Attachment 20 - Drawings Part-19.pdf

PDF 14 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks Federal contract opportunity
Solicitation number
36C77623R0009
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This solicitation seeks a general contractor to provide infrastructure upgrades at the St. Louis Jefferson Barracks VA Medical Center. The scope of work includes electrical panel upgrades and power systems work, building management system integration, HVAC assessments and upgrades, facility renovations including demolition, construction and finishes, data center renovations, physical security enhancements, fiber infrastructure assessment and upgrades between buildings, installation of a diversified wide area network path to the datacenter, and hazardous material abatement. The project involves improvements to Buildings 1, 2, 3, 3T, 18, 23, 24, 25, 51, 51T, 52, 53, 53T, 55, 56, 57, 58, 59, 60, 60T, 61, 75 and associated site work. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks, newest first.
File Type Posted
36C77623R0009 0005.pdf PDF
329000-05-R1 Sod Certificate.pdf PDF
36C77623R0009 0004.pdf PDF
657-21-701JB - 100 PC - Basis of Design.pdf PDF
32 32 23 01R1 - Mechanically Stabilized Earth Wall System RESPONSE.pdf PDF
36C77623R0009 0003.pdf PDF
Attachment 43 - Construction Wage Rates - St. Louis 3-3-23.pdf PDF
36C77623R0009 0002.pdf PDF
Site Visit Sign-in Sheet - St. Louis 2-28-23.pdf PDF
36C77623R0009 0001.pdf PDF
Attachment 4 - Drawings Part-3.pdf PDF
Attachment 10 - Drawings Part-9.pdf PDF
Attachment 14 - Drawings Part-13.pdf PDF
Attachment 21 - Drawings Part-20.pdf PDF
Attachment 25 - Drawings Part-24.pdf PDF
Attachment 26 - Drawings Part-25.pdf PDF
Attachment 28 - Drawings Part-27.pdf PDF
Attachment 29 - Drawings Part-28.pdf PDF
Attachment 32 - Drawings Part-31.pdf PDF
Attachment 39 - ICRA ILSM Tool - MCM 001S-03 Att B.zip ZIP file
36C77623R0009 - 2-16-23.pdf PDF
Attachment 7 - Drawings Part-6.pdf PDF
Attachment 11 - Drawings Part-10.pdf PDF
Attachment 12 - Drawings Part-11.pdf PDF
Attachment 13 - Drawings Part-12.pdf PDF
Attachment 18 - Drawings Part-17.pdf PDF
Attachment 31 - Drawings Part-30.pdf PDF
Attachment 35 - Envr. Report - Appendix A.pdf PDF
Attachment 38 - Envr. Report - Drawings.pdf PDF
Attachment 42 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 45 - Site Visit Instructions.pdf PDF
Attachment 1 - Specifications.pdf PDF
Attachment 5 - Drawings Part-4.pdf PDF
Attachment 6 - Drawings Part-5.pdf PDF
Attachment 9 - Drawings Part-8.pdf PDF
Attachment 16 - Drawings Part-15.pdf PDF
Attachment 22 - Drawings Part-21.pdf PDF
Attachment 24 - Drawings Part-23.pdf PDF
Attachment 36 - Envr. Report - Appendix B.pdf PDF
Attachment 41 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Attachment 44 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 2 - Drawings Part-1.pdf PDF
Attachment 3 - Drawings Part-2.pdf PDF
Attachment 8 - Drawings Part-7.pdf PDF
Attachment 15 - Drawings Part-14.pdf PDF
Attachment 17 - Drawings Part-16.pdf PDF
Attachment 19 - Drawings Part-18.pdf PDF
Attachment 23 - Drawings Part-22.pdf PDF
Attachment 27 - Drawings Part-26.pdf PDF
Attachment 30 - Drawings Part-29.pdf PDF
Show all 50

Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

657-21-701JB

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES 25EP701

BLDG 25 - ELECTRICAL

SCHEDULES 25

LRL/WNM LLT/JPS

CONSTRUCTION

DOCUMENTS

03/31/2022

Notes:

Total Est. Demand: 68 A

Total Conn.: 96 A

Power 2766 VA 100.00% 2766 VA Total Est. Demand: 24566 VA

Receptacle 30000 VA 66.67% 20000 VA Total Conn. Load: 34566 VA

Other 1800 VA 100.00% 1800 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 107 A 94 A 88 A

Total Load: 12760 VA 11206 VA 10600 VA

17 -- -- -- 3533... 3533... -- -- -- 18

15 -- -- -- 3735... 3735... -- -- -- 16

13 25-204BB 20 A 3 4253... 4253... 3 20 A 25-313AB 14

11 -- -- -- 0 VA 3533... -- -- -- 12

9 -- -- -- 0 VA 3735... -- -- -- 10

7 PANEL 25L2 250 A 3 0 VA 4253... 3 20 A 25-117AB 8

5 -- -- -- 0 VA 0 VA -- -- -- 6

3 -- -- -- 0 VA 0 VA -- -- -- 4

1 PANEL 25L01A 250 A 3 0 VA 0 VA 3 250 A PANEL 25L1A 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 600A / 3P

Supply From: 25-XF2-BLDG 25 Phases: 3 Mains Rating: 600 A

Location: PIPE BASEMENT Z002 Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: 25DP

Notes:

Total Est. Demand: 65 A

Total Conn.: 96 A

Total Est. Demand: 23480 VA

Receptacle 32160 VA 65.55% 21080 VA Total Conn. Load: 34560 VA

Other 2400 VA 100.00% 2400 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 108 A 90 A 90 A

Total Load: 12960 VA 10800 VA 10800 VA

29 SPARE 20 A 1 0 VA 100 VA -- -- -- 30

27 SPARE 20 A 1 0 VA 100 VA -- -- -- 28

25 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 26

23 SPARE 20 A 1 0 VA 100 VA -- -- -- 24

21 SPARE 20 A 1 0 VA 100 VA -- -- -- 22

19 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 -- -- -- 3533... 0 VA 1 20 A SPARE 12

9 -- -- -- 3533... 0 VA 1 20 A SPARE 10

7 PANEL 25-313AA 100 A 3 4253... 0 VA 1 20 A SPARE 8

5 -- -- -- 3533... 3533... -- -- -- 6

3 -- -- -- 3533... 3533... -- -- -- 4

1 PANEL 25-117AA 100 A 3 4253... 4253... 3 100 A PANEL 25-204BA 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 225A / 3P

Supply From: ATS1-EDP25 Phases: 3 Mains Rating: 225 A

Location: CORRIDOR H102 Volts: 120/208 Wye A.I.C. Rating: 65k

Branch Panel: 25-DP-TRA

GENERAL NOTES

KEY NOTES

Revisions: Date:

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY

AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.

REFERENCE ONELINE DIAGRAM ON SHEET 25EP601 FOR ADDITIONAL

INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.

THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT

PROVIDED TO SHOW OVERALL LOAD OF PANEL.

LRL/WNM LLT/JPS

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

51EP701

BLDG 51, 51A, AND 51T -

ELECTRICAL SCHEDULESSPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL/WNM LLT/JPS

CONSTRUCTION

DOCUMENTS

Revisions: Date:

GENERAL NOTES

KEY NOTES

1 UTILIZE EXISTING SPARE CIRCUIT BREAKER TO SUPPLY NEW LOAD.

Notes:

Total Est. Demand: 84 A

Total Conn.: 130 A

Lighting 808 VA 100.00% 808 VA Total Est. Demand: 30248 VA

Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 46688 VA

Other 3000 VA 100.00% 3000 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 136 A 123 A 133 A

Total Load: 16177 VA 14737 VA 15773 VA

41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42

39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40

37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38

35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36

33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34

31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 -- -- -- 3533... 0 VA 1 20 A SPARE 16

13 -- -- -- 3735... 0 VA 1 20 A SPARE 14

11 PANEL 51-1A183A 100 A 3 4253... 3533... -- -- -- 12

9 -- -- -- 3533... 3735... -- -- -- 10

7 -- -- -- 3735... 4253... 3 100 A PANEL 51-1A139A 8

5 PANEL 51-BE111A 100 A 3 4253... 3533... -- -- -- 6

3 SPARE 20 A 1 0 VA 3735... -- -- -- 4

1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 51-1A102A 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 225A / 3P

Supply From: DP-51 Phases: 3 Mains Rating: 225 A

Location: Volts: 120/208 Wye A.I.C. Rating: 65kAIC

Branch Panel: 51-DP-TRA

Notes:

Total Est. Demand: 84 A

Total Conn.: 130 A

Lighting 808 VA 100.00% 808 VA Total Est. Demand: 30248 VA

Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 46688 VA

Other 3000 VA 100.00% 3000 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 136 A 123 A 133 A

Total Load: 16177 VA 14737 VA 15773 VA

35 -- -- -- 0 VA 36

33 -- -- -- 0 VA 34

31 SPARE 250 A 3 0 VA 32

29 -- -- -- 0 VA 1577... -- -- -- 30

27 -- -- -- 0 VA 1473... -- -- -- 28

25 51-PANEL-DP1 400 A 3 0 VA 1617... 3 400 A 51-DP-TRA 26

23 -- -- -- 0 VA 0 VA -- -- -- 24

21 -- -- -- 0 VA 0 VA -- -- -- 22

19 51-PANEL-DP2 225 A 3 0 VA 0 VA 3 100 A 51-PANEL-LP4 20

17 -- -- -- 0 VA 0 VA -- -- -- 18

15 -- -- -- 0 VA 0 VA -- -- -- 16

13 SPARE 50 A 3 0 VA 0 VA 3 225 A SPARE 14

11 -- -- -- 0 VA 0 VA -- -- -- 12

9 -- -- -- 0 VA 0 VA -- -- -- 10

7 SPARE 225 A 3 0 VA 0 VA 3 250 A 51-PANEL-PP2 8

5 -- -- -- 0 VA 0 VA -- -- -- 6

3 -- -- -- 0 VA 0 VA -- -- -- 4

1 SPARE 225 A 3 0 VA 0 VA 3 250 A 51-PANEL-PP4 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 800A / 3P

Supply From: 51-ATS51 Phases: 3 Mains Rating: 800 A

Location: BE-114 Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: DP-51

2 EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.

REFERENCE ONE-LINE DIAGRAM ON SHEET 51EP602 FOR ADDITIONAL

INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.

THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT

PROVIDED TO SHOW OVERALL LOAD OF PANEL.

Notes:

Total Est. Demand: 80 A

Total Conn.: 126 A

Total Est. Demand: 28840 VA

Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 45280 VA

Other 2400 VA 100.00% 2400 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 132 A 118 A 132 A

Total Load: 15573 VA 14133 VA 15573 VA

29 -- -- -- -- -- -- -- -- 30

27 -- -- -- -- -- -- -- -- 28

25 SPACE -- 3 -- -- 3 -- SPACE 26

23 -- -- -- -- -- -- -- -- 24

21 -- -- -- -- -- -- -- -- 22

19 SPACE -- 3 -- -- 3 -- SPACE 20

17 -- -- -- -- -- -- -- -- 18

15 -- -- -- -- -- -- -- -- 16

13 SPACE -- 3 -- -- 3 -- SPACE 14

11 -- -- -- -- -- -- -- -- 12

9 -- -- -- -- -- -- -- -- 10

7 PNL-MP51 (TAPPED OFF BUS) -- 3 -- -- 3 -- SPACE 8

5 -- -- -- 0 VA 1557... -- -- -- 6

3 -- -- -- 0 VA 1413... -- -- -- 4

1 SPARE 600 A 3 0 VA 1557... 3 400 A 51-DP-TRB 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 800A/3P

Supply From: 51-XF2-BLDG 51 Phases: 3 Mains Rating: 225 A

Location: Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: CB51

Notes:

Total Est. Demand: 80 A

Total Conn.: 126 A

Total Est. Demand: 28840 VA

Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 45280 VA

Other 2400 VA 100.00% 2400 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 132 A 118 A 132 A

Total Load: 15573 VA 14133 VA 15573 VA

41 SPARE 20 A 1 0 VA 0 VA -- -- -- 42

39 SPARE 20 A 1 0 VA 0 VA -- -- -- 40

37 SPARE 20 A 1 0 VA 0 VA 3 20 A SPD 38

35 SPARE 20 A 1 0 VA 0 VA -- -- -- 36

33 SPARE 20 A 1 0 VA 0 VA -- -- -- 34

31 SPARE 20 A 1 0 VA 0 VA 3 20 A DIGITAL POWER METER 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 -- -- -- 3533... 0 VA 1 20 A SPARE 16

13 -- -- -- 3533... 0 VA 1 20 A SPARE 14

11 PANEL 51-1A183B 100 A 3 4253... 3533... -- -- -- 12

9 -- -- -- 3533... 3533... -- -- -- 10

7 -- -- -- 3533... 4253... 3 100 A PANEL 51-1A139B 8

5 PANEL 51-BE111B 100 A 3 4253... 3533... -- -- -- 6

3 SPARE 20 A 1 0 VA 3533... -- -- -- 4

1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 51-1A102B 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 225A / 3P

Supply From: DP-51 Phases: 3 Mains Rating: 225 A

Location: Volts: 120/208 Wye A.I.C. Rating: 65kAIC

Branch Panel: 51-DP-TRB

3 PROVIDE NEW CIRCUIT BREAKER TO SUPPLY NEW LOAD.

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY

AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

51EP702

BLDG 51, 51A, AND 51T -

ELECTRICAL SCHEDULESSPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 Checker Author

CONSTRUCTION

DOCUMENTS

Revisions: Date:

GENERAL NOTES

KEY NOTES

1 PROVIDE NEW CIRCUIT BREAKER IN EXISTING SPACE TO SUPPLY NEW LOAD.

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY

AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

52EP701

BLDG 52 - ELECTRICAL

SCHEDULESSPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL/WNM LLT/JPS

CONSTRUCTION

DOCUMENTS

GENERAL NOTES

KEY NOTES

Notes:

Total Est. Demand: 101 A

Total Conn.: 162 A

Lighting 1010 VA 100.00% 1010 VA Total Est. Demand: 36410 VA

Receptacle 53600 VA 59.33% 31800 VA Total Conn. Load: 58210 VA

Other 3600 VA 100.00% 3600 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 168 A 152 A 169 A

Total Load: 19913 VA 18271 VA 20027 VA

41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42

39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40

37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38

35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36

33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34

31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 -- -- -- 3533... 0 VA 1 20 A SPARE 22

19 -- -- -- 3735... 0 VA 1 20 A SPARE 20

17 PANEL 52-1S33A 100 A 3 4253... 0 VA 1 20 A SPARE 18

15 -- -- -- 3533... 0 VA 1 20 A SPARE 16

13 -- -- -- 3735... 0 VA 1 20 A SPARE 14

11 PANEL 52-1N82AA 100 A 3 4253... 3533... -- -- -- 12

9 -- -- -- 3533... 3735... -- -- -- 10

7 -- -- -- 3735... 4253... 3 100 A PANEL 52-2N91A 8

5 PANEL 52-GN29AA 100 A 3 4253... 3533... -- -- -- 6

3 SPARE 20 A 1 0 VA 3735... -- -- -- 4

1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 52-2N86BA 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 250A / 3P

Supply From: ATS52-DP52CR Phases: 3 Mains Rating: 250 A

Location: MECH GS09 Volts: 120/208 Wye A.I.C. Rating: 65k

Branch Panel: 52-DP-TRA

Revisions: Date:

Notes:

Total Est. Demand: 98 A

Total Conn.: 159 A

Total Est. Demand: 35400 VA

Receptacle 53600 VA 59.33% 31800 VA Total Conn. Load: 57200 VA

Other 3600 VA 100.00% 3600 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 163 A 149 A 169 A

Total Load: 19307 VA 17867 VA 20027 VA

41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42

39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40

37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38

35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36

33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34

31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 -- -- -- 3533... 0 VA 1 20 A SPARE 22

19 -- -- -- 3533... 0 VA 1 20 A SPARE 20

17 PANEL 52-2N91B 100 A 3 4253... 0 VA 1 20 A SPARE 18

15 -- -- -- 3533... 0 VA 1 20 A SPARE 16

13 -- -- -- 3533... 0 VA 1 20 A SPARE 14

11 PANEL 52-1S33B 100 A 3 4253... 3533... -- -- -- 12

9 -- -- -- 3533... 3533... -- -- -- 10

7 -- -- -- 3533... 4253... 3 100 A PANEL 52-2N86BB 8

5 PANEL 52-GN29AB 100 A 3 4253... 3533... -- -- -- 6

3 SPARE 20 A 1 0 VA 3533... -- -- -- 4

1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 52-1N82AB 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 250A / 3P

Supply From: MCB Phases: 3 Mains Rating: 250 A

Location: MECH GS09 Volts: 120/208 Wye A.I.C. Rating: 65k

Branch Panel: 52-DP-TRB

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY

AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

53EP701

BLDG 53 AND 53T - ELECTRICAL

SCHEDULESSPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL/WNM JPS/LLT

CONSTRUCTION

DOCUMENTS

Revisions: Date:

GENERAL NOTES

KEY NOTES

1 PROVIDE NEW CIRCUIT BREAKER TO SUPPLY NEW LOAD.

Notes:

Total Est. Demand: 101 A

Total Conn.: 162 A

Lighting 1010 VA 100.00% 1010 VA Total Est. Demand: 36410 VA

Receptacle 53600 VA 59.33% 31800 VA Total Conn. Load: 58210 VA

Other 3600 VA 100.00% 3600 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 171 A 154 A 162 A

Total Load: 20431 VA 18473 VA 19307 VA

41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42

39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40

37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38

35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36

33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34

31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 3533... -- -- -- 18

15 -- -- -- 3533... 3735... -- -- -- 16

13 -- -- -- 3735... 4253... 3 100 A PANEL 53-GS02AA 14

11 PANEL 53-1S01A 100 A 3 4253... 3533... -- -- -- 12

9 -- -- -- 3533... 3735... -- -- -- 10

7 -- -- -- 3735... 4253... 3 100 A PANEL 53-2S001A 8

5 PANEL 53-GS10A 100 A 3 4253... 3533... -- -- -- 6

3 SPARE 20 A 1 0 VA 3735... -- -- -- 4

1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 53-1S002A 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 225A / 3P

Supply From: BLDG 53-SWBD Phases: 3 Mains Rating: 225 A

Location: MECH RM GS12 Volts: 120/208 Wye A.I.C. Rating: 65kAIC

Branch Panel: 53-DP-TRA

Notes:

Total Est. Demand: 101 A

Total Conn.: 162 A

Lighting 1010 VA 100.00% 1010 VA Total Est. Demand: 36410 VA

Receptacle 53600 VA 59.33% 31800 VA Total Conn. Load: 58210 VA

Other 3600 VA 100.00% 3600 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 171 A 154 A 162 A

Total Load: 20431 VA 18473 VA 19307 VA

47 -- -- -- 0 VA 0 VA -- -- -- 48

45 -- -- -- 0 VA 0 VA -- -- -- 46

43 SPARE 800 A 3 0 VA 0 VA 3 800 A SPARE 44

41 -- -- -- 0 VA 1930... -- -- -- 42

39 -- -- -- 0 VA 1847... -- -- -- 40

37 SPARE 800 A 3 0 VA 2043... 3 225 A 53-DP-TRA 38

35 -- -- -- 0 VA 0 VA -- -- -- 36

33 -- -- -- 0 VA 0 VA -- -- -- 34

31 53-PANEL-GB1-1 200 A 3 0 VA 0 VA 3 800 A SPARE 32

29 -- -- -- 0 VA 0 VA -- -- -- 30

27 -- -- -- 0 VA 0 VA -- -- -- 28

25 53-PANEL-GA 100 A 3 0 VA 0 VA 3 225 A 53-PANEL-2C 26

23 -- -- -- 0 VA 0 VA -- -- -- 24

21 -- -- -- 0 VA 0 VA -- -- -- 22

19 53-PANEL-GB, 53-PANEL-1B, 53-PANEL-2B-1 400 A 3 0 VA 0 VA 3 225 A 53-PANEL-GC-1 20

17 -- -- -- 0 VA 0 VA -- -- -- 18

15 -- -- -- 0 VA 0 VA -- -- -- 16

13 53-PANEL-GP 400 A 3 0 VA 0 VA 3 600 A 53-PANEL-MCC 14

11 -- -- -- 0 VA 0 VA -- -- -- 12

9 -- -- -- 0 VA 0 VA -- -- -- 10

7 53-PANEL-P2 400 A 3 0 VA 0 VA 3 100 A 53-PANEL-KP 8

5 -- -- -- 0 VA 0 VA -- -- -- 6

3 -- -- -- 0 VA 0 VA -- -- -- 4

1 SPARE 800 A 3 0 VA 0 VA 3 225 A 53-PANEL-1A-1, 53-PANEL-2A-1 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: LUGS ONLY

Supply From: 53-ATS-53 Phases: 3 Mains Rating: 800 A

Location: MECH RM GS12 Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: 53-SWBD

2 EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.

REFERENCE ONELINE DIAGRAM ON SHEET 53EP701 FOR ADDITIONAL

INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.

THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT

PROVIDED TO SHOW OVERALL LOAD OF PANEL.

3 PROVIDE NEW CIRCUIT BREAKER IN EXISTING SPACE TO SUPPLY NEW LOAD.

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY

AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

Notes:

Total Est. Demand: 98 A

Total Conn.: 159 A

Total Est. Demand: 35400 VA

Receptacle 53600 VA 59.33% 31800 VA Total Conn. Load: 57200 VA

Other 3600 VA 100.00% 3600 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 169 A 149 A 163 A

Total Load: 20027 VA 17867 VA 19307 VA

41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42

39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40

37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38

35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36

33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34

31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 3533... -- -- -- 18

15 -- -- -- 3533... 3533... -- -- -- 16

13 -- -- -- 3533... 4253... 3 100 A PANEL 53-GS02AB 14

11 PANEL 53-1S01B 100 A 3 4253... 3533... -- -- -- 12

9 -- -- -- 3533... 3533... -- -- -- 10

7 -- -- -- 3533... 4253... 3 100 A PANEL 53-2S001B 8

5 PANEL 53-GS10B 100 A 3 4253... 3533... -- -- -- 6

3 SPARE 20 A 1 0 VA 3533... -- -- -- 4

1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 53-1S002B 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 225A / 3P

Supply From: 53-PANEL-MDP-53 Phases: 3 Mains Rating: 225 A

Location: MECH RM GS12 Volts: 120/208 Wye A.I.C. Rating: 65kAIC

Branch Panel: 53-DP-TRB

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

55EP701

BLDG 55 - ELECTRICAL

SCHEDULESSPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL/WNM JBB

CONSTRUCTION

DOCUMENTS

GENERAL NOTES

KEY NOTES

1 EXISTING PANELBOARD TO BE MODIFIED; PROVIDE CIRCUIT BREAKER AS

INDICATED.

Notes:

Total Est. Demand: 59 A

Total Conn.: 98 A

Lighting 1414 VA 100.00% 1414 VA Total Est. Demand: 48734 VA

Receptacle 75040 VA 56.66% 42520 VA Total Conn. Load: 81254 VA

Other 4800 VA 100.00% 4800 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 109 A 96 A 90 A

Total Load: 29973 VA 26347 VA 24933 VA

31 SPACE -- 1 -- 32

29 -- -- -- 0 VA 30

27 -- -- -- 0 VA 28

25 SPARE 60 A 3 0 VA 26

23 -- -- -- 0 VA 2493... -- -- -- 24

21 -- -- -- 0 VA 2634... -- -- -- 22

19 SPARE 60 A 3 0 VA 2997... 3 225 A 55-DP-TRA VIA XFMR 20

17 -- -- -- 0 VA 0 VA -- -- -- 18

15 -- -- -- 0 VA 0 VA -- -- -- 16

13 PANEL 55-2C1 100 A 3 0 VA 0 VA 3 100 A PANEL 55-3C3 14

11 -- -- -- 0 VA 0 VA -- -- -- 12

9 -- -- -- 0 VA 0 VA -- -- -- 10

7 PANEL 55-1C3 100 A 3 0 VA 0 VA 3 100 A PANEL 55-3C1 8

5 -- -- -- 0 VA 0 VA -- -- -- 6

3 -- -- -- 0 VA 0 VA -- -- -- 4

1 PANEL 55-1C1 100 A 3 0 VA 0 VA 3 100 A PANEL 55-2C3 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Recessed Wires: 4 Mains: 400A / 3P

Supply From: Phases: 3 Mains Rating: 400 A

Location: Volts: 480/277 Wye A.I.C. Rating: 42k

Branch Panel: DP 55-C1

Notes:

Total Est. Demand: 135 A

Total Conn.: 226 A

Lighting 1414 VA 100.00% 1414 VA Total Est. Demand: 48734 VA

Receptacle 75040 VA 56.66% 42520 VA Total Conn. Load: 81254 VA

Other 4800 VA 100.00% 4800 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 252 A 221 A 208 A

Total Load: 29973 VA 26347 VA 24933 VA

41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42

39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40

37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38

35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36

33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34

31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 -- -- -- 3533... 0 VA 1 20 A SPARE 24

21 -- -- -- 3735... 0 VA 1 20 A SPARE 22

19 PANEL 55-3C149A 100 A 3 4253... 0 VA 1 20 A SPARE 20

17 -- -- -- 3533... 3533... -- -- -- 18

15 -- -- -- 3735... 3735... -- -- -- 16

13 PANEL 55-2C144A 100 A 3 4253... 4253... 3 100 A PANEL 55-3A120A 14

11 -- -- -- 3533... 3533... -- -- -- 12

9 -- -- -- 3735... 3735... -- -- -- 10

7 PANEL 55-1C132A 100 A 3 4253... 4253... 3 100 A PANEL 55-2A136A 8

5 -- -- -- 3533... 3533... -- -- -- 6

3 -- -- -- 3735... 3735... -- -- -- 4

1 PANEL 55-1A129A 100 A 3 4253... 4253... 3 100 A PANEL 55-1B104A 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Recessed Wires: 4 Mains: 400A / 3P

Supply From: DP/55-C1 Phases: 3 Mains Rating: 400 A

Location: MECH 1M 1a Volts: 120/208 Wye A.I.C. Rating: 65k

Branch Panel: 55-DP-TRA

Revisions: Date:

Notes:

Total Est. Demand: 131 A

Total Conn.: 222 A

Total Est. Demand: 47320 VA

Receptacle 75040 VA 56.66% 42520 VA Total Conn. Load: 79840 VA

Other 4800 VA 100.00% 4800 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 250 A 208 A 208 A

Total Load: 29973 VA 24933 VA 24933 VA

11 -- -- -- 0 VA 2493... -- -- -- 12

9 -- -- -- 0 VA 2493... -- -- -- 10

7 55-1N3-1 200 A 3 0 VA 2997... 3 400 A 55-DP-TRB 8

5 -- -- -- 0 VA 0 VA -- -- -- 6

3 -- -- -- 0 VA 0 VA -- -- -- 4

1 55-3N3-1 200 A 3 0 VA 0 VA 3 150 A 55-2N3-1 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: SURFACE Wires: 4 Mains: LUGS ONLY

Supply From: TR-55-1N3 Phases: 3 Mains Rating: 500 A

Location: Volts: 120/208 Wye A.I.C. Rating: 22k

Branch Panel: DP/55-1N3

Notes:

Total Est. Demand: 131 A

Total Conn.: 222 A

Total Est. Demand: 47320 VA

Receptacle 75040 VA 56.66% 42520 VA Total Conn. Load: 79840 VA

Other 4800 VA 100.00% 4800 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 250 A 208 A 208 A

Total Load: 29973 VA 24933 VA 24933 VA

41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42

39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40

37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38

35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36

33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34

31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 -- -- -- 3533... 0 VA 1 20 A SPARE 24

21 -- -- -- 3533... 0 VA 1 20 A SPARE 22

19 PANEL 55-3C149B 100 A 3 4253... 0 VA 1 20 A SPARE 20

17 -- -- -- 3533... 3533... -- -- -- 18

15 -- -- -- 3533... 3533... -- -- -- 16

13 PANEL 55-2C144B 100 A 3 4253... 4253... 3 100 A PANEL 55-3A120B 14

11 -- -- -- 3533... 3533... -- -- -- 12

9 -- -- -- 3533... 3533... -- -- -- 10

7 PANEL 55-1C132B 100 A 3 4253... 4253... 3 100 A PANEL 55-2A136B 8

5 -- -- -- 3533... 3533... -- -- -- 6

3 -- -- -- 3533... 3533... -- -- -- 4

1 PANEL 55-1A129B 100 A 3 4253... 4253... 3 100 A PANEL 55-1B104B 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Recessed Wires: 4 Mains: 400A / 3P

Supply From: DP/55-1N3 Phases: 3 Mains Rating: 400 A

Location: ELEC 1C 111 Volts: 120/208 Wye A.I.C. Rating: 22k

Branch Panel: 55-DP-TRB

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY

AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

56EP701

BLDG 56 - ELECTRICAL

SCHEDULESSPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM - INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL/WNM LLT/JPS

CONSTRUCTION

DOCUMENTS

Revisions: Date:

Notes:

Total Est. Demand: 84 A

Total Conn.: 130 A

Lighting 808 VA 100.00% 808 VA Total Est. Demand: 30248 VA

Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 46688 VA

Other 3000 VA 100.00% 3000 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 136 A 123 A 133 A

Total Load: 16177 VA 14737 VA 15773 VA

41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42

39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40

37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38

35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36

33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34

31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 -- -- -- 3533... 0 VA 1 20 A SPARE 16

13 -- -- -- 3735... 0 VA 1 20 A SPARE 14

11 PANEL 56-2A122A 100 A 3 4253... 3533... -- -- -- 12

9 -- -- -- 3533... 3735... -- -- -- 10

7 -- -- -- 3735... 4253... 3 100 A PANEL 56-3A122A 8

5 PANEL 56-BA105A 100 A 3 4253... 3533... -- -- -- 6

3 SPARE 20 A 1 0 VA 3735... -- -- -- 4

1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 56-1A109A 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: SURFACE Wires: 4 Mains: 225A / 3P

Supply From: DP/56C Phases: 3 Mains Rating: 225 A

Location: BB 129 Volts: 120/208 Wye A.I.C. Rating: 65k

Branch Panel: 56-DP-TRA

GENERAL NOTES

KEY NOTES

REMOVE EXISTING SPARE CIRCUIT BREAKER AND INSTALL NEW CIRCUIT

BREAKER TO SUPPLY NEW LOAD.

EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.

REFERENCE ONE-LINE DIAGRAM ON SHEET 56EP601 FOR ADDITIONAL

INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.

THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT

PROVIDED TO SHOW OVERALL LOAD OF PANEL.

Notes:

Total Est. Demand: 84 A

Total Conn.: 130 A

Lighting 808 VA 100.00% 808 VA Total Est. Demand: 30248 VA

Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 46688 VA

Other 3000 VA 100.00% 3000 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 136 A 123 A 133 A

Total Load: 16177 VA 14737 VA 15773 VA

17 -- -- -- 0 VA 1577... -- -- -- 18

15 -- -- -- 0 VA 1473... -- -- -- 16

13 PANEL 56-3CR 60 A 3 0 VA 1617... 3 225 A 56-DP-TRA 14

11 -- -- -- 0 VA 0 VA -- -- -- 12

9 -- -- -- 0 VA 0 VA -- -- -- 10

7 PANEL 56-1CR 60 A 3 0 VA 0 VA 3 60 A PANEL 56-2CR 8

5 -- -- -- 0 VA 0 VA -- -- -- 6

3 -- -- -- 0 VA 0 VA -- -- -- 4

1 PANEL 56-CR 60 A 3 0 VA 0 VA 3 60 A PANEL 56-SP1 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Recessed Wires: 4 Mains: 1600A / 3P

Supply From: TR-56-C Phases: 3 Mains Rating: 1600 A

Location: EMERG ELEC BB 129 Volts: 120/208 Wye A.I.C. Rating: 42k

Branch Panel: DP 56-C

Notes:

Total Est. Demand: 80 A

Total Conn.: 126 A

Total Est. Demand: 28840 VA

Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 45280 VA

Other 2400 VA 100.00% 2400 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 132 A 118 A 132 A

Total Load: 15573 VA 14133 VA 15573 VA

41 SPARE 20 A 1 0 VA 0 VA -- -- -- 42

39 SPARE 20 A 1 0 VA 0 VA -- -- -- 40

37 SPARE 20 A 1 0 VA 0 VA 3 20 A SPD 38

35 SPARE 20 A 1 0 VA 0 VA -- -- -- 36

33 SPARE 20 A 1 0 VA 0 VA -- -- -- 34

31 SPARE 20 A 1 0 VA 0 VA 3 20 A DIGITAL POWER METER 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 -- -- -- 3533... 0 VA 1 20 A SPARE 16

13 -- -- -- 3533... 0 VA 1 20 A SPARE 14

11 PANEL 56-2A122B 100 A 3 4253... 3533... -- -- -- 12

9 -- -- -- 3533... 3533... -- -- -- 10

7 -- -- -- 3533... 4253... 3 100 A PANEL 56-3A122B 8

5 PANEL 56-BA105B 100 A 3 4253... 3533... -- -- -- 6

3 SPARE 20 A 1 0 VA 3533... -- -- -- 4

1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 56-1A109B 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: SURFACE Wires: 4 Mains: 225A / 3P

Supply From: TR-56-DP-TRAB Phases: 3 Mains Rating: 225 A

Location: BB 129 Volts: 120/208 Wye A.I.C. Rating: 65k

Branch Panel: 56-DP-TRB

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY

AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

57EP701

BLDG 57 - ELECTRICAL

SCHEDULESSPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL/WNM LLT/JPS

CONSTRUCTION

DOCUMENTS

Revisions: Date:

GENERAL NOTES

KEY NOTES

Notes:

Total Est. Demand: 34 A

Total Conn.: 36 A

Lighting 202 VA 100.00% 202 VA Total Est. Demand: 12122 VA

Receptacle 11440 VA 93.71% 10720 VA Total Conn. Load: 12842 VA

Other 1200 VA 100.00% 1200 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 43 A 33 A 31 A

Total Load: 5173 VA 3935 VA 3733 VA

41 -- -- -- 0 VA 200 VA -- -- -- 42

39 -- -- -- 0 VA 200 VA -- -- -- 40

37 IT PANEL 57-1T4-1 - 1B 140 60 A 3 0 VA 920 VA 3 100 A 57-1B139B 38

35 SPARE 20 A 1 0 VA 3533... -- -- -- 36

33 SPARE 20 A 1 0 VA 3735... -- -- -- 34

31 SPARE 20 A 1 0 VA 4253... 3 100 A 57-1B139A 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 RESERVED FOR DDC SYSTEM 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 RESERVED FOR DDC SYSTEM 20 A 1 0 VA 0 VA -- -- -- 24

21 RECEPTACLES - ROOF 20 A 1 0 VA 0 VA 2 20 A HEATING WATER PUMP 57-HWP-3 22

19 RECEPTACLES - MEZZANINE 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - MEZZANINE 20

17 RECEPTACLES - C1-16,C1-18 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 138,143 18

15 57-FCU-7 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 DOOR HARDWARE 20 A 1 0 VA 0 VA 1 20 A FIRE ALARM EQPT - 1B 137 14

11 MICROWAVE - 1B 138c 20 A 1 0 VA 0 VA 1 20 A EWC - 1B 138g 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A COFFEE - 1B 138c 10

7 REFRIGERATOR - 1B 138c 20 A 1 0 VA 0 VA 1 20 A RECEPTACLE - 1B 138c 8

5 SINK - 1B 138a 20 A 1 0 VA 0 VA 1 20 A SINK - 1B 138b 6

3 RECEPTACLES - 1B 138c,g 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 138a,b 4

1 RECEPTACLES - 1B 136 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 136 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 150A / 3P

Supply From: TR 57-1N4 Phases: 3 Mains Rating: 225 A

Location: ELEC 1B 137 Volts: 120/208 Wye A.I.C. Rating: 10k

Branch Panel: 57-1N4

Notes:

Total Est. Demand: 34 A

Total Conn.: 36 A

Lighting 202 VA 100.00% 202 VA Total Est. Demand: 12122 VA

Receptacle 11440 VA 93.71% 10720 VA Total Conn. Load: 12842 VA

Other 1200 VA 100.00% 1200 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 43 A 33 A 31 A

Total Load: 5173 VA 3935 VA 3733 VA

83 -- -- -- 200 VA 0 VA -- -- -- 84

81 -- -- -- 200 VA 0 VA -- -- -- 82

79 57-1B120B 100 A 3 920 VA 0 VA 3 60 A IT PANEL 571T6-2 - 1B 121 80

77 -- -- -- 3533... 0 VA 1 20 A SPARE 78

75 -- -- -- 3735... 0 VA 1 20 A SPARE 76

73 57-1B120A 100 A 3 4253... 0 VA 1 20 A SPARE 74

71 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 72

69 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 70

67 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 68

65 COUNTER RECEPT 1B 106A 20 A 1 0 VA 0 VA 1 20 A SPARE 66

63 WALK-THRU METAL DET C1-1 20 A 1 0 VA 0 VA 1 20 A HEAT TRACE - ROOF DRAWIN 64

61 57-UH-4 20 A 1 0 VA 0 VA 1 20 A 57-UH-5 62

59 57-FCU-3 20 A 1 0 VA 0 VA 1 20 A 57-FCU-4 60

57 DOOR HARDWARE 20 A 1 0 VA 0 VA 1 20 A FIRE ALARM EQPT - 1B 117 58

55 RESERVED FOR DDC SYSTEM 20 A 1 0 VA 0 VA 1 20 A DOOR HARDWARE 56

53 RESERVED FOR DDC SYSTEM 20 A 1 0 VA 0 VA 1 20 A TRACK HOIST - 1A 100a 54

51 EWC - C1-12 20 A 1 0 VA 0 VA 1 20 A PLOTTER - 1B 125 52

49 SHRED IT - 1B 106a 20 A 1 0 VA 0 VA 1 20 A VENDING - 1B 122 50

47 COPIER - 1B 106a 20 A 1 0 VA 0 VA 1 20 A TV - 1B 100 48

45 OVERHEAD DOOR - 1A 100 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - C1-8 46

43 RECEPTACLE - EAST EXTERIOR 20 A 1 0 VA 0 VA 1 20 A VENDING - 1B 122 44

41 COFFEE - 1B 122 20 A 1 0 VA 0 VA 1 20 A VENDING MACH - 1B 122 42

39 TOASTER - 1B 122 20 A 1 0 VA 0 VA 1 20 A MICROWAVE - 1B 122 40

37 RECEPTACLES - 1B 122 20 A 1 0 VA 0 VA 1 20 A RECEPTACLE - 1B 122 38

35 RECEPTACLES - 1B 125a 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 125 36

33 RECEPTACLES - 1B 123,124 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 125a 34

31 RECEPTACLES - C1-12 20 A 1 0 VA 0 VA 1 20 A SINKS - 1B 123,124 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A DOOR POWER 28

25 RECEPTACLES - 1B 118 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 119 26

23 RECEPTACLES - C1-3,4 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - C1-3,4,31 24

21 RECEPTACLES - 1B 106 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 106 22

19 RECEPTACLES - 1B 100 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - C1-4,31 20

17 RECEPTACLES - 1B 116 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - C1-4,5 18

15 RECEPTACLES - 1B 105 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 115 16

13 RECEPTACLES - 1B 103 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 104 14

11 RECEPTACLES - 1B 101 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 102 12

9 RECEPTACLES - 1B 108 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 107 10

7 RECEPTACLES - 1B 110 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 109 8

5 RECEPTACLES - 1B 112 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 111 6

3 RECEPTACLES - 1B 114 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 113 4

1 RECEPTACLES - C1-1,2,31 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 117 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 225A / 3P

Supply From: TR 57-1N4 Phases: 3 Mains Rating: 225 A

Location: ELEC 1B 117 Volts: 120/208 Wye A.I.C. Rating: 10k

Branch Panel: 57-1N6

SECTION 1

SECTION 2

1 EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.

REFERENCE ONELINE DIAGRAM ON SHEET 57EP601 FOR ADDITIONAL

INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.

THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT

PROVIDED TO SHOW OVERALL LOAD OF PANEL.

2 REMOVE EXISTING SPARE CIRCUIT BREAKERS AND INSTALL NEW CIRCUIT

BREAKER TO SUPPLY NEW LOAD.

3 REMOVE EXISTING CIRCUIT BREAKER FEEDING EXISTING PANEL 57-1T6-1.

INSTALL NEW CIRCUIT BREAKER TO SUPPLY NEW LOAD.

4 REMOVE EXISTING CIRCUIT BREAKER FEEDING EXISTING PANEL 57-1T4-2.

INSTALL NEW CIRCUIT BREAKER TO SUPPLY NEW LOAD.

SECTION 1

SECTION 2

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY

AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

58EP701

BLDG 58 - ELECTRICAL

SCHEDULESSPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

JEFFERSON BARRACKS - 1 JEFFERSON BARRACKS

DRIVE - ST. LOUIS, MO 63125

657-21-701JB

03/31/2022 LRL/WNM LLT/JPS

CONSTRUCTION

DOCUMENTS

Revisions: Date:

Notes:

Total Est. Demand: 34 A

Total Conn.: 36 A

Lighting 202 VA 100.00% 202 VA Total Est. Demand: 12122 VA

Receptacle 11440 VA 93.71% 10720 VA Total Conn. Load: 12842 VA

Other 1200 VA 100.00% 1200 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 43 A 33 A 31 A

Total Load: 5173 VA 3935 VA 3733 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 -- -- -- -- 200 VA -- -- -- 30

27 -- -- -- -- 200 VA -- -- -- 28

25 SPACE -- 3 -- 920 VA 3 100 A PANEL 58-104B 26

23 -- -- -- 0 VA 3533... -- -- -- 24

21 -- -- -- 0 VA 3735... -- -- -- 22

19 SPD 60 A 3 0 VA 4253... 3 100 A PANEL 58-104A 20

17 -- -- -- 0 VA 0 VA -- -- -- 18

15 -- -- -- 0 VA 0 VA -- -- -- 16

13 PANEL 58P2 400 A 3 0 VA 0 VA 3 100 A PANEL 58P4 14

11 -- -- -- 0 VA 0 VA -- -- -- 12

9 -- -- -- 0 VA 0 VA -- -- -- 10

7 PANEL 58P1 225 A 3 0 VA 0 VA 3 225 A PANEL 58L2 8

5 -- -- -- 0 VA 0 VA -- -- -- 6

3 -- -- -- 0 VA 0 VA -- -- -- 4

1 PANEL DP-1 400 A 3 0 VA 0 VA 3 225 A PANEL 58L1 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: LUGS ONLY

Supply From: Phases: 3 Mains Rating: 1000 A

Location: Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: MDP-58

GENERAL NOTES

KEY NOTES

INSTALL NEW CIRCUIT BREAKER TO SUPPLY NEW LOAD.

EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.

REFERENCE ONELINE DIAGRAM ON SHEET 58EP601 FOR ADDITIONAL

INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.

THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT

PROVIDED TO SHOW OVERALL LOAD OF PANEL.

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY

AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

60EP701

BLDG 60 AND 60T - ELECTRICAL

SCHEDULESSPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL/WNM JGE

CONSTRUCTION

DOCUMENTS

Notes:

Total Est. Demand: 18 A

Total Conn.: 18 A

Total Est. Demand: 6320 VA

Total Conn. Load: 6320 VA

Receptacle 6320 VA 100.00% 6320 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 22 A 16 A 16 A

Total Load: 2587 VA 1867 VA 1867 VA

35 -- -- -- 0 VA 36

33 -- -- -- 0 VA 34

31 SPARE 400 A 3 0 VA 32

29 -- -- -- 0 VA 0 VA -- -- -- 30

27 -- -- -- 0 VA 0 VA -- -- -- 28

25 SPARE 100 A 3 0 VA 0 VA 3 400 A SPARE 26

23 -- -- -- 0 VA 1867... -- -- -- 24

21 -- -- -- 0 VA 1867... -- -- -- 22

19 SPARE 100 A 3 0 VA 2587... 3 100 A 60-102B 20

17 -- -- -- 0 VA 0 VA -- -- -- 18

15 -- -- -- 0 VA 0 VA -- -- -- 16

13 SPARE 100 A 3 0 VA 0 VA 3 100 A SPARE 14

11 -- -- -- 0 VA 0 VA -- -- -- 12

9 -- -- -- 0 VA 0 VA -- -- -- 10

7 SPARE 20 A 3 0 VA 0 VA 3 100 A SPARE 8

5 -- -- -- 0 VA 0 VA -- -- -- 6

3 -- -- -- 0 VA 0 VA -- -- -- 4

1 90-ATS 90-1 400 A 3 0 VA 0 VA 3 800 A 90-ATS 90-2 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 1600

Supply From: 60-XF2-BLDG 60 Phases: 3 Mains Rating: 1600 A

Location: TRANSFORMER RM 119 Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: MDP-60

GENERAL NOTES

KEY NOTES

UTILIZE EXISTING SPARE CIRCUIT BREAKER TO SUPPLY NEW LOAD.

PROVIDE NEW CIRCUIT BREAKER IN EXISTING SPACE TO SUPPLY NEW LOAD.

EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.

REFERENCE ONELINE DIAGRAM ON SHEET 60EP601 FOR ADDITIONAL

INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.

THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT

PROVIDED TO SHOW OVERALL LOAD OF PANEL.

1. ALL CIRCUITS EXISTING UNLESS OTHERWISE NOTED.

2. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY AND

ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

3. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND SOURCE-B

PANEL SCHEDULES.

Revisions: Date:

Notes:

Total Est. Demand: 18 A

Total Conn.: 18 A

Total Est. Demand: 6522 VA

Lighting 202 VA 100.00% 202 VA Total Conn. Load: 6522 VA

Receptacle 6320 VA 100.00% 6320 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 22 A 17 A 16 A

Total Load: 2587 VA 2069 VA 1867 VA

29 -- -- -- 1867... 30

27 -- -- -- 2069... 28

25 60-102A 20 A 3 2587... 26

23 -- -- -- 0 VA 0 VA -- -- -- 24

21 -- -- -- 0 VA 0 VA -- -- -- 22

19 60-B1 225 A 3 0 VA 0 VA 3 100 A P4A 20

17 -- -- -- 0 VA 0 VA -- -- -- 18

15 -- -- -- 0 VA 0 VA -- -- -- 16

13 EM LIGHTS 100 A 3 0 VA 0 VA 3 400 A MDP-60T 14

11 -- -- -- 0 VA 0 VA -- -- -- 12

9 -- -- -- 0 VA 0 VA -- -- -- 10

7 GB BLDG 90 225 A 3 0 VA 0 VA 3 100 A EXHAUST HOODS 8

5 -- -- -- 0 VA 0 VA -- -- -- 6

3 -- -- -- 0 VA 0 VA -- -- -- 4

1 PNL-B 400 A 3 0 VA 0 VA 3 400 A 60-P2 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 800A/3P

Supply From: 90-ATS 90-2 Phases: 3 Mains Rating: 1200 A

Location: Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: DP-60EM

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

75EP701

BLDG 75 - ELECTRICAL

SCHEDULESSPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL./WNM LLT/JPS

CONSTRUCTION

DOCUMENTS

Revisions: Date:

KEY NOTES

GENERAL NOTES

Notes:

Total Est. Demand: 49 A

Total Conn.: 65 A

Lighting 202 VA 100.00% 202 VA Total Est. Demand: 17722 VA

Receptacle 21440 VA 73.32% 15720 VA Total Conn. Load: 23442 VA

Other 1800 VA 100.00% 1800 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 73 A 62 A 61 A

Total Load: 8707 VA 7469 VA 7267 VA

29 SPARE 20 A 1 0 VA 100 VA -- -- -- 30

27 SPARE 20 A 1 0 VA 100 VA -- -- -- 28

25 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 26

23 SPARE 20 A 1 0 VA 100 VA -- -- -- 24

21 SPARE 20 A 1 0 VA 100 VA -- -- -- 22

19 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8

5 -- -- -- 3533... 3533... -- -- -- 6

3 -- -- -- 3735... 3533... -- -- -- 4

1 PANEL 75-1B105A 100 A 3 4253... 4253... 3 100 A PANEL 75-1B105B 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 200A / 3P

Supply From: TR 75N Phases: 3 Mains Rating: 200 A

Location: BOILER BAY 1A 101 Volts: 120/208 Wye A.I.C. Rating: 22k

Branch Panel: 75-DP-TRAB 1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY

AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EP701

TYPICAL ELECTRICAL SCHEDULES

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

ST. LOUIS VA MEDICAL CENTER - JEFFERSON

BARRACKS MO

657-21-701JB

03/31/2022 LRL/WNM WNM

CONSTRUCTION

DOCUMENTS

Revisions: Date:

Notes:

Total Est. Demand: 30 A

Lighting 202 VA 100.00% 202 VA Total Conn.: 28 A

Receptacle 720 VA 100.00% 720 VA Total Est. Demand: 10942 VA

Other 5600 VA 100.00% 5600 VA Total Conn. Load: 10058 VA

Motor 3536 VA 125.00% 4420 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 38 A 17 A 32 A

Total Load: 4355 VA 2069 VA 3635 VA

29 SPARE 20 A 1 0 VA 100 VA -- -- -- 30

27 SPARE 20 A 1 0 VA 100 VA -- -- -- 28

25 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 26

23 SPARE 20 A 1 0 VA 100 VA -- -- -- 24

21 SPARE 20 A 1 0 VA 100 VA -- -- -- 22

19 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 SPARE 20 A 1 0 VA 1768... -- -- -- 8

5 -- -- -- 1667... 1768... 2 20 A DUCTLESS SPLIT COOLING UNIT 6

3 -- -- -- 1667... 202 VA 1 20 A LIGHTING - TR ROOM 4

1 SERVER RACK RACEPTACLE 20 A 3 1667... 720 VA 1 20 A RECEPTACLES - TR ROOM 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 100A / 3P

Supply From: SEE PANEL SCHEDULE NOTE Phases: 3 Mains Rating: 100 A

Location: SEE PANEL SCHEDULE NOTE Volts: 120/208 Wye A.I.C. Rating: 22k

Branch Panel: SOURCE A POWER TR PANEL, TYPICAL - TYPE 1

Notes:

Total Est. Demand: 18 A

Total Conn.: 18 A

Total Est. Demand: 6320 VA

Receptacle 720 VA 100.00% 720 VA Total Conn. Load: 6320 VA

Other 5600 VA 100.00% 5600 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 22 A 16 A 16 A

Total Load: 2587 VA 1867 VA 1867 VA

29 SPARE 20 A 1 0 VA 100 VA -- -- -- 30

27 SPARE 20 A 1 0 VA 100 VA -- -- -- 28

25 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 26

23 SPARE 20 A 1 0 VA 100 VA -- -- -- 24

21 SPARE 20 A 1 0 VA 100 VA -- -- -- 22

19 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8

5 -- -- -- 1667... 0 VA 1 20 A SPARE 6

3 -- -- -- 1667... 0 VA 1 20 A SPARE 4

1 SERVER RACK RECEPTACLE 20 A 3 1667... 720 VA 1 20 A RECEPTACLES - TR ROOM 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 100A / 3P

Supply From: SEE PANEL SCHEDULE NOTE Phases: 3 Mains Rating: 100 A

Location: SEE PANEL SCHEDULE NOTE Volts: 120/208 Wye A.I.C. Rating: 22k

Branch Panel: SOURCE B POWER TR PANEL, TYPICAL - TYPE 1

Notes:

Total Est. Demand: 44 A

Lighting 202 VA 100.00% 202 VA Total Conn.: 42 A

Receptacle 720 VA 100.00% 720 VA Total Est. Demand: 15942 VA

Other 10600 VA 100.00% 10600 VA Total Conn. Load: 15058 VA

Motor 3536 VA 125.00% 4420 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 52 A 31 A 46 A

Total Load: 6021 VA 3736 VA 5301 VA

29 SPARE 20 A 1 0 VA 100 VA -- -- -- 30

27 SPARE 20 A 1 0 VA 100 VA -- -- -- 28

25 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 26

23 SPARE 20 A 1 0 VA 100 VA -- -- -- 24

21 SPARE 20 A 1 0 VA 100 VA -- -- -- 22

19 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A…