Attachment 36 - Envr. Report - Appendix B.pdf

PDF 2 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks Federal contract opportunity
Solicitation number
36C77623R0009
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This is a solicitation for a construction contract to provide infrastructure upgrades at multiple buildings on the St. Louis Jefferson Barracks VA Medical Center campus. The selected contractor will furnish all labor, materials, and equipment to perform electrical upgrades including new and upgraded panels, power systems, UPS, and BMS interfaces; HVAC reconfigurations and expansions; data center renovations including piping and walls; communication upgrades including new data outlets and fiber backbone; physical security upgrades; and hazardous material abatement. Project locations include Buildings 1, 2, 3, 3T, 18, 23, 24, 25, 51, 51T, 52, 53, 53T, 55, 56, 57, 58, 59, 60, 60T, 61, and 75. The Department of Veterans Affairs Technology Acquisition Center Austin issued the solicitation.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks, newest first.
File Type Posted
36C77623R0009 0005.pdf PDF
329000-05-R1 Sod Certificate.pdf PDF
36C77623R0009 0004.pdf PDF
657-21-701JB - 100 PC - Basis of Design.pdf PDF
32 32 23 01R1 - Mechanically Stabilized Earth Wall System RESPONSE.pdf PDF
36C77623R0009 0003.pdf PDF
Attachment 43 - Construction Wage Rates - St. Louis 3-3-23.pdf PDF
36C77623R0009 0002.pdf PDF
Site Visit Sign-in Sheet - St. Louis 2-28-23.pdf PDF
36C77623R0009 0001.pdf PDF
Attachment 4 - Drawings Part-3.pdf PDF
Attachment 10 - Drawings Part-9.pdf PDF
Attachment 14 - Drawings Part-13.pdf PDF
Attachment 20 - Drawings Part-19.pdf PDF
Attachment 21 - Drawings Part-20.pdf PDF
Attachment 25 - Drawings Part-24.pdf PDF
Attachment 26 - Drawings Part-25.pdf PDF
Attachment 28 - Drawings Part-27.pdf PDF
Attachment 29 - Drawings Part-28.pdf PDF
Attachment 32 - Drawings Part-31.pdf PDF
Attachment 39 - ICRA ILSM Tool - MCM 001S-03 Att B.zip ZIP file
36C77623R0009 - 2-16-23.pdf PDF
Attachment 7 - Drawings Part-6.pdf PDF
Attachment 11 - Drawings Part-10.pdf PDF
Attachment 12 - Drawings Part-11.pdf PDF
Attachment 13 - Drawings Part-12.pdf PDF
Attachment 18 - Drawings Part-17.pdf PDF
Attachment 31 - Drawings Part-30.pdf PDF
Attachment 35 - Envr. Report - Appendix A.pdf PDF
Attachment 38 - Envr. Report - Drawings.pdf PDF
Attachment 42 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 45 - Site Visit Instructions.pdf PDF
Attachment 1 - Specifications.pdf PDF
Attachment 5 - Drawings Part-4.pdf PDF
Attachment 6 - Drawings Part-5.pdf PDF
Attachment 9 - Drawings Part-8.pdf PDF
Attachment 16 - Drawings Part-15.pdf PDF
Attachment 22 - Drawings Part-21.pdf PDF
Attachment 24 - Drawings Part-23.pdf PDF
Attachment 41 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Attachment 44 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 2 - Drawings Part-1.pdf PDF
Attachment 3 - Drawings Part-2.pdf PDF
Attachment 8 - Drawings Part-7.pdf PDF
Attachment 15 - Drawings Part-14.pdf PDF
Attachment 17 - Drawings Part-16.pdf PDF
Attachment 19 - Drawings Part-18.pdf PDF
Attachment 23 - Drawings Part-22.pdf PDF
Attachment 27 - Drawings Part-26.pdf PDF
Attachment 30 - Drawings Part-29.pdf PDF
Show all 50

Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MANAGEMENT PLAN REMOVAL PRIORITY ASSESSMENT CHARTS

Qualitative (Descriptive) Rankings for Current Condition of ACM Qualitative Ranking Example Descriptions of Current Condition

Good (G) Surfacing material has no visible damage; covering on TSI is intact; miscellaneous materials are intact; no visible debris.

Damaged (D) Surfacing material has moderate but not extensive visible damage; covering on TSI is cut or torn, exposing small but not extensive amounts of insulation; miscellaneous materials have moderate but not extensive damage; moderate but not extensive amounts of visible debris

Significantly Damaged (SD) Extensive damage to surfacing material; covering on TSI is cut or torn extensively and insulation itself is damaged; miscellaneous materials such as floor tile is extensively damaged and underlying mastic exposed; extensive amounts of dust and debris.

Note: Damage is considered “extensive” when the total area of distributed damage exceeds 10%, or 25% localized damage.

Qualitative Rankings for Potential for Disturbance of ACM Level of Potential Disturbance Frequency of Potential

Contact (accessibility) Influence of Vibration Potential for Air Erosion or

Water Damage

HIGH (H)

(potential for significant damage) High Any Value Any Value

Any Value High Any Value Any Value Any Value High

MODERATE (M)

(potential for damage)

Moderate Moderate or Low Moderate or Low Moderate or Low Moderate Moderate or Low Moderate or Low Moderate or Low Moderate

LOW (L) Low Low Low Note: Overall rating determined by assigning disturbance probabilities under all 3 categories then adopting highest individual score for each material.

Qualitative Rankings and Numerical Ratings for Removal Priority of ACM Hazard Rank/

Removal Priority ACBM Condition ACBM Disturbance

Potential Recommended Response Actions

1 Significantly Damaged

Any Evacuate or isolate area immediately. Remove ACBM immediately. O&M Required for all friable ACBM.

2 Damaged High Evacuate or isolate area immediately. Remove, enclose, encapsulate or repair ACBM to correct immediately. Reduce potential for disturbance of remaining materials. O&M Required for all friable ACBM.

3 Damaged Moderate Remove, enclose, encapsulate, or repair to correct damage as soon as feasible.

O&M Required for all friable ACBM.

4 Damaged Low Remove, enclose, encapsulate, or repair to correct damage as needed to facilitate future projects. Take steps to reduce potential for disturbance. O&M Required for all friable ACBM.

5 Good High Take steps to reduce potential for disturbance. O&M Required for all friable ACBM.

6 Good Moderate O&M Required for all friable ACBM.

7 Good Low O&M Required for all friable ACBM, but measures need not be as extensive as

Category 6.

VA JEFFERSON BARRACKS CAMPUS

BUILDING 1

SIX MONTH PERIODIC SURVELLIANCE FORM

09/01/21-09/29/21

Homogeneous Area No. Bldg Floor Material Description

Friable Yes/No

Previous Condition Winter 2019/2020

Current Condition Summer 2020

Potential for Disturbance Removal

Priority Comments

Rating Based On Rating Based On

Rating Based On

Building 1 – Basement

HMA-A1 1 B 12"x12" floor tile – gray w/ black mastic No G Intact G Intact L Floor

Maintenance 7 Gc17c-01 all tile, mastic, and pipes abated

HMA-B1 1 B 9"x9" floor tile - brown w/ black mastic No G Intact G Intact L Floor

Maintenance 7 Gc14-01 all tile, mastic, and pipes abated

HMA-C1 1 B 12”x12” floor tile - green w/ black mastic No D Damaged D Damaged M Floor

Maintenance 3 Gc15-01 all tile, mastic, and pipes abated

HMA-D1 1 B 12"x12" floor tile - white w/ black mastic No G Intact G Intact L Floor

Maintenance 7 Gc15a all tile, mastic and pipes abated

HMA-J1 1 B 9"x9" floor tile - gray w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-K1 1 B 9"x9" floor tile - dark brown w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-L1 1 B 9"x9" floor tile - tan w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-M1 1 B 9”x9” floor tile - dark grey w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-N1 1 B 12"x12" floor tile - brown w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-Q 1 B 12”x12” floor tile – light white No G Intact G Intact L Floor Maintenance 7

HMA-1 1 B Black mastic No G Intact G Intact L Maintenance 7

HMA-19 1 B ACM pipe insulation and mudded fittings Yes SD Significantly

Damaged SD Significantly Damaged M Access/

Maintenance 1 See maps for SD locations.

