Attachment 32 - Drawings Part-31.pdf
PDF 13 MB Posted
- Attached to
- Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks Federal contract opportunity
- Solicitation number
- 36C77623R0009
About this file
This solicitation seeks a general contractor to provide infrastructure upgrades at the St. Louis Jefferson Barracks VA Medical Center. The scope of work includes electrical panel upgrades and power systems work, building management system integration, HVAC assessments and upgrades, facility renovation and construction, data center upgrades, communication infrastructure installation, physical security improvements, fiber optic network assessments and upgrades across multiple campus buildings. The opportunity is identified as solicitation number 36C77623R0009 issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. Services required include electrical, HVAC, construction, communications and security systems at various medical center buildings.
View the file
Other files for this federal contract opportunity
Show all 50
Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W W
C
5.5
E
TR
1A 109
78 SF
TELEPHONE
TERMINAL
BOARD
TYP.
5.5
E
DATA RACK, TYP.
5.5
E
TR
1A 109
78 SF
TELEPHONE
TERMINAL
BOARD
5.5
E
DATA
RACK,
TYP.ET502
B-SIDE:
TO TRs 1A109, 2A122, AND 3A122
FROM MCR BB102,
FROM FLR 00 TO 01
B-SIDE:
CONTINUE TO TR 2A122;
SEE SHEET 56ET101
A-SIDE:
TO TR 1A109
FROM BLDG
56 BB 102
1A 109
TR
1A 109
78 SF
TYP
5.5
E
DATA
RACK,
TYP.ET502
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR
SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED
CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH
EQUIPMENT TO BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE,
UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE
UPGRADED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY
VACATED BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO
ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION
OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY
INDICATED.
7. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT 6A
CABLING FROM EACH WAO (WORK AREA OUTLET) TO ITS RESPECTIVE TR.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND
INSTALLATION OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP
MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO
ARCHITECTURAL DRAWINGS FOR PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
12. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS
OWN RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
13. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
14. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
AREA OF WORK
KEY PLAN
1/4" = 1'-0"56ET101
1 RM 1A109 - DEMOLITION FLOOR PLAN
1/4" = 1'-0"56ET101
2 RM 1A109 - TELECOMMUNICATIONS PLAN
0' 2' 4' 8' 0' 2' 4' 8'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 56ET401
BLDG 56 - FLOOR 1 - ENLARGED
TELECOMMUNICATIONS PLANS 56
LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
03/31/2022
Revisions: Date:
GENERAL NOTES
KEY NOTES
1/4" = 1'-0"56ET101
3 RM 1A109 - OVERHEAD PLAN LEVEL 1
0' 2' 4' 8'
4 NOT USED
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SLEEVES
SHALL BE HILTI QUICK RELEASE SLEEVES, OR REVIEWED EQUAL. REFERENCE
DETAIL '2' ON SHEET ET503 FOR ADDITIONAL INFORMATION.
ALL BACKBONE CABLING ROUTES ARE
DIAGRAMMATICAL; CONTRACTOR SHALL ENSURE
A-SIDE AND B-SIDE ROUTING IS AS DIVERSE AS
PRACTICAL. REFERENCE COMMUNICATIONS
DRAWINGS FOR ALL REQUIRED FIBER-OPTIC
CABLING.
W
C
W
2A 122
5.5
F
TR
2A 122
76 SF
DATA RACK
TYP.
TELEPHONE
TERMINAL
BOARD
5.5
TYP
F
5.5
F
TR
2A 122
76 SF
TELEPHONE
TERMINAL
BOARD
5.5
DATA
TACK,
TYP.
ET502
B-SIDE:
CONTINUE TO MCR
BB102; SEE SHEET
56ET102
F
A-SIDE:
TO TR 2A122 FROM
BLDG 56 BB 102
5.5
F
5.2
TR
2A 122
76 SF
TYP
5.5
DATA
TACK,
TYP.
ET502
F
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR
SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED
CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH
EQUIPMENT TO BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE,
UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE
UPGRADED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY
VACATED BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO
ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION
OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY
INDICATED.
7. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT 6A
CABLING FROM EACH WAO (WORK AREA OUTLET) TO ITS RESPECTIVE TR.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND
INSTALLATION OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP
MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO
ARCHITECTURAL DRAWINGS FOR PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
12. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS
OWN RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
13. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
14. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
AREA OF WORK
1/4" = 1'-0"56ET102
1 RM 2A122 - DEMOLITION FLOOR PLAN
1/4" = 1'-0"56ET102
2 RM 2A122 - TELECOMMUNICATIONS PLAN
0' 2' 4' 8' 0' 2' 4' 8'
KEY PLAN
GENERAL NOTES
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 56ET402
BLDG 56 - FLOOR 2 - ENLARGED
TELECOMMUNICATIONS PLANS 56
LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
03/31/2022
Revisions: Date:
1/4" = 1'-0"56ET102
3 RM 2A122 - OVERHEAD PLAN LEVEL 1
0' 2' 4' 8'
4 NOT USED
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
ALL BACKBONE CABLING ROUTES ARE
DIAGRAMMATICAL; CONTRACTOR SHALL ENSURE
A-SIDE AND B-SIDE ROUTING IS AS DIVERSE AS
PRACTICAL. REFERENCE COMMUNICATIONS
DRAWINGS FOR ALL REQUIRED FIBER-OPTIC
CABLING.
EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SLEEVES
SHALL BE HILTI QUICK RELEASE SLEEVES, OR REVIEWED EQUAL. REFERENCE
DETAIL '2' ON SHEET ET503 FOR ADDITIONAL INFORMATION.
W W
C
5.5
E
TR
3A 122
76 SF
COMBINER & SPLITTER
FIBER OPTIC
5.5
E
DATA RACK, TYP.
TYP
TELEPHONE
TERMINAL
BOARD
5.5
E
TR
3A 122
76 SF
COMBINER & SPLITTER
FIBER OPTIC
5.5
E
TELEPHONE
TERMINAL
BOARD
DATA
RACK,
TYP.ET502
A-SIDE:
TO TR 3A122 FROM
BLDG 56 BB102
B-SIDE:
TO TR 3A122 FROM
MCR BB102, FROM
FLR 02 TO 03
2A 122
TR
3A 122
76 SF
TYP
5.5
E
DATA
RACK,
TYP.ET502
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR
SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED
CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH
EQUIPMENT TO BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE,
UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE
UPGRADED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY
VACATED BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO
ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION
OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY
INDICATED.
7. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT 6A
CABLING FROM EACH WAO (WORK AREA OUTLET) TO ITS RESPECTIVE TR.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND
INSTALLATION OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP
MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO
ARCHITECTURAL DRAWINGS FOR PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
12. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS
OWN RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
13. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
14. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
AREA OF WORK
1/4" = 1'-0"56ET103
1 RM 3A122 - DEMOLITION FLOOR PLAN
1/4" = 1'-0"56ET103
2 RM 3A122 - TELECOMMUNICATIONS PLAN
0' 2' 4' 8'
KEY PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 56ET403
BLDG 56 - FLOOR 3 - ENLARGED
TELECOMMUNICATIONS PLANS 56
LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
03/31/2022
Revisions: Date:
GENERAL NOTES
KEY NOTES
1/4" = 1'-0"56ET103
3 RM 3A122 - OVERHEAD PLAN LEVEL 1
0' 2' 4' 8'
0' 2' 4' 8'
4 NOT USED
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SLEEVES
SHALL BE HILTI QUICK RELEASE SLEEVES, OR REVIEWED EQUAL. REFERENCE
DETAIL '2' ON SHEET ET503 FOR ADDITIONAL INFORMATION.
ALL BACKBONE CABLING ROUTES ARE
DIAGRAMMATICAL; CONTRACTOR SHALL ENSURE
A-SIDE AND B-SIDE ROUTING IS AS DIVERSE AS
PRACTICAL. REFERENCE COMMUNICATIONS
DRAWINGS FOR ALL REQUIRED FIBER-OPTIC
CABLING.
F E
C F
E C
FEC
FECFEC
FECFEC
FEC
F E
C F
E C
F E
C F
E C
FECFEC
FECFEC
F E
C F
E C
F E
C F
E C
FEC
FECFEC
F E
C F
E C
F E
C F
E C
FEC
FECFEC
FEC
F E
C F
E C
FEC
GFI
GFI
AE721B2
AE721
C7
F7
4 4 4
CR
W
0°180°
W
C
1B120
6 6.1
D.4
TYP
TELEPHONE
TERMINAL
BOARD
DATA RACK, TYP.
PANEL BOARD
TR
1B 120
81 SF
6 6.1
D.4
DATA
RACK,
TYP.
TR
1B 120
81 SF
TELEPHONE
TERMINAL
BOARD
PANEL BOARD
ET502
B-SIDE:
CONTINUE TO
SHEET 57ET101
A-SIDE:
TO TR 1B120 FROM
BLDG 01 GC12
6 6.1
D.4
TR
1B 120
81 SF
TYP
DATA
RACK,
TYP.
ET502
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR
SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED
CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH
EQUIPMENT TO BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE,
UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 5E AND BELOW SHALL BE
UPGRADED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY
VACATED BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO
ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION
OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY
INDICATED.
7. PROVIDE 1" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE CEILING SPACE FOR
ALL OUTLETS IDENTIFIED AS NEW.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND
INSTALLATION OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP
MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO
ARCHITECTURAL DRAWINGS FOR PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IF FIELD;
DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
12. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS
OWN RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
13. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
14. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
AREA OF WORK
3/8" = 1'-0"57ET101
1 RM 1B120 - DEMOLITION FLOOR PLAN
3/8" = 1'-0"57ET101
2 RM 1B120 - TELECOMMUNICATIONS PLAN
KEY PLAN
GENERAL NOTES
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 57ET401a
BLDG 57 - FLOOR 1 - ENLARGED
TELECOMMUNICATION PLANS 57
LRL/WNM JPS/LLT
CONSTRUCTION
DOCUMENTS
03/31/2022
Revisions: Date:
3/8" = 1'-0"57ET101
3 RM 1B120 - OVERHEAD PLAN LEVEL 1
0' 2' 4' 8'
EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND
CABLING SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SLEEVES
SHALL BE HILTI QUICK RELEASE SLEEVES, OR REVIEWED EQUAL. REFERENCE
DETAIL '2' ON SHEET ET503 FOR ADDITIONAL INFORMATION.
0' 2' 4' 8'
0' 2' 4' 8'
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
4 NOT USED
ALL BACKBONE CABLING ROUTES ARE
DIAGRAMMATICAL; CONTRACTOR SHALL
ENSURE A-SIDE AND B-SIDE ROUTING IS
AS DIVERSE AS PRACTICAL. REFERENCE
COMMUNICATIONS DRAWINGS FOR ALL
REQUIRED FIBER-OPTIC CABLING.
W
W W
W
C
180° W
W W
W
AE721B2
AE721
C7
F7
8.4
H
TR
1B 139
85 SF
TYP
DATA
RACK,
TYP.
ET502
8.4
H
TYP
TR
1B 139
85 SF
DATA
RACK,
TYP.
COMBINER &
SPLITTER FIBER
OPTIC
PANEL BOARD
TELEPHONE TERMINAL BOARD
8.4
H
TR
1B 139
85 SF
DATA
RACK,
TYP.
COMBINER &
SPLITTER FIBER
OPTIC
PANEL BOARD
TELEPHONE TERMINAL BOARD
ET502
SIDE B:
CONTINUE TO
SHEET 57ET101
A-SIDE:
TO TR 1B139 FROM
BLDG 01 GC12
1B139
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR
SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED
CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH
EQUIPMENT TO BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE,
UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 5E AND BELOW SHALL BE
UPGRADED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY
VACATED BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO
ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION
OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY
INDICATED.
7. PROVIDE 1" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE CEILING SPACE FOR
ALL OUTLETS IDENTIFIED AS NEW.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND
INSTALLATION OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP
MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO
ARCHITECTURAL DRAWINGS FOR PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IF FIELD;
DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
12. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS
OWN RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
13. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
14. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 57ET401b
BLDG 57 - FLOOR 1 - ENLARGED
TELECOMMUNICATION PLANS 57
LRL/WNM JPS/LLT
CONSTRUCTION
DOCUMENTS
03/31/2022
Revisions: Date:
3/8" = 1'-0"57ET101
3 RM 1B139 - OVERHEAD PLAN LEVEL 1
0' 2' 4' 8'
KEY PLAN
GENERAL NOTES
KEY NOTES
EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND
CABLING SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED.
SLEEVES SHALL BE HILTI QUICK RELEASE SLEEVES, OR REVIEWED EQUAL.
REFERENCE DETAIL '2' ON SHEET ET503 FOR ADDITIONAL INFORMATION.
3/8" = 1'-0"57ET101
1 RM 1B139 - DEMOLITION FLOOR PLAN
3/8" = 1'-0"57ET101
2 RM 1B139 - TELECOMMUNICATIONS PLAN
0' 2' 4' 8'
0' 2' 4' 8'
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
4 NOT USED
ALL BACKBONE CABLING ROUTES ARE
DIAGRAMMATICAL; CONTRACTOR SHALL
ENSURE A-SIDE AND B-SIDE ROUTING IS
AS DIVERSE AS PRACTICAL. REFERENCE
COMMUNICATIONS DRAWINGS FOR ALL
C
W
180°
RM 104
DC1
TR
117 SF
TYP
DC1
TR
117 SF
DATA RACK.
TYP. ET502
SIDE B:
CONTINUE TO
SHEET 58ET101
A-SIDE:
TO TR 104 FROM
BLDG 1 GC12
DC1
TR
117 SF
TYP
DATA RACK.
TYP. ET502
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR
SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED
CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH
EQUIPMENT TO BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE,
UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE
UPGRADED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY
VACATED BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO
ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION
OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY
INDICATED.
7. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT 6A
CABLING FROM EACH WAO (WORK AREA OUTLET) TO ITS RESPECTIVE TR.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND
INSTALLATION OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP
MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO
ARCHITECTURAL DRAWINGS FOR PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
12. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS
OWN RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
13. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
14. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
- AREA OF WORK
0' 1' 2' 4'
0' 1' 2' 4'
1/2" = 1'-0"58ET101
1 RM 104 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"58ET101
2 RM 104 - TELECOMMUNICATIONS PLAN
KEY PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 58ET401a
BLDG 58 - FLOOR 1 - ENLARGED
TELECOMMUNICATIONS PLANS 58
LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
03/31/2022
1/2" = 1'-0"58ET101
3 RM 104 - OVERHEAD PLAN LEVEL 1
0' 1' 2' 4'
Revisions: Date:
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
KEY NOTES
GENERAL NOTES
1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SLEEVES
SHALL BE HILTI QUICK RELEASE SLEEVES, OR REVIEWED EQUAL. REFERENCE
DETAIL '2' ON SHEET ET503 FOR ADDITIONAL INFORMATION.
4 NOT USED
PROJECT
NORTH
ALL BACKBONE CABLING ROUTES ARE
DIAGRAMMATICAL; CONTRACTOR SHALL
ENSURE A-SIDE AND B-SIDE ROUTING IS AS
DIVERSE AS PRACTICAL. REFERENCE
COMMUNICATIONS DRAWINGS FOR ALL
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
C1
TYP
DATA RACK, TYP1
TELECOM
ENTRANCE
TERMINAL
PANEL
TELEPHONE
TERMINAL
BOARD
TELECOM
PANEL
C1
TELECOM
66 SF
ENTRANCE
TERMINAL
PANEL
TELECOM
PANEL
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR
SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED
CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH
EQUIPMENT TO BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE,
UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE
UPGRADED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY
VACATED BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO
ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION
OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY
INDICATED.
7. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT 6A
CABLING FROM EACH WAO (WORK AREA OUTLET) TO ITS RESPECTIVE TR.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND
INSTALLATION OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP
MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO
ARCHITECTURAL DRAWINGS FOR PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
12. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS
OWN RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
13. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
14. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
- AREA OF WORK
RM 149
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 58ET401b
BLDG 58 - FLOOR 1 - ENLARGED
TELECOMMUNICATIONS PLANS 58
LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
03/31/2022
1/2" = 1'-0"58ET101
1 RM 149 - DEMOLITION FLOOR PLAN
Revisions: Date:
1/2" = 1'-0"58ET101
2 RM 149 - TELECOMMUNICATIONS PLAN
0' 1' 2' 4'
PROJECT
NORTH
0' 1' 2' 4'
PROJECT
NORTH
KEY PLAN
KEY NOTES
GENERAL NOTES
1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROJECT
NORTH
W
C
180°
W
GG
OI&T
101A
7 SF
WALL MOUNTED
DATA RACK
DOOR ACCESS PANEL
TELEPHONE
TERMINAL
BOARD
H
21.5
TR
54 SF
TELEPHONE
TERMINAL
BOARD
ACCESS DOOR
CONTROLLER
ACCESS POWER
CONTROLLER PANEL
FIBER OPTIC
PATCH PANEL
DATA RACK1
TR
54 SF
H
21.5
TELEPHONE
TERMINAL
BOARD
ACCESS DOOR
CONTROLLER
FABRIC OPTIC
PATCH PANEL
DATA
RACK ET502
SIDE B:
CONTINUE TO
SHEET 58ET101
A-SIDE:
TO TR 102 FROM
BLDG 1 GC12
- AREA OF WORK
101A
H
21.5
TYP
TR
54 SF
DATA
RACK ET502
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE
NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 5E AND BELOW SHALL BE UPGRADED
WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. PROVIDE 1" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE CEILING SPACE FOR ALL
OUTLETS IDENTIFIED AS NEW.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF
HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN
AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IF FIELD;
DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION. COORDINATE
WITH VA AS REQUIRED.
12. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL SYSTEMS.
WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN RACEWAY.
WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS CABLE
TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY, CABLE
TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO SEGREGATE
SYSTEMS FROM ONE ANOTHER.
13. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD
BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS
REQUIRED.
14. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY
OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
0' 1' 2' 4'0' 1' 2' 4'
1/2" = 1'-0"60ET101
1 RM 101A - DEMOLITION FLOOR PLAN
KEY PLAN
GENERAL NOTES
KEY NOTES
EXISTING EQUIPMENT TO BE DEMOLISHED ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SLEEVES
SHALL BE HILTI QUICK RELEASE SLEEVES, OR REVIEWED EQUAL.
REFERENCE DETAIL '2' ON SHEET ET503 FOR ADDITIONAL INFORMATION.
UTILIZE EXISTING PACS SECURITY HEAD END LOCATION FOR NEW OR RELOCATED
PACS SECURITY TR EQUIPMENT. UPGRADE OR MODIFY EXISTING HEAD END
LOCATION AS REQUIRED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL TR PACS
SECURITY SYSTEM. PROVIDE EQUIPMENT, RACEWAYS, AND CABLING AS REQUIRED.
COORDINATE WITH VA PRIOR TO CONSTRUCTION. CONTRACTOR SHALL VERIFY
EXACT HEAD END LOCATION AS REQUIRED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 60ET401
BLDG 60 - FLOOR 1 - ENLARGED
TELECOMMUNICATIONS PLANS 60
LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
03/31/2022
Revisions: Date:
1/2" = 1'-0"60ET101
2 RM 102 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"60ET101
3 RM 102 - TELECOMMUNICATION PLAN
0' 1' 2' 4'
1/2" = 1'-0"60ET101
4 RM 102 - OVERHEAD PLAN LEVEL 1
0' 1' 2' 4'
5 NOT USED
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
ALL BACKBONE CABLING ROUTES ARE
DIAGRAMMATICAL; CONTRACTOR
SHALL ENSURE A-SIDE AND B-SIDE
ROUTING IS AS DIVERSE AS
PRACTICAL. REFERENCE
COMMUNICATIONS DRAWINGS FOR ALL
REQUIRED FIBER-OPTIC CABLING.
W
C
W
- AREA OF WORK
TR
31 SF
WALL MOUNTED
DATA RACK
TYP TELEPHONE TERMINAL
BOARD
TELECOM
PANEL
FIRE
ALARM
PANEL
MDP - 60T
ACCESS POWER
CONTROLLER
PANEL
TR
31 SF
FIRE
ALARM
PANEL
TELECOM
PANEL
WALL MOUNTED
DATA RACK
TELEPHONE TERMINAL
BOARD
MDP - 60T
SIDE B:
CONTINUE TO
SHEET 60TET101
A-SIDE :
TO TR 3A122 FROM
BLDG 01 GC12
ACCESS POWER
CONTROLLER PANEL
TR
31 SF
TYP
WALL MOUNTED
DATA RACK
TELEPHONE
TERMINAL
BOARD
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR
SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED
CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH
EQUIPMENT TO BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE,
UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE
UPGRADED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY
VACATED BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO
ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION
OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY
INDICATED.
7. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT 6A
CABLING FROM EACH WAO (WORK AREA OUTLET) TO ITS RESPECTIVE TR.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND
INSTALLATION OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP
MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO
ARCHITECTURAL DRAWINGS FOR PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
12. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS
OWN RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
13. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
14. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
0' 1' 2' 4' 0' 1' 2' 4'1/2" = 1'-0"60TET101
1 RM 108 - DEMOLITION FLOOR PLAN
1/2" = 1'-0"60TET101
2 RM 108 - TELECOMMUNICATIONS PLAN
KEY PLAN
GENERAL NOTES
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO
REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT
SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE SHEET DETAIL
'1' ON SHEET ET503 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL
INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SLEEVES
SHALL BE HILTI QUICK RELEASE SLEEVES, OR REVIEWED EQUAL. REFERENCE
DETAIL '2' ON SHEET ET503 FOR ADDITIONAL INFORMATION.
REPLACE EXISTING FIBER DISTRIBUTION CABINET WITH NEW FIBER DISTRIBUTION
CABINET AND CASSETES AS REQUIRED. LEVITON ANGLED OPT-X UHDX WITH HDX
ENTERPRISES MTP CASSETTES, OR EQUAL.
UTILIZE EXISTING PACS SECURITY HEAD END LOCATION FOR NEW OR RELOCATED
PACS SECURITY TR EQUIPMENT. UPGRADE OR MODIFY EXISTING HEAD END
LOCATION AS REQUIRED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL TR
PACS SECURITY SYSTEM. PROVIDE EQUIPMENT, RACEWAYS, AND CABLING AS
REQUIRED. COORDINATE WITH VA PRIOR TO CONSTRUCTION. CONTRACTOR SHALL
VERIFY EXACT HEAD END LOCATION AS REQUIRED.
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 60TET401
BLDG 60T - FLOOR 1 - ENLARGED
TELECOMMUNICATIONS PLANS 60T
LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
03/31/2022
Revisions: Date:
1/2" = 1'-0"60TET101
3 RM 108 - OVERHEAD PLAN LEVEL 1
0' 1' 2' 4'
4 NOT USED
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
ALL BACKBONE CABLING ROUTES ARE
DIAGRAMMATICAL; CONTRACTOR SHALL
ENSURE A-SIDE AND B-SIDE ROUTING IS AS
DIVERSE AS PRACTICAL. REFERENCE
COMMUNICATIONS DRAWINGS FOR ALL
REQUIRED FIBER-OPTIC CABLING.
S
180°
W W
C
180°
1B105
- AREA OF WORK
54.5
TYP
DATA RACK, TYP 1
TR
1B 105
108 SF
FIRE ALARM
SPEAKER
TELEPHONE
TERMINAL BOARD
FD
54.5
DATA
RACK,
TYP.
ET502
1 TELEPHONE
TERMINAL BOARDTR
1B 105
108 SF
SIDE B:
CONTINUE
TO SHEET
75ET101
A-SIDE:
TO TR 1B105 FROM
BLDG 01 GC12
54.5
TR
1B 105
108 SF
TYP
DATA RACK,
TYP. ET502
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR
SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED
CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH
EQUIPMENT TO BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE,
UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 5E AND BELOW SHALL BE
UPGRADED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY
VACATED BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL
RACEWAYS TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION
OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY
INDICATED.
7. PROVIDE 1" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE CEILING SPACE FOR
ALL OUTLETS IDENTIFIED AS NEW.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND
INSTALLATION OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP
MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO
ARCHITECTURAL DRAWINGS FOR PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IF FIELD;
DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
12. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS
INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL
SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS
OWN RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL
SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;
ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS
REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
13. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED
PLYWOOD BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE
DRAWINGS AS REQUIRED.
14. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ACRHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
1/4" = 1'-0"75ET101
1 RM 1B105 - DEMOLITION FLOOR PLAN
1/4" = 1'-0"75ET101
2 RM 1B105 - TELECOMMUNICATIONS PLAN
KEY PLAN
GENERAL NOTES
KEY NOTES
1 EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED RACEWAYS AND CABLING
SHALL BE DEMOLISHED BACK TO SOURCE.
PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SLEEVES
SHALL BE HILTI QUICK RELEASE SLEEVES, OR REVIEWED EQUAL. REFERENCE DETAIL
'2' ON SHEET ET503 FOR ADDITIONAL INFORMATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 75ET401
BLDG 75 - FLOOR 1 - ENLARGED
TELECOMMUNICATIONS PLANS 75
LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
03/31/2022
0' 2' 4' 8'
1/4" = 1'-0"75ET101
3 RM 1B105 -OVERHEAD PLAN LEVEL 1
0' 2' 4' 8'
0' 2' 4' 8'
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
Revisions: Date:
4 NOT USED
ALL BACKBONE CABLING ROUTES ARE
DIAGRAMMATICAL; CONTRACTOR SHALL
ENSURE A-SIDE AND B-SIDE ROUTING IS
AS DIVERSE AS PRACTICAL. REFERENCE
COMMUNICATIONS DRAWINGS FOR ALL
TELECOMMUNICATIONS
EQUIPMENT BONDING
CONDUCTOR (TEBC) AWG
IRREVERSIBLE CRIMP
CONNECTOR, TYP.
CABLE TRAY BONDING
CONDUCTOR. TYPICAL AT
EACH SECTION
CONNECTION POINT
TO PRIMARY OR SECONDARY
BONDING BUSBAR
IRREVERSIBLE
COMPRESSION
CONNECTION
RACK BONDING
CONDUCTOR
(6 AWG)
TEBC
(TELECOMMUNICATIONS
EQUIPMENT BONDING
CONDUCTOR - 4 AWG)
RACK BONDING CONDUCTOR (6 AWG)
UNIT BONDING CONDUCTOR (6 AWG)
TOP-MOUNTED
RACK BONDING
BUSBAR
IRREVERSIBLE CRIMP
CONNECTOR, TYP.
GROUND TO PRIMARY
BONDING BUSBAR.
COORDINATE WITH VA
FOR EXACT
CONDUCTOR ROUTING
TWO-HOLE COMPRESSION LUGS (RACKS SHALL NOT
BE MODIFIED IF ONLY ONE-HOLE IS PROVIDED; USE
ONE-HOLE COMPRESSION LUGS IN THIS CASE)
TWO-HOLE
COMPRESSION LUGS (RACKS
SHALL NOT BE MODIFIED IF
ONLY ONE-HOLE IS PROVIDED;
USE ONE-HOLE COMPRESSION
LUGS IN THIS CASE)
RACK ISOLATION PADS
CABLE FROM SP AND CABLE
TO OTHER CAMPUS BUILDINGS
HOOK AND LOOP STRAPS
EVERY 12 INCHES.
CABLE TO WORK AREA OUTLETS (WAOs)
24-STRAND OM4 (A SIDE)
1 RU CABLE MANAGER
RESERVED FOR SERVICE
PROVIDER, DVRs, AND OTHER
TELECOMMUNICATIONS
EQUIPMENT.
CUBE - iT WALL MOUNT CABINET;
GEN 3; 48"H x 24"W x 30"D (1220 mm x 610 mm X 760 mm) ;
26U; #12 - 24 TAPPED RAILS;
TEMPERED GLASS DOOR;
GLACIER WHITE OR EQUIVALENT
FIBER PATCH PANEL FOR INCOMING
CIRCUITS
IF ISP: 24-STRAND OM4 PER SIDE
12-STRAND OS1 PER SIDE
IF OSP: 24-STRAND OS2 PER SIDE
ANALOG TELEPHONY PATCH
PANEL (IF REQUIRED)
PATCH PANELS TO WORK AREAS
PATCH PANELS TO WORK AREAS
(MAX 96 POSITIONS)
VA LAN SWITCH
VA LAN SWITCH
VA ROUTER (FOR NCA MDA ONLY)
SHELF FOR NON- RACKMOUNT EQUIPMENT
RACK MOUNT PDU. L5- 30 INPUT. NEMA 5-20
OUTPUT. 1 RU. TWO PER ENCLOSURE. ONE ENERGIZED
BY UPS. ONE ENERGIZED BY WALL OUTLET. (SHOWN
HERE FRONT FACING, BUT ARE TO BE INSTALLED ON
THE BACK RAIL.)
RACK MOUNT UPS. L5-30 INPUT.
L5-30 OUTPUT. CAPACITY NTE 2880 VA. 2 RU.
METERED. (APC SMX3000RMLV2U OR EQUIVALENT)
O U
T
IN
O
CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
12-STRAND OS1 (A SIDE)
UTP SURGE PROTECTOR
(IF REQUIRED)
2 RU CABLE MANAGER
2 RU CABLE MANAGER
2 RU CABLE MANAGER
1 RU CABLE MANAGER
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
24-STRAND OM4 (B-SIDE)
12-STRAND OS1 (B-SIDE)
BONDING CONDUCTOR TO
PANEL BOARD GROUND LUG (ACEG)
USE TWO-HOLE LUGS FOR
BONDING CONNECTOR
TELECOMMUNICATIONS
BONDING BUSBAR
BOND RBB TO CABINET LUG. AWG #6
BOND RBB TO EACH SWITCH
AND ROUTER CHASIS
BOND RBB TO TELECOMMUNICATIONS BONDING BUSBAR. AWG #6
RACK BONDING BUSBAR (RBB)
OTHER CONNECTIONS
AS REQUIRED
(BONDING CONDUIT,
CABLE TRAYS,
BUILDING STEEL, TO
THE PBB OR SBB,
ETC.)
CHATSWORTH PRODUCTS
#40158-012, OR APPROVED
EQUAL
MOUNTING BRACKETS
1/4" THICK
L= 12"
D
INSULATOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .