Attachment 20 - Drawings Part-19.pdf
PDF 14 MB Posted
- Attached to
- Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks Federal contract opportunity
- Solicitation number
- 36C77623R0009
About this file
This solicitation seeks a general contractor to provide infrastructure upgrades at the St. Louis Jefferson Barracks VA Medical Center. The scope of work includes electrical panel upgrades and power systems work, building management system integration, HVAC assessments and upgrades, facility renovations including demolition, construction and finishes, data center renovations, physical security enhancements, fiber infrastructure assessment and upgrades between buildings, installation of a diversified wide area network path to the datacenter, and hazardous material abatement. The project involves improvements to Buildings 1, 2, 3, 3T, 18, 23, 24, 25, 51, 51T, 52, 53, 53T, 55, 56, 57, 58, 59, 60, 60T, 61, 75 and associated site work. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.
View the file
Other files for this federal contract opportunity
Show all 50
Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 25EP701
BLDG 25 - ELECTRICAL
SCHEDULES 25
LRL/WNM LLT/JPS
CONSTRUCTION
DOCUMENTS
03/31/2022
Notes:
Total Est. Demand: 68 A
Total Conn.: 96 A
Power 2766 VA 100.00% 2766 VA Total Est. Demand: 24566 VA
Receptacle 30000 VA 66.67% 20000 VA Total Conn. Load: 34566 VA
Other 1800 VA 100.00% 1800 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 107 A 94 A 88 A
Total Load: 12760 VA 11206 VA 10600 VA
17 -- -- -- 3533... 3533... -- -- -- 18
15 -- -- -- 3735... 3735... -- -- -- 16
13 25-204BB 20 A 3 4253... 4253... 3 20 A 25-313AB 14
11 -- -- -- 0 VA 3533... -- -- -- 12
9 -- -- -- 0 VA 3735... -- -- -- 10
7 PANEL 25L2 250 A 3 0 VA 4253... 3 20 A 25-117AB 8
5 -- -- -- 0 VA 0 VA -- -- -- 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 PANEL 25L01A 250 A 3 0 VA 0 VA 3 250 A PANEL 25L1A 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 600A / 3P
Supply From: 25-XF2-BLDG 25 Phases: 3 Mains Rating: 600 A
Location: PIPE BASEMENT Z002 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: 25DP
Notes:
Total Est. Demand: 65 A
Total Conn.: 96 A
Total Est. Demand: 23480 VA
Receptacle 32160 VA 65.55% 21080 VA Total Conn. Load: 34560 VA
Other 2400 VA 100.00% 2400 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 108 A 90 A 90 A
Total Load: 12960 VA 10800 VA 10800 VA
29 SPARE 20 A 1 0 VA 100 VA -- -- -- 30
27 SPARE 20 A 1 0 VA 100 VA -- -- -- 28
25 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 26
23 SPARE 20 A 1 0 VA 100 VA -- -- -- 24
21 SPARE 20 A 1 0 VA 100 VA -- -- -- 22
19 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14
11 -- -- -- 3533... 0 VA 1 20 A SPARE 12
9 -- -- -- 3533... 0 VA 1 20 A SPARE 10
7 PANEL 25-313AA 100 A 3 4253... 0 VA 1 20 A SPARE 8
5 -- -- -- 3533... 3533... -- -- -- 6
3 -- -- -- 3533... 3533... -- -- -- 4
1 PANEL 25-117AA 100 A 3 4253... 4253... 3 100 A PANEL 25-204BA 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 225A / 3P
Supply From: ATS1-EDP25 Phases: 3 Mains Rating: 225 A
Location: CORRIDOR H102 Volts: 120/208 Wye A.I.C. Rating: 65k
Branch Panel: 25-DP-TRA
GENERAL NOTES
KEY NOTES
Revisions: Date:
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY
AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND
SOURCE-B PANEL SCHEDULES.
EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.
REFERENCE ONELINE DIAGRAM ON SHEET 25EP601 FOR ADDITIONAL
INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.
THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT
PROVIDED TO SHOW OVERALL LOAD OF PANEL.
LRL/WNM LLT/JPS
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
51EP701
BLDG 51, 51A, AND 51T -
ELECTRICAL SCHEDULESSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM LLT/JPS
CONSTRUCTION
DOCUMENTS
Revisions: Date:
GENERAL NOTES
KEY NOTES
1 UTILIZE EXISTING SPARE CIRCUIT BREAKER TO SUPPLY NEW LOAD.
Notes:
Total Est. Demand: 84 A
Total Conn.: 130 A
Lighting 808 VA 100.00% 808 VA Total Est. Demand: 30248 VA
Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 46688 VA
Other 3000 VA 100.00% 3000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 136 A 123 A 133 A
Total Load: 16177 VA 14737 VA 15773 VA
41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42
39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40
37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38
35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36
33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34
31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 -- -- -- 3533... 0 VA 1 20 A SPARE 16
13 -- -- -- 3735... 0 VA 1 20 A SPARE 14
11 PANEL 51-1A183A 100 A 3 4253... 3533... -- -- -- 12
9 -- -- -- 3533... 3735... -- -- -- 10
7 -- -- -- 3735... 4253... 3 100 A PANEL 51-1A139A 8
5 PANEL 51-BE111A 100 A 3 4253... 3533... -- -- -- 6
3 SPARE 20 A 1 0 VA 3735... -- -- -- 4
1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 51-1A102A 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 225A / 3P
Supply From: DP-51 Phases: 3 Mains Rating: 225 A
Location: Volts: 120/208 Wye A.I.C. Rating: 65kAIC
Branch Panel: 51-DP-TRA
Notes:
Total Est. Demand: 84 A
Total Conn.: 130 A
Lighting 808 VA 100.00% 808 VA Total Est. Demand: 30248 VA
Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 46688 VA
Other 3000 VA 100.00% 3000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 136 A 123 A 133 A
Total Load: 16177 VA 14737 VA 15773 VA
35 -- -- -- 0 VA 36
33 -- -- -- 0 VA 34
31 SPARE 250 A 3 0 VA 32
29 -- -- -- 0 VA 1577... -- -- -- 30
27 -- -- -- 0 VA 1473... -- -- -- 28
25 51-PANEL-DP1 400 A 3 0 VA 1617... 3 400 A 51-DP-TRA 26
23 -- -- -- 0 VA 0 VA -- -- -- 24
21 -- -- -- 0 VA 0 VA -- -- -- 22
19 51-PANEL-DP2 225 A 3 0 VA 0 VA 3 100 A 51-PANEL-LP4 20
17 -- -- -- 0 VA 0 VA -- -- -- 18
15 -- -- -- 0 VA 0 VA -- -- -- 16
13 SPARE 50 A 3 0 VA 0 VA 3 225 A SPARE 14
11 -- -- -- 0 VA 0 VA -- -- -- 12
9 -- -- -- 0 VA 0 VA -- -- -- 10
7 SPARE 225 A 3 0 VA 0 VA 3 250 A 51-PANEL-PP2 8
5 -- -- -- 0 VA 0 VA -- -- -- 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 SPARE 225 A 3 0 VA 0 VA 3 250 A 51-PANEL-PP4 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 800A / 3P