HMA-24 1 B Fire Door No G Intact G Intact L Maintenance 7

HMA-25 1 B Interior window caulk-gray No G Intact G Intact L Maintenance 7

HMA-29 1 B Penetration caulk-white No G Intact G Intact L Maintenance 7

Homogeneous Area No. Bldg Floor Material Description

Friable Yes/No

Previous Condition Winter 2019/2020

Current Condition Summer 2020

Potential for Disturbance Removal

Priority Comments

Rating Based On Rating Based On

Rating Based On

HMA-31 1 B Wall mounted heater (PACM) No G Intact G Intact L Maintenance 7

HMA-41 1 B Flange gasket (PACM) No G Intact G Intact L Maintenance 7

HMA-43 1 B Ceiling mounted heater No G Intact G Intact L Maintenance 7

HMA-46 1 B Thick gray caulk on AHU No G Intact G Intact M Maintenance 6

HMA-71 1 B Transite panels No G Intact G Intact L Access/ Maintenance 7

HMA-72 1 B 12”x12” floor tile- green w/ pattern w/black mastic No D Damaged D Damaged M Floor

Maintenance 3

HMA-73 1 B

Black mastic under 12”x12” floor tile-green/gray w/ splotches

No G Intact G Intact L Floor Maintenance 7

HMA-74 1 B Hard gray material on duct Yes G Intact G Intact M Maintenance 6

HMA-75 1 B Felt roofing tar No G Intact G Intact L Maintenance 7

Building 1 – 1st Floor

HMA-A1 1 1 12"x12" floor tile – gray w/ black mastic No G Intact G Intact L Floor

Maintenance 7 1E-23-01-JB All Tile Abated

HMA-B1 1 1 9"x9" floor tile - brown w/ black mastic No G Intact G Intact L Floor

Maintenance 7 1e01,1e02,1e04,1eo7,1e08,1e09, 1e12,1e14,1e15,1e16,1e17

HMA-D1 1 1 12” floor tile- white w/ black mastic No G Intact G Intact L Floor

Maintenance 7 1e17a,1e18 tsi pipes tile mastic

HMA-J1 1 1 9"x9" floor tile - gray w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-N1 1 1 12"x12" floor tile - brown w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-Q1 1 1 12"x12" floor tile - light whit w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-R1 1 1 9”x9” floor tile – green w/ black mastic No G Intact G Intact L Floor

Maintenance 7

Friable Yes/No

Previous Condition Winter 2019/2020

Current Condition Summer 2020

Potential for Disturbance Removal

Priority Comments

Rating Based On Rating Based On

Rating Based On

HMA-T1 1 1 12”x12” floor tile – light brown w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-19 1 1 ACM pipe insulation and mudded fittings Yes SD Damaged SD Significantly

Damaged M Access/ Maintenance 1 See maps for SD locations.

HMA-24 1 1 Fire Door No G Intact G Intact L Maintenance 7 South rooms on east abated pipe tile mastic

HMA-31 1 1 Wall mounted heater (PACM) No G Intact G Intact L Maintenance 7

HMA-41 1 1 Flange gasket (PACM) No G Intact G Intact L Maintenance 7

HMA-43 1 1 Ceiling mounted heater (PACM) No G Intact G Intact L Maintenance 7

Building 1 – 2nd Floor

HMA-D1 1 2 12"x12" floor tile - white w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-N1 1 2 12"x12" floor tile - brown w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-P1 1 2 Linoleum floor w/ black mastic Yes G Intact G Intact L Floor Maintenance 7

HMA-Q1 1 2 12"x12" floor tile - light white w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-T1 1 2 12”x12” floor tile – light brown w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-W1 1 2 12”x12” floor tile – dark white w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-19 1 2 ACM pipe insulation and mudded fittings Yes SD Significantly

Damaged SD Significantly Damaged M Maintenance 1 See maps for SD locations.

HMA-24 1 2 Fire Door No G Intact G Intact L Access/ Maintenance 7

HMA-31 1 2 Wall mounted heater (PACM) No G Intact G Intact L Maintenance 7

HMA-41 1 2 Flange gasket (PACM) No G Intact G Intact L Maintenance 7

HMA-43 1 2 Ceiling mounted heater (PACM) No G Intact G Intact L Maintenance 7

Friable Yes/No

Previous Condition Winter 2019/2020

Current Condition Summer 2020

Potential for Disturbance Removal

Priority Comments

Rating Based On Rating Based On

Rating Based On

HMA-62 1 2 Black lab countertop No G Intact G Intact L Maintenance 7

HMA-65 1 2 Transite vent hood No G Intact G Intact L Maintenance 7

Building 1 – 3rd Floor

HMA-B1 1 3 9"x9" floor tile - brown w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-D1 1 3 12”x12” floor tile - white w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-P1 1 3 Linoleum floor w/ black mastic Yes G Intact G Intact L Floor Maintenance 7

HMA-Q1 1 3 12"x12" floor tile - light white w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-T1 1 3 12”x12” floor tile – light brown w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-W 1 2 12”x12” floor tile – dark white No G Intact G Intact L Floor Maintenance 7

HMA-19 1 3 ACM pipe insulation and mudded fittings Yes G Intact G Intact M Access/

Maintenance 6 3c14-01 tsi pipes abated

HMA-24 1 3 Fire Door No G Intact G Intact L Maintenance 7

HMA-25 1 3 Interior window caulk - gray No G Intact G Intact L Maintenance 7

HMA-31 1 3 Wall mounted heater (PACM) No G Intact G Intact L Maintenance 7

HMA-41 1 3 Flange gasket (PACM) No G Intact G Intact L Maintenance 7

HMA-43 1 3 Ceiling mounted heater (PACM) No G Intact G Intact L Maintenance 7

HMA-62 1 3 Black lab countertop No G Intact G Intact L Maintenance 7

HMA-64 1 3 Black tar – covered duct insulation Yes G Intact G Intact L Maintenance 7

HMA-65 1 3 Transite vent hood No G Intact G Intact L Maintenance 7

Friable Yes/No

Previous Condition Winter 2019/2020

Current Condition Summer 2020

Potential for Disturbance Removal

Priority Comments

Rating Based On Rating Based On

Rating Based On

HMA-71 1 3 Transite panels No G Intact G Intact L Access/ Maintenance 7

Building 1 – Penthouse

HMA-D1 1 P 12"x12" floor tile – white w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-R1 1 P 9”x9” floor tile – green w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-19 1 P ACM pipe insulation and mudded fittings Yes G Intact G Intact M Access/

Maintenance 6

HMA-24 1 P Fire door No G Intact G Intact L Maintenance 7

HMA-41 1 P Flange gasket (PACM) No G Intact G Intact L Maintenance 7

Building 1 – Exterior

HMA-69 1 Ext Roofing mastic No G Intact G Intact M Maintenance 6

HMA-70 1 Ext Stucco surfacing material-tan Yes D Damaged D Damaged M Maintenance 6 Damaged material is friable.

HMA-75 1 Ext Roofing tar No G Intact G Intact M Maintenance 6

Good (G) Surfacing material has no visible damage; covering on TSI is intact; miscellaneous materials are intact; no visible debris.

Damaged (D) Surfacing material has moderate but not extensive visible damage; covering on TSI is cut or torn, exposing small but not extensive amounts of insulation; miscellaneous materials have moderate but not extensive damage; moderate but not extensive amounts of visible debris

Significantly Damaged (SD) Extensive damage to surfacing material; covering on TSI is cut or torn extensively and insulation itself is damaged; miscellaneous materials such as floor tile is extensively damaged and underlying

Note: Damage is considered “extensive” when the total area of distributed damage exceeds 10%, or 25% localized damage.

Contact (accessibility) Influence of Vibration Potential for Air Erosion or

Water Damage

HIGH (H)

(potential for significant damage) High Any Value Any Value

Any Value High Any Value Any Value Any Value High

MODERATE (M)

(potential for damage)

Moderate Moderate or Low Moderate or Low Moderate or Low Moderate Moderate or Low Moderate or Low Moderate or Low Moderate

LOW (L) Low Low Low Note: Overall rating determined by assigning disturbance probabilities under all 3 categories then adopting highest individual score for each material.

Qualitative Rankings and Numerical Ratings for Removal Priority of ACM Hazard Rank/

Removal Priority ACBM Condition ACBM Disturbance

Potential Recommended Response Actions

1 Significantly Damaged

Any Evacuate or isolate area immediately. Remove ACBM immediately. O&M Required for all friable ACBM.

2 Damaged High Evacuate or isolate area immediately. Remove, enclose, encapsulate or repair ACBM to correct immediately. Reduce potential for disturbance of remaining materials. O&M Required for all friable ACBM.

3 Damaged Moderate Remove, enclose, encapsulate, or repair to correct damage as soon as feasible.

O&M Required for all friable ACBM.

4 Damaged Low Remove, enclose, encapsulate, or repair to correct damage as needed to facilitate future projects. Take steps to reduce potential for disturbance. O&M Required for all friable ACBM.

5 Good High Take steps to reduce potential for disturbance. O&M Required for all friable ACBM.

6 Good Moderate O&M Required for all friable ACBM.

VA JOHN COCHRAN CAMPUS

BUILDING 1

SIX MONTH PERIODIC SURVELLIANCE FORM

09/01/21-09/27-21

Homogeneous Area No. Bldg Floor Material Description

Friable Yes/No

Previous Condition Current Condition 1 Potential for Disturbance 2 Removal

Priority 3 Comments

Rating Based On Rating Based On

Rating Based On

Building 1 – Basement

HMA-A1 1 B 12"x12" floor tile – gray w/ black mastic No G Intact G Intact L Floor

Maintenace 7

HMA-B1 1 B 9"x9" floor tile - brown w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-C1 1 B 12”x12” floor tile - green w/ black mastic No D Damaged D Damaged M Floor

Maintenance 3

HMA-D1 1 B 12"x12" floor tile - white w/ black mastic No G Intact

G Intact L Floor

HMA-J1 1 B 9"x9" floor tile - gray w/ black mastic No G Intact

G Intact L Floor

HMA-K1 1 B 9"x9" floor tile - dark brown w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-L1 1 B 9"x9" floor tile - tan w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-M1 1 B 9”x9” floor tile - dark grey w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-N1 1 B 12"x12" floor tile - brown w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-Q 1 B 12”x12” floor tile – light white No G Intact G Intact L Floor Maintenance 7

HMA-1 1 B Black mastic No G Intact G Intact L Floor Maintenance 7

HMA-19 1 B ACM pipe insulation and mudded fittings Yes SD Intact SD Significantly

Damaged M Maintenance 1

Building 1 – Basement

HMA- D1 1 0 12”x12” Floor Tile- Light Tan w/ Black Mastic No G Intact G Intact M Floor

Maintenance 6

HMA- E1 1 0 9”x9” Floor Tile- White w/ Black Mastic No G Intact G Intact M Floor

Maintenance 6

Friable Yes/No

Previous Condition Current Condition 1 Potential for Disturbance 2 Removal

Priority 3 Comments

Rating Based On Rating Based On

Rating Based On

HMA-F1 1 0

12”x12” Floor Tile- White w/ Brown Streaks w/ Black

Mastic No G Intact G Intact M Floor

Maintenance 6 B003 Tile removed/ but mastic remains

HMA-01 1 0 Pipe Insulation & Fittings Yes D Damage to TSI D Damage to

TSI M Access 3 See maps for specific locations of Damaged TSI

HMA-01 1 0 Pipe Insulation & Fittings Yes SD Significant Damage to

TSI

SD

Significant Damage to

TSI

M Access 1 See maps for specific locations of

Significantly Damaged TSI

HMA-05 1 0 Fire Doors (Assumed) No G Intact G Intact L Maintenance 7

HMA-19 1 0 Black Tar on Fiberglass Pipe Insulation No G Intact G Intact M Access 6

HMA-20 1 0

Wall Mounted Heaters/Steam Convector

Units (Heat Shields Presumed)

No G Intact G Intact L Access 8

HMA-34 1 0

Black Mastic Under

12”x12” White w/ Charcoal Streaks

No G Intact G Intact L Maintenance 7

HMA-102 1 0

12”x12” Floor Tile- Off White/Cream w/

Gray/White Specs w/ Black Mastic

No G Intact G Intact M Floor

HMA-128 1 0 TSI Insulation Saddles on CWS Pipe Hangars Yes G Intact G Intact M Access 6 CB03 all fittgs abated

HMA-140 1 0

Black Mastic Under

Unknown Layer Under

HMA 41

HMA-151 1 0

Unknown Layer Under

HMA 91

HMA-163 1 0 HVAC Duct Insulation, Soft Gray Yes G Intact G Intact M Access 6 No Visibility

HMA-173 1 0 Cork and Tar Pipe Insulation No G Intact G Intact M Access 6 Loose cork substrate damaged in locations noted on maps; tar intact

Building 1 – 1st Floor

Friable Yes/No

Previous Condition Current Condition 1 Potential for Disturbance 2 Removal

Priority 3 Comments

Rating Based On Rating Based On

Rating Based On

HMA-C1 1 1 12”x12” Floor Tile w/ Black Mastic No G Intact G Intact M Floor

Maintenance 7

HMA-G1 1 1 9”x9” Floor Tile- Brown w/ Black Mastic No G Intact G Intact M Floor

Maintenance 7

HMA-H1 1 1

12”x12” Floor Tile- White w/ Green Streaks w/ Black

Mastic

HMA-01 1 1 Pipe Insulation & Fittings Yes D Damage to TSI D Damage to

TSI M Access 3 See maps for specific locations of Damaged TSI

HMA-01 1 1 Pipe Insulation & Fittings Yes SD Significant Damage to

TSI

SD

Significant Damage to

TSI

M Access 1 See maps for specific locations of

Significantly Damaged TSI

HMA-05 1 1 Fire Doors (Assumed) No G Intact G Intact L Maintenance 7

HMA-19 1 1 Black Tar on Fiberglass Pipe Insulation No G Intact G Intact M Access 6

HMA-20 1 1

Wall Mounted Heaters/Steam Convector

Units (Heat Shields

HMA-77 1 1

12”x12” Floor Tile- White w/ Large Beige Specs

HMA-128 1 1 TSI Insulation Saddles on CWS Pipe Hangars Yes G Intact G Intact M Access 6

HMA-133 1 1 Black Wrap TSI No G Intact G Intact M Access 6

HMA-140 1 1

Black Mastic Under

Unknown Layer Under

HMA 41

HMA-143 1 1 Unknown Floor Tile Layer Under HMA32 No G Intact G Intact L Floor

Maintenance 7

HMA-151 1 1

Black Mastic Under

Unknown Layer Under

HMA 91

HMA-163 1 1 HVAC Duct Insulation, Soft

Friable Yes/No

Previous Condition Current Condition 1 Potential for Disturbance 2 Removal

Priority 3 Comments

Rating Based On Rating Based On

Rating Based On

HMA-173 1 1 Cork and Tar Pipe Insulation No G Intact G Intact M Access 6 Loose cork substrate damaged in locations noted on maps; tar intact

Building 1 – 2nd Floor

HMA- D1 1 2 12”x12” Floor Tile- Light Tan w/ Black Mastic No G Intact G Intact M Floor

Maintenance 6

HMA-F1 1 2

12”x12” Floor Tile- White w/ Brown Streaks w/ Black

Mastic

HMA-I1 1 2

12”x12” Floor Tile- White w/ Brown/Gray Spots w/

Black Mastic

HMA-J1 1 2 12”x12” Floor Tile- Green w/ Black Mastic No G Intact G Intact M Floor

Maintenance 6

HMA-01 1 2 Pipe Insulation & Fittings Yes D Damage to TSI D Damage to

TSI M Access 3 See maps for specific locations of Damaged TSI

HMA-01 1 2 Pipe Insulation & Fittings Yes SD Significant Damage to

TSI

SD

Significant Damage to

TSI

M Access 1 See maps for specific locations of

Significantly Damaged TSI

HMA-05 1 2 Fire Doors (Assumed) No G Intact G Intact L Maintenance 7

HMA-19 1 2 Black Tar on Fiberglass Pipe Insulation No G Intact G Intact M Access 6

HMA-20 1 2

Wall Mounted Heaters/Steam Convector

Units (Heat Shields

HMA-70 1 2

12”x12” Floor Tile- Dark Blue w/ White Specs

HMA-128 1 2 TSI Insulation Saddles on

HMA-143 1 2 Unknown Layer Under HMA32 No G Intact G Intact L Floor

Maintenance 7

HMA-147 1 2 Unknown Layer Under HMA 32 No G Intact G Intact L Floor

Maintenance 7

HMA-163 1 2 HVAC Duct Insulation, Soft

Friable Yes/No

Previous Condition Current Condition 1 Potential for Disturbance 2 Removal

Priority 3 Comments

Rating Based On Rating Based On

Rating Based On

HMA-173 1 2 Cork and Tar Pipe Insulation No G Intact G Intact M Access 6 Loose cork substrate damaged in locations noted on maps; tar intact

Building 1 – 3rd Floor

HMA- D1 1 3 12”x12” Floor Tile- Light Tan w/ Black Mastic No G Intact G Intact M Floor

Maintenance 6

HMA- E1 1 3 9”x9” Floor Tile- White w/ Black Mastic No G Intact G Intact M Floor

Maintenance 6

HMA-I1 1 3

12”x12” Floor Tile- White w/ Brown/Gray Spots w/

Black Mastic

HMA-01 1 3 Pipe Insulation & Fittings Yes D Damaged to

TSI M Access 3 See maps for specific locations of Damaged TSI

HMA-01 1 3 Pipe Insulation & Fittings Yes SD Significant Damage to

TSI

SD

Significant Damage to

TSI

M Access 1 See maps for specific locations of

Significantly Damaged TSI

HMA-05 1 3 Fire Doors (Assumed) No G Intact G Intact L Maintenance 7

HMA-19 1 3 Black Tar on Fiberglass Pipe Insulation No G Intact G Intact M Access 6

HMA-20 1 3

Wall Mounted Heaters/Steam Convector

Units (Heat Shields

HMA-128 1 3 TSI Insulation Saddles on

HMA-163 1 3 HVAC Duct Insulation, Soft Gray Yes G Intact G Intact M Access 6 Limited Visibility

HMA-173 1 3 Cork and Tar Pipe Insulation No G Intact G Intact M Access 6 Loose cork substrate damaged in locations noted on maps; tar intact

Building 1 – 4th Floor

HMA-D1 1 4 12”x12” Floor Tile- Light Tan w/ Black Mastic No G Intact G Intact M Floor

Maintenance 7 412-all piping abated- new floor tle

HMA-E1 1 4 9”x9” Floor Tile- White w/ Black Mastic No G Intact G Intact M Floor

Maintenance 7

HMA-K1 1 4 12”x12” Floor Tile- Light Tan w/ Brown Spots w/ No G Intact G Intact M Floor

Friable Yes/No

Previous Condition Current Condition 1 Potential for Disturbance 2 Removal

Priority 3 Comments

Rating Based On Rating Based On

Rating Based On

Black Mastic

HMA-K2 1 4

12”x12” Floor Tile- Light Tan w/ Brown Spots w/

Yellow Mastic

HMA-N1 1 4

12”x12” Floor Tile- Green w/ Brown Spots w/ Black

Mastic

HMA-N2 1 4

w/ Brown Spots w/ Yellow

Mastic

HMA-O1 1 4 9”x9” Floor Tile- Gray w/

Maintenance 7

HMA-P1 1 4

12”x12” Floor Tile- White w/ Black Stripes w/ Black

Mastic No G Intact G Intact M Floor

Maintenance 7

Tsi abated-a400.h403h,402,435,426,427,428,4 25,424,429,430,423,422,431,421,4

HMA-01 1 4 Pipe Insulation & Fittings Yes D Damage to TSI D Intact L Access 8

A401,476,407,408,443,442,442a,4 40a tsi abated

HMA-01 1 4 Pipe Insulation & Fittings Yes SD Significant Damage to

TSI

SD

Significant Damage to

TSI

M Access 1 See maps for specific locations of

Significantly Damaged TSI

HMA-05 1 4 Fire Doors (Assumed) No G Intact G Intact L Maintenance 7

HMA-17 1 4 Sink Soundproofing- White No G Intact G Intact H Access 8

HMA-19 1 4 Black Tar on Fiberglass Pipe Insulation No G Intact G Intact M Access 6

HMA-20 1 4

Wall Mounted Heaters/Steam Convector

Units (Heat Shields

HMA-128 1 4 TSI Insulation Saddles on

HMA-142 1 4 Unknown Floor Tile Layer Under HMA 51 No G Intact G Intact L Floor

Friable Yes/No

Previous Condition Current Condition 1 Potential for Disturbance 2 Removal

Priority 3 Comments

Rating Based On Rating Based On

Rating Based On

HMA-143 1 4 Unknown Floor Tile Layer Under HMA32 No G Intact G Intact L Floor

Maintenance 7

HMA-151 1 4

Black Mastic Under

Unknown Layer Under

HMA 91

No G Intact G Intact L Floor Maintenance 8

HMA-163 1 4 HVAC Duct Insulation, Soft

HMA-173 1 4 Cork and Tar Pipe Insulation No G Intact G Intact M Access 6 Loose cork substrate damaged in locations noted on maps; tar intact

Building 1 – 5th Floor

HMA-D1 1 5 12”x12” Floor Tile- Light Tan w/ Black Mastic No G Intact G Intact M Floor

Maintenance 7 506-aal piping abated-new floor tile

HMA-E1 1 5 9”x9” Floor Tile- White w/ Black Mastic No G Intact G Intact M Floor

Maintenance 7

HMA-I1 1 5

12”x12” Floor Tile- White w/ Brown/Gray Spots w/

Black Mastic

HMA-J2 1 5 12”x12” Floor Tile- Green w/ Yellow Mastic No G Intact G Intact M Floor

Maintenance 6

HMA-N1 1 5

12”x12” Floor Tile- Green w/ Brown Spots w/ Black

Mastic

HMA-N2 1 5

w/ Brown Spots w/ Yellow

Mastic

HMA-P2 1 5 12”x12” Floor Tile- White w/ Black Stripes No G Intact G Intact M Floor

Maintenance 7

HMA-Q1 1 5

12”x12” Floor Tile- Light Brown w/ Dark Brown and Tan Spots w/ Black Mastic

HMA-X1 1 5 9”x9” Floor Tile- Tan w/

Maintenance 8 575 tsi abated

HMA-01 1 5 Pipe Insulation & Fittings Yes D Damage to TSI D Damage to

TSI M Access 3 See maps for specific locations of Damaged TSI

HMA-01 1 5 Pipe Insulation & Fittings Yes SD Significant Damage to

TSI

SD Intact L Access 1

Tsi abated h505h,504,557,555,558a,556,556a, 554,559,559a,552,561,562,550,549

Friable Yes/No

Previous Condition Current Condition 1 Potential for Disturbance 2 Removal

Priority 3 Comments

Rating Based On Rating Based On

Rating Based On

HMA-05 1 5 Fire Doors (Assumed) No G Intact G Intact L Maintenance 7 549a,548,571,573,548,568a,568b,5 67a,576b,566,569,570a,565a,565,5

HMA-17 1 5 Sink Soundproofing- White No G Intact G Intact H Access 8

HMA-19 1 5 Black Tar on Fiberglass Pipe Insulation No G Intact G Intact M Access 6

HMA-20 1 5

Wall Mounted Heaters/Steam Convector

Units (Heat Shields

HMA-39 1 5

12”x12” Floor Tile White w/ Large Dark Gray Specs

HMA-48 1 5

12”x12” Floor Tile – Slate Blue w/ Gray and White

Markings

HMA-127 1 5 Black Tar Wrap on Fiberglass HVAC No G Intact D Intact M Access 6

HMA-128 1 5 TSI Insulation Saddles on CWS Pipe Hangars Yes G Intact G Intact M Access 6

HMA-140 1 5

Black Mastic Under

Unknown Layer Under

HMA 41

HMA-142 1 5 Unknown Layer Under HMA 51 No G Intact G Intact L Floor

Maintenance 8

HMA-143 1 5 Unknown Layer Under HMA 32 No G Intact G Intact L Floor

Maintenance 8

HMA-163 1 5 HVAC Duct Insulation, Soft Gray Yes G Intact G Intact M Access 6 Limited Visibility

HMA-173 1 5 Cork and Tar Pipe Insulation No G Intact G Intact M Access 6 Loose cork substrate damaged in locations noted on maps; tar intact

Building 1 – 6th Floor

HMA-D1 1 6 12”x12” Floor Tile- Light Tan w/ Black Mastic No G Intact G Intact M Floor

Maintenance 7

HMA-K2 1 6 12”x12” Floor Tile- Light Tan w/ Brown Spots w/ No G Intact G Intact M Floor

Friable Yes/No

Previous Condition Current Condition 1 Potential for Disturbance 2 Removal

Priority 3 Comments

Rating Based On Rating Based On

Rating Based On

Yellow Mastic

HMA-N1 1 6

12”x12” Floor Tile- Green w/ Brown Spots w/ Black

Mastic

HMA-S1 1 6

12”x12” Floor Tile- Dark Tan w/ Tan and Brown Spots w/ Black Mastic

No G Intact G Intact M Floor Maintenance 7

Tsi abated A614,h601,610,611,611a,61a,612,6 09,613,608,613a,613b,697,605,606

HMA-01 1 6 Pipe Insulation & Fittings Yes D Damage to TSI D Intact L Access 8 Tsi abated

HMA-01 1 6 Pipe Insulation & Fittings Yes SD Significant Damage to

TSI

SD

Significant Damage to

TSI

M Access 1 See maps for specific locations of

Significantly Damaged TSI

HMA-05 1 6 Fire Doors (Assumed) No G Intact G Intact L Maintenance 7

HMA-19 1 6 Black Tar on Fiberglass Pipe Insulation No G Intact G Intact M Access 6

HMA-20 1 6

Wall Mounted Heaters/Steam Convector

Units (Heat Shields

HMA-34 1 6 12”x12” Floor Tile- White w/ Charcoal Streaks No G Intact G Intact M Floor

Maintenance 8

HMA-39 1 6

Black Mastic Under

12”x12” Floor Tile White w/ Large Dark Gray Specs

HMA-128 1 6 TSI Insulation Saddles on

HMA-143 1 6 Unknown Layer Under HMA 32 No G Intact G Intact L Floor

Maintenance 8

HMA-163 1 6 HVAC Duct Insulation, Soft Gray Yes G Intact G Intact M Access 6 No Visibility

HMA-173 1 6 Cork and Tar Pipe Insulation No G Intact G Intact M Access 6 Loose cork substrate damaged in locations noted on maps; tar intact

Building 1 – 7th Floor

HMA-A1 1 7 Black Mastic Under Linoleum No G Intact G Intact L Floor

Friable Yes/No

Previous Condition Current Condition 1 Potential for Disturbance 2 Removal

Priority 3 Comments

Rating Based On Rating Based On

Rating Based On

HMA-D1 1 7 12”x12” Floor Tile- Light Tan w/ Black Mastic No G Intact G Intact M Floor

Maintenance 7

HMA-H1 1 7

12”x12” Floor Tile- White w/ Green Streaks w/ Black

Mastic

HMA-M1 1 7

12”x12” Floor Tile- Dark

Tan w/ Brown Spots w/Black Mastic

HMA-01 1 7 Pipe Insulation & Fittings Yes D Damage to

TSI M Access 3 See maps for specific locations of Damaged TSI

HMA-01 1 7 Pipe Insulation & Fittings Yes SD Significant Damage to

TSI

SD

Significant Damage to

TSI

M Access 1 See maps for specific locations of

Significantly Damaged TSI

HMA-05 1 7 Fire Doors (Assumed) No G Intact G Intact L Maintenance 7

HMA-17 1 7 Sink Soundproofing- White No G Intact G Intact H Access 5

HMA-19 1 7 Black Tar on Fiberglass Pipe Insulation No G Intact G Intact M Access 6

HMA-20 1 7

Wall Mounted Heaters/Steam Convector

Units (Heat Shields

HMA-34 1 7

12”x12” Floor Tile- White w/ Charcoal Streaks

HMA-35 1 7

12”x12” Floor Tile- Light Tan w/ Gray Streaks

HMA-36 1 7

12”x12” Floor Tile- White w/ Navy Streaks and Specs

HMA-106 1 7

12”x12” Floor Tile- Peach w/ White and Faint Peach

Specs

HMA-128 1 7 TSI Insulation Saddles on

Friable Yes/No

Previous Condition Current Condition 1 Potential for Disturbance 2 Removal

Priority 3 Comments

Rating Based On Rating Based On

Rating Based On

HMA-143 1 7 Unknown Layer Under HMA 32 No G Intact G Intact L Floor

Maintenance 8

HMA-153 1 7

Black Mastic Under

Unknown Layer Under

HMA 36

HMA-163 1 7 HVAC Duct Insulation, Soft

HMA-164 1 7

12”x12” Floor Tile- Beige w/ Gray and Red Specs w/

Black Mastic

HMA-173 1 7 Cork and Tar Pipe Insulation No G Intact G Intact M Access 6 Loose cork substrate damaged in locations noted on maps; tar intact

Building 1 – 8th Floor

HMA-J1 1 8 12”x12” Floor Tile- Green w/ Black Mastic No G Intact G Intact M Floor

Maintenance 7

HMA-N1 1 8

12”x12” Floor Tile- Green w/ Brown Spots w/ Black

Mastic

HMA-O1 1 8 9”x9” Floor Tile- Gray w/

Maintenance 7

HMA-T1 1 8

12”x12” Floor Tile- White w/ Brown Splotches w/ Black Mastic

HMA-01 1 8 Pipe Insulation & Fittings Yes D Damage to

TSI M Access 3 See maps for specific locations of Damaged TSI

HMA-01 1 8 Pipe Insulation & Fittings Yes SD Significant Damage to

TSI

SD

Significant Damage to

TSI

M Access 1 See maps for specific locations of

Significantly Damaged TSI

HMA-05 1 8 Fire Doors (Assumed) No G Intact G Intact L Maintenance 7

HMA-17 1 8 Sink Soundproofing- White No G Intact G Intact H Access 5

HMA-19 1 8 Black Tar on Fiberglass Pipe Insulation No G Intact G Intact M Access 6

HMA-20 1 8

Wall Mounted

Heaters/Steam Convector Units (Heat Shields

Friable Yes/No

Previous Condition Current Condition 1 Potential for Disturbance 2 Removal

Priority 3 Comments

Rating Based On Rating Based On

Rating Based On

Presumed)

HMA-128 1 8 TSI Insulation Saddles on CWS Pipe Hangars Yes G Intact D Intact M Access 6 Free saddle sitting above cables, see map

HMA-163 1 8 HVAC Duct Insulation, Soft Gray Yes G Intact G Intact M Access 6 Limited Visibility

HMA-173 1 8 Cork and Tar Pipe Insulation No G Intact G Intact M Access 6 Loose cork substrate damaged in locations noted on maps; tar intact

Building 1 – 9th Floor

HMA-F2 1 9 12”x12” Floor Tile- White w/ Brown Streaks No G Intact G Intact M Floor

Maintenance 7 901-all piping,tile,mastic,and duct insulation abated

HMA-X1 1 9 9”x9” Floor Tile- Tan w/ Black Mastic No G Intact G Intact M Floor

Maintenance 7

HMA-18 1 9

12”x12” Floor Tile- Tan w/

Brown Streaks w/ Black Mastic

HMA-01 1 9 Pipe Insulation & Fittings Yes D Damage to

TSI M Access 3 See maps for specific locations of Damaged TSI

HMA-01 1 9 Pipe Insulation & Fittings Yes SD Significant Damage to

TSI

SD

Significant Damage to

TSI

M Access 1 See maps for specific locations of

Significantly Damaged TSI

HMA-05 1 9 Fire Doors (Assumed) No G Intact G Intact L Maintenance 7

HMA-08 1 9 Transite Counters No G Intact G Intact M Maintenance 6

HMA-17 1 9 Sink Soundproofing- White No G Intact G Intact H Access 5

HMA-18 1 9

12”x12” Floor Tile- Tan w/

Brown Streaks w/ Black Mastic

HMA-19 1 9 Black Tar on Fiberglass Pipe Insulation No G Intact G Intact M Access 6

HMA-20 1 9

Wall Mounted Heaters/Steam Convector

Units (Heat Shields

Friable Yes/No

Previous Condition Current Condition 1 Potential for Disturbance 2 Removal

Priority 3 Comments

Rating Based On Rating Based On

Rating Based On

HMA-127 1 9 Black Tar Wrap on Fiberglass HVAC No G Intact G Intact M Access 6

HMA-128 1 9 TSI Insulation Saddles on CWS Pipe Hangars Yes G Intact G Intact M Access 6

HMA-163 1 9 HVAC Duct Insulation, Soft Gray Yes G Intact G Intact M Access 6 No Visibility

HMA-173 1 9 Cork and Tar Pipe Insulation No G Intact G Intact M Access 6 Loose cork substrate damaged in locations noted on maps; tar intact

Building 1 – 10th Floor

No ACM

Building 1 – 11th Floor

No ACM

Building 1 – Exterior

HMA-124 1 Ext Residual Exterior Door Caulk- White (Old/Brittle) Yes G Intact G Intact M Maintenance 6 Appears to be caulking from old door frame; loading dock area

Good (G) Surfacing material has no visible damage; covering on TSI is intact; miscellaneous materials are intact; no visible debris.

Damaged (D) Surfacing material has moderate but not extensive visible damage; covering on TSI is cut or torn, exposing small but not extensive amounts of insulation; miscellaneous materials have moderate but not extensive damage; moderate but not extensive amounts of visible debris

Significantly Damaged (SD) Extensive damage to surfacing material; covering on TSI is cut or torn extensively and insulation itself is damaged; miscellaneous materials such as floor tile is extensively damaged and underlying

Note: Damage is considered “extensive” when the total area of distributed damage exceeds 10%, or 25% localized damage.

Contact (accessibility) Influence of Vibration Potential for Air Erosion or

Water Damage

HIGH (H)

(potential for significant damage) High Any Value Any Value

Any Value High Any Value Any Value Any Value High

MODERATE (M)

(potential for damage)

Moderate Moderate or Low Moderate or Low Moderate or Low Moderate Moderate or Low Moderate or Low Moderate or Low Moderate

LOW (L) Low Low Low Note: Overall rating determined by assigning disturbance probabilities under all 3 categories then adopting highest individual score for each material.

Qualitative Rankings and Numerical Ratings for Removal Priority of ACM Hazard Rank/

Removal Priority ACBM Condition ACBM Disturbance

Potential Recommended Response Actions

1 Significantly Damaged

Any Evacuate or isolate area immediately. Remove ACBM immediately. O&M Required for all friable ACBM.

2 Damaged High Evacuate or isolate area immediately. Remove, enclose, encapsulate or repair ACBM to correct immediately. Reduce potential for disturbance of remaining materials. O&M Required for all friable ACBM.

3 Damaged Moderate Remove, enclose, encapsulate, or repair to correct damage as soon as feasible.

O&M Required for all friable ACBM.

4 Damaged Low Remove, enclose, encapsulate, or repair to correct damage as needed to facilitate future projects. Take steps to reduce potential for disturbance. O&M Required for all friable ACBM.

5 Good High Take steps to reduce potential for disturbance. O&M Required for all friable ACBM.

6 Good Moderate O&M Required for all friable ACBM.

BUILDING 1T

SIX MONTH PERIODIC SURVELLIANCE FORM

09/01/21-09/29/21

Homogeneous Area No. Bldg Floor Material Description

Friable Yes/No

Previous Condition Current Condition Potential for Disturbance Removal

Priority Comments

Rating Based On Rating Based On

Rating Based On

Building 1T – 1st Floor

HMA-8 1T 1 Fire door (PACM) No G Intact G Intact L Renovation 7

Building 1T – Exterior

No ACM Detected

Good (G) Surfacing material has no visible damage; covering on TSI is intact; miscellaneous materials are intact; no visible debris.

Damaged (D) Surfacing material has moderate but not extensive visible damage; covering on TSI is cut or torn, exposing small but not extensive amounts of insulation; miscellaneous materials have moderate but not extensive damage; moderate but not extensive amounts of visible debris

Significantly Damaged (SD) Extensive damage to surfacing material; covering on TSI is cut or torn extensively and insulation itself is damaged; miscellaneous materials such as floor tile is extensively damaged and underlying

Note: Damage is considered “extensive” when the total area of distributed damage exceeds 10%, or 25% localized damage.

Contact (accessibility) Influence of Vibration Potential for Air Erosion or

Water Damage

HIGH (H)

(potential for significant damage) High Any Value Any Value

Any Value High Any Value Any Value Any Value High

MODERATE (M)

(potential for damage)

Moderate Moderate or Low Moderate or Low Moderate or Low Moderate Moderate or Low Moderate or Low Moderate or Low Moderate

LOW (L) Low Low Low Note: Overall rating determined by assigning disturbance probabilities under all 3 categories then adopting highest individual score for each material.

Qualitative Rankings and Numerical Ratings for Removal Priority of ACM Hazard Rank/

Removal Priority ACBM Condition ACBM Disturbance

Potential Recommended Response Actions

1 Significantly Damaged

Any Evacuate or isolate area immediately. Remove ACBM immediately. O&M Required for all friable ACBM.

2 Damaged High Evacuate or isolate area immediately. Remove, enclose, encapsulate or repair ACBM to correct immediately. Reduce potential for disturbance of remaining materials. O&M Required for all friable ACBM.

3 Damaged Moderate Remove, enclose, encapsulate, or repair to correct damage as soon as feasible.

O&M Required for all friable ACBM.

4 Damaged Low Remove, enclose, encapsulate, or repair to correct damage as needed to facilitate future projects. Take steps to reduce potential for disturbance. O&M Required for all friable ACBM.

5 Good High Take steps to reduce potential for disturbance. O&M Required for all friable ACBM.

6 Good Moderate O&M Required for all friable ACBM.

BUILDING 2

SIX MONTH PERIODIC SURVELLIANCE FORM

09/01/21-09/29/21

Homogeneous Area No. Bldg Floor Material Description

Friable Yes/No

Previous Condition Current Condition Potential for Disturbance Removal

Priority Comments

Rating Based On Rating Based On

Rating Based On

Building 2 – Basement

HMA-6 2 B Fire Door (Assumed) No G Intact G Intact L Maintenance 7

HMA-17 2 B Flange Gasket (PACM) No G Intact G Intact L Maintenance 7

HMA-39 2 B Seam Sealant – White No G Intact G Intact L Maintenance 7

Building 1 – 1st Floor

HMA-D 2 1 12”x12” Floor Tile- Tan No G Intact G Intact L Floor Maintenance 6

HMA-E1 2 1 9”x9” Floor Tile- Tan w/ Black Mastic No G Intact G Intact L Floor

Maintenance 6

HMA-F1 2 1 9”x9” Floor Tile- Gray w/ Black Mastic No G Intact G Intact L Floor

Maintenance 6

HMA-G1 2 1 9”x9”x Floor Tile- Brown w/ Black Mastic No G Intact G Intact L Floor

Maintenance 6

HMA-5 2 1 Pipe Insulation and Fittings Yes D Damage G Intact L Access 7 Encapsulated

HMA-6 2 1 Fire Door (Assumed) No G Intact G Intact L Maintenance 7

HMA-17 2 1 Flange Gasket (PACM) No G Intact G Intact L Maintenance 7

HMA-28 2 1 Steam Convector Unit (PACM) No G Intact G Intact L Maintenance 7

HMA-39 2 1 Seam Sealant -White No G Intact G Intact L Maintenance 7

Building 2 – 2nd Floor

HMA-B1 2 2 Black Mastic Under 12”x12” Floor Tile- White No G Intact G Intact L Floor

Friable Yes/No

Previous Condition Current Condition Potential for Disturbance Removal

Priority Comments

Rating Based On Rating Based On

Rating Based On

HMA-D 2 2 12”x12” Floor Tile- Tan No G Intact G Intact L Floor Maintenance 6

HMA-F1 2 2 9”x9” Floor Tile- Gray w/ Black Mastic No G Intact G Intact L Floor

Maintenance 6

HMA-5 2 2 Pipe Insulation and Fittings Yes D Damaged G Intact L Access 7 Encapsulated

HMA-6 2 2 Fire Door (Assumed) No G Intact G Intact L Maintenance 7

HMA-17 2 2 Flange Gasket (PACM) No G Intact G Intact L Maintenance 7

HMA-28 2 2 Steam Convector Unit (PACM) No G Intact G Intact L Maintenance 7

HMA-32 2 2 Sink Soundproofing- White, Textured No G Intact G Intact L Maintenance 6

HMA-39 2 2 Seam Sealant -White No G Intact G Intact L Maintenance 7

Building 2 – 3rd Floor

HMA-B1 2 3 Black Mastic Under 12”x12” Floor Tile- White No G Intact G Intact L Floor

Maintenance 7

HMA-D 2 3 12”x12” Floor Tile- Tan No G Intact G Intact L Floor Maintenance 6

HMA-F1 2 3 9”x9” Floor Tile- Gray w/ Black Mastic No G Intact G Intact L Floor

Maintenance 6

HMA-6 2 3 Fire Door (Assumed) No G Intact G Intact L Maintenance 7

HMA-17 2 3 Flange Gasket (PACM) No G Intact G Intact L Maintenance 7

HMA-28 2 3 Steam Convector Unit (PACM) No G Intact G Intact L Maintenance 7

HMA-32 2 3 Sink Soundproofing- White, Textured No G Intact G Intact L Maintenance 6

HMA-35 2 3 Penetration Caulk- Brown No G Intact G Intact L Maintenance 7

HMA-39 2 3 Seam Sealant -White No G Intact G Intact L Maintenance 7

Friable Yes/No

Previous Condition Current Condition Potential for Disturbance Removal

Priority Comments

Rating Based On Rating Based On

Rating Based On

Building 2 – Attic

HMA-39 2 Attic Seam Sealant -White No G Intact G Intact L Maintenance 7

Building 2 – Exterior

HMA-15 2 Ext Exterior Louver Sill Sealant

– Black No G Intact G Intact L Maintenance 7

Good (G) Surfacing material has no visible damage; covering on TSI is intact; miscellaneous materials are intact; no visible debris.

Damaged (D) Surfacing material has moderate but not extensive visible damage; covering on TSI is cut or torn, exposing small but not extensive amounts of insulation; miscellaneous materials have moderate but not extensive damage; moderate but not extensive amounts of visible debris

Significantly Damaged (SD) Extensive damage to surfacing material; covering on TSI is cut or torn extensively and insulation itself is damaged; miscellaneous materials such as floor tile is extensively damaged and underlying

Note: Damage is considered “extensive” when the total area of distributed damage exceeds 10%, or 25% localized damage.

Contact (accessibility) Influence of Vibration Potential for Air Erosion or

Water Damage

HIGH (H)

(potential for significant damage) High Any Value Any Value

Any Value High Any Value Any Value Any Value High

MODERATE (M)

(potential for damage)

Moderate Moderate or Low Moderate or Low Moderate or Low Moderate Moderate or Low Moderate or Low Moderate or Low Moderate

LOW (L) Low Low Low Note: Overall rating determined by assigning disturbance probabilities under all 3 categories then adopting highest individual score for each material.

Qualitative Rankings and Numerical Ratings for Removal Priority of ACM Hazard Rank/

Removal Priority ACBM Condition ACBM Disturbance

Potential Recommended Response Actions

1 Significantly Damaged

Any Evacuate or isolate area immediately. Remove ACBM immediately. O&M Required for all friable ACBM.

2 Damaged High Evacuate or isolate area immediately. Remove, enclose, encapsulate or repair ACBM to correct immediately. Reduce potential for disturbance of remaining materials. O&M Required for all friable ACBM.

3 Damaged Moderate Remove, enclose, encapsulate, or repair to correct damage as soon as feasible.

O&M Required for all friable ACBM.

4 Damaged Low Remove, enclose, encapsulate, or repair to correct damage as needed to facilitate future projects. Take steps to reduce potential for disturbance. O&M Required for all friable ACBM.

5 Good High Take steps to reduce potential for disturbance. O&M Required for all friable ACBM.

6 Good Moderate O&M Required for all friable ACBM.

BUILDING 3

SIX-MONTH PERIODIC SURVELLIANCE FORM

09/01/21-09/29/21

Homogeneous Area No. Bldg Floor Material Description

Friable Yes/No

Previous Condition Current Condition Potential for Disturbance Removal

Priority Comments

Rating Based On Rating Based On

Rating Based On

Building 3 – Basement

HMA-5 3 B Fire Door (PACM) No G Intact G Intact L Maintenance 7

HMA-10 3 B Flange Gasket (PACM) No G Intact G Intact L Maintenance 7

HMA-18 3 B Interior Textured Wall Material No G Intact G Intact L Maintenance 7

HMA-33 3 B TSI Pipe Insulation Yes SD Significantly Damaged SD Significantly

Damage M Access/ Maintenance 1 Sealed confined space entry to tunnels

HMA-33 3 B TSI Pipe Insulation Yes G Intact G Intact L Maintenance 6

Building 3 – 1st Floor

HMA-B1 3 1 12”x12” Floor Tile – Gray w/ Black Mastic No G Intact G Intact L Flooring

Maintenance 7 Assumed underneath wood sub-floor

HMA-C1 3 1 9”x9” Floor Tile – Green w/ Black Mastic No G Intact G Intact L Flooring

Maintenance 7 Assumed underneath wood sub-floor

HMA-D1 3 1 9”x9” Floor Tile – Brown w/ Black Mastic No G Intact G Intact L Flooring

Maintenance 7 Assumed underneath wood sub-floor

HMA-F 3 1 Felt No G Intact G Intact L Flooring Maintenance 7 Assumed underneath wood sub-floor

HMA-1 3 1 Black Mastic Under Carpet No G Intact G Intact L Flooring Maintenance 7

HMA-5 3 1 Fire Door (PACM) No G Intact G Intact L Maintenance 7

HMA-10 3 1 Flange Gasket (PACM) No G Intact G Intact L Maintenance 7

HMA-13 3 1 Wall Mounted Heater (PACM) No G Intact G Intact L Maintenance 7

HMA-18 3 1 Interior Textured Wall Material No G Intact G Intact L Maintenance 7

Friable Yes/No

Previous Condition Current Condition Potential for Disturbance Removal

Priority Comments

Rating Based On Rating Based On

Rating Based On

HMA-24 3 1 Interior Window Caulk – Grey No G Intact G Intact L Maintenance 7

HMA-33 3 1 TSI Pipe Insulation Yes G Intact G Intact L Access/ Maintenance 6

Building 3 – 2nd Floor

HMA-B1 3 2 12”x12” Floor Tile – Gray w/ Black Mastic No G Intact G Intact L Flooring

Maintenance 7 Assumed underneath wood sub-floor

HMA-D1 3 2 9”x9” Floor Tile – Brown w/ Black Mastic No G Intact G Intact L Flooring

Maintenance 7 Assumed underneath wood sub-floor

HMA-F 3 2 Felt No G Intact G Intact L Flooring Maintenance 7 Assumed underneath wood sub-floor

HMA-5 3 2 Fire Door (PACM) No G Intact G Intact L Maintenance 7

HMA-10 3 2 Flange Gasket (PACM) No G Intact G Intact L Maintenance 7

HMA-13 3 2 Wall Mounted Heater (PACM) No G Intact G Intact L Maintenance 7

HMA-18 3 2 Interior Textured Wall Material No G Intact G Intact L Maintenance 7

HMA-33 3 2 TSI Pipe Insulation No G Intact G Intact L Access/ Maintenance 6

Building 3 – Attic

HMA-10 3 A Flange Gasket (PACM) No G Intact G Intact L Maintenance 7

Building 3 – Exterior

No ACM Detected No records of ACM stucco abatement. ACM layer may exist under non- ACM layer.

Good (G) Surfacing material has no visible damage; covering on TSI is intact; miscellaneous materials are intact; no visible debris.

Damaged (D) Surfacing material has moderate but not extensive visible damage; covering on TSI is cut or torn, exposing small but not extensive amounts of insulation; miscellaneous materials have moderate but not extensive damage; moderate but not extensive amounts of visible debris

Significantly Damaged (SD) Extensive damage to surfacing material; covering on TSI is cut or torn extensively and insulation itself is damaged; miscellaneous materials such as floor tile is extensively damaged and underlying

Note: Damage is considered “extensive” when the total area of distributed damage exceeds 10%, or 25% localized damage.

Contact (accessibility) Influence of Vibration Potential for Air Erosion or

Water Damage

HIGH (H)

(potential for significant damage) High Any Value Any Value

Any Value High Any Value Any Value Any Value High

MODERATE (M)

(potential for damage)

Moderate Moderate or Low Moderate or Low Moderate or Low Moderate Moderate or Low Moderate or Low Moderate or Low Moderate

LOW (L) Low Low Low Note: Overall rating determined by assigning disturbance probabilities under all 3 categories then adopting highest individual score for each material.

Qualitative Rankings and Numerical Ratings for Removal Priority of ACM Hazard Rank/

Removal Priority ACBM Condition ACBM Disturbance

Potential Recommended Response Actions

1 Significantly Damaged

Any Evacuate or isolate area immediately. Remove ACBM immediately. O&M Required for all friable ACBM.

2 Damaged High Evacuate or isolate area immediately. Remove, enclose, encapsulate or repair ACBM to correct immediately. Reduce potential for disturbance of remaining materials. O&M Required for all friable ACBM.

3 Damaged Moderate Remove, enclose, encapsulate, or repair to correct damage as soon as feasible.

O&M Required for all friable ACBM.

4 Damaged Low Remove, enclose, encapsulate, or repair to correct damage as needed to facilitate future projects. Take steps to reduce potential for disturbance. O&M Required for all friable ACBM.

5 Good High Take steps to reduce potential for disturbance. O&M Required for all friable ACBM.

6 Good Moderate O&M Required for all friable ACBM.

BUILDING 3T

SIX MONTH PERIODIC SURVELLIANCE FORM

09/01/21-09/29/21

Homogeneous Area No. Bldg Floor Material Description

Friable Yes/No

Previous Condition Current Condition Potential for Disturbance Removal

Priority Comments

Rating Based On Rating Based On

Rating Based On

Building 3T- Crawlspace

No ACM Detected

Building 3T – 1st Floor

No ACM Detected

Building 3T – Exterior

Good (G) Surfacing material has no visible damage; covering on TSI is intact; miscellaneous materials are intact; no visible debris.

Damaged (D) Surfacing material has moderate but not extensive visible damage; covering on TSI is cut or torn, exposing small but not extensive amounts of insulation; miscellaneous materials have moderate but not extensive damage; moderate but not extensive amounts of visible debris

Significantly Damaged (SD) Extensive damage to surfacing material; covering on TSI is cut or torn extensively and insulation itself is damaged; miscellaneous materials such as floor tile is extensively damaged and underlying

Note: Damage is considered “extensive” when the total area of distributed damage exceeds 10%, or 25% localized damage.

Contact (accessibility) Influence of Vibration Potential for Air Erosion or

Water Damage

HIGH (H)

(potential for significant damage) High Any Value Any Value

Any Value High Any Value Any Value Any Value High

MODERATE (M)

(potential for damage)

Moderate Moderate or Low Moderate or Low Moderate or Low Moderate Moderate or Low Moderate or Low Moderate or Low Moderate

LOW (L) Low Low Low Note: Overall rating determined by assigning disturbance probabilities under all 3 categories then adopting highest individual score for each material.

Qualitative Rankings and Numerical Ratings for Removal Priority of ACM Hazard Rank/

Removal Priority ACBM Condition ACBM Disturbance

Potential Recommended Response Actions

1 Significantly Damaged

Any Evacuate or isolate area immediately. Remove ACBM immediately. O&M Required for all friable ACBM.

2 Damaged High Evacuate or isolate area immediately. Remove, enclose, encapsulate or repair ACBM to correct immediately. Reduce potential for disturbance of remaining materials. O&M Required for all friable ACBM.

3 Damaged Moderate Remove, enclose, encapsulate, or repair to correct damage as soon as feasible.

O&M Required for all friable ACBM.

4 Damaged Low Remove, enclose, encapsulate, or repair to correct damage as needed to facilitate future projects. Take steps to reduce potential for disturbance. O&M Required for all friable ACBM.

5 Good High Take steps to reduce potential for disturbance. O&M Required for all friable ACBM.

6 Good Moderate O&M Required for all friable ACBM.

BUILDING 18

SIX MONTH PERIODIC SURVELLIANCE FORM

09/01/21-09/29/21

Homogeneous Area No. Bldg Floor Material Description

Friable Yes/No

Previous Condition Current Condition Potential for Disturbance Removal

Priority Comments

Rating Based On Rating Based On

Rating Based On

Building 18 – Crawlspace

HMA-52 18 C Contaminated crawlspace soil Yes SD Significant damage SD Significant Damage M Maintenance/

Access 1 Crawlspace soil exists under thick rubber flooring

Building 18 – Basement

HMA-A1 18 B 12”x12” floor tile – white w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-B1 18 B 12”x12” floor tile – tan w/ black mastic No G Intact G Intact L Floor

Maintenance 7

HMA-6 18 B ACM pipe insulation and mudded fittings Yes G Intact G Intact L Maintenance/

Access 5

HMA-6 18 B ACM pipe insulation and mudded fittings Yes D Damaged D Damaged M Maintenance/

Acc…