657-21-701JB - Addendum 1_03_24_23.pdf

PDF 6 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks Federal contract opportunity
Solicitation number
36C77623R0009
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This federal contract opportunity solicitation seeks a general contractor to provide infrastructure upgrades at the St. Louis Jefferson Barracks VA Medical Center. Work will include electrical panel upgrades and power systems work, building management system integration, HVAC assessments and upgrades, data center renovations, communications infrastructure installation including upgrading outlets and cables to Cat6a, physical security enhancements, fiber optic backbone assessment and upgrades both within and between buildings, and hazardous material abatement. The locations include Buildings 1-3, 3T, 18, 23-25, 51, 51T, 52-53, 53T, 55-58, 59-61, 75 and associated site work. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks, newest first.
File Type Posted
36C77623R0009 0005.pdf PDF
FOLLOW-UP Technical Questions - St. Louis 4-6-23.pdf PDF
329000-05-R1 Sod Certificate.pdf PDF
32 32 23 01R1 - Mechanically Stabilized Earth Wall System RESPONSE.pdf PDF
Technical Questions - FINAL - St. Louis 3-28-23.pdf PDF
329000-5 - Sod Certificate.pdf PDF
Attachment 43 - Construction Wage Rates - St. Louis 3-24-23.pdf PDF
36C77623R0009 0003.pdf PDF
36C77623R0009 0001.pdf PDF
Attachment 45 - Site Visit Instructions Updated 2-16-23.pdf PDF
Attachment 4 - Drawings Part-3.pdf PDF
Attachment 10 - Drawings Part-9.pdf PDF
Attachment 14 - Drawings Part-13.pdf PDF
Attachment 20 - Drawings Part-19.pdf PDF
Attachment 21 - Drawings Part-20.pdf PDF
Attachment 25 - Drawings Part-24.pdf PDF
Attachment 26 - Drawings Part-25.pdf PDF
Attachment 28 - Drawings Part-27.pdf PDF
Attachment 29 - Drawings Part-28.pdf PDF
Attachment 32 - Drawings Part-31.pdf PDF
Attachment 39 - ICRA ILSM Tool - MCM 001S-03 Att B.zip ZIP file
Attachment 1 - Specifications.pdf PDF
Attachment 5 - Drawings Part-4.pdf PDF
Attachment 6 - Drawings Part-5.pdf PDF
Attachment 9 - Drawings Part-8.pdf PDF
Attachment 16 - Drawings Part-15.pdf PDF
Attachment 22 - Drawings Part-21.pdf PDF
Attachment 24 - Drawings Part-23.pdf PDF
Attachment 36 - Envr. Report - Appendix B.pdf PDF
Attachment 41 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Attachment 44 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 2 - Drawings Part-1.pdf PDF
Attachment 3 - Drawings Part-2.pdf PDF
Attachment 8 - Drawings Part-7.pdf PDF
Attachment 15 - Drawings Part-14.pdf PDF
Attachment 17 - Drawings Part-16.pdf PDF
Attachment 19 - Drawings Part-18.pdf PDF
Attachment 23 - Drawings Part-22.pdf PDF
Attachment 27 - Drawings Part-26.pdf PDF
Attachment 30 - Drawings Part-29.pdf PDF
Attachment 33 - Drawings Part-32.pdf PDF
Attachment 34 - Envr. Report - Narrative.pdf PDF
Attachment 37 - Envr. Report - Appendix C.pdf PDF
Attachment 40 - NARA RM Contract Language Clause.pdf PDF
Attachment 43 - Construction Wage Rates - St. Louis 1-20-23.pdf PDF
36C77623R0009 - 2-16-23.pdf PDF
Attachment 7 - Drawings Part-6.pdf PDF
Attachment 11 - Drawings Part-10.pdf PDF
Attachment 12 - Drawings Part-11.pdf PDF
Attachment 13 - Drawings Part-12.pdf PDF
Show all 50

Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AB

ABA

AC(T)

ACM

ACW

ADA

ADJ

A/E

AF

AFF

AGG

ALT

ALUM

APPROX

ARCH

ASPH

A/V

BARR

BATH

BB

BLDG

BLK

BLKG

BLW

BM

BMTU

BO

BOC

BOS

BRC

BRKT

BRNG

BTM

BTWN

CAB

CC

CD

CJ

CLG

CLR

CMU

CO

COL

COMP

CONC

CONN

CONST

CONT

COORD

COR

CORR

CS

CT

CTR

CV

AND

ANGLE

AT

CENTERLINE

DEGREES

NUMBER

ANCHOR BOLT

ARCHITECTURAL BARRIERS ACT

ACOUSTICAL CEILING (TILE)

ASBESTOS CONTAINING MATERIAL

ACOUSTICAL WALL

AMERICANS W/ DISABILITIES ACT

ADJACENT

ARCHITECT/ENGINEER

ACCESS FLOOR

ABOVE FINISH FLOOR

AGGREGATE

ALTERNATE

ALUMINUM

APPROXIMATELY

ARCHITECT(URAL)

ASPHALT

AUDIO / VIDEO

BARRIER

BATHROOM

BACKER BOARD

BUILDING

BLOCK

BLOCKING

BELOW

BEAM

BONE MARROW TRANSPLANT UNIT

BOTTOM OF

BOTTOM OF CURB

BOTTOM OF SLAB

BRACE, BRACING

BRACKET

BEARING

BOTTOM

BETWEEN

CABINET

CONTRACTOR FURN, CONTRACTOR INST

CONSTRUCTION/CONTRACT DOCUMENTS

CONTROL JOINT

CEILING

CLEAR(ANCE)

CONCRETE MASONRY UNIT

CONTRACTING OFFICER

COLUMN

COMPOSITION

CONCRETE

CONNECTION

CONSTRUCTION

CONTINUOUS

COORDINATE

CONTRACTING OFFICER REPRESENTATIVE

CORRIDOR

CONCRETE SEALER

CERAMIC TILE

CENTER

CONTRACTOR FURNISHED, VA INSTALLED

HDR

HDWE

HM

HORZ

HPDL

HR

HT

HVAC

ICRA

ID

ILSM

INCL

INST

INSUL

INT

JT

KV

LAM

LAV

LCM

LT

MAT

MAX

MDF

MECH

MEP

MFR

MIN

MISC

MOD

MTL

N N/A

NEG

NO.

NOM

NTS

O.C.

OPNG

OPP

OPT

OVHD

P

PCONC

PCRA

PL

PLAM

PLY(WD)

PNL

PR

PRFB

PS

PT

PTN(S)

PVMT

QTY

HEADER

HARDWARE

HOLLOW METAL

HORIZONTAL

HIGH PRESSURE DECORATIVE LAM

HOUR

HEIGHT

HEATING, VENTILATION & AIR CONDITIONING

INFECTIOUS CONTROL RISK ASSESSMENT

INSIDE DIAMETER OR DIM

INTERIM LIFE SAFETY MEASURES

INCLUDE(D,ING)

INSTALL

INSULATION

INTERIOR

JOINT

KILOVOLT

LAMINATE(D)

LAVATORY

LEAD CONTAINING MATERIAL(S)

LIGHT

MATERIAL(S)

MAXIMUM

MEDIUM-DENSITY FIBREBOARD

MECHANIC(AL)

MECHANICAL, ELECTRICAL, PLUMBING

MANUFACTURE(R)

MINIMUM

MISCELLANEOUS

MODIFIED

METAL

NORTH

NOT APPLICABLE

NEGATIVE

NUMBER

NOMINAL

NOT TO SCALE

ON CENTER(S)

OPENING

OPPOSITE

OPTION(AL)

OVERHEAD

PAINT

PRECAST CONCRETE

PRE-CONSTRUCTION RISK ASSESSMENT

PLATE

PLASTIC LAMINATE

PLYWOOD

PANEL

PAIR

PREFABRICATED

PLASTIC

PRESSURE TREATED

PARTITION(S)

PAVEMENT

QUANTITY

RAD

RCP

REF

REINF

REP

REQ(s,(')D)

RESIL

REV

RF

RM

RMV

RO

S

SCHED

SD

SECT

SF

SFRM

SHG

SHT(G)

SIM

SM

SOW

SPEC

SQ

SS

ST

STDG

STL

STOR

STRUCT

SUSP

SV

SYS

TEMP

T&G

THK

THRESH

TOC

TOS

TPH

TRANS

TS

TYP

UON

VA

VAR

VB

VC

VERT

VIF

VV

W W/

WD

WDW

WGHT

W/O

WP

WR

RADIUS

REFLECTED CEILING PLAN

REFERENCE

REINFORCE(D,ING)

REPRESENTATIVE

REQUIRE(D,S,MENT(S))

RESILIENT

REVERSE

RADIO FREQUENCY / ROOF

ROOM

REMOVE

ROUGH OPENING

SOUTH

SCHEDULE

SCHEMATIC DESIGN

SECTION

SQUARE FEET

SPRAY APPLIED FIRE-RESISTIVE MATERIAL

SHINGLES

SHEET (SHEATHING)

SIMILAR

SEAM

SCOPE OF WORK

SPECIFICATION

SQUARE

STAINLESS STEEL

STAIN

STANDING

STEEL

STORAGE

STRUCTURAL

SUSPENDED

SHEET VINYL

SYSTEM

TEMPORARY

TONGUE AND GROOVE

THICK(NESS)

THRESHOLD

TABLE OF CONTENTS

TOP OF SLAB

TOILET PAPER HOLDER

TRANSITION

TUBE STEEL

TYPICAL

UNLESS OTHERWISE NOTED

VETERANS AFFAIRS

VARIES

VAPOR BARRIER

VA FURNISHED, CONTRACTOR INSTALLED

VERTICAL

VERIFY IN FIELD

VA FURNISHED, VA INSTALLED

WEST

WITH

WOOD

WINDOW

WEIGHT

WITHOUT

WATERPROOF(ING)

WATER RESISTANT

DBL

DC

DD

DEMO

DEPT

DG

DIA

DIM

DWN

DR

DTL

DWG

E

EA

EJ

ELEC

ELEV

ENG

EOC

EOP

EPDM

EQ

EQUIP

ES

ETS

EX(IST)

EXP

EXT

FA

FD

FE(C)

FF

FFB

FFL

FIN

FLASH

FLR

FLRSNT

FNDN

FOC

FOF

FOS

FP

FR

FRM

FT

FTG

FUR

FURN

GA

GALV

GE

G(W)B

GC

GL

GLB

GMU

GOV(T)

GYP

DOUBLE

DIRECT CURRENT

DESIGN DEVELOPMENT

DEMOLISH(ION)

DEPARTMENT

DESIGN GUIDE

DIAMETER

DIMENSION

DOWN

DOOR

DETAIL

DRAWING(S)

EAST

EACH

EXPANSION JOINT

ELECTRIC(AL)

ELEVATION OR ELEVATOR

ENGINEER(ING)

EDGE OF CURB

EDGE OF PAVEMENT

ETHYLENE PROPYLENE DIENE TERPOLYMER

EQUAL

EQUIPMENT

EACH SIDE

EXPOSED TO STRUCTURE

EXISTING

EXPANSION

EXTERIOR

FIRE ALARM

FLOOR DRAIN

FIRE EXTINGUISHER (CABINET)

FACTORY FINISH

FINISH FLOOR BREAK

FINISH FLOOR LINE

FINISH(ED)

FLASHING

FLOOR(ING)

FLORESCENT

FOUNDATION

FACE OF CONCRETE

FACE OF FINISH

FACE OF STUDS

FIRE PROOF

FIRE RATED

FRAME

FOOT, FEET

FOOTING

FURRING

FURNISHED

GAGE, GAUGE

GALVANIZED

GENERAL ELECTRIC

GYPSUM (WALL) BOARD

GENERAL CONTRACTOR

GRID LINE

GLUE LAMINATED BEAM

GLASS MASONRY UNIT

GOVERNMENT

GYPSUM BOARD

A101

1 TYP

101.1

A-101

SIM

EXTERIOR ELEVATION

INTERIOR ELEVATION

BUILDING SECTION FLAG

WALL SECTION FLAG

CALLOUT FLAG

VERTICAL GRID LINE

HORIZONTAL GRID LINE

TRUE NORTH ARROW

PROJECT NORTH ARROW

(TRUE NORTH DASHED)

ELEVATION MARKER

KEY NOTE

ROOM TAG (SF OPTIONAL)

CEILING HEIGHT TAG

ROOM NAME

150 SF

A

A-101

SIM

01A

TRUE

NORTH

W1

A-101

PROJECT

NORTH

WALL TAG

FLOOR TAG

ROOF TAG

DOOR TAG

WINDOW TAG

SPECIALTY EQUIPMENT TAG

SIGNAGE TAG

SIGNAGE KEY NOTE

(AW SHEETS ONLY)

SIGNAGE MATERIAL TAG

(AW SHEETS ONLY)

EXISTING TO REMAIN

NEW CONSTRUCTION

TO DEMOLISH

HIDDEN ABOVE OR BELOW

EXISTING DOOR TO REMAIN

EXISTING DOOR TO DEMOLISH

NEW DOOR

SMOKE ZONE

1 HR FIRE RATED WALL

2 HR FIRE RATED WALL

SMOKE RATED WALL

SMOKE & 1 HR FIRE RATED WALL

PATIENT NON-SLEEPING SUITE

AREA OF WORK / AREA SHOWN

CONSTRUCTION ZONE, ( - - )

PRESSURE

ANTE ROOM, ( - ) PRESSURE

TEMPORARY ICRA BARRIER

TEMPORARY ICRA DOOR

PATH OF TRAVEL

EMERGENCY EGRESS PATHWAY

SEISMIC JOINT

BATT INSULATION

RIGID INSULATION

GYPSUM BOARD, TYPE X

ACOUSTICAL CEILING TILE, 2' x 2'

CONCRETE

STEEL

PLYWOOD, FIRE RATED

EARTH

SUPPLY GRILLE PER MECHANICAL

(SIZE & PROPORTIONS MAY VARY)

RETURN GRILLE PER MECHANICAL

(SIZE & PROPORTIONS MAY VARY)

LIGHTING PER ELECTRICAL

(SIZE & PROPORTIONS MAY VARY)

FIRE EXTINGUISHER CABINET

A-101

A01

D88

A5175SOAP DISH

IN-04.02-01

AFF

GYP ON MTL STUD

9' - 0"

FEC

F-1

R-1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

A-001

ARCHITECTURAL SYMBOLS &

ABBREVIATIONSSPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 EM AJ

CONSTRUCTION

DOCUMENTS

SYMBOLS ABBREVIATIONS

GENERAL NOTES

APPLICABLE PUBLICATIONS

1. MAINTAIN A SAFE, CLEAN CONSTRUCTION ZONE AT ALL TIMES.

2. DO NOT SCALE DRAWINGS.

3. DIMENSIONS ARE NOT ADJUSTABLE UNLESS NOTED WITH A +/- SYMBOL. ONLY NORMAL

INDUSTRY STANDARD TOLERANCES ARE ACCEPTABLE DEVIATIONS FROM DIMENSIONS

INDICATED.

4. ALL DIMENSIONS NOTED AS CLEAR SHALL MAINTAIN THE FULL SPACE INDICATED WITHOUT

ENCROACHMENTS.

5. FURNISH ALL MATERIALS & PRODUCTS TO COMPLY WITH THE CONTRACT DOCUMENTS.

6. ALL VERTICAL HEIGHTS INDICATED ARE FROM THE FINISH FLOOR ELEVATION, UON.

7. ANY AND ALL WALL MOUNTED EQUIPMENT SHALL HAVE BLOCKING IN WALL BEHIND, THIS

INCLUDES BACKING FOR WALL MOUNTED DOOR STOPS. ENSURE THAT ALL REQUIRED

BACKING IS INSTALLED IN WALLS PRIOR TO INSTALLING DRYWALL.

8. IN TOILET ROOMS PROVIDE STAINLESS STEEL FILLER BEHIND ANY MIRRORS AND OTHER

WALL MOUNTED ACCESSORIES WHEN ITEM IS INSTALLED PARTIALLY OVER CERAMIC TILE.

9. CONTRACTOR SHALL INSTALL FASCIA COVERS FOR HEADWALLS.

10. SEGREGATE ALL NURSE CALL, FIRE ALARM AND SECURITY SYSTEM ALARM WIRES FROM

THE DATA CABLES WHEN THEY ARE INTERMIXED. CONTRACTOR SHOULD EXPECT WIRES

TO BE INTERMIXED IN CERTAIN AREAS OF THE FACILITY TO INCLUDE BUT NOT LIMITED TO

CABLE TRAYS, J-HOOKS AND IN OPENINGS.

11. MOVE AND STORE ALL FURNITURE, FIXTURES, AND EQUIPMENT (FFE) AS NEEDED. FFE WILL

BE COVERED WITH PLASTIC BEFORE BEING MOVED. FFE WILL BE MOVED BACK TO THE SAME

LOCATION IT WAS ORIGINALLY LOCATED WHEN CONTRACTORS WORK IS COMPLETE. IF

EQUIPMENT NEEDS TO BE MOVED OUTSIDE THE ROOM IT IS THE CONTRACTOR'S

RESPONSIBILITY TO COVER ALL COSTS ASSOCIATED WITH MOVING, STORING, AND

REINSTALLING FFE.

12. WHEN THE CONTRACTOR MOVES FFE, THE CONTRACTOR IS RESPONSIBLE FOR UNPLUGGING

ALL EQUIPMENT FROM WALLS APPROPRIATELY. DURING REINSTALLATION OF FFE, IT IS THE

CONTRACTOR'S RESPONSIBILITY TO RECONNECT POWER PLUGS. THE VA WILL RECONNECT

ALL DATA TO THE NEW CAT 6A DATA PORTS.

APPLICABLE PUBLICATIONS GENERAL NOTES

AS AN AGENCY OF THE FEDERAL GOVERNMENT, THE VA IS NOT SUBJECT TO LOCAL IMPOSITIONS

OF CODE ENFORCEMENT PROCEDURES ( DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS,

FEES, ETC). THE VA SHALL FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ).

VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD

APPLICATION GUIDE AND OTHER GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL).

INTERNATIONAL BUILDING CODE (IBC) 2018.

INTERNATIONAL EXISTING BUILDING CODE (IEBC) 2018.

NATIONAL FIRE PROTECTION AGENCY (NFPA) 101 LIFE SAFETY CODE. NFPA 101 TAKES

PRECEDENCE OVER IBC.

NFPA NATIONAL FIRE CODES, WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900.

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.

VA SEISMIC DESIGN REQUIREMENTS, H-18-8.

NATIONAL ELECTRICAL CODE (NEC).

INTERNATIONAL PLUMBING CODE (IPC).

SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAL SOCIETY OF MECHANICAL

ENGINEERS (ASME) A 17.1.

ASME BOILER AND PRESSURE VESSEL CODE

ASME CODE FOR PRESSURE PIPING

ARCHITECTURAL BARRIER ACT ACCESSIBILITY STANDARDS (ABAAS), INCLUDING VA SUPPLEMENT

BARRIER FREE DESIGN GUIDE (PG-18-3)

BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE INSTITUTE

AND COMMENTARY (ACI 318)

MANUAL OF STEEL CONSTRUCTION , LOAD AND RESISTANCE FACTOR DESIGN SPECIFICATIONS FOR

STRUCTURAL STEEL BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)

ENERGY POLICY ACT OF 2005 (EPACT)

DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL

AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-RESE RESIDENTIAL

BUILDINGS, 10 CFR PARTS 433,434 AND 435.

FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF

UNDERSTANDING (MOU)

EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY AND

TRANSPORTATION MANAGEMENT.

THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL

REQUIREMENTS SECTION 01 01 0 OF THE VA MASTER CONSTRUCTION SPECIFICATION.

VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY - ASHRAE STANDARD 62.1 - 2004.

SAFETY STANDARD FOR REFRIGERATION SYSTEMS - ASHRAE STANDARD 15 - 2007.

VAMC APPROVED HARDWARE LOCKING STANDARDS

AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM)

FEDERAL COMMUNICATIONS COMMISSION (FCC), ALL REGULATIONS, PROCEDURES AND

STANDARDS FOR TWO-WAY RADIO EQUIPMENT, SYSTEMS AND OPERATION

ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IESNA)

INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE)

INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO), STANDARDS FOR PROTOCOLS AND

INTERFACES THAT INCLUDE OPEN SYSTEM INTERCONNECTIONS (OSI)

JOINT COMMISSION ON ACCREDITATION OF HEALTHCARE ORGANIZATIONS (JACHO),

ENVIRONMENT OF CARE GUIDELINES AND STANDARDS

FACILITIES GUIDELINES INSTITUTE (FGI): 2010 , OR MOST CURRENT ISSUE, GUIDELINES FOR THE

DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES

THE AMERICAN INSTITUTE OF ARCHITECTS (AIA) AND NATIONAL SOCIETY OF PROFESSIONAL

ENGINEERS(NSPE) RECENT ADDITIONS TO THEIR PROFESSIONAL CODES OF ETHICS ENCOURAGING

“ENVIRONMENTALLY RESPONSIBLE DESIGN”

Revisions: Date:

13. REMOVAL OF EXISTING CEILING AND TURNING UPRIGHT EXISTING SPRINKLER HEADS NEED

TO BE COORDINATED TO HAPPEN CONCURRENTLY.

14. REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.

15. IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE

WORK SHIFT DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRE STOPPING

COMPOSED OF MINERAL WOOL SHOULD BE INSTALLED IN THE PENETRATION TO PROVIDE

PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED PENETRATION.

16. CONTRACTOR TO REPLACE EXISTING FIRE EXTINGUISHER WITHIN 75' WITH A CLEAN AGENT

FIRE EXTINGUISHER IN ACCORDANCE TO THE FIRE PROTECTION MANUAL AT ALL TELECOM

ROOMS.

17. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING HANDRAILS TO INSTALL NEW OIT

TELECOM ROOM DOORS. CONTRACTORS SHALL REINSTALL AND/OR KICK RAILS ON BOTH

SIDES OF NEW DOOR AS NEEDED, ALL RAILS AND KICK RAILS WILL BE TO CODE.

18. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING DAMAGED FLOOR TILES AFTER NEW

OIT TELECOM DOORS ARE INSTALLED. CONTACT COR TO SEE IF EXTRA FLOORING IS

AVAILABLE FOR TO MATCH EXISTING, IF NOT, PROVIDE REPLACEMENT FLOORING THAT IS AS

CLOSE AS POSSIBLE TO MATCH EXISTING.

03/10/23General Notes Clarification

B.2

B.8

5 6

" 3

" 13

23A-100

B.2

B.8

105 SF

TR

G09B

107 SF

LOCK SHOP

G09

10' - 3"

G09

2' - 4 3/4"

G B

523 SF

CORRIDOR

H002

01a

2' - 10" 2' - 3 1/2"

12 SF

CLOSET

H002A

E X

IS

T

F

L O

O R

IN

G

N E

W

F L O

O R

IN

G

23A-100

B.2

B.8

10' - 0"

B.2

B.8

10' - 0"

EXPOSED

105 SF

TR

G09B

107 SF

LOCK SHOP

G09

195 SF

CARPENTER

STORAGE

G10

523 SF

CORRIDOR

H002

12 SF

CLOSET

H002A

211 SF

LOCK SHOP

G09

12 SF

CLOSET

H002A

523 SF

CORRIDOR

H002

TO DEMOLISH

EXISTING DOOR TO REMAIN

EXISTING DOOR TO DEMOLISH

NEW DOOR

EXISTING WALL TO DEMOLISH (NON-BEARING METAL STUD WALL)

EXISTING LIGHTS TO DEMOLISH

211 SF

LOCK SHOP

G09

12 SF

CLOSET

H002A

523 SF

CORRIDOR

H002

( + ) PRESSURE

CONSTRUCTION ZONE, ( - - ) PRESSURE

ANTE ROOM, ( - ) PRESSURE

TEMPORARY ICRA BARRIER

TEMPORARY ICRA DOOR

CONSTRUCTION TACKY MATT

NEGATIVE AIR MACHINE

EXISTING RESILIENT BASE:

CUT AS REQUIRED FOR

NEW DOOR AND PATCH

CLEANLY TO NEW FRAME.

EXISTING WINDOW TO BE DEMOLISHED.

WHERE DOOR OCCURS: CAREFULLY CUT EXISTING

KICK-RAIL. SALVAGE END CAPS FOR REUSE. REINSTALL

KICK-RAILAND INSTALL SALVAGED END CAPS. PROVIDE

ADDITIONAL BLOCKING AND SUPPORTS FOR NEW END

OF KICK-RAIL AS NEEDED.

INFILL WALL WITH GWB WHERE WINDOW WAS

DEMOLISHED, PATCH AND PAINT TO MATCH EXISTING.

3' - 0"

RM G09

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

EHRM INFRASTRUCTURE

UPGRADES

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

657-21-701JB

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES 23A-100

BLDG 23 - FLOOR 0 - DEMO,

FLOOR PLANS & RCPS 23

EM AJ/ST/KBIssue Date

KEY PLAN

PROJECT

NORTH

LEGEND

1/4" = 1'-0"

RM G09 - DEMO FLOOR PLAN

1/4" = 1'-0"

RM G09 - FLOOR PLAN

1/4" = 1'-0"

RM G09 - DEMO RCP

1/4" = 1'-0"

RM G09 - RCP

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

GENERAL NOTES

1. ALL PRODUCTS AND WALL FINISHES SHALL MATCH EXISTING OR ADJACENT

EXISTING UNLESS OTHERWISE NOTED.

2. PATCH AND REPAIR WALLS WHERE MECHANICAL, PLUMBING, AND ELECTRICAL

ITEMS DEMO'D.

3. PATCH AND REPAIR FLOOR WHERE CONDUITS, PIPING AND SIMILAR ARE DEMO'D.

4. PATCH AND REPAIR EXISTING CEILING GRID AND TILES WHERE NEW WALLS

INSTALLED.

5. PATCH AND REPAIR GWB WHERE DOORS ARE DEMO'D AND NEW DOORS ARE

INSTALLED.

6. PROTECT FINISHES IN ROOMS ADJACENT TO NEW TELECOMMUNICATION ROOMS

AND AREAS NOT SCHEDULED FOR NEW WORK.

KEYNOTES

CONSTRUCT NEW WALL AND PATCH/PAINT TO MATCH EXISTING ON ROOM G09

SIDE.

INSTALL NEW DOOR/FRAME. INFILL WALL AS NECESSARY ABOVE DOOR WHERE

DEMOLISHED WINDOW WAS LLOCATED. SEE DETAIL 1/23A-100.

DEMO EXISTING SINK. SALVAGE SINK FOR REUSE.

DEMO EXISTING WINDOW, SAWCUT TO FLOOR. PREP FOR NEW DOOR/FRAME.

DEMO EXISTING DOOR/FRAME.

DEMO EXISTING LVT FLOORING TO EXPOSED CONCRETE SLAB UNDERNEATH.

REMOVE EXISTING ADHESIVE AND PREP FOR NEW FLOORING.

APPLY ANTI-STATIC COATING TO EXPOSED CONCRETE FLOOR. PROVIDE VINYL

REDUCER STRIP AT EXISTING FLOORING TRANSITION.

DEMO EXISTING WALLS. SEE MECHANICAL SHEETS FOR COORDINATION ON

PLUMBING.

DEMO EXISTIGN ACT COMPLETELY INCLUDING ALL GRID, SUPPORTING WIRES,

CLIPS, AND PERIMETER WALL ANGLES IN ROOM TO EXPOSE UNDERSIDE OF

STRUCTURE ABOVE. PATCH WALLS WHERE CEILING IS REMOVED.

PATCH AND REPAINT WALL AS NECESSARY TO MATCH EXISTING ON CORRIDOR

SIDE.

NEW FRT PLYWOOD OVER WALLS PER DETAIL 4/AE421.

INSTALL PHYSICAL SECURITY AT INTERIOR AND EXTERIOR OF EXISTING WINDOW.

REFERENCE DETAIL 4/A-603.

PLACE ADHESIVE WALK OFF MATS AT ENTRANCE AND EXIT SIDE OF

CONSTRUCTION AREA, TYP.

DEMO EXISTING BASE, PREP FOR NEW BASE.

INSTALL NEW BASE ON ALL WALLS OF NEW TELECOM ROOM.

Revisions: Date:

ICRA LEGEND

1/2" = 1'-0"

H002 CORRIDOR - NORTH INTERIOR ELEVATION

CONSTRUCTION

DOCUMENTS

Building 23 Floor Plan Update 03/10/23

B.2

B.8

5 6

9' - 3 1/2"

/4

CONFIRM WITH DOOR

MANUFACTURER, TYP

3' - 4" 4' - 4"

23A-101

1Sim

B.2

B.8

5 6

11 SF

OI&T

115B

102 SF

TR

121A

107 SF

PROSTHETICS

RESTORATION

A

9' - 3"

0' - 6"

169 SF

CORRIDOR

C119

54 SF

PROSTHETICS

RESTORATION

OFFICE

36 SF

ALCOVE

122A

284 SF

LAB DUSTER

115A

01a

PATCH AND REPAIR WALLS AND

FLOOR TO MATCH EXISTING

WHERE CABINETS AND

PLUMBING ARE REMOVED.

E X

IS

T

F

L O

O R

IN

G

N E

W

F L O

O R

IN

G

10' - 0"

B.2

B.8

5 6

9' - 11"

DEMO EXISTING LIGHTS

B.2

B.8

5 6

10' - 0"

10' - 0"

EXPOSED

102 SF

TR

121A

107 SF

PROSTHETICS

RESTORATION

284 SF

LAB DUSTER

115A

169 SF

CORRIDOR

C119

11 SF

OI&T

115B

416 SF

LAB WORK

INSTALL NEW ACT PANELS,

TO MATCH EXISTING

214 SF

PROSTHETICS

RESTORATION

LAB

11 SF

OI&T

115B

169 SF

CORRIDOR

C119

284 SF

LAB DUSTER

115A

416 SF

LAB WORK

54 SF

PROSTHETICS

RESTORATION

OFFICE

36 SF

ALCOVE

122A

TO DEMOLISH

EXISTING DOOR TO REMAIN

EXISTING DOOR TO DEMOLISH

NEW DOOR

EXISTING WALL TO DEMOLISH (NON-BEARING METAL STUD WALL)

EXISTING LIGHTS TO DEMOLISH

214 SF

PROSTHETICS

RESTORATION

LAB

11 SF

OI&T

115B

54 SF

PROSTHETICS

RESTORATION

OFFICE

36 SF

ALCOVE

122A

169 SF

CORRIDOR

C119

284 SF

LAB DUSTER

115A

416 SF

LAB WORK

WHERE NEW DOOR OCCURS: CAREFULLY

CUT EXISTING RAILING AND KICK-RAIL.

SALVAGE END CAPS FOR REUSE. REINSTALL

RAILING AND KICK-RAIL AND INSTALL

SALVAGED END CAPS. PROVIDE ADDITIONAL

BLOCKING AND SUPPORTS FOR NEW END OF

RAILING AND KICK-RAIL AS NEEDED.

EXISTING RESILIENT BASE:

CUT AS REQUIRED FOR NEW

DOOR AND PATCH CLEANLY

TO NEW FRAME.

( + ) PRESSURE

CONSTRUCTION ZONE, ( - - ) PRESSURE

ANTE ROOM, ( - ) PRESSURE

TEMPORARY ICRA BARRIER

TEMPORARY ICRA DOOR

CONSTRUCTION TACKY MATT

NEGATIVE AIR MACHINE

RM 121

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

EHRM INFRASTRUCTURE

UPGRADES

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

657-21-701JB

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES 23A-101

BLDG 23 - FLOOR 1 - DEMO,

FLOOR PLANS & RCPS 23

EM AJ/ST/ KBIssue Date

KEY PLAN

PROJECT

NORTH

LEGEND

1/4" = 1'-0"

RM 121 - DEMO FLOOR PLAN

1/4" = 1'-0"

RM 121 - FLOOR PLAN

1/4" = 1'-0"

RM 121 - DEMO RCP

1/4" = 1'-0"

RM 121- RCP

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

Revisions: Date:

GENERAL NOTES

1. ALL PRODUCTS AND WALL FINISHES SHALL MATCH EXISTING OR ADJACENT

EXISTING UNLESS OTHERWISE NOTED.

2. PATCH AND REPAIR WALLS WHERE MECHANICAL, PLUMBING, AND ELECTRICAL

ITEMS DEMO'D.

3. PATCH AND REPAIR FLOOR WHERE CONDUITS, PIPING AND SIMILAR ARE DEMO'D.

4. PATCH AND REPAIR EXISTING CEILING GRID AND TILES WHERE NEW WALLS

INSTALLED.

5. PATCH AND REPAIR GWB WHERE DOORS ARE DEMO'D AND NEW DOORS ARE

INSTALLED.

6. PROTECT FINISHES IN ROOMS ADJACENT TO NEW TELECOMMUNICATION ROOMS

AND AREAS NOT SCHEDULED FOR NEW WORK.

7. PATCH CONCRETE FLOOR WHERE CONDUITS OCCUR AT EXISTING WALL

LOCATIONS.

KEYNOTES

1 CONSTRUCT NEW WALL AND PATCH/PAINT TO MATCH EXISTING IN ROOM 121

SIDE.

INSTALL NEW DOOR/FRAME.

DEMO EXISTING CABINETRY AND SINK.

DEMO EXISTING WALL AND RAILING. PREP FOR NEW DOOR/FRAME. SEE DETAIL

1/23A-101.

DEMO EXISTING VCT FLOORING TO EXPOSED CONCRETE SLAB UNDERNEATH.

REMOVE EXISTING ADHESIVE AND PREP FOR NEW FLOORING.

APPLY ANTI-STATIC COATING TO EXPOSED CONCRETE FLOOR. PROVIDE VINYL

REDUCER STRIP AT EXISTING FLOORING TRANSITION.

DEMO EXISTING ACT COMPLETELY INCLUDING ALL GRID, SUPPORTING WIRES,

CLIPS, AND PERIMETER WALL ANGLES IN ROOM TO EXPOSE UNDERSIDE OF

STRUCTURE ABOVE. PATCH WALLS WHERE CEILING IS REMOVED.

PATCH AND REPAINT WALL AS NECESSARY ON CORRIDOR SIDE TO MATCH

EXISTING.

NEW FRT PLYWOOD OVER WALLS PER DETAIL 4/AE421.

INSTALL PHYSICAL SECURITY AT INTERIOR AND EXTERIOR OF EXISTING

WINDOW. REFERENCE DETAIL 4/A-603.

PLACE ADHESIVE WALK OFF MATS AT ENTRANCE AND EXIT SIDE OF

CONSTRUCTION AREA, TYP.

DEMO EXISTING BASE, PREP FOR NEW BASE.

INSTALL NEW BASE ON ALL WALLS OF NEW TELECOM ROOM.

NTS

C119 - CORRIDOR

ICRA LEGEND

CONSTRUCTION

DOCUMENTS

Building 23 Floor Plan Update 03/10/23

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

EP704

ELECTRICAL SCHEDULE

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 Checker Author

CONSTRUCTION

DOCUMENTS

Revisions: Date:

REVISED SCHEDULES.1 03/10/2023

DN

UP

4160 VO

LTS

DUST CO

LLECTO

R

LIQ UEFIED PETRO LEUM G AS

FLAM M ABLE G AS 2

TRASH COM

PACTO

R

P

SILVERBUILDING 1 23

VA PO

LICE

E

LECTRIC ACCESS

TRANSFO

RM

ER

TRANSFO

RM

ER

TRANSFO

RM

ER

HVAC UNIT

E

LECTRIC PANEL

HVAC UNIT

S&C PAD M

O

UNTED G

EAR

CATALO

G

# 55152-C3DGIG

2P1V M

O

DEL# PM

H-9

EE13299 SG

-52

13278

BUILDING

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

TR

G09B

23ET400

23ET400

5 6

LOCK SHOP

G09

CARPENTER STORAGE

G10

CARPENTER SHOP OFFICE/ KEY

PICK-UP

G25

TRASH RM.

G13B

BREAK RM. / STORAGE

G23

CARPENTER SHOP

G26

LOCKER, MALE

G15

TOILET / SHOWER

G16

STORAGE

G14

STAIRWELL NO. 1

S1

CORRIDOR

H001

TOILET, MEN

G12

STORAGE

G13

LOCKER, MALE

G11

CHARGING STATION

G07

STORAGE

G08

KEY SHOP

G09A

BREAK RM.

G04 STORAGE

G05

OFFICE

G01A

ELEC RM.

G01

MECH. RM.

G02

ELEC RM.

G03

CORRIDOR

H002

BATTERY STORAGE

G13C

WASH RM.

G13A

STAIRWELL NO. 2

S2

MECH. RM.

G17

CORRIDOR

H000

ELEVATOR

E-1

B

C

D

E

F

G

A

B.2

B.8

C.6

D.4

E.2

E.8

1 2 3 4 7

3.4

E.5

D.5

C.5

B.5

E.6

23ET400

TYP

WAP 1

HAND HOLE

TYP.

SIDE-B FIBER-OPTIC BACKBONE:

REFERENCE COMMUNICATION

SHEETS FOR ADDITIONAL

INFORMATION REGARDING

HANDHOLE,CONDUIT, BUILDING

PENETRATIONS, FIBER-OPTIC

CABLING, AND RACEWAY

INFORMATION

TDU 5

TYP.

EXISTING SIDE-A FIBER-OPTIC BACKBONE

BUILDING ENTRY POINT (APPROXIMATE

LOCATION). ROUTE FIBER-OPTIC CABLES TO TRs

AS INDICATED ON COMMUNICATIONS DRAWINGS;

REFERENCE COMMUNICATIONS DRAWINGS FOR

ALL FIBER-OPTIC CABLING, RACEWAY TYPES,

SPECIFICATIONS, AND RATINGS. REFERENCE KEY

NOTES ON THIS SHEET REGARDING CABLE TRAY

AND VERTICAL/HORIZONTAL ROUTING FOR

ADDITIONAL FIBER BACKBONE CABLING

REQUIREMENTS.

DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE

SERVED FROM TELECOMMUNICATION ROOM G09B.

ALL BACKBONE CABLING ROUTES ARE

DIAGRAMMATICAL; CONTRACTOR SHALL ENSURE A-

SIDE AND B-SIDE ROUTING IS AS DIVERSE AS

PRACTICAL. REFERENCE COMMUNICATIONS

DRAWINGS FOR ALL REQUIRED FIBER-OPTIC

CABLING.

9.99.89.79.59.38.57.86.36.1

V

U

CORRIDOR

UTILITY

LOBBY

ELEVATOR LOBBY

EQUIPMENT

ELEVATOR

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO

BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE ACCEPTANCE OF THE

OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF REQUIRED.

COORDINATE WITH ARCHITECTURAL DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE UPGRADED WITH CAT6A PORTS AND CABLE

QUANTITIES INDICATED, UNLESS NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED BY EXISTING CABLING. PROVIDE

RACEWAYS TO EXTEND TO ASSOCIATED TR.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET

WITH THE PORT QUANTITY INDICATED.

7. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT 6A CABLING FROM EACH WAO (WORK AREA

OUTLET) TO ITS RESPECTIVE TR.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT CONDUIT RUNS, OR CONDUIT CONTAINING

BENDS TOTALING MORE THAN 180 DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF HORIZONTAL AND BACKBONE CABLING.

PROVIDE FIRE-STOP MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD; DOCUMENT VARIANCES ON AS-BUILT

DRAWINGS.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING TRANSPORTATION, FOR ALL WORK TO

DESIRED VA STORAGE LOCATION. COORDINATE WITH VA AS REQUIRED.

12. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN RACEWAY.

WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO SEGREGATE

SYSTEMS FROM ONE ANOTHER.

13. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS, ACRHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY

OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.

AREA OF WORK

- 1/8" = 1'-0"

1 BLDG 23 - FLOOR 0 - TELECOMMUNICATIONS PLAN

0' 4' 8' 16'

PROJECT

NORTH

BLDG 23

KEY PLAN

GENERAL NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

657-21-701JB

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES 23ET100

BLDG 23 - FLOOR 0 -

TELECOMMUNICATIONS PLAN 23

LRL/WNM JGE/JBB

CONSTRUCTION

DOCUMENTS

03/31/2022

PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE EXISTING TELECOMMUNICATIONS OUTLET;

EXISTING OUTLET CONDUIT SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE SHEET DETAIL '1' ON SHEET ET503 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET

PLACEMENT.

EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH CAT 6A CABLING.

REMOVE AND REPLACE EXISTING CABLE TRAY IN THE AREAS SHOWN AS REQUIRED; IF CABLE TRAY IS NON-EXISTENT, PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL '6' ON SHEET ET503 AND TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET ET701. WHERE WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO CONDUIT SLEEVES [(2) 4", MINIMUM] WITH APPROPRIATE FIRE-PROOFING AND CAULKING TO PASS THROUGH WALL. WHERE EXISTING CABLE TRAY AND/OR SLEEVES ARE DISCOVERED, EVALUATE CONDITION AND RACEWAY CAPACITY; IF CABLE TRAY AND/OR

SLEEVES APPEAR TO BE REUSABLE, NOTIFY COR FOR POSSIBLE REUSE.

FIBER-OPTIC CABLE HORIZONTAL ROUTING SHALL BE CONCEALED ABOVE DROP CEILING WHEREVER POSSIBLE. UTILIZE CABLE TRAY AS APPLICABLE. PROVIDE CONDUIT SLEEVE WITH FIREPROOFING AS REQUIRED WHERE WALL PENETRATIONS ARE

REQUIRED. REFERENCE DETAIL 2 ON SHEET ET503 FOR ADDITIONAL INFORMATION.

TUBE DISTRIBUTION UNIT (TDU). REFERENCE COMMUNICATION DRAWING FOR ADDITIONAL INFORMATION.

KEY NOTES

Revisions: Date:

03/10/2023

PROJECT

NORTH

1 REVISED ARCHITECTURAL BACKGROUND.

CONTINUE TO SHEET

CET103 FOR ADDITIONAL

BACKBONE ROUTING

CONTRACTOR SHALL DEMOLISH EXISTING FIBER-OPTIC

BACKBONE CABLING AND RACEWAY AFTER A-SIDE

FIBER-OPTIC BACKBONE IS COMPLETELY INSTALLED.

A-SIDE FIBER-OPTIC BACKBONE. ROUTE FIBER-OPTIC

CABLES TO TRs AS INDICATED ON COMMUNICATIONS

DRAWINGS; REFERENCE COMMUNICATIONS DRAWINGS

FOR ALL FIBER-OPTIC CABLING, RACEWAY TYPES,

SPECIFICATIONS, AND RATINGS. REFERENCE KEY

NOTES ON THIS SHEET REGARDING CABLE TRAY

AND VERTICAL/HORIZONTAL ROUTING FOR

ADDITIONAL FIBER BACKBONE CABLING

REQUIREMENTS.

1. "GENERAL NOTES" APPLY TO ALL ELECTRICAL DRAWINGS. "SHEET NOTES" APPLY TO ONLY THE

SHEETS ON WHICH THEY OCCUR. "KEYNOTES" APPLY ONLY WHERE CALLED OUT.

2. ALL EQUIPMENT SHOWN IN BOLD IS TO BE PROVIDED, OR MODIFIED BY CONTRACTOR UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FROM ALL CONTROL DEVICES TO

LUMINAIRES FOR CONTROL OF LUMINAIRES SHOWN.

4. LUMINAIRES SHOWN ON DRAWINGS FOR QUALITY AND CIRCUITING ONLY. SEE ARCHITECTURAL

DRAWINGS FOR EXACT LOCATIONS AND ELEVATIONS.

5. ALL FEEDERS AND BRANCH CIRCUITS SHALL CONTAIN AN EQUIPMENT GROUND CONDUCTOR

SIZED PER NEC TABLE 250.122. ALL WIRING IS BASED ON COPPER PER NEC TABLE

310.15(B),USING 75° C AMPACITIES FOR FEEDERS.

6. BRANCH CIRCUIT CONDUCTORS, NOT OTHERWISE IDENTIFIED SHALL BE A MINIMUM 12 AWG

FOR RUNS 70 FEET OR LESS AND A MINIMUM 10 AWG FOR RUNS GREATER THAN 70 FEET.

QUANTITY AND SIZE SHALL BE "AS REQUIRED" TO SERVE AND CONTROL DEVICE(S) OR

EQUIPMENT WITH A MAXIMUM VOLTAGE DROP OF THREE PERCENT. WHERE CONTRACTOR

CHOOSES TO RUN MORE THAN THREE CURRENT CARRYING CONDUCTORS WITHIN ONE

RACEWAY OR CABLE, CONDUCTORS SHALL BE INCREASED IN SIZE TO COMPENSATE FOR THE

DERATING REQUIRED PER NEC SECTION 310.15. CONDUCTOR AMPACITIES SHALL BE TAKEN

FROM THE 75° C COLUMN.

7. MINIMUM CONDUIT SIZE IN EXTERIOR AND UNDERGROUND LOCATIONS TO BE 1" UNLESS

NOTED OTHERWISE ON PLANS. CONDUITS FROM LUMINAIRES TO LOCAL USER CONTROL

DEVICES (SWITCHES, OCCUPANCY SENSORS, ETC.) MAY BE 3/4" OR AS INDICATED IN

SPECIFICATIONS. PROVIDE ADDITIONAL CONDUCTOR FOR UNSWITCHED "HOT" TO LIGHTING

LUMINAIRES WITH EMERGENCY POWER BATTERIES OR GENERATOR TRANSFER DEVICES.

8. WIRING FOR EMERGENCY LIGHTING CIRCUITS OR OTHER EMERGENCY EQUIPMENT SHALL BE

KEPT ENTIRELY INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT AND SHALL MEET ALL

REQUIREMENTS OF NEC SECTION 700.10.

9. CONTRACTORS SHALL PROVIDE CONDUIT AND WIRE FOR ALL CIRCUITS SHOWN ON DRAWINGS.

10. WHERE EQUIPMENT PART NUMBERS ARE SHOWN ON THESE PLANS THEY SHALL SUPERCEDE

THE REQUIREMENTS OF THE SPECIFICATIONS.

11. ALL CONDUITS SHALL BE CONCEALED UNLESS OTHERWISE NOTED.

12. COORDINATE EXACT LOCATION OF ALL OUTLETS, COMBINATION CLOCK/SPEAKERS, SPEAKER, FA DEVICES, ETC., WITH THE ARCHITECTURAL ELEVATIONS PRIOR TO COMMENCING WORK.

13. COORDINATE USE OF CEILING SPACE WITH ALL TRADES PRIOR TO COMMENCING WORK. MANY

AREAS ARE VERY CONGESTED AND REQUIRE CLOSE COORDINATION.

14. COORDINATE INSTALLATION REQUIREMENTS FOR OCCUPANCY SENSOR LIGHTING CONTROL

WITH THE MANUFACTURER. PROVIDE ALL APPURTENANCES AS REQUIRED BY THE

MANUFACTURER. PROVIDE ADDITIONAL SENSORS WHERE NECESSARY TO PROVIDE COMPLETE

COVERAGE IN EACH ROOM CONTROLLED BY OCCUPANCY SENSORS.

15. COORDINATE THE INSTALLATION OF ALL EXTERIOR OUTLET BOXES WITH THE TYPE OF

MASONRY IN EACH AREA. CUT ALL FLUTED BLOCKS SO THAT THE BOX IS INSTALLED FLUSH.

SEE ARCHITECTURAL DETAILS FOR MOUNTING REQUIREMENTS.

16. SEAL ALL CONDUIT PENETRATIONS OF FLOORS AND FIRE RATED ASSEMBLIES WITH U.L.

APPROVED MATERIALS AND METHODS TO MAINTAIN FIRE RATING. PROTECT ALL OPENINGS

FOR STEEL ELECTRICAL BOXES IN FIRE RATED WALLS WITH U.L. APPROVED MATERIALS AND

METHODS TO MAINTAIN THE FIRE INTEGRITY.

17. PROVIDE ADDITIONAL CONDUIT SLEEVES THROUGH WALLS WHERE REQUIRED FOR ROUTING

OF SIGNAL SYSTEM WIRING NOT REQUIRED TO BE RUN IN CONDUIT. EACH SLEEVE SHALL BE

DEDICATED TO EACH SIGNAL SYSTEMS. SLEEVES ROUTED THROUGH RATED WALLS SHALL BE

SEALED WITH U.L. MATERIALS AND METHODS TO MAINTAIN FIRE RATING OF WALL.

18. SEE MECHANICAL/PLUMBING DRAWINGS AND SUBMITTALS FOR EXACT LOCATIONS AND

ADDITIONAL ELECTRICAL REQUIREMENTS PRIOR TO INSTALLATION.

19. ALL LOW VOLTAGE SYSTEMS NOT RUN IN CONDUIT SHALL HAVE MINIMUM 3/4"C. ROUTED FROM

THE DEVICE THROUGH WALLS INTO THE ACCESSIBLE CEILING SPACE. NO CABLING SHALL BE

ROUTED IN THE WALLS OR INACCESSIBLE LOCATION WITHOUT CONDUIT.

20. GFCI RECEPTACLES ARE REQUIRED WITHIN 6 FT OF ALL SINKS, ON THE EXTERIOR BELOW 8FT

FROM THE FINISH FLOOR, AND ON ALL ROOFS.

21. UNLESS SPECIFICALLY SHOWN ON THESE PLANS NO STRUCTURAL MEMBER SHALL BE CUT,

NEITHER DRILLED NOR NOTCHED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM THE

STRUCTURAL ENGINEER AND THE COR.

22. CONTRATOR SHALL PROVIDE DUCT SEAL WHERE CONDUITS TRANSITION FROM AREAS THAT

CREATE TEMPERATURE DIFFERENTIAL PER NEC.

23. PRIMARY CONDUIT SWEEPS SHALL BE LONG RADIUS.

24. ALL "RMC" - RIGID METAL CONDUIT IN CONTACT WITH THE EARTH SHALL BE WRAPPED WITH

CORROSION PROTECTION TAPE PER NEC.

25. ALL J-BOXES SHALL BE MATKED WITH INDELIBLE MARKER INDICATING CONDUIT NUMBER AND

PANEL NUMBER.

26. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL 120 VOLT POWER FOR

THE MECHANICAL CONTROLS. COORDINATE EXACT REQUIREMENTS WITH THE CONTROL

CONTRACTOR.

27. ALL ELECTRICAL WORK SHALL BE COMPLETED WITH ALL PROXIMATE ELECTRICAL CIRCUITS DE-

ENERGIZED (I.E. A NEW BREAKER OR CIRCUIT CANNOT BE ADDED TO A PANEL UNLESS THE

PANEL IS COMPLETELY DE-ENERGIZED), OR THE CONTRACTOR MUST COMPLY WITH NFPA 70E

FOR WORK ON ENERGIZED SERVICE. THE VA WILL DETERMINE IF THE ELECTRICAL SERVICE

CAN BE SHUTDOWN OR IT WILL HAVE TO BE WORKED HOT DEPENDING ON THE CRITICALITY OF

THE AREA BEING AFFECTED. IF THE WORK MUST BE DONE WITH THE SERVICE LIVE, THE

CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL REQUIRED PROTECTIVE TOOLS,

EQUIPMENT AND CLOTHING, AND MUST FOLLOW THE JOB SPECIFIC WORK PLAN PREPARED BY

THE VA. WORK THAT REQUIRES SHUTTING DOWN ELECTRICAL SERVICE MAY HAVE TO BE

ACCOMPLISHED DURING OTHER THAN NORMAL DUTY HOURS.

28. WHENEVER FIRE ALARM WORK TAKES PLACE IN AN AREA THAT IS BEING REMODELED, AT THE

CONCLUSION OF THE WORK, THE FIRE ALARM CONTRACTOR SHALL TEST ALL FIRE ALARM

DEVICES WITHIN THE AREA OF REMODEL.

29. DEMOLITION PLAN/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD DRAWINGS. IF

DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY NOTIFY VA AND ENGINEER

OF SAID DISCREPANCY.

30. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF DEVICES SHALL

COMPLY WITH ALL APPROPRIATE CODES.

31. FIELD VERIFY RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO PERFORMING WORK.

32. ALL EQUIPMENT, CABLING, CONNECTORS AND APPURTENANCES SHALL BE LABELED PER THE

VA STANDARD "INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACE" VERSION 3.1

OR NEWER.

33. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER

OBSTRUCTIONS PRIOR TO INSTALLATION.

34. ALL ETHERNET CATEGORY CABLES SHALL FOLLOW THE FOLLOWING CABLE COLOR SCHEME:

DATA SHALL BLUE/TEAL, PHONES SHALL BE GRAY, AND (WIRELESS) ACCESS POINTS SHALL BE

YELLOW. COORDINATE WITH VA FOR ALL CABLING COLOR SCHEMES AS REQUIRED PRIOR TO

SUBMITTAL PROCESS.

35. TOTAL NUMBER OF DATA CONNECTIONS AND CABLING FOR WAOs AND WAPs SHALL BE

VERIFIED BY CONTRACTOR PRIOR TO ACQUISITION OF EQUIPMENT AND CABLING.

CONTRACTOR SHALL PROVIDE AN INITIAL SURVEY OF ALL AREAS TO HAVE UPGRADED WAOs

AND OTHER DATA CONNECTED EQUIPMENT IN ORDER TO VERIFY EXACT LOCATIONS AND

QUANTITIES PRIOR TO CONSTRUCTION.

36. CONTRACTOR MAY USE TEMPORARY CABLE HANGERS OR OTHER MEANS WHILE ROUTING

CABLE TO ITS INTENDED DESTINATION; HOWEVER, PRIOR TO FINAL INSTALLATION, CABLE

SHALL BE INSTALLED TO BE HOUSED WITHIN CABLE TRAY AND NOT ON TEMPORARY CABLE

HANGERS.

37. SEGREGATE ALL NURSE CALL, FIRE ALARM, AND SECURITY SYSTEM ALARM WIRES FROM THE

DATA CABLES WHEN THEY SHARE A CABLE TRAY OR ARE INTERMIXED. CONTRACTOR SHALL

EXPECT WIRES TO BE INTERMIXED IN CERTAIN AREAS OF THE FACILITY TO INCLUDE BUT NOT

LIMITED TO CABLE TRAYS, J-HOOKS, AND IN OPENINGS.

G E N E R A L N O T E S

THIS SHEET IS FOR REFERENCE ONLY AND ALL SYMBOLS, NOTES

AND ABBREVIATIONS MAY NOT APPLY TO THIS PROJECT

S H E E T I N D E X

ETG001 - TELECOMMUNICATIONS LEGEND, GENERAL NOTES, AND ABBREVIATIONS

01ET100 - BLDG 01 - FLOOR 0 - TELECOMMUNICATION PLANS

01ET101 - BLDG 01 - FLOOR 1 - TELECOMMUNICATION PLANS

01ET102 - BLDG 01 - FLOOR 2 - TELECOMMUNICATION PLANS

01ET103 - BLDG 01 - FLOOR 3 - TELECOMMUNICATION PLANS

02ET100 - BLDG 02 - FLOOR 0 - TELECOMMUNICATION PLANS

02ET101 - BLDG 02 - FLOOR 1 - TELECOMMUNICATION PLANS

02ET102 - BLDG 02 - FLOOR 2 - TELECOMMUNICATION PLANS

02ET103 - BLDG 02 - FLOOR 3 - TELECOMMUNICATION PLANS

03ET100 - BLDG 03 - FLOOR 0 - TELECOMMUNICATIONS PLAN

03ET101 - BLDG 03 - FLOOR 1 - TELECOMMUNICATIONS PLAN

03ET102 - BLDG 03 - FLOOR 2 - TELECOMMUNICATIONS PLAN

03TET101 - BLDG 03T - FLOOR 1 - TELECOMMUNICATIONS PLAN

18ET100 - BLDG 18 - FLOOR 0 - TELECOMMUNICATIONS PLAN

18ET101 - BLDG 18 - FLOOR 1 - TELECOMMUNICATIONS PLAN

18ET102 - BLDG 18 - FLOOR 2 - TELECOMMUNICATIONS PLAN

18ET103 - BLDG 18 - FLOOR 3 - TELECOMMUNICATIONS PLAN

23ET100 - BLDG 23 - FLOOR 0 - TELECOMMUNICATIONS PLAN

23ET101 - BLDG 23 - FLOOR 1 - TELECOMMUNICATIONS PLAN

24ET100 - BLDG 24 - FLOOR 0 - TELECOMMUNICATIONS PLAN

24ET101 - BLDG 24 - FLOOR 1 - TELECOMMUNICATIONS PLAN

24ET102 - BLDG 24 - FLOOR 2 - TELECOMMUNICATIONS PLAN

25ET100 - BLDG 25 - FLOOR 0 - TELECOMMUNICATIONS PLAN

25ET101 - BLDG 25 - FLOOR 1 - TELECOMMUNICATIONS PLAN

25ET102 - BLDG 25 - FLOOR 2 - TELECOMMUNICATIONS PLAN

25ET103 - BLDG 25 - FLOOR 3 - TELECOMMUNICATIONS PLAN

25ET104 - BLDG 25 - PENTHOUSE - TELECOMMUNICATIONS PLAN

51ET100a - BLDG 51 - FLOOR 0 - AREA A & C - TELECOMMUNICATIONS PLAN 51ET100b - BLDG 51 - FLOOR 0 - AREA E - TELECOMMUNICATIONS PLAN 51ET101a - BLDG 51 - FLOOR 1 - AREA A - TELECOMMUNICATIONS PLAN 51ET101b - BLDG 51 - FLOOR 1 - AREA B TELECOMMUNICATIONS PLAN 51ET101c - BLDG 51 - FLOOR 1 - AREA C TELECOMMUNICATIONS PLAN 51ET101d - BLDG 51 - FLOOR 1 - AREA D TELECOMMUNICATIONS PLAN 51ET101e- BLDG 51 - FLOOR 1 - AREA E TELECOMMUNICATIONS PLAN

51TET101 - BLDG 51T - FLOOR 1 - TELECOMMUNICATIONS PLAN

52ET100 - BLDG 52 - FLOOR 0 - TELECOMMUNICATIONS PLAN

52ET101 - BLDG 52 - FLOOR 1 - TELECOMMUNICATIONS PLAN

52ET102 - BLDG 52 - FLOOR 2 - TELECOMMUNICATIONS PLAN

53ET100 - BLDG 53 - FLOOR 0 - TELECOMMUNICATIONS PLAN

53ET101 - BLDG 53 - FLOOR 1 - TELECOMMUNICATIONS PLAN

53ET102 - BLDG 53 - FLOOR 2 - TELECOMMUNICATIONS PLAN

53ET103 - BLDG 53 - PENTHOUSE - TELECOMMUNICATIONS PLAN

53TET101 - BLDG 53T - FLOOR 1 - TELECOMMUNICATIONS PLAN

54ET100 - BLDG 54 - FLOOR 0 - TELECOMMUNICATIONS PLAN

54ET101 - BLDG 54 - FLOOR 1 - TELECOMMUNICATIONS PLAN

54ET102 - BLDG 54 - FLOOR 2 - TELECOMMUNICATIONS PLAN

55ET101a - BLDG 55 - FLOOR 1 - AREA A - TELECOMMUNICATIONS PLAN 55ET101b - BLDG 55 - FLOOR 1 - AREA B - TELECOMMUNICATIONS PLAN 55ET102a - BLDG 55 - FLOOR 2 - AREA A - TELECOMMUNICATIONS PLAN 55ET102b - BLDG 55 - FLOOR 2 - AREA B - TELECOMMUNICATIONS PLAN 55ET103a - BLDG 55 - FLOOR 3 - AREA A - TELECOMMUNICATIONS PLAN 55ET103b - BLDG 55 - FLOOR 3 - AREA B - TELECOMMUNICATIONS PLAN

56ET100 - BLDG 56 - FLOOR 0 - TELECOMMUNICATIONS PLAN

56ET101 - BLDG 56 - FLOOR 1 - TELECOMMUNICATIONS PLAN

56ET102 - BLDG 56 - FLOOR 2 - TELECOMMUNICATIONS PLAN

56ET103 - BLDG 56 - FLOOR 3 - TELECOMMUNICATIONS PLAN

57ET101 - BLDG 57 - FLOOR 1 - TELECOMMUNICATIONS PLAN

58ET101 - BLDG 58 - FLOOR 1 - TELECOMMUNICATIONS PLAN

60ET101 - BLDG 60 - FLOOR 1 - TELECOMMUNICATIONS PLAN

60TET101 - BLDG 60T - FLOOR 1 - TELECOMMUNICATIONS PLAN

75ET101 - BLDG 75 - FLOOR 1 - TELECOMMUNICATIONS PLAN

75ET102 - BLDG 75 - MEZZANINE - TELECOMMUNICATIONS PLAN

CET101 - BLDG 1-24 - FLOOR 0 - CORRIDOR WIRELESS ACCESS POINT

TELECOMMUNICATIONS PLAN

CET102 - BLDG 1-24 - FLOOR 1 - CORRIDOR WIRELESS ACCESS POINT

TELECOMMUNICATIONS PLAN

CET103 - BLDG 23-51-65 - FLOOR 1 - CORRIDOR WIRELESS ACCESS POINT

TELECOMMUNICATIONS PLAN

CET104 - BLDG 51-52-53-60 - FLOOR 1 - CORRIDOR WIRELESS ACCESS POINT

TELECOMMUNICATIONS PLAN

01ET400a - BLDG 01 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 01ET400b - BLDG 01 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 01ET401a - BLDG 01 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 01ET401b - BLDG 01 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

01ET402 - BLDG 01 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

01ET403a - BLDG 01 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS 01ET403b - BLDG 01 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS

02ET400 - BLDG 02 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

02ET401 - BLDG 02 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

02ET402 - BLDG 02 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

02ET403 - BLDG 02 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS

03ET400 - BLDG 03 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

03ET401 - BLDG 03 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

03ET402 - BLDG 03 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

03TET401 - BLDG 03T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

18ET400 - BLDG 18 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

18ET401 - BLDG 18 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

18ET402 - BLDG 18 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

18ET403 - BLDG 18 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS

23ET400 - BLDG 23 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

23ET401 - BLDG 23 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

24ET400 - BLDG 24 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

24ET401 - BLDG 24 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

24ET402 - BLDG 24 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

25ET401 - BLDG 25 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

25ET402 - BLDG 25 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

25ET403 - BLDG 25 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS

51ET400 - BLDG 51 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

51ET401a - BLDG 51 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 51ET401b - BLDG 51 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 51ET401c - BLDG 51 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

51TET401 - BLDG 51T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

52ET400 - BLDG 52 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

52ET401a - BLDG 52 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 52ET401b - BLDG 52 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 52ET401c - BLDG 52 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 52ET402a - BLDG 52 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 52ET402b - BLDG 52 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 53ET400a - BLDG 53 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 53ET400b - BLDG 53 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 53ET401a - BLDG 53 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 53ET401b - BLDG 53 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

53ET402 - BLDG 53 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

53TET401 - BLDG 53T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

55ET401a - BLDG 55 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 55ET401b - BLDG 55 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 55ET401c - BLDG 55 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 55ET402a - BLDG 55 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 55ET402b - BLDG 55 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 55ET403a - BLDG 55 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS 55ET403b - BLDG 55 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS

56ET400 - BLDG 56 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

56ET401 - BLDG 56 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

56ET402 - BLDG 56 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

56ET403 - BLDG 56 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS

57ET401a - BLDG 57 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 57ET401b - BLDG 57 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 58ET401a - BLDG 58 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 58ET401b - BLDG 58 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

60ET401 - BLDG 60 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

60TET401 - BLDG 60T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

75ET401 - BLDG 75 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

ET501 - TELECOMMUNICATIONS DETAILS

ET502 - TELECOMMUNICATIONS DETAILS

ET503 - TELECOMMUNICATIONS DETAILS

ET601 - FIBER OPTIC NETWORK DIAGRAM

ET602 - FIBER OPTIC NETWORK DIAGRAM

ET603 - FIBER OPTIC NETWORK DIAGRAM

ET701 - TELECOMMUNICATIONS SCHEDULES

FLEXIBLE CONDUIT

CONDUIT TURNED UP OR TOWARD

CONDUIT TURNED DOWN OR AWAY

CONDUIT CAPPED

T E L E C O M M U N I C A T I O N S L E G E N D

COMMUNICATION OUTLETS

FLOOR MOUNTED TELECOMMUNICATIONS OUTLET.

# = INDICATES QUANTITY OF VOICE AND DATA JACKS

WALL MOUNTED TELECOMMUNICATIONS OUTLET. 18" AFF UON

# = INDICATES QUANTITY OF VOICE AND DATA JACKS

OUTLET; LETTER INDICATES AS FOLLOWS:

A=AUDIO V=VIDEO I=INTERCOM

OUTLET, TELEVISION

BLANK = 4 11/16" MASTER ANTENNA OUTLET BOX WITH BLANK

COVER, MTD. 18" AFF UNLESS OTHERWISE NOTED.

C = CAMERA (CCTV SYSTEM), MTD 18" AFF

M = MONITOR (CCTV SYSTEM).

TELECOMMUNICATIONS OUTLET, SPECIAL PURPOSE.

REFERENCE KEY NOTES ON PLANS FOR ADDITIONAL

INFORMATION.

S

WAP

A/V

S C

C

TGB

FNC

FIBEROPTICS LINE = FO

TELEPHONE LINE = T

SPEAKER, CEILING MOUNTED

SPEAKER, WALL MOUNTED, MTD. 7'-6" AFF UON.

RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" AFF UON.

M = SPEAKER PROGRAM SELECTOR SWITCH & VOLUME

CONTROL

3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD.

4'-6" AFF.

REMOTE DICTATING OUTLET MTD 1'-6" AFF. UON.

INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL

OPERATION OF INSTRUMENT & TYPE REQUIRED).

S = STAFF STATION

WIRELESS ACCESS PORT

WALL MOUNTED SPEAKER/CLOCK COMBINATION

WALL CLOCK

CABLE TRAY

RECESSED AUDIO FLOOR BACK BOX, OUTLET AND CONDUIT

TELECOMMUNICATIONS SYSTEMS BONDING BUSBAR

FIBER OPTIC NETWORK CARD

COMMUNICATION

SECTION A

XXX

SECTION LETTER

SHEET WHERE

SECTION IS TAKEN

FROM

A

XXX

SECTION LETTER

SHEET WHERE

SECTION IS TAKEN

FROM

XXX

DETAIL NUMBER

SHEET ON WHICH

DETAIL APPEARS

DETAIL AREA

SCALE

XXXNG

CONDUIT & WIRE TAG

(REFER TO CONDUIT

AND WIRE SCHEDULE)

XX FAULT CURRENT TAG

(3 PH, SYM AMPS)

1 KEY NOTE

XXX

FIGURE OR PHOTO

DETAIL NUMBER

IF PHOTO, ARROW

DENOTES DIRECTION

TAKEN

SHEET WHERE DETAIL

IS TAKEN FROM

DETAIL/PLAN

DETAIL/PLAN NUMBER

G E N E R A L S Y M B O L S

AFC

AFG

AF

AFCI

AFF

AIC

AHJ

ATS

C

CATV

CB

CCTV

CL

CO

DDC

DP

EC

EL

EMER

EN

EMT

ER

EX

FAAP

FACP

FCIO

FOIC

GFCI

GFP

GND

HTR

IG

IMC

J-BOX

LCP

MCA

MCB

MCC

MDP

MLO

MS

MTD

NAC

NEC

NFC

NIC

NL

NTS

OC

OH

OS

PIV

PNL

PS

PVC

R

RECPT

RMC

SAC

SB, SWBDm

SG

SM

SPD

TEL

TR

TYP

UON

UL

UG

VD

VFD

W

WP

XFMR

ABOVE FINISHED COUNTER

ABOVE FINISHED GRADE

AMP FRAME

ARC FLASH CIRCUIT INTERRUPTER

ABOVE FINISHED FLOOR

AMPERE INTERRUPTING CAPACITY

AUTHORITY HAVING JURISDICTION

AUTOMATIC TRANSFER SWITCH

CONDUIT OR CEILING

COMMUNITY ANTENNA TELEVISION

CIRCUIT BREAKER

CLOSED CIRCUIT TELEVISION

CONNECTOR LIGHTING

CONDUIT ONLY

DIRECT DIGITAL CONTROLS

DISTRIBUTION PANELBOARD

EMPTY CONDUIT

ELEVATION

EMERGENCY

EXISTING IN NEW LOCATION

ELECTRICAL METALLIC TUBING

EXISTING TO REMAIN

EXISTING

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

FURNISHED BY CONTRACTOR, INSTALLED

BY OWNER

FURNISHED BY OWNER, INSTALLED BY

CONTRACTOR

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT PROTECTION

GROUND

HEATER

ISOLATED GROUND

INTERMEDIATE METