to display the time on the Main display.
Clock display The clock can be displayed in 12-hour format (AM/PM before or after the time) and 24-hour format.
Room temp.
display *3
Displays the room temperature on the Main display in the "Full" mode during operation.
Error information When an error occurs, an error code and the unit address appear.
Air conditioning unit model, serial number, and contact number can be set to appear when an error occurs. (The information above needs to be entered in advance.)
* An error code may not appear depending on the error.
Filter information A filter sign will appear when it is time to clean the filter.
:Each group :Not available
2. Schedule and timer setting Item Description Setting Display
Timer ON/OFF timer Turns ON and OFF daily at a set time.
• Time can be set in 5-minute increments.
• It is also possible to set the ON time only or the OFF time only.
Auto-OFF timer Turns off the unit after a certain period of operation.
• Operation time can be set to a value from 30 to 240 minutes in
10-minute increments.
Weekly timer Weekly ON/OFF times and set temperatures can be set.
• Time can be set in 5-minute increments. Up to 8 schedule patterns can be set per day of the week.
* Not valid when the ON/OFF timer is set.
Night setback The temperature range and the start/stop times can be set.
:Each group :Not available
3. Restriction settings Item Description Setting Display
Allows/disallows local operation
Temperature range restriction
The following operation can be prohibited by making certain settings on the centralized controller: ON/OFF, operation mode setting, temperature setting, and filter sign reset.
* While an operation is prohibited, the operation icon lights up
(only on the Main display in the "Full" mode).
Operation lock The following operation can be prohibited respectively: ON/OFF, operation mode setting, temperature setting, and airflow direction setting.
The room temperature range for each operation mode can be restricted.
Auto return The units operate at the preset temperature after a designated period.
(Time can be set to a value from 30 to 120 in 10-minute increments.)
* Not valid when the temperature setting range is restricted.
password Administrator password (required for schedule setting etc.) and Maintenance password (required for test run and function setting etc.) can be set.
:Each group :Not available
4. Miscellaneous items Item Description Setting Display
Language Selection
Manual vane Angle *1
Select the display language from the following 8 languages.
English, French, German, Spanish, Italian,Portuguese, Swedish, and Russian
Contrast Adjusts LCD contrast.
Fixes the vane position for each air outlet.
Service *1 Contains Test run, Function setting, Refrigerant volume check, Refrigerant leak check, Smooth maintenance, Request code, and Error history.
*1 This function is active only for the units that support the function.
*2 The clock is accurate within 50 seconds per month (at the temperature of 25ºC [77°F]). The clock is backed up for 7 days.
*3 Temperature will be displayed either in Centigrade in 0.5- or 1-degree increments, or in Fahrenheit, depending on the indoor unit model and the display mode setting on the remote controller.
:Each group :Not available
MA
remote controller
Non-polarized 2-wire
Non-polarized 2-wire
MA
remote controller
System
*When a PAR-31MAA is connected to a group, no other MA remote controllers can be connected to the same group.
example
3/4 [1- ]13/16
[3
9 /
(Front view) (Side view) (Rear view) External dimension
Unit:mm[in.]
[ ] 4619
.5
[4- ]3/4120
[4
3 /
Backlit LCD Can be set and shown by 0.5°C degree.
Fri
Mode Temp. Fan
Room
Cool AutoSet temp.
Notes:
Notes:
1340 Satellite Boulevard Suwanee, GA 30024 Tele: 678-376-2900 • Fax: 800-889-9904 Toll Free: 800-433-4822 www.mehvac.comSpecifications are subject to change without notice.
© 2013 Mitsubishi Electric US, Inc.
FORM# PAR-31MAA - 201309
Model: PAR-31MAA - DIMENSIONS
3/4
[1- ]13/16
(Front view) (Side view)
(Rear view)
Unit:mm[in.]
.5
[4- ]3/4120
3/4
[1- ]13/16
(Front view) (Side view)
(Rear view)
Unit:mm[in.]
.5
[4- ]3/4120
Notes
Contractor:
Engineer:
Architect:
Rep/Distributor:
Project Detail:
Customer:
Address:
City:
State:
Zip:
Submittal Date:
10/28/2025
Submitted By:
Name:
Company:
Email:
Phone:
Submittal Stage: Design Only
Submittal Project Name:
10199 Alburg Springs Inspection Booth (Revision 1)
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
MSZ-GX24NL & MUZ-GX24NLHZ
22,400 BTU/H WALL-MOUNTED INDOOR UNIT
22,400 BTU/H INVERTER HYPER HEAT PUMP OUTDOOR UNIT
Indoor Unit� MSZ-GX24NL
Outdoor Unit� MUZ-GX24NLHZ
Job Name:
System Reference: Date:
INDOOR UNIT FEATURES
• Dual Barrier Coating: The patented Dual Barrier Coating reduces the collection of contaminants like dust, fibers, smoke, and oil on the inner surface of the heat pump, resulting in optimal airflow and easier maintenance.
• Econo Cool: Econo Cool temporarily and automatically adjusts the airflow based on heat exchanger temperature. The set temperature is increased slightly, which saves energy, while maintaining comfort.
• Filter: Electrostatic Enzyme filter (built-in) that is charged with static electricity and designed to attract and filter charged particles which can include airborne non-living particulates. and Microparticle filter (optional) that removes non-living particulate matter, which can include dust and smoke.
• Multiple control options including: Back-lit screen hand-held Remote Controller (provided with unit), comfort app, third-party interfaces and both wired and wireless controllers
| • | Multiple fan speed options: Low, Medium, High, Powerful, Auto |
| • | Powerful Mode: Temporarily drops or raises the set point and fan speed in order to quickly bring the room to the desired temperature. |
| • | Quiet operation: Outdoor units are as quiet as a typical conversation, and most indoor units are whisper quiet. |
| • | Slim wall-mounted indoor units provide zone comfort control |
| • | Smart Dry Mode: Improves humidity control with minimal over-cooling of the space |
| • | Smart Set: recalls a preferred preset temperature setting at the touch of a button |
| • | Wi-Fi enabled units pair with the Comfort app for complete control over temperature, fan speeds, modes, schedules, and more. |
OUTDOOR UNIT FEATURES
• Blue Fin Coating: An anti-corrosion treatment applied to the aluminum fins of the heat exchanger of the outdoor unit to protect against corrosion caused by salt, sulfur, and other airborne contaminants, especially in coastal and industrial areas.
| • | Built-in base pan heater |
| • | DC Fan Motor |
| • | Hot-start technology: The fan only blows air when the heat exchanger has warmed, preventing blasts of cold air at start-up. |
| • | Hyper-Heating INVERTER® (H2i®): 100% heating capacity down to 5° F with guaranteed heating down to -22° F. |
Submittal Documents
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
SPECIFICATIONS: MSZ-GX24NL & MUZ-GX24NLHZ
Cooling at 95F1
Maximum Capacity Btu/h 27,000 Rated Capacity Btu/h 22,400 Minimum Capacity Btu/h 7,400 Maximum Power Input W 2,890 Rated Power Input W 1,720 Moisture Removal Pints/h 4.5 Sensible Heat Factor - 0.78 Power Factor [208V / 230V] % 98 / 98
Heating at 47F2
Maximum Capacity Btu/h 32,000 Rated Capacity Btu/h 21,200 Minimum Capacity Btu/h 6,800 Maximum Power Input W 4,000 Rated Power Input W 1,500 Power Factor [208V / 230V] % 97 / 97
Heating at 17F3
Maximum Capacity Btu/h 25,400 Rated Capacity Btu/h 14,000 Maximum Power Input W 3,500 Rated Power Input W 1,400
Heating at 5F4 Maximum Capacity Btu/h 21,200 Maximum Power Input W 3,450
Heating at -5F6 Maximum Capacity Btu/h 18,070 Heating at -10F7 Maximum Capacity Btu/h 16,410 Heating at -22F9 Maximum Capacity Btu/h 11,380
Efficiency
SEER2 21.5
EER21 13
HSPF2 [IV] 10
COP at 47°F2 4.14 COP at 17°F at Maximum Capacity3 2.12 COP at 5°F at Maximum Capacity4 1.8 COP at -5°F at Maximum Capacity6 1.68 COP at -10°F at Maximum Capacity7 1.56 ENERGY STAR® Certified Yes
Electrical
Voltage, Phase, Frequency V AC / V AC, ø, Hz 208 / 230, 1, 60 Guaranteed Voltage Range V AC 187 - 253 Voltage: Indoor - Outdoor, S1-S2 V AC 230 Voltage: Indoor - Outdoor, S2-S3 V DC 24 Short-circuit Current Rating [SCCR] kA 5 Recommended Fuse/Breaker Size (Outdoor) A 25 Recommended Wire Size [Indoor - Outdoor] AWG 14
Indoor Unit
MCA A 1
Fan Motor Output W 56 Airflow Rate at Cooling, Dry CFM 324, 392, 454, 636, 765 Airflow Rate at Cooling, Wet CFM 292, 353, 408, 573, 688 Airflow Rate at Heating, Dry CFM 344, 392, 454, 530, 765 Sound Pressure Level [Cooling] dB (A) 30, 37, 41, 48, 53 Sound Pressure Level [Heating] dB (A) 30, 37, 41, 45, 50 Drain Pipe Size O.D. inch [mm] 5/8 [15.88] Dual Barrier Coating on Heat Exchanger Yes External Finish Color Munsell 0.7PB 9.2/0.4
Unit Dimensions (W x D x H) inch x inch x inch [mm x mm x mm] 43-5/16 x 10-1/8 x 12-13/16 [1,100 x 257 x 325]
Package Dimensions (W x D x H) inch x inch x inch [mm x mm x mm] 45-1/2 x 15-1/2 x 13-1/2 [1,160 x 400 x 340]
Unit Weight lbs [kg] 37 [16.50] Package Weight lbs [kg] 42 [18.80] Fan Motor Type DC Motor
IDU Operating Temp. Range Cooling Intake Air Temp [Maximum / Minimum] °FDB, °FWB / °FDB, °FWB 90, 73 / 67, 57
Heating Intake Air Temp [Maximum / Minimum] °FDB 80 / 70
NOTES
1Cooling at 95°F (Indoor: 80°F DB, 67°F WB // Outdoor: 95°F DB, 75°F WB) 2Heating at 47°F (Indoor: 70°F DB, 60°F WB // Outdoor: 47°F DB, 43°F WB) 3Heating at 17°F (Indoor: 70°F DB, 60°F WB // Outdoor: 17°F DB, 15°F WB) 4Heating at 5°F (Indoor: 70°F DB, 60°F WB // Outdoor: 5°F DB, 4°F WB) 6Heating at -5°F (Indoor: 70°F DB, 60°F WB // Outdoor: -5°F DB, -6°F WB) 7Heating at -10°F (Indoor: 70°F DB, 60°F WB // Outdoor: -10°F DB, -11°F WB) 9Heating at -22°F (Indoor: 70°F DB, 60°F WB // Outdoor: -22°F DB, -23°F WB)
* Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):
• Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
** Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
SPECIFICATIONS: MSZ-GX24NL & MUZ-GX24NLHZ
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Outdoor Unit
MCA A 23
MOCP A 25
Fan Motor Full Load Amperage A 0.76 Fan Motor Output W 55 Airflow Rate Cooling CFM 2,202 Airflow Rate Heating CFM 1,934 Defrost Method Reverse Cycle Coating on Heat Exchanger (Bluefin, Sea Coast) Yes, Yes Sound Pressure Level, Cooling1 dB (A) 55 Sound Pressure Level, Heating2 dB (A) 55 Compressor Type Twin Rotary Compressor Model SRB172FQHMT Compressor Oil [Type // Charge] Type // oz RM68EH // 14.5 External Finish Color Munsell 3Y 7.8/1.1 Base Pan Heater Built-in
Unit Dimensions (W x D x H) inch x inch x inch [mm x mm x mm] 33-1/16 x 13 x 34-5/8 [840 x 330 x 880]
Package Dimensions (W x D x H) inch x inch x inch [mm x mm x mm] 38-3/4 x 16-3/4 x 40-3/4 [980 x 420 x 1,030]
Unit Weight lbs [kg] 117 [52.80] Package Weight lbs [kg] 137 [61.70]
ODU Operating Temp. Range
Cooling Intake Air Temp [Maximum / Minimum*] °FDB 115 / 14 Cooling Thermal Lock-out / Re-start Temperatures** °FDB -1 / 3
Heating Intake Air Temp [Maximum / Minimum] °FDB, °FWB / °FDB, °FWB 75, 65 / -22, -23
Heating Thermal Lock-out / Re-start Temperatures** °FDB -34 / -22.5
Refrigerant
Type R454B Pre-Charged Refrigerant Amount lbs, oz 3, 12 Maximum Pre-Charged Piping Length ft [m] 50 [15] Additional Refrigerant Charge Per Additional Piping Length oz/ft 0.22
Piping
Gas Pipe Size O.D. [Flared] inch [mm] 5/8 [15.88] Liquid Pipe Size O.D. [Flared] inch [mm] 1/4 [6.35] Maximum Piping Length ft [m] 100 [30] Maximum Height Difference ft [m] 50 [15] Maximum Number of Bends 10
NOTES
1Cooling at 95°F (Indoor: 80°F DB, 67°F WB // Outdoor: 95°F DB, 75°F WB) 2Heating at 47°F (Indoor: 70°F DB, 60°F WB // Outdoor: 47°F DB, 43°F WB) 3Heating at 17°F (Indoor: 70°F DB, 60°F WB // Outdoor: 17°F DB, 15°F WB) 4Heating at 5°F (Indoor: 70°F DB, 60°F WB // Outdoor: 5°F DB, 4°F WB) 6Heating at -5°F (Indoor: 70°F DB, 60°F WB // Outdoor: -5°F DB, -6°F WB) 7Heating at -10°F (Indoor: 70°F DB, 60°F WB // Outdoor: -10°F DB, -11°F WB) 9Heating at -22°F (Indoor: 70°F DB, 60°F WB // Outdoor: -22°F DB, -23°F WB)
* Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):
• Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
** Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
INDOOR UNIT ACCESSORIES: MSZ-GX24NL
Wired Remote Controller
Deluxe MA Wired Remote Controller 1 PAR-42MAAUB Simple Direct Wired Remote Controller PAC-SDW01RC-1 Simple MA Remote Controller 1 PAC-YT53CRAU-J Touch MA Wired Remote Controller 1 PAR-CT01MAU-SB
Filter
Electro Static Anti-allergy Enzyme Filter MAC-2310FT-E Electro Static Anti-allergy Enzyme Filter MAC-2320FT-E Microparticle Filter MAC-EMF615FT-E Microparticle Filter MAC-EMF515FT-E
Control Interface
Airzone Wired Blueface Controller Black AZZBSBLUEZEROCN Airzone Wired Blueface Controller White AZZBSBLUEZEROCB Airzone Wireless Lite Controller Black AZZBSLITERN Airzone Wireless Lite Controller White AZZBSLITERB Airzone Wireless Think Controller Black AZZBSTHINKRN Airzone Wireless Think Controller White AZZBSTHINKRB IT Extender for kumo station PAC-WHS01IE-E kumo station for the Comfort app PAC-WHS01HC-E M-Net I/O Control Interface for M-Series 2 MAC-334IF-E Procon BACnet and Modbus Interface PAC-UKPRC001-CN-1 Thermostat Interface for 3rd Party Thermostats PAC-US445CN-1 Wireless Interface Adapter for the Comfort app PAC-USWHS002-WF-2
Lineset
100 x 1/4 x 100 x 5/8 Lineset Twin-Tube Insulation MLS145812T-100 15 x 1/4 x 15 x 5/8 Lineset Twin-Tube Insulation MLS145812T-15 30 x 1/4 x 30 x 5/8 Lineset Twin-Tube Insulation MLS145812T-30 50 x 1/4 x 50 x 5/8 Lineset Twin-Tube Insulation MLS145812T-50 65 x 1/4 x 65 x 5/8 Lineset Twin-Tube Insulation MLS145812T-65
Condensate
Blue Diamond Advanced Mini Condensate Pump w Reservoir Sensor 208230V recommended X87-721 Blue Diamond MaxiBlue Advanced Mini Condensate Pump w Reservoir Sensor 110V up to 48000 BTUH recommended X87-711 Blue Diamond MegaBlue Advanced Condensate Pump w Reservoir Sensor X87-835 Blue Diamond Sensor Extension Cable 15 Ft C13-103 Drain Pan Level SensorControl SS610E Refco Condensate Pump 100-240 VAC GOBI-II Refco Condensate Pump 100-240 VAC up to 120000 BTUH COMBI Sauermann Condensate Pump SI30-230
Disconnect Switch 30A600VUL fits 2 X 4 utility box - Black TAZ-MS303 30A600VUL fits 2 X 4 utility box - White TAZ-MS303W
Remote Sensor Remote Temperature Sensor for MFZ MLZ and MSZ models M21EAA307 Wireless temperature and humidity sensor for the Comfort app PAC-USWHS003-TH-1
Wireless Remote Controller Lockdown Bracket for Wireless Handheld Remote Controllers RCMKP1CB RedLINK Wireless Remote Controller MHK2
Power Supplies and Auxiliary Components Backup Heat Relay Kit Adapter for CN24 or CN152 Connector CN24RELAY-KIT-CM3
Drain Hose Flexible Mini-Split Drain Hose DRX-16
NOTES
2Allows IDU Connection to MA Controller:
Deluxe MA Remote Controller Simple MA Controller Touch MA Controller 1Requires MAC-334IF-E Adapter 1Requires MAC-334IF-E Adapter 1Requires MAC-334IF-E Adapter
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
OUTDOOR UNIT ACCESSORIES: MUZ-GX24NLHZ
Mini-Split Wire
14 Gauge 4 wire Armored MiniSplit Cable250 ft roll SW144-250 14 Gauge 4 wire Armored MiniSplit Cable50 ft roll SW144-50 14 Gauge 4 wire MiniSplit Cable250 ft roll S144-250 14 Gauge 4 wire MiniSplit Cable50 ft roll S144-50 16 Gauge 4 wire Armored MiniSplit Cable250 ft roll SW164-250 16 Gauge 4 wire Armored MiniSplit Cable50 ft roll SW164-50 16 Gauge 4 wire MiniSplit Cable250 ft roll S164-250 16 Gauge 4 wire MiniSplit Cable50 ft roll S164-50
Stand
18 Single Fan Stand QSMS1801M 24 Single Fan Stand QSMS2401M Condenser Wall Bracket QSWB2000M-1 Condenser Wall Bracket - Stainless Steel Finish QSWBSS Outdoor Unit 3-14 inch Mounting Base Pair - Plastic DSD-400P Outdoor Unit Stand 12 High QSMS1201M
Snow/Rain Diverter SnowRain Diverter SRD-3
Control/Service Tool M- & P-Series Maintenance Tool Cable Set M21EC0397 Maintenance Tool Interface PAC-USCMS-MN-1
Air Outlet Guide Air Outlet Guide MAC-890SG-E Mounting Pad Condensing Unit Mounting Pad 16 x 36 x 3 ULTRILITE1 Hail Guards Hail Guard HG-A7
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
MSZ-GX18NL- U1 MSY-GX18NL- U1
MSZ-GX24NL- U1 MSY-GX24NL- U1
MSZ-GX30NL- U1 MSY-GX30NL- U1
MSZ-GX36NL- U1 MSY-GX36NL- U1
INDOOR UNIT DIMENSIONS: MSZ-GX24NL
METUS_2025-03_PROPIN
1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 https://mitsubishicomfort.com
Specifications are subject to change without notice.� © 2025 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
16-7/16
1-9/16
-3
/4
-5 /8
-3
/8
/1
OVAL HOLES 2× 3/8 × 13/16
→AIR IN
AIR IN
↓ AIR OUT
BO
LT
P
IT
C H
F O
R
IN
ST
AL
LA
TI
O N
DRAIN HOLE ø1-21/32
-5
/8
-2
5/
5/
6-7/8 19-11/16
33-1/16 3-3/16
HANDLE
3-
/3
6- 1/
7-11/16
19/32
GAS REFRIGERANT
PIPE JOINT
LIQUID
REFRIGERANT
PIPE JOINT
SERVICE PANEL
VALVE COVER
SERVICE PORT
4 in OR MORE.
BA
SI
CA
LL
Y
OP
EN
in O
R
MO
RE
W
ITH
OU
T
AN
Y
OB
ST
RU
CT
IO
N
IN
FR
ON
T A
ND
B
OT
H
SI
DE
S
OF
TH
E
UN
IT.
14 in OR MORE.
20 in OR MORE.
OPEN TWO SIDES OF RIGHT,
LEFT OR REAR SIDE.
4 in OR MORE.
REQUIRED SPACE
REFRIGERANT
PIPE JOINT
LIQUID REFRIGERANT PIPE FLARED 1/4ʺ
FLARED 1/2"GAS REFRIGERANT PIPE
MUZ-GX18NL MUZ-GX18NLHZ
MUY-GX18NL
REFRIGERANT
PIPE JOINT
LIQUID REFRIGERANT PIPE FLARED 1/4ʺ
FLARED 5/8"GAS REFRIGERANT PIPE
MUZ-GX24/30/36NL MUZ-GX24NLHZ
MUY-GX24/30/36NL
MUZ-GX18NL-U1
MUZ-GX24NL-U1
MUZ-GX18NLHZ-U1
MUZ-GX24NLHZ-U1
MUY-GX18NL-U1
MUY-GX24NL-U1
MUZ-GX30NL-U1
MUZ-GX36NL-U1
MUY-GX30NL-U1
MUY-GX36NL-U1
OUTDOOR UNIT DIMENSIONS: MUZ-GX24NLHZ
Notes
| hp 1 |
| Cover Page |
| Submittal Documents |
| Notes |
| HP 2 |
| Cover Page |
| Submittal Documents |
| Notes |
| Job Name 12: |
| System Reference 12: |
| Date 12: |
| accessoryCheckBox 10: Off |
| accessoryCheckBox 11: Off |
| accessoryCheckBox 12: Off |
| accessoryCheckBox 13: Off |
| accessoryCheckBox 14: Off |
| accessoryCheckBox 15: Off |
| accessoryCheckBox 16: Off |
| accessoryCheckBox 17: Off |
| accessoryCheckBox 18: Off |
| accessoryCheckBox 19: Off |
| accessoryCheckBox 110: Off |
| accessoryCheckBox 111: Off |
| accessoryCheckBox 112: Off |
| accessoryCheckBox 113: Off |
| accessoryCheckBox 114: Off |
| accessoryCheckBox 115: Off |
| accessoryCheckBox 116: Off |
| accessoryCheckBox 117: Off |
| accessoryCheckBox 118: Off |
| accessoryCheckBox 119: Off |
| accessoryCheckBox 120: Off |
| accessoryCheckBox 121: Off |
| accessoryCheckBox 122: Off |
| accessoryCheckBox 123: Off |
| accessoryCheckBox 124: Off |
| accessoryCheckBox 125: Off |
| accessoryCheckBox 126: Off |
| accessoryCheckBox 127: Off |
| accessoryCheckBox 128: Off |
| accessoryCheckBox 129: Off |
| accessoryCheckBox 130: Off |
| accessoryCheckBox 131: Off |
| accessoryCheckBox 132: Off |
| accessoryCheckBox 133: Off |
| accessoryCheckBox 134: Off |
| accessoryCheckBox 135: Off |
| accessoryCheckBox 136: Off |
| accessoryCheckBox 137: Off |
| accessoryCheckBox 138: Off |
| accessoryCheckBox 139: Off |
| accessoryCheckBox 140: Off |
| accessoryCheckBox 141: Off |
| accessoryCheckBox 142: Off |
| accessoryCheckBox 143: Off |
| accessoryCheckBox 144: Off |
| accessoryCheckBox 145: Off |
| accessoryCheckBox 146: Off |
| accessoryCheckBox 147: Off |
| accessoryCheckBox 148: Off |
| accessoryCheckBox 149: Off |
| accessoryCheckBox 150: Off |
| accessoryCheckBox 151: Off |
| accessoryCheckBox 152: Off |
| accessoryCheckBox 153: Off |
| accessoryCheckBox 154: Off |
| accessoryCheckBox 155: Off |
| accessoryCheckBox 156: Off |
| accessoryCheckBox 157: Off |
| accessoryCheckBox 158: Off |
| accessoryCheckBox 159: Off |
| accessoryCheckBox 160: Off |
| accessoryCheckBox 161: Off |
| accessoryCheckBox 162: Off |
| accessoryCheckBox 163: Off |
| accessoryCheckBox 164: Off |
| accessoryCheckBox 165: Off |
| accessoryCheckBox 166: Off |
| Job Name 12#1: |
| System Reference 12#1: |
| Date 12#1: |
| accessoryCheckBox 10#1: Off |
| accessoryCheckBox 11#1: Off |
| accessoryCheckBox 12#1: Off |
| accessoryCheckBox 13#1: Off |
| accessoryCheckBox 14#1: Off |
| accessoryCheckBox 15#1: Off |
| accessoryCheckBox 16#1: Off |
| accessoryCheckBox 17#1: Off |
| accessoryCheckBox 18#1: Off |
| accessoryCheckBox 19#1: Off |
| accessoryCheckBox 110#1: Off |
| accessoryCheckBox 111#1: Off |
| accessoryCheckBox 112#1: Off |
| accessoryCheckBox 113#1: Off |
| accessoryCheckBox 114#1: Off |
| accessoryCheckBox 115#1: Off |
| accessoryCheckBox 116#1: Off |
| accessoryCheckBox 117#1: Off |
| accessoryCheckBox 118#1: Off |
| accessoryCheckBox 119#1: Off |
| accessoryCheckBox 120#1: Off |
| accessoryCheckBox 121#1: Off |
| accessoryCheckBox 122#1: Off |
| accessoryCheckBox 123#1: Off |
| accessoryCheckBox 124#1: Off |
| accessoryCheckBox 125#1: Off |
| accessoryCheckBox 126#1: Off |
| accessoryCheckBox 127#1: Off |
| accessoryCheckBox 128#1: Off |
| accessoryCheckBox 129#1: Off |
| accessoryCheckBox 130#1: Off |
| accessoryCheckBox 131#1: Off |
| accessoryCheckBox 132#1: Off |
| accessoryCheckBox 133#1: Off |
| accessoryCheckBox 134#1: Off |
| accessoryCheckBox 135#1: Off |
| accessoryCheckBox 136#1: Off |
| accessoryCheckBox 137#1: Off |
| accessoryCheckBox 138#1: Off |
| accessoryCheckBox 139#1: Off |
| accessoryCheckBox 140#1: Off |
| accessoryCheckBox 141#1: Off |
| accessoryCheckBox 142#1: Off |
| accessoryCheckBox 143#1: Off |
| accessoryCheckBox 144#1: Off |
| accessoryCheckBox 145#1: Off |
| accessoryCheckBox 146#1: Off |
| accessoryCheckBox 147#1: Off |
| accessoryCheckBox 148#1: Off |
| accessoryCheckBox 149#1: Off |
| accessoryCheckBox 150#1: Off |
| accessoryCheckBox 151#1: Off |
| accessoryCheckBox 152#1: Off |
| accessoryCheckBox 153#1: Off |
| accessoryCheckBox 154#1: Off |
| accessoryCheckBox 155#1: Off |
| accessoryCheckBox 156#1: Off |
| accessoryCheckBox 157#1: Off |
| accessoryCheckBox 158#1: Off |
| accessoryCheckBox 159#1: Off |
| accessoryCheckBox 160#1: Off |
File details come from the government source that posted it. Updated .