PUH - Propeller Unit Heater Cutsheet.pdf

PDF 414 KB Posted

Attached to
Design Bid Build (DBB) Construction Requirement for Alburg Springs Land Port of Entry (LPOE), Alburg, Vermont
Solicitation number
47PB5126R0008
Issued by
Not on record

About this file

This is a technical submittal document for Vulcan Radiator horizontal unit heaters used in HVAC systems.

The document provides comprehensive dimensional, performance, and specification data for two product lines: steam and hot water coil models (HV-18 through HV-360 in header type configuration) and serpentine hot water coil models (HV-108A through HV-136A). Dimensional tables specify detailed measurements for height, width, depth, louver counts, fan diameters, and approximate shipping weights across all model sizes. Performance data tables present heating output in BTU per hour and gallons per minute, outlet temperatures, motor specifications, and acoustic ratings for both hot water operation (based on 200°F entering water temperature and 20°F temperature differential) and steam operation (based on 2 PSI steam pressure). Motor options include totally enclosed fan-cooled designs in single-phase (115/1/60 and 230/1/60) and three-phase (208-230/460/3/60) configurations, ranging from 16-watt units to 1/2 horsepower motors, with horsepower ratings from 1/20 HP to 1/2 HP. Optional explosion-proof motors compliant with National Electrical Code classifications (Class I Group D, Class II Groups F and G, Division I & II) are available. Standard features include 20-gauge steel casings with polyester melamine paint finish, seamless copper tubing coils rated to 150 PSI, aluminum blade fans, and individually adjustable horizontal louvers. OSHA fan guards are standard on specified smaller models. The document includes mounting height and throw distance recommendations for proper installation planning.

View the file

Other files

File Type Posted
27. Amendment 47PB5126R0008 0008 2026 07 13.pdf PDF
3. Agreement Rev 2 2026 06 18.pdf PDF
25. Amendment 47PB5126R0008 0007 2026 06 18.pdf PDF
6. WD VT20250027 2026 05 18.pdf PDF
1. Solicitation Rev 1_2026 06 11.pdf PDF
2. SF1442 Rev 1 dated 2026 06 15.pdf PDF
3. Agreement Rev 1 2026 06 12.pdf PDF
21. Amendment 47PB5126R0008 0006 2026 06 15.pdf PDF
20. Amendment 47PB5126R0008 0005 2026 06 02.pdf PDF
19. Amendment 47PB5126R0008 0004 2026 05 29.pdf PDF
16. Alburg Springs - Port Signage SOW-ASR 01.pdf PDF
15. Amendment 47PB5126R0008 0003 2026 05 21.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes_Rev 1 Amendment 0002_ 2026 05 15.pdf PDF
14. Amendment 47PB5126R0008 0002 2026 05 15.pdf PDF
13. Amendment 47PB5126R0008 0001 2026 05 12.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
Alburg Springs LPOE Conference-Site Visit meeting minutes 2026 05 06.pdf PDF
RP - Vertical Radiant Panel Cutsheet.pdf PDF
RG - Return Grille Cutsheet.pdf PDF
SG - Supply Grille Cutsheet.pdf PDF
ET - Expansion Tank Cutsheet.pdf PDF
FT - Fin Tube Cutsheet.pdf PDF
GFT - Glycol Feed Tank Cutsheet.pdf PDF
BT - Buffer Tank Cutsheet.pdf PDF
FB - Filter Box Cutsheet.pdf PDF
GI and GR - Gravity Intake and Relief Cutsheet.pdf PDF
DH - Duct Mounted Humidifier Cutsheet.pdf PDF
SG and EG - Security Grille Cutsheet.pdf PDF
BSF - Booth Supply Fan Cut Sheet.pdf PDF
RP - Horizontal Radiant Panel Cutsheet.pdf PDF
AS - Air Separator Cutsheet.pdf PDF
EHC - Electric Heating Coil Cutsheet.pdf PDF
2026-02-06 Review of Proposed Renovations - Historic Context (1).pdf PDF
4. GSA527-21a 2026 04 15.pdf PDF
FCU - Fan Coil Unit Cutsheet.pdf PDF
6. WD VT20250027 2026 04 15.pdf PDF
CP and GP - Pump Cutsheets.pdf PDF
3. Agreement 2026 04 15.pdf PDF
EH - Electric Wall Heater Cutsheet.pdf PDF
7. PBS PPQ 2026 04 15.pdf PDF
GSHP - Ground Source Heat Pump Cutsheet.pdf PDF
L - Louver Cutsheet.pdf PDF
HP and CU - Heat Pump Mini-Split Cutsheet.pdf PDF
8. Tips on Preparing a Subcontracting Plan 2026 04 15.pdf PDF
HUM - Steam Humidifier Cutsheet.pdf PDF
Alburg Springs VT LPOE Code Report - 20260206 (1).pdf PDF
9. Model Subcontracting Plan 2026 04 15.docx DOCX document
5. Proprietary Information Agreement 2026 04 15.docx DOCX document
EF - Exhaust Fan Cutsheet.pdf PDF
Show 40 more

Latest 50 of 56 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Horizontal Unit Heaters – Submittal HVD-16

PROJECT:

LOCATION:

ARCHITECT:

ENGINEER:

CONTRACTOR:

PO NUMBER:

DATE:

MODELS HV-18 THRU 360 (HEADER TYPE)

MODELS HV-108A THRU 136A

260 North Elm Street
Westfield, Massachusetts 01085
(413) 568-9571 • Fax (413) 564-5661
www.vulcanrad.com

* APPLIES TO STANDARD MOTOR WITH STANDARD FAN GUARD. WHEN OPTIONAL MOTORS OR OSHA FAN GUARDS ARE REQUESTED, DIMENSIONS WILL CHANGE ACCORDING TO THE SUBSTITUTIONS MADE.

NOTES:1. OSHA guard standard on models HV-18 thru HV-48 (dimensions shown in table).
2. Standard motor and standard guard shown in both tables.
3. Optional OSHA guards available for all units with standard single phase motors.
4. All three phase and explosion proof motors are shelf mounted.

* Dimension “C” is to back of motor, not motor conduit connector as shown.

NOTE: OSHA type fan guard standard on models HV-108A thru HV-136A.

Dimensional Data Steam and Hotwater Coil

Serpentine Hotwater Coil

145⁄8 (371) 145⁄8 (371) 171⁄8 (435) 171⁄8 (435) 183⁄8 (467) 207⁄8 (530) 195⁄8 (498) 207⁄8 (530) 233⁄8 (594) 233⁄8 (594) 245⁄8 (625) 277⁄8 (708) 277⁄8 (708) 333⁄8 (848)

12¼ (311) 12¼ (311) 14¾ (375) 14¾ (375)

(406) 18½ (470) 17¼ (438) 18½ (470)

(533)

(533) 22¼ (565) 25½ (648) 25½ (648)

(787)

75⁄16 (186) 75⁄16 (186) 89⁄16 (217) 89⁄16 (217) 93⁄16 (233) 107⁄16 (265) 913⁄16 (249) 107⁄16 (265) 1111⁄16 (297) 1111⁄16 (297) 125⁄16 (313) 1315⁄16 (354) 1315⁄16 (354) 1611⁄16 (424)

(381)

(457) 20½ (521) 20½ (521) 21¾ (552) 24¼ (616)

(610) 25¼ (641) 27¾ (705) 27¾ (705)

(737) 30¼ (768) 30¼ (768) 37¾ (959)

7½ (191)

(229) 10¼ (260) 10¼ (260) 107⁄8 (276) 121⁄8 (308)

(305) 125⁄8 (321) 137⁄8 (352) 137⁄8 (352) 14½ (368) 151⁄8 (384) 151⁄8 (384) 187⁄8 (479)

61⁄8 (156) 61⁄8 (156) 57⁄8 (149) 57⁄8 (149)

(152) 61⁄8 (156) 65⁄16 (160) 65⁄16 (160) 65⁄16 (160) 65⁄16 (160) 63⁄8 (162) 81⁄8 (206) 81⁄8 (206)

(229)

215⁄16 (75) 215⁄16 (75) 215⁄16 (75) 215⁄16 (75) 215⁄16 (75) 215⁄16 (75) 33⁄16 (81) 33⁄16 (81) 33⁄16 (81) 33⁄16 (81) 33⁄16 (81) 33⁄16 (81) 33⁄16 (81) 33⁄16 (81)

3¼ (83) 3¼ (83) 511⁄16 (144) 51⁄16 (129) 51⁄16 (129) 511⁄16 (144) 7½ (191) 611⁄16 (170) 75⁄8 (194) 77⁄16 (194) 77⁄16 (194) 57⁄8 (149) 95⁄8 (244) 95⁄8 (244)

93⁄8 (238) 93⁄8 (238) 117⁄16 (291) 1015⁄16 (278) 111⁄16 (281) 1113⁄16 (300) 1313⁄16 (351)

(330)

(356) 13¾ (349) 13¾ (349)

(356) 17¾ (451) 185⁄8 (473)

9½ (241) 12½ (318)

(381)

(381) 16¼ (413) 18¾ (476) 17½ (445) 18¾ (476) 21¼ (540) 21¼ (540) 22½ (572) 23¾ (603) 23¾ (603) 31¼ (794)

1¼ (32) 1¼ (32) 1¼ (32) 1¼ (32) 1¼ (32) 1¼ (32) 1½ (38) 1½ (38) 1½ (38) 1½ (38) 1½ (38)

(51)

(51)

(51)

2¼ (57) 2¼ (57) 1¾ (44) 1¾ (44) 1¾ (44) 1¾ (44) 1¾ (44) 1¾ (44) 1¾ (44) 1¾ (44) 1¾ (44) 1¾ (44) 1¾ (44) 1¾ (44)

127⁄8 (327) 127⁄8 (327) 153⁄8 (391) 153⁄8 (391) 165⁄8 (422) 191⁄8 (486) 177⁄8 (454) 191⁄8 (486) 215⁄8 (549) 215⁄8 (549) 227⁄8 (581) 261⁄8 (664) 261⁄8 (664) 315⁄8 (803)

(229)

(254)

(305)

(305)

(356)

(356)

(406)

(457)

(457)

(457)

(457)

(508)

(508)

(610)

(11.8)

(13.6)

(18.6)

(18.6)

(19.9)

(21.3)

(22.2)

(26.7)

(33.5)

(33.5)

(40.8) (65) (70) (92)

Approx.

Ship Wt.

lbs. (kg)

Nom. Fan Diam.

inches (mm)

Number of

Louvers Unit Size

ABCDEFG*H*JKLMN
inchesinchesinchesinchesinchesinchesinch,esinchesinchesinchesinchesinchesinches
(mm)(mm)(mm)(mm)(mm)(mm)(mm)(mm)(mm)(mm)(mm)(mm)(mm)

Unit Size

H inches (mm)

W inches (mm)

A inches (mm)

B inches (mm)

C inches (mm)

Number of

Louvers

Nominal Fan Diameter inches (mm)

Approx.

Ship Wt.

lb.

(kg)

108A

(406)

(457) 167⁄32 (412)

11¼ (286)

4¼

(108) 5 9

(229)

(10.0)

118A

(406)

(457) 167⁄32 (412)

11¼ (286)

4¼

(108) 5 10

(254)

(10.9)

125A

(406)

(457) 167⁄32 (412)

11¼ (286)

4¼

(108) 5 10

(254)

(11.3)

136A* 18½ (470)

20½ (521)

1822⁄32 (475)

13¾ (349)

511⁄16

(144) 6 12

(305)

(14.0)

2/19

H o t W at er

P er fo rm an ce

D at a St ea m

P er fo rm an ce

D at a

P er fo rm an ce b as ed o n

0°

E W

T, 0° E

.A .T

° T D

Fo r t he lo w er o ut pu t, an o pt io na l S pe ed

C on tr ol le r m us t b e or de re d.

S ta te d

A M

P is fu ll lo ad

(F

LA

A

M P dr aw v ar ie s by m ot or m an uf ac tu re r ± .2

A M

PS

† M ot or H

P lis te d is a pp lic ab le to s ta nd ar d m ot or ty pe o nl y.

F or e xp lo si on p ro of m ot or H

P, s ee m ot or d at a se ct io n.

P er fo rm an ce b as ed o n 2# s te am p re ss ur e at h ea te r w ith a ir en te rin g

0° F.

M ax im um w or ki ng p re ss ur e

PS

I, 6° F

* F or th e lo w er o ut pu t, an o pt io na l S pe ed C on tr ol le r m us t b e or de re d.

† S ta te d A

M P is fu ll lo ad (F

LA

A M

P dr aw v ar ie s by m ot or m an uf ac tu re r ±

.2 A

M

PS

‡ M ot or

H P lis te d is a pp lic ab le to s ta nd ar d m ot or ty pe o nl y.

F or e xp lo si on p ro of m ot or

H P, s ee m ot or d at a se ct io n.

°F

0°

F

4° F

6°

F

2° F

6°

F

9° F

0°

F

5° F

9°

F

6° F

8°

F

3° F

3°

F

3° F

1°

F

5° F

2°

F

4° F

6°

F

0° F

6°

F

6° F

3°

F

0° F

3°

F

2° F

4°

F

4°

F

0°

F

0°

F

7°

F

6°

F

6°

F

2°

F

3°

F

II I II I II I II I II I II I II I II I II I II I III II III II III II III IV — IV — IV — III — IV — IV — IV — IV — IV —

,0

,8

8, 5, 4, 1, 5, 2, 3, 1, 7, 5, 6, 3, 4, 1, 3, 9, 2, 7, 1, 4, 9, 2, 8, 0, 7,

— 9 5, 4, 3, 8, 8, 4, 9, 0, 1, .8

1.

2.

3.

1.

1.

2.

3.

4.

5.

6.

7.

7.

8.

9.

.4

.3

.8

.9

.4

.0

.0

.2

G

PM

B TU Pe r

H ou r*

U ni t

Si ze

H V-

8A

H V-

8A

H V-

5A

H V-

6A

H V-

8B

H V-

4B

H V-

6B

H V-

8B

H V-

0B

H V-

2B

H V-

4B

H V-

6B

H V-

8B

H V-

0B

H V-

2B

H V-

4B

H V-

6B

H V-

0B

H V-

4B

H V-

0B

H V-

0B

H V-

0B

H V-

0B

Fi na l

A ir

Te m p

W at t

W at t

1/

W at t

1/

1/

1/

1/

1/

1/ 12 1/

1/

1/

1/

1/

1/

1/

1/

1/

.8

2.

2.

3.

.0

.0 14 .0

.1

.1

.2

.2

.2

.3

.3

.4

.4

.5

.6

.7

1.

1.

33 2.

2.

M ot or

H P†

Pr es su re

D ro p

Ft /H

2O

50 — 10 00 — 11 50 — 8 00 — 10 00 — 9 00 — 9 80 — 7 00 — 10 00 —

00 — 22 00 — 26 00 — 22 00 — 29 00 — 35 00 — 42 00 — 50 00 — 55 00 —

40 — 11 40 — 11 40 — 11 40 — 11 40 — 11 40 — 11 00 — 11 00 — 11 00 —

N om in al

A m ps A t

5V A C

.8

1.

1.

1.

1.

1.

1.

.4

.4

.4

.4

.4

.4

.2

.2

.2

.2

.2

.2

.5 4.

5 — 4.

5 — 4.

5 — 4.

5 — 4.

5 — 4.

5 — 5.

4 — 5.

4 — 5.

4 —

So un d

R at in g

O ut le t

FP

M

N om in al

C

FM

R

PM

—11

1/

W at t

W at t

W at t

M ot or

M od el

O ut pu t

— 18

— 18

— 18

— 18

— 20

— 20

— 24

— 24

— 11 40 — 11 40 — 11 40 — 11 40 — 11 40 — 11 40 — 11 00 — 11 00 — 11 00 —

W at t

W at t

1/

1/

1/

1/

1/

1/ 12 1/

1/

1/

1/

1/

1/

1/

1/

1/

1/

HV

-0

B

HV

-0

B

HV

-0

B

HV

-0

B

HV

-0

B

HV

-0

B

HV

-0

B

HV

-0

B

HV

-1

B

HV

-1

B

HV

-1

B

HV

-1

B

HV

-1

B

HV

-1

B

HV

-2

B

HV

-2

B

HV

-2

B

HV

-3

B

HV

-3

B

8, 6, 4, 1, 6, 2, 8, 3, 0, 4, 2, 4, 4, 5, 6, 6, 8, 7, 0, 2, 4, 6, 0, 4, 0, 0, 0, 0, —B TU Pe r

H ou r*

U ni t

Si ze

Fi na l

A ir

Te m p

M ot or

H P‡

R

PM

Fo ot

ED

R

Pe r

H ou r

8.

6.

4.

2.

7.

3.

9.

4.

1.

5.

3.

6.

5.

6.

7.

8.

0.

8.

2.

— 13

4.

6.

0.

0.

8.

4.

0.

0.

6.

— 5

— 6

00 — 6 50 — 7 70 — 8 50 — 10 00 — 11 00 — 12 50 — 15 00 —

2°

F

5° F

9°

F

2° F

9°

F

0° F

9°

F

3° F

1°

F

1° F

0°

F

3° F

5°

F

3° F

3°

F

2° F

5°

F

0° F

8°

F

1°

F

0°

F

5°

F

5°

F

4°

F

3°

F

1°

F

7°

F

0°

F

1.

1.

.4

.4

.4

.4

.4

.4

.2

.2

.2

.2

.2

.2

.5

4.

5 — 4.

5 — 4.

5 — 4.

5 — 4.

5 — 4.

5 — 5.

4 — 5.

4 — 5.

4 —

— 9 50 — 10 00 — 11 50 — 8 00 — 10 00 — 9 00 — 9 80 — 7 00 — 10 00 —

— 20 00 — 22 00 — 26 00 — 22 00 — 29 00 — 35 00 — 42 00 — 50 00 — 55 00 —

N om in al

A m ps

A t

5V

AC

N om in al

Fa n

D ia m et er

O ut le t

FP

M

N om in al

C

FM

W at t

M od el

O ut pu t

Lb s

Co nd en sa te

Sq ua re

M ot or

Steam and Hot Water Coil Specifications

Serpentine Coil Specifications

GENERAL

Furnish and install, where indicated or scheduled on plans, Vulcan Model HVA horizontal hot water unit heaters. Unit shall be equipped as specified herein. All units shall be installed in a neat and workmanlike manner in accordance with this specification and the manufacturer's installation instructions.

CASING

Casings shall be 20-gauge die-formed steel. Paint finish shall be of lead-free, chromate free, polyester melamine resin base. Finish shall be baked at 400°F.

COIL MODELS 108A - 136A

Coil is a serpentine design with seamless copper tubing. Aluminum fins shall have drawn collars to assure permanent bond with expanded tubes. Tubing connection shall be 3/8 in copper tubing, type “M” (.500 OD). Coils shall be factory tested at 200 PSI. Coils have a max operating entering water temperature of 320°F.

MOTORS

Motors shall be totally enclosed fan cooled, resilient mounted with class “B” windings. All motors shall be designed for horizontal mounting.

FANS

Fans shall be of aluminum blade type, designed and balanced to assure maximum air delivery, low motor horsepower requirements and quiet operation.

OSHA FAN GUARDS

OSHA fan guards shall be welded steel, zinc plated or painted.

OSHA fan guard standard on sizes 108A thru 136A.

AIR DEFLECTION LOUVERS

Units shall be equipped with horizontal, individually adjustable louvers.

The following table is based on 60°F entering air and either 2 lbs steam or 200°F TD. The data is based on the higher speed CFM throughout and velocity. Care should be exercised in locating adjacent unit heaters and allowance should be made for obstructions in the air pattern and conflicting air currents from other air moving devices.

GENERAL

Furnish and install where indicated or scheduled on plans horizontal steam/hot water unit heater. Unit shall be equipped as specified herein. All units shall be installed in a neat and workmanlike manner in accordance with this specification and the manufacturer's installation instructions.

CASING

Casings shall be 20-gauge die-formed steel. Paint finish shall be of lead-free, chromate free, polyester melamine resin base. Finish shall be baked at 400°F.

COIL SIZES 18 - 360

Coil elements and headers shall be of heavy wall drawn seamless copper tubing. Element tubes shall be brazed into extruded header junctions. Pipe connection saddles shall be of cast bronze.

Aluminum fins shall have drawn collars to assure permanent bond with expanded element tubes and exact spacing. All Element Assemblies are submersion tested at the factory at 200 PSI. Under maximum conditions, coils are rated at 150 PSI at 366°F for steam and 150 PSI at 320°F for hot water. We recommend operating pressure of 75 PSI at 320°F for long life.

MOTORS

Motors shall be totally enclosed fan cooled, resilient mounted with class “B” windings. All motors shall be designed for horizontal mounting.

Motors under 1/3 HP are totally enclosed, frame mounted, 115/1/60 with thermal overload protection and permanently lubricated sleeve bearings with optional solid state speed controller available. 1/3 HP (115/1/60) motors are open frame construction, with thermal overload protection and ball bearings. 1/3 HP at (230 Volt) and all 1/2 HP motors are open frame construction, with thermal overload protection and ball bearings. 1/3 and 1/2 HP motors are available in single and three phase in open frame construction or explosion-proof housings, all the above are available as options.

EXPLOSION PROOF MOTORS

An enclosed motor whose enclosure is designed and constructed to withstand an explosion of a specified gas or vapor which may occur within the motor and to prevent the ignition of this gas or vapor surrounding the machine.

Horizontal unit heater motors comply with the National Electrical Code classification as follows:

Class I, Group D; all sizes
Class II, Group F; all sizes
Class II, Group G; all sizes
Division I & II Installations
T-code (T3B)

Explosion proof equipment is not generally available for Class I, Group

A and B and it is necessary to isolate motors from the hazardous area. All explosion proof motors are shelf mounted.

FANS

Fans shall be of aluminum blade, hub type designed and balanced to assure maximum air delivery, low motor horsepower requirements and quiet operation. Blades are spark proof.

FAN GUARDS

Fan guards shall be welded steel, zinc plated or painted. Units mounted below 8 feet from floor must be equipped with an OSHA fan guard to meet ETL and OSHA requirements. OSHA fan guard standard on sizes 18 thru 48.

AIR DEFLECTION LOUVERS

Units shall be equipped with horizontal, individually adjustable louvers. Vertical louvers for four-way air control shall be available as an optional extra.

Mounting Heights and Throws

HV-108A

HV-118A

HV-125A

HV-136A

HV-18

HV-24

HV-36

HV-48

HV-60

HV-72

HV-84

HV-96

Model/Unit Size

40'

40'

54'

55'

55'

53'

55'

57'

57'

58'

60'

11'

12'

13'

13'

13'

13'

13'

14'

14'

15'

15'

HV-108

HV-120

HV-132

HV-144

HV-156

HV-180

HV-204

HV-240

HV-280

HV-300

HV-360

20'

25'

29'

29'

20'

24'

28'

30'

30'

29'

30'

38'

8'

8'

9'

9'

8'

8'

9'

9'

10'

10'

10'

11'

Maximum Mounting Height

Approximate Maximum Throw

Model/Unit Size

Maximum Mounting Height

Approximate Maximum Throw

Maximum Mounting

Height

Maximum Distance of Throw

Horizontal Unit Heaters Motor Characteristics

115/1/60

230/1/60

208-230/460/3/60

1.8 1.5 1.8 2.8

5.6

6.8

0.5

1.8 0.8 1.8 2.8

5.6

6.8

3.3-3.3/1.6

NOTE 1: All motors are constant speed and operate at top speed as indicated in motor data. Unit sizes 18 through 108, including 108A, 118A, 125A and 136A can be run at reduced speed with addition of optional variable speed switch. This switch is factory-calibrated for low and high speed ratings, with intermediate speeds infinitely controllable. Models 120 through 360 operate at constant speed as indicated in motor data. All 1/4 HP motors are PSC.

NOTE 2: Motors under 1/3 HP are totally enclosed, frame mounted, 115/1/60 with thermal overload protection and permanently lubricated sleeve bearings with optional speed controller available. 1/3 HP (115/1/60) motors are open frame constant speed with thermal over-load protection and ball bearings. 1/3 HP (230 Volt) and 1/2 HP (230 Volt) motors are open frame constant speed with thermal overload protection and ball bearings.

NOTE 3: 1/3 and 1/2 HP motors are available as 230 Volt single and 3 phase in open frame and explosion-proof housings, all available as options. 1/3 and 1/2 HP motors operate at single speed only.

NOTE 4: Stated AMP draw is full load amp (FLA). AMP draw varies by motor manufacturer ± .2 AMPS. Verify FLA per unit motor data plate.

CAUTION: Select appropriate AMP and MCA for the multiple voltage motors. For example, the AMP and MCA for Models 360 with a 460 volt Totally Enclosed motor is 1.3 and 1.6 respectively.

NOTICE: Also refer to Maintenance section for additional motor data.

TOTALLY ENCLOSED

MOTOR TYPE

16W*

1/20* 25W* 1/20* 1/12*

1/3

1/2

16W

1/20† 25W 1/20† 1/12†

1/3†

1/2†

1/2**

18, 24, 108A, 118A 136A

36, 125A 48, 60, 72 84, 96,108

120, 132,144, 156, 180, 204, 280, 300, 360

18, 24, 108A, 118A

136A 36, 125A 48, 60, 72 84, 96, 108

120, 132, 144, 156, 180, 204, 280, 300, 360

48, 60, 72, 84, 96, 108, 120, 132, 144, 156, 180, 204, 240, 280, 300, 360

0.8

1.4 1.2 1.4 2.2

4.5

5.4

0.4

1.4 0.6 1.4 2.2

4.5

5.4

2.6-2.6/1.3

Unit

Sizes

AMP

MCA

HP

RPM

*Optional variable speed switch is available.

**These motors are without thermal overload protection.

Motors without thermal overload protection must be installed with optional manual starter or field provided overload protection.

48, 60, 72, 84, 96, 108, 120, 132 144, 156, 180, 204

280, 300, 48, 60, 72, 84, 96, 108, 120, 132 144, 156, 180, 204

280, 300, 144, 156, 180, 204, 240, 280, 300, 360

115/1/60

230/1/60

230/460/3/60

***These motors are 115/230 volts.

†230/1/60 unit has 115/1/60 motor supplied with field installed stepdown transformer.

EXPLOSION PROOF

WITH THERMAL OVERLOAD MOTOR TYPE

1/6

1/4

1/3***

1/2***

1/6†

1/4†

1/3***

1/2***

1/3

4.6

6.8

9.8

12.0

4.6

6.8

4.9

6.0

2.8/1.4

3.7

5.4

7.8

9.6

3.7

5.4

3.9

4.8

2.2/1.1

Unit

Sizes

AMP

MCA

HP

RPM