Supply From: 51-ATS51 Phases: 3 Mains Rating: 800 A
Location: BE-114 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: DP-51
2 EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.
REFERENCE ONE-LINE DIAGRAM ON SHEET 51EP602 FOR ADDITIONAL
INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.
THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT
PROVIDED TO SHOW OVERALL LOAD OF PANEL.
Notes:
Total Est. Demand: 80 A
Total Conn.: 126 A
Total Est. Demand: 28840 VA
Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 45280 VA
Other 2400 VA 100.00% 2400 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 132 A 118 A 132 A
Total Load: 15573 VA 14133 VA 15573 VA
29 -- -- -- -- -- -- -- -- 30
27 -- -- -- -- -- -- -- -- 28
25 SPACE -- 3 -- -- 3 -- SPACE 26
23 -- -- -- -- -- -- -- -- 24
21 -- -- -- -- -- -- -- -- 22
19 SPACE -- 3 -- -- 3 -- SPACE 20
17 -- -- -- -- -- -- -- -- 18
15 -- -- -- -- -- -- -- -- 16
13 SPACE -- 3 -- -- 3 -- SPACE 14
11 -- -- -- -- -- -- -- -- 12
9 -- -- -- -- -- -- -- -- 10
7 PNL-MP51 (TAPPED OFF BUS) -- 3 -- -- 3 -- SPACE 8
5 -- -- -- 0 VA 1557... -- -- -- 6
3 -- -- -- 0 VA 1413... -- -- -- 4
1 SPARE 600 A 3 0 VA 1557... 3 400 A 51-DP-TRB 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 800A/3P
Supply From: 51-XF2-BLDG 51 Phases: 3 Mains Rating: 225 A
Location: Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: CB51
Notes:
Total Est. Demand: 80 A
Total Conn.: 126 A
Total Est. Demand: 28840 VA
Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 45280 VA
Other 2400 VA 100.00% 2400 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 132 A 118 A 132 A
Total Load: 15573 VA 14133 VA 15573 VA
41 SPARE 20 A 1 0 VA 0 VA -- -- -- 42
39 SPARE 20 A 1 0 VA 0 VA -- -- -- 40
37 SPARE 20 A 1 0 VA 0 VA 3 20 A SPD 38
35 SPARE 20 A 1 0 VA 0 VA -- -- -- 36
33 SPARE 20 A 1 0 VA 0 VA -- -- -- 34
31 SPARE 20 A 1 0 VA 0 VA 3 20 A DIGITAL POWER METER 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 -- -- -- 3533... 0 VA 1 20 A SPARE 16
13 -- -- -- 3533... 0 VA 1 20 A SPARE 14
11 PANEL 51-1A183B 100 A 3 4253... 3533... -- -- -- 12
9 -- -- -- 3533... 3533... -- -- -- 10
7 -- -- -- 3533... 4253... 3 100 A PANEL 51-1A139B 8
5 PANEL 51-BE111B 100 A 3 4253... 3533... -- -- -- 6
3 SPARE 20 A 1 0 VA 3533... -- -- -- 4
1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 51-1A102B 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 225A / 3P
Supply From: DP-51 Phases: 3 Mains Rating: 225 A
Location: Volts: 120/208 Wye A.I.C. Rating: 65kAIC
Branch Panel: 51-DP-TRB
3 PROVIDE NEW CIRCUIT BREAKER TO SUPPLY NEW LOAD.
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY
AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND
SOURCE-B PANEL SCHEDULES.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
51EP702
BLDG 51, 51A, AND 51T -
ELECTRICAL SCHEDULESSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 Checker Author
CONSTRUCTION
DOCUMENTS
Revisions: Date:
GENERAL NOTES
KEY NOTES
1 PROVIDE NEW CIRCUIT BREAKER IN EXISTING SPACE TO SUPPLY NEW LOAD.
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY
AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND
SOURCE-B PANEL SCHEDULES.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
52EP701
BLDG 52 - ELECTRICAL
SCHEDULESSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM LLT/JPS
CONSTRUCTION
DOCUMENTS
GENERAL NOTES
KEY NOTES
Notes:
Total Est. Demand: 101 A
Total Conn.: 162 A
Lighting 1010 VA 100.00% 1010 VA Total Est. Demand: 36410 VA
Receptacle 53600 VA 59.33% 31800 VA Total Conn. Load: 58210 VA
Other 3600 VA 100.00% 3600 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 168 A 152 A 169 A
Total Load: 19913 VA 18271 VA 20027 VA
41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42
39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40
37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38
35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36
33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34
31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24
21 -- -- -- 3533... 0 VA 1 20 A SPARE 22
19 -- -- -- 3735... 0 VA 1 20 A SPARE 20
17 PANEL 52-1S33A 100 A 3 4253... 0 VA 1 20 A SPARE 18
15 -- -- -- 3533... 0 VA 1 20 A SPARE 16
13 -- -- -- 3735... 0 VA 1 20 A SPARE 14
11 PANEL 52-1N82AA 100 A 3 4253... 3533... -- -- -- 12
9 -- -- -- 3533... 3735... -- -- -- 10
7 -- -- -- 3735... 4253... 3 100 A PANEL 52-2N91A 8
5 PANEL 52-GN29AA 100 A 3 4253... 3533... -- -- -- 6
3 SPARE 20 A 1 0 VA 3735... -- -- -- 4
1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 52-2N86BA 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 250A / 3P
Supply From: ATS52-DP52CR Phases: 3 Mains Rating: 250 A
Location: MECH GS09 Volts: 120/208 Wye A.I.C. Rating: 65k
Branch Panel: 52-DP-TRA
Revisions: Date:
Notes:
Total Est. Demand: 98 A
Total Conn.: 159 A
Total Est. Demand: 35400 VA
Receptacle 53600 VA 59.33% 31800 VA Total Conn. Load: 57200 VA
Other 3600 VA 100.00% 3600 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 163 A 149 A 169 A
Total Load: 19307 VA 17867 VA 20027 VA
41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42
39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40
37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38
35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36
33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34
31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24
21 -- -- -- 3533... 0 VA 1 20 A SPARE 22
19 -- -- -- 3533... 0 VA 1 20 A SPARE 20
17 PANEL 52-2N91B 100 A 3 4253... 0 VA 1 20 A SPARE 18
15 -- -- -- 3533... 0 VA 1 20 A SPARE 16
13 -- -- -- 3533... 0 VA 1 20 A SPARE 14
11 PANEL 52-1S33B 100 A 3 4253... 3533... -- -- -- 12
9 -- -- -- 3533... 3533... -- -- -- 10
7 -- -- -- 3533... 4253... 3 100 A PANEL 52-2N86BB 8
5 PANEL 52-GN29AB 100 A 3 4253... 3533... -- -- -- 6
3 SPARE 20 A 1 0 VA 3533... -- -- -- 4
1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 52-1N82AB 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 250A / 3P
Supply From: MCB Phases: 3 Mains Rating: 250 A
Location: MECH GS09 Volts: 120/208 Wye A.I.C. Rating: 65k
Branch Panel: 52-DP-TRB
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY
AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND
SOURCE-B PANEL SCHEDULES.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
53EP701
BLDG 53 AND 53T - ELECTRICAL
SCHEDULESSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM JPS/LLT
CONSTRUCTION
DOCUMENTS
Revisions: Date:
GENERAL NOTES
KEY NOTES
1 PROVIDE NEW CIRCUIT BREAKER TO SUPPLY NEW LOAD.
Notes:
Total Est. Demand: 101 A
Total Conn.: 162 A
Lighting 1010 VA 100.00% 1010 VA Total Est. Demand: 36410 VA
Receptacle 53600 VA 59.33% 31800 VA Total Conn. Load: 58210 VA
Other 3600 VA 100.00% 3600 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 171 A 154 A 162 A
Total Load: 20431 VA 18473 VA 19307 VA
41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42
39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40
37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38
35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36
33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34
31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20
17 SPARE 20 A 1 0 VA 3533... -- -- -- 18
15 -- -- -- 3533... 3735... -- -- -- 16
13 -- -- -- 3735... 4253... 3 100 A PANEL 53-GS02AA 14
11 PANEL 53-1S01A 100 A 3 4253... 3533... -- -- -- 12
9 -- -- -- 3533... 3735... -- -- -- 10
7 -- -- -- 3735... 4253... 3 100 A PANEL 53-2S001A 8
5 PANEL 53-GS10A 100 A 3 4253... 3533... -- -- -- 6
3 SPARE 20 A 1 0 VA 3735... -- -- -- 4
1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 53-1S002A 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 225A / 3P
Supply From: BLDG 53-SWBD Phases: 3 Mains Rating: 225 A
Location: MECH RM GS12 Volts: 120/208 Wye A.I.C. Rating: 65kAIC
Branch Panel: 53-DP-TRA
Notes:
Total Est. Demand: 101 A
Total Conn.: 162 A
Lighting 1010 VA 100.00% 1010 VA Total Est. Demand: 36410 VA
Receptacle 53600 VA 59.33% 31800 VA Total Conn. Load: 58210 VA
Other 3600 VA 100.00% 3600 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 171 A 154 A 162 A
Total Load: 20431 VA 18473 VA 19307 VA
47 -- -- -- 0 VA 0 VA -- -- -- 48
45 -- -- -- 0 VA 0 VA -- -- -- 46
43 SPARE 800 A 3 0 VA 0 VA 3 800 A SPARE 44
41 -- -- -- 0 VA 1930... -- -- -- 42
39 -- -- -- 0 VA 1847... -- -- -- 40
37 SPARE 800 A 3 0 VA 2043... 3 225 A 53-DP-TRA 38
35 -- -- -- 0 VA 0 VA -- -- -- 36
33 -- -- -- 0 VA 0 VA -- -- -- 34
31 53-PANEL-GB1-1 200 A 3 0 VA 0 VA 3 800 A SPARE 32
29 -- -- -- 0 VA 0 VA -- -- -- 30
27 -- -- -- 0 VA 0 VA -- -- -- 28
25 53-PANEL-GA 100 A 3 0 VA 0 VA 3 225 A 53-PANEL-2C 26
23 -- -- -- 0 VA 0 VA -- -- -- 24
21 -- -- -- 0 VA 0 VA -- -- -- 22
19 53-PANEL-GB, 53-PANEL-1B, 53-PANEL-2B-1 400 A 3 0 VA 0 VA 3 225 A 53-PANEL-GC-1 20
17 -- -- -- 0 VA 0 VA -- -- -- 18
15 -- -- -- 0 VA 0 VA -- -- -- 16
13 53-PANEL-GP 400 A 3 0 VA 0 VA 3 600 A 53-PANEL-MCC 14
11 -- -- -- 0 VA 0 VA -- -- -- 12
9 -- -- -- 0 VA 0 VA -- -- -- 10
7 53-PANEL-P2 400 A 3 0 VA 0 VA 3 100 A 53-PANEL-KP 8
5 -- -- -- 0 VA 0 VA -- -- -- 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 SPARE 800 A 3 0 VA 0 VA 3 225 A 53-PANEL-1A-1, 53-PANEL-2A-1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: LUGS ONLY
Supply From: 53-ATS-53 Phases: 3 Mains Rating: 800 A
Location: MECH RM GS12 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: 53-SWBD
2 EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.
REFERENCE ONELINE DIAGRAM ON SHEET 53EP701 FOR ADDITIONAL
INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.
THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT
PROVIDED TO SHOW OVERALL LOAD OF PANEL.
3 PROVIDE NEW CIRCUIT BREAKER IN EXISTING SPACE TO SUPPLY NEW LOAD.
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY
AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND
SOURCE-B PANEL SCHEDULES.
Notes:
Total Est. Demand: 98 A
Total Conn.: 159 A
Total Est. Demand: 35400 VA
Receptacle 53600 VA 59.33% 31800 VA Total Conn. Load: 57200 VA
Other 3600 VA 100.00% 3600 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 169 A 149 A 163 A
Total Load: 20027 VA 17867 VA 19307 VA
41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42
39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40
37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38
35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36
33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34
31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20
17 SPARE 20 A 1 0 VA 3533... -- -- -- 18
15 -- -- -- 3533... 3533... -- -- -- 16
13 -- -- -- 3533... 4253... 3 100 A PANEL 53-GS02AB 14
11 PANEL 53-1S01B 100 A 3 4253... 3533... -- -- -- 12
9 -- -- -- 3533... 3533... -- -- -- 10
7 -- -- -- 3533... 4253... 3 100 A PANEL 53-2S001B 8
5 PANEL 53-GS10B 100 A 3 4253... 3533... -- -- -- 6
3 SPARE 20 A 1 0 VA 3533... -- -- -- 4
1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 53-1S002B 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 225A / 3P
Supply From: 53-PANEL-MDP-53 Phases: 3 Mains Rating: 225 A
Location: MECH RM GS12 Volts: 120/208 Wye A.I.C. Rating: 65kAIC
Branch Panel: 53-DP-TRB
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
55EP701
BLDG 55 - ELECTRICAL
SCHEDULESSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM JBB
CONSTRUCTION
DOCUMENTS
GENERAL NOTES
KEY NOTES
1 EXISTING PANELBOARD TO BE MODIFIED; PROVIDE CIRCUIT BREAKER AS
INDICATED.
Notes:
Total Est. Demand: 59 A
Total Conn.: 98 A
Lighting 1414 VA 100.00% 1414 VA Total Est. Demand: 48734 VA
Receptacle 75040 VA 56.66% 42520 VA Total Conn. Load: 81254 VA
Other 4800 VA 100.00% 4800 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 109 A 96 A 90 A
Total Load: 29973 VA 26347 VA 24933 VA
31 SPACE -- 1 -- 32
29 -- -- -- 0 VA 30
27 -- -- -- 0 VA 28
25 SPARE 60 A 3 0 VA 26
23 -- -- -- 0 VA 2493... -- -- -- 24
21 -- -- -- 0 VA 2634... -- -- -- 22
19 SPARE 60 A 3 0 VA 2997... 3 225 A 55-DP-TRA VIA XFMR 20
17 -- -- -- 0 VA 0 VA -- -- -- 18
15 -- -- -- 0 VA 0 VA -- -- -- 16
13 PANEL 55-2C1 100 A 3 0 VA 0 VA 3 100 A PANEL 55-3C3 14
11 -- -- -- 0 VA 0 VA -- -- -- 12
9 -- -- -- 0 VA 0 VA -- -- -- 10
7 PANEL 55-1C3 100 A 3 0 VA 0 VA 3 100 A PANEL 55-3C1 8
5 -- -- -- 0 VA 0 VA -- -- -- 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 PANEL 55-1C1 100 A 3 0 VA 0 VA 3 100 A PANEL 55-2C3 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Recessed Wires: 4 Mains: 400A / 3P
Supply From: Phases: 3 Mains Rating: 400 A
Location: Volts: 480/277 Wye A.I.C. Rating: 42k
Branch Panel: DP 55-C1
Notes:
Total Est. Demand: 135 A
Total Conn.: 226 A
Lighting 1414 VA 100.00% 1414 VA Total Est. Demand: 48734 VA
Receptacle 75040 VA 56.66% 42520 VA Total Conn. Load: 81254 VA
Other 4800 VA 100.00% 4800 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 252 A 221 A 208 A
Total Load: 29973 VA 26347 VA 24933 VA
41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42
39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40
37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38
35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36
33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34
31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 -- -- -- 3533... 0 VA 1 20 A SPARE 24
21 -- -- -- 3735... 0 VA 1 20 A SPARE 22
19 PANEL 55-3C149A 100 A 3 4253... 0 VA 1 20 A SPARE 20
17 -- -- -- 3533... 3533... -- -- -- 18
15 -- -- -- 3735... 3735... -- -- -- 16
13 PANEL 55-2C144A 100 A 3 4253... 4253... 3 100 A PANEL 55-3A120A 14
11 -- -- -- 3533... 3533... -- -- -- 12
9 -- -- -- 3735... 3735... -- -- -- 10
7 PANEL 55-1C132A 100 A 3 4253... 4253... 3 100 A PANEL 55-2A136A 8
5 -- -- -- 3533... 3533... -- -- -- 6
3 -- -- -- 3735... 3735... -- -- -- 4
1 PANEL 55-1A129A 100 A 3 4253... 4253... 3 100 A PANEL 55-1B104A 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Recessed Wires: 4 Mains: 400A / 3P
Supply From: DP/55-C1 Phases: 3 Mains Rating: 400 A
Location: MECH 1M 1a Volts: 120/208 Wye A.I.C. Rating: 65k
Branch Panel: 55-DP-TRA
Revisions: Date:
Notes:
Total Est. Demand: 131 A
Total Conn.: 222 A
Total Est. Demand: 47320 VA
Receptacle 75040 VA 56.66% 42520 VA Total Conn. Load: 79840 VA
Other 4800 VA 100.00% 4800 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 250 A 208 A 208 A
Total Load: 29973 VA 24933 VA 24933 VA
11 -- -- -- 0 VA 2493... -- -- -- 12
9 -- -- -- 0 VA 2493... -- -- -- 10
7 55-1N3-1 200 A 3 0 VA 2997... 3 400 A 55-DP-TRB 8
5 -- -- -- 0 VA 0 VA -- -- -- 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 55-3N3-1 200 A 3 0 VA 0 VA 3 150 A 55-2N3-1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: SURFACE Wires: 4 Mains: LUGS ONLY
Supply From: TR-55-1N3 Phases: 3 Mains Rating: 500 A
Location: Volts: 120/208 Wye A.I.C. Rating: 22k
Branch Panel: DP/55-1N3
Notes:
Total Est. Demand: 131 A
Total Conn.: 222 A
Total Est. Demand: 47320 VA
Receptacle 75040 VA 56.66% 42520 VA Total Conn. Load: 79840 VA
Other 4800 VA 100.00% 4800 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 250 A 208 A 208 A
Total Load: 29973 VA 24933 VA 24933 VA
41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42
39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40
37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38
35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36
33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34
31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 -- -- -- 3533... 0 VA 1 20 A SPARE 24
21 -- -- -- 3533... 0 VA 1 20 A SPARE 22
19 PANEL 55-3C149B 100 A 3 4253... 0 VA 1 20 A SPARE 20
17 -- -- -- 3533... 3533... -- -- -- 18
15 -- -- -- 3533... 3533... -- -- -- 16
13 PANEL 55-2C144B 100 A 3 4253... 4253... 3 100 A PANEL 55-3A120B 14
11 -- -- -- 3533... 3533... -- -- -- 12
9 -- -- -- 3533... 3533... -- -- -- 10
7 PANEL 55-1C132B 100 A 3 4253... 4253... 3 100 A PANEL 55-2A136B 8
5 -- -- -- 3533... 3533... -- -- -- 6
3 -- -- -- 3533... 3533... -- -- -- 4
1 PANEL 55-1A129B 100 A 3 4253... 4253... 3 100 A PANEL 55-1B104B 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Recessed Wires: 4 Mains: 400A / 3P
Supply From: DP/55-1N3 Phases: 3 Mains Rating: 400 A
Location: ELEC 1C 111 Volts: 120/208 Wye A.I.C. Rating: 22k
Branch Panel: 55-DP-TRB
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY
AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND
SOURCE-B PANEL SCHEDULES.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
56EP701
BLDG 56 - ELECTRICAL
SCHEDULESSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM - INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM LLT/JPS
CONSTRUCTION
DOCUMENTS
Revisions: Date:
Notes:
Total Est. Demand: 84 A
Total Conn.: 130 A
Lighting 808 VA 100.00% 808 VA Total Est. Demand: 30248 VA
Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 46688 VA
Other 3000 VA 100.00% 3000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 136 A 123 A 133 A
Total Load: 16177 VA 14737 VA 15773 VA
41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42
39 SPARE 20 A 1 0 VA 100 VA -- -- -- 40
37 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 38
35 SPARE 20 A 1 0 VA 100 VA -- -- -- 36
33 SPARE 20 A 1 0 VA 100 VA -- -- -- 34
31 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 -- -- -- 3533... 0 VA 1 20 A SPARE 16
13 -- -- -- 3735... 0 VA 1 20 A SPARE 14
11 PANEL 56-2A122A 100 A 3 4253... 3533... -- -- -- 12
9 -- -- -- 3533... 3735... -- -- -- 10
7 -- -- -- 3735... 4253... 3 100 A PANEL 56-3A122A 8
5 PANEL 56-BA105A 100 A 3 4253... 3533... -- -- -- 6
3 SPARE 20 A 1 0 VA 3735... -- -- -- 4
1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 56-1A109A 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: SURFACE Wires: 4 Mains: 225A / 3P
Supply From: DP/56C Phases: 3 Mains Rating: 225 A
Location: BB 129 Volts: 120/208 Wye A.I.C. Rating: 65k
Branch Panel: 56-DP-TRA
GENERAL NOTES
KEY NOTES
REMOVE EXISTING SPARE CIRCUIT BREAKER AND INSTALL NEW CIRCUIT
BREAKER TO SUPPLY NEW LOAD.
EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.
REFERENCE ONE-LINE DIAGRAM ON SHEET 56EP601 FOR ADDITIONAL
INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.
THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT
PROVIDED TO SHOW OVERALL LOAD OF PANEL.
Notes:
Total Est. Demand: 84 A
Total Conn.: 130 A
Lighting 808 VA 100.00% 808 VA Total Est. Demand: 30248 VA
Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 46688 VA
Other 3000 VA 100.00% 3000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 136 A 123 A 133 A
Total Load: 16177 VA 14737 VA 15773 VA
17 -- -- -- 0 VA 1577... -- -- -- 18
15 -- -- -- 0 VA 1473... -- -- -- 16
13 PANEL 56-3CR 60 A 3 0 VA 1617... 3 225 A 56-DP-TRA 14
11 -- -- -- 0 VA 0 VA -- -- -- 12
9 -- -- -- 0 VA 0 VA -- -- -- 10
7 PANEL 56-1CR 60 A 3 0 VA 0 VA 3 60 A PANEL 56-2CR 8
5 -- -- -- 0 VA 0 VA -- -- -- 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 PANEL 56-CR 60 A 3 0 VA 0 VA 3 60 A PANEL 56-SP1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Recessed Wires: 4 Mains: 1600A / 3P
Supply From: TR-56-C Phases: 3 Mains Rating: 1600 A
Location: EMERG ELEC BB 129 Volts: 120/208 Wye A.I.C. Rating: 42k
Branch Panel: DP 56-C
Notes:
Total Est. Demand: 80 A
Total Conn.: 126 A
Total Est. Demand: 28840 VA
Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 45280 VA
Other 2400 VA 100.00% 2400 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 132 A 118 A 132 A
Total Load: 15573 VA 14133 VA 15573 VA
41 SPARE 20 A 1 0 VA 0 VA -- -- -- 42
39 SPARE 20 A 1 0 VA 0 VA -- -- -- 40
37 SPARE 20 A 1 0 VA 0 VA 3 20 A SPD 38
35 SPARE 20 A 1 0 VA 0 VA -- -- -- 36
33 SPARE 20 A 1 0 VA 0 VA -- -- -- 34
31 SPARE 20 A 1 0 VA 0 VA 3 20 A DIGITAL POWER METER 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 -- -- -- 3533... 0 VA 1 20 A SPARE 16
13 -- -- -- 3533... 0 VA 1 20 A SPARE 14
11 PANEL 56-2A122B 100 A 3 4253... 3533... -- -- -- 12
9 -- -- -- 3533... 3533... -- -- -- 10
7 -- -- -- 3533... 4253... 3 100 A PANEL 56-3A122B 8
5 PANEL 56-BA105B 100 A 3 4253... 3533... -- -- -- 6
3 SPARE 20 A 1 0 VA 3533... -- -- -- 4
1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 56-1A109B 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: SURFACE Wires: 4 Mains: 225A / 3P
Supply From: TR-56-DP-TRAB Phases: 3 Mains Rating: 225 A
Location: BB 129 Volts: 120/208 Wye A.I.C. Rating: 65k
Branch Panel: 56-DP-TRB
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY
AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND
SOURCE-B PANEL SCHEDULES.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
57EP701
BLDG 57 - ELECTRICAL
SCHEDULESSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM LLT/JPS
CONSTRUCTION
DOCUMENTS
Revisions: Date:
GENERAL NOTES
KEY NOTES
Notes:
Total Est. Demand: 34 A
Total Conn.: 36 A
Lighting 202 VA 100.00% 202 VA Total Est. Demand: 12122 VA
Receptacle 11440 VA 93.71% 10720 VA Total Conn. Load: 12842 VA
Other 1200 VA 100.00% 1200 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 43 A 33 A 31 A
Total Load: 5173 VA 3935 VA 3733 VA
41 -- -- -- 0 VA 200 VA -- -- -- 42
39 -- -- -- 0 VA 200 VA -- -- -- 40
37 IT PANEL 57-1T4-1 - 1B 140 60 A 3 0 VA 920 VA 3 100 A 57-1B139B 38
35 SPARE 20 A 1 0 VA 3533... -- -- -- 36
33 SPARE 20 A 1 0 VA 3735... -- -- -- 34
31 SPARE 20 A 1 0 VA 4253... 3 100 A 57-1B139A 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28
25 RESERVED FOR DDC SYSTEM 20 A 1 0 VA 0 VA 1 20 A SPARE 26
23 RESERVED FOR DDC SYSTEM 20 A 1 0 VA 0 VA -- -- -- 24
21 RECEPTACLES - ROOF 20 A 1 0 VA 0 VA 2 20 A HEATING WATER PUMP 57-HWP-3 22
19 RECEPTACLES - MEZZANINE 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - MEZZANINE 20
17 RECEPTACLES - C1-16,C1-18 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 138,143 18
15 57-FCU-7 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 DOOR HARDWARE 20 A 1 0 VA 0 VA 1 20 A FIRE ALARM EQPT - 1B 137 14
11 MICROWAVE - 1B 138c 20 A 1 0 VA 0 VA 1 20 A EWC - 1B 138g 12
9 SPARE 20 A 1 0 VA 0 VA 1 20 A COFFEE - 1B 138c 10
7 REFRIGERATOR - 1B 138c 20 A 1 0 VA 0 VA 1 20 A RECEPTACLE - 1B 138c 8
5 SINK - 1B 138a 20 A 1 0 VA 0 VA 1 20 A SINK - 1B 138b 6
3 RECEPTACLES - 1B 138c,g 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 138a,b 4
1 RECEPTACLES - 1B 136 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 136 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 150A / 3P
Supply From: TR 57-1N4 Phases: 3 Mains Rating: 225 A
Location: ELEC 1B 137 Volts: 120/208 Wye A.I.C. Rating: 10k
Branch Panel: 57-1N4
Notes:
Total Est. Demand: 34 A
Total Conn.: 36 A
Lighting 202 VA 100.00% 202 VA Total Est. Demand: 12122 VA
Receptacle 11440 VA 93.71% 10720 VA Total Conn. Load: 12842 VA
Other 1200 VA 100.00% 1200 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 43 A 33 A 31 A
Total Load: 5173 VA 3935 VA 3733 VA
83 -- -- -- 200 VA 0 VA -- -- -- 84
81 -- -- -- 200 VA 0 VA -- -- -- 82
79 57-1B120B 100 A 3 920 VA 0 VA 3 60 A IT PANEL 571T6-2 - 1B 121 80
77 -- -- -- 3533... 0 VA 1 20 A SPARE 78
75 -- -- -- 3735... 0 VA 1 20 A SPARE 76
73 57-1B120A 100 A 3 4253... 0 VA 1 20 A SPARE 74
71 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 72
69 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 70
67 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 68
65 COUNTER RECEPT 1B 106A 20 A 1 0 VA 0 VA 1 20 A SPARE 66
63 WALK-THRU METAL DET C1-1 20 A 1 0 VA 0 VA 1 20 A HEAT TRACE - ROOF DRAWIN 64
61 57-UH-4 20 A 1 0 VA 0 VA 1 20 A 57-UH-5 62
59 57-FCU-3 20 A 1 0 VA 0 VA 1 20 A 57-FCU-4 60
57 DOOR HARDWARE 20 A 1 0 VA 0 VA 1 20 A FIRE ALARM EQPT - 1B 117 58
55 RESERVED FOR DDC SYSTEM 20 A 1 0 VA 0 VA 1 20 A DOOR HARDWARE 56
53 RESERVED FOR DDC SYSTEM 20 A 1 0 VA 0 VA 1 20 A TRACK HOIST - 1A 100a 54
51 EWC - C1-12 20 A 1 0 VA 0 VA 1 20 A PLOTTER - 1B 125 52
49 SHRED IT - 1B 106a 20 A 1 0 VA 0 VA 1 20 A VENDING - 1B 122 50
47 COPIER - 1B 106a 20 A 1 0 VA 0 VA 1 20 A TV - 1B 100 48
45 OVERHEAD DOOR - 1A 100 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - C1-8 46
43 RECEPTACLE - EAST EXTERIOR 20 A 1 0 VA 0 VA 1 20 A VENDING - 1B 122 44
41 COFFEE - 1B 122 20 A 1 0 VA 0 VA 1 20 A VENDING MACH - 1B 122 42
39 TOASTER - 1B 122 20 A 1 0 VA 0 VA 1 20 A MICROWAVE - 1B 122 40
37 RECEPTACLES - 1B 122 20 A 1 0 VA 0 VA 1 20 A RECEPTACLE - 1B 122 38
35 RECEPTACLES - 1B 125a 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 125 36
33 RECEPTACLES - 1B 123,124 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 125a 34
31 RECEPTACLES - C1-12 20 A 1 0 VA 0 VA 1 20 A SINKS - 1B 123,124 32
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 SPARE 20 A 1 0 VA 0 VA 1 20 A DOOR POWER 28
25 RECEPTACLES - 1B 118 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 119 26
23 RECEPTACLES - C1-3,4 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - C1-3,4,31 24
21 RECEPTACLES - 1B 106 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 106 22
19 RECEPTACLES - 1B 100 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - C1-4,31 20
17 RECEPTACLES - 1B 116 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - C1-4,5 18
15 RECEPTACLES - 1B 105 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 115 16
13 RECEPTACLES - 1B 103 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 104 14
11 RECEPTACLES - 1B 101 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 102 12
9 RECEPTACLES - 1B 108 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 107 10
7 RECEPTACLES - 1B 110 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 109 8
5 RECEPTACLES - 1B 112 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 111 6
3 RECEPTACLES - 1B 114 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 113 4
1 RECEPTACLES - C1-1,2,31 20 A 1 0 VA 0 VA 1 20 A RECEPTACLES - 1B 117 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 225A / 3P
Supply From: TR 57-1N4 Phases: 3 Mains Rating: 225 A
Location: ELEC 1B 117 Volts: 120/208 Wye A.I.C. Rating: 10k
Branch Panel: 57-1N6
SECTION 1
SECTION 2
1 EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.
REFERENCE ONELINE DIAGRAM ON SHEET 57EP601 FOR ADDITIONAL
INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.
THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT
PROVIDED TO SHOW OVERALL LOAD OF PANEL.
2 REMOVE EXISTING SPARE CIRCUIT BREAKERS AND INSTALL NEW CIRCUIT
BREAKER TO SUPPLY NEW LOAD.
3 REMOVE EXISTING CIRCUIT BREAKER FEEDING EXISTING PANEL 57-1T6-1.
INSTALL NEW CIRCUIT BREAKER TO SUPPLY NEW LOAD.
4 REMOVE EXISTING CIRCUIT BREAKER FEEDING EXISTING PANEL 57-1T4-2.
INSTALL NEW CIRCUIT BREAKER TO SUPPLY NEW LOAD.
SECTION 1
SECTION 2
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY
AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND
SOURCE-B PANEL SCHEDULES.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
58EP701
BLDG 58 - ELECTRICAL
SCHEDULESSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
JEFFERSON BARRACKS - 1 JEFFERSON BARRACKS
DRIVE - ST. LOUIS, MO 63125
657-21-701JB
03/31/2022 LRL/WNM LLT/JPS
CONSTRUCTION
DOCUMENTS
Revisions: Date:
Notes:
Total Est. Demand: 34 A
Total Conn.: 36 A
Lighting 202 VA 100.00% 202 VA Total Est. Demand: 12122 VA
Receptacle 11440 VA 93.71% 10720 VA Total Conn. Load: 12842 VA
Other 1200 VA 100.00% 1200 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 43 A 33 A 31 A
Total Load: 5173 VA 3935 VA 3733 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 -- -- -- -- 200 VA -- -- -- 30
27 -- -- -- -- 200 VA -- -- -- 28
25 SPACE -- 3 -- 920 VA 3 100 A PANEL 58-104B 26
23 -- -- -- 0 VA 3533... -- -- -- 24
21 -- -- -- 0 VA 3735... -- -- -- 22
19 SPD 60 A 3 0 VA 4253... 3 100 A PANEL 58-104A 20
17 -- -- -- 0 VA 0 VA -- -- -- 18
15 -- -- -- 0 VA 0 VA -- -- -- 16
13 PANEL 58P2 400 A 3 0 VA 0 VA 3 100 A PANEL 58P4 14
11 -- -- -- 0 VA 0 VA -- -- -- 12
9 -- -- -- 0 VA 0 VA -- -- -- 10
7 PANEL 58P1 225 A 3 0 VA 0 VA 3 225 A PANEL 58L2 8
5 -- -- -- 0 VA 0 VA -- -- -- 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 PANEL DP-1 400 A 3 0 VA 0 VA 3 225 A PANEL 58L1 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: LUGS ONLY
Supply From: Phases: 3 Mains Rating: 1000 A
Location: Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: MDP-58
GENERAL NOTES
KEY NOTES
INSTALL NEW CIRCUIT BREAKER TO SUPPLY NEW LOAD.
EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.
REFERENCE ONELINE DIAGRAM ON SHEET 58EP601 FOR ADDITIONAL
INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.
THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT
PROVIDED TO SHOW OVERALL LOAD OF PANEL.
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY
AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND
SOURCE-B PANEL SCHEDULES.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
60EP701
BLDG 60 AND 60T - ELECTRICAL
SCHEDULESSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM JGE
CONSTRUCTION
DOCUMENTS
Notes:
Total Est. Demand: 18 A
Total Conn.: 18 A
Total Est. Demand: 6320 VA
Total Conn. Load: 6320 VA
Receptacle 6320 VA 100.00% 6320 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 22 A 16 A 16 A
Total Load: 2587 VA 1867 VA 1867 VA
35 -- -- -- 0 VA 36
33 -- -- -- 0 VA 34
31 SPARE 400 A 3 0 VA 32
29 -- -- -- 0 VA 0 VA -- -- -- 30
27 -- -- -- 0 VA 0 VA -- -- -- 28
25 SPARE 100 A 3 0 VA 0 VA 3 400 A SPARE 26
23 -- -- -- 0 VA 1867... -- -- -- 24
21 -- -- -- 0 VA 1867... -- -- -- 22
19 SPARE 100 A 3 0 VA 2587... 3 100 A 60-102B 20
17 -- -- -- 0 VA 0 VA -- -- -- 18
15 -- -- -- 0 VA 0 VA -- -- -- 16
13 SPARE 100 A 3 0 VA 0 VA 3 100 A SPARE 14
11 -- -- -- 0 VA 0 VA -- -- -- 12
9 -- -- -- 0 VA 0 VA -- -- -- 10
7 SPARE 20 A 3 0 VA 0 VA 3 100 A SPARE 8
5 -- -- -- 0 VA 0 VA -- -- -- 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 90-ATS 90-1 400 A 3 0 VA 0 VA 3 800 A 90-ATS 90-2 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 1600
Supply From: 60-XF2-BLDG 60 Phases: 3 Mains Rating: 1600 A
Location: TRANSFORMER RM 119 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: MDP-60
GENERAL NOTES
KEY NOTES
UTILIZE EXISTING SPARE CIRCUIT BREAKER TO SUPPLY NEW LOAD.
PROVIDE NEW CIRCUIT BREAKER IN EXISTING SPACE TO SUPPLY NEW LOAD.
EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.
REFERENCE ONELINE DIAGRAM ON SHEET 60EP601 FOR ADDITIONAL
INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.
THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT
PROVIDED TO SHOW OVERALL LOAD OF PANEL.
1. ALL CIRCUITS EXISTING UNLESS OTHERWISE NOTED.
2. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY AND
ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
3. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND SOURCE-B
PANEL SCHEDULES.
Revisions: Date:
Notes:
Total Est. Demand: 18 A
Total Conn.: 18 A
Total Est. Demand: 6522 VA
Lighting 202 VA 100.00% 202 VA Total Conn. Load: 6522 VA
Receptacle 6320 VA 100.00% 6320 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 22 A 17 A 16 A
Total Load: 2587 VA 2069 VA 1867 VA
29 -- -- -- 1867... 30
27 -- -- -- 2069... 28
25 60-102A 20 A 3 2587... 26
23 -- -- -- 0 VA 0 VA -- -- -- 24
21 -- -- -- 0 VA 0 VA -- -- -- 22
19 60-B1 225 A 3 0 VA 0 VA 3 100 A P4A 20
17 -- -- -- 0 VA 0 VA -- -- -- 18
15 -- -- -- 0 VA 0 VA -- -- -- 16
13 EM LIGHTS 100 A 3 0 VA 0 VA 3 400 A MDP-60T 14
11 -- -- -- 0 VA 0 VA -- -- -- 12
9 -- -- -- 0 VA 0 VA -- -- -- 10
7 GB BLDG 90 225 A 3 0 VA 0 VA 3 100 A EXHAUST HOODS 8
5 -- -- -- 0 VA 0 VA -- -- -- 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 PNL-B 400 A 3 0 VA 0 VA 3 400 A 60-P2 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 800A/3P
Supply From: 90-ATS 90-2 Phases: 3 Mains Rating: 1200 A
Location: Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: DP-60EM
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
75EP701
BLDG 75 - ELECTRICAL
SCHEDULESSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL./WNM LLT/JPS
CONSTRUCTION
DOCUMENTS
Revisions: Date:
KEY NOTES
GENERAL NOTES
Notes:
Total Est. Demand: 49 A
Total Conn.: 65 A
Lighting 202 VA 100.00% 202 VA Total Est. Demand: 17722 VA
Receptacle 21440 VA 73.32% 15720 VA Total Conn. Load: 23442 VA
Other 1800 VA 100.00% 1800 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 73 A 62 A 61 A
Total Load: 8707 VA 7469 VA 7267 VA
29 SPARE 20 A 1 0 VA 100 VA -- -- -- 30
27 SPARE 20 A 1 0 VA 100 VA -- -- -- 28
25 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 26
23 SPARE 20 A 1 0 VA 100 VA -- -- -- 24
21 SPARE 20 A 1 0 VA 100 VA -- -- -- 22
19 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14
11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12
9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10
7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8
5 -- -- -- 3533... 3533... -- -- -- 6
3 -- -- -- 3735... 3533... -- -- -- 4
1 PANEL 75-1B105A 100 A 3 4253... 4253... 3 100 A PANEL 75-1B105B 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 200A / 3P
Supply From: TR 75N Phases: 3 Mains Rating: 200 A
Location: BOILER BAY 1A 101 Volts: 120/208 Wye A.I.C. Rating: 22k
Branch Panel: 75-DP-TRAB 1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY
AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND
SOURCE-B PANEL SCHEDULES.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EP701
TYPICAL ELECTRICAL SCHEDULES
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON
BARRACKS MO
657-21-701JB
03/31/2022 LRL/WNM WNM
CONSTRUCTION
DOCUMENTS
Revisions: Date:
Notes:
Total Est. Demand: 30 A
Lighting 202 VA 100.00% 202 VA Total Conn.: 28 A
Receptacle 720 VA 100.00% 720 VA Total Est. Demand: 10942 VA
Other 5600 VA 100.00% 5600 VA Total Conn. Load: 10058 VA
Motor 3536 VA 125.00% 4420 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 38 A 17 A 32 A
Total Load: 4355 VA 2069 VA 3635 VA
29 SPARE 20 A 1 0 VA 100 VA -- -- -- 30
27 SPARE 20 A 1 0 VA 100 VA -- -- -- 28
25 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 26
23 SPARE 20 A 1 0 VA 100 VA -- -- -- 24
21 SPARE 20 A 1 0 VA 100 VA -- -- -- 22
19 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14
11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12
9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10
7 SPARE 20 A 1 0 VA 1768... -- -- -- 8
5 -- -- -- 1667... 1768... 2 20 A DUCTLESS SPLIT COOLING UNIT 6
3 -- -- -- 1667... 202 VA 1 20 A LIGHTING - TR ROOM 4
1 SERVER RACK RACEPTACLE 20 A 3 1667... 720 VA 1 20 A RECEPTACLES - TR ROOM 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 100A / 3P
Supply From: SEE PANEL SCHEDULE NOTE Phases: 3 Mains Rating: 100 A
Location: SEE PANEL SCHEDULE NOTE Volts: 120/208 Wye A.I.C. Rating: 22k
Branch Panel: SOURCE A POWER TR PANEL, TYPICAL - TYPE 1
Notes:
Total Est. Demand: 18 A
Total Conn.: 18 A
Total Est. Demand: 6320 VA
Receptacle 720 VA 100.00% 720 VA Total Conn. Load: 6320 VA
Other 5600 VA 100.00% 5600 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 22 A 16 A 16 A
Total Load: 2587 VA 1867 VA 1867 VA
29 SPARE 20 A 1 0 VA 100 VA -- -- -- 30
27 SPARE 20 A 1 0 VA 100 VA -- -- -- 28
25 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 26
23 SPARE 20 A 1 0 VA 100 VA -- -- -- 24
21 SPARE 20 A 1 0 VA 100 VA -- -- -- 22
19 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14
11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12
9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10
7 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 8
5 -- -- -- 1667... 0 VA 1 20 A SPARE 6
3 -- -- -- 1667... 0 VA 1 20 A SPARE 4
1 SERVER RACK RECEPTACLE 20 A 3 1667... 720 VA 1 20 A RECEPTACLES - TR ROOM 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 100A / 3P
Supply From: SEE PANEL SCHEDULE NOTE Phases: 3 Mains Rating: 100 A
Location: SEE PANEL SCHEDULE NOTE Volts: 120/208 Wye A.I.C. Rating: 22k
Branch Panel: SOURCE B POWER TR PANEL, TYPICAL - TYPE 1
Notes:
Total Est. Demand: 44 A
Lighting 202 VA 100.00% 202 VA Total Conn.: 42 A
Receptacle 720 VA 100.00% 720 VA Total Est. Demand: 15942 VA
Other 10600 VA 100.00% 10600 VA Total Conn. Load: 15058 VA
Motor 3536 VA 125.00% 4420 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 52 A 31 A 46 A
Total Load: 6021 VA 3736 VA 5301 VA
29 SPARE 20 A 1 0 VA 100 VA -- -- -- 30
27 SPARE 20 A 1 0 VA 100 VA -- -- -- 28
25 SPARE 20 A 1 0 VA 100 VA 3 20 A SPD 26
23 SPARE 20 A 1 0 VA 100 VA -- -- -- 24
21 SPARE 20 A 1 0 VA 100 VA -- -- -- 22
19 SPARE 20 A 1 0 VA 100 VA 3 20 A DIGITAL POWER METER 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14
11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12
9 SPARE 20 A 1 0 VA 0 VA 1 20 A…
This is the start of the file's text. The full file is on GovTribe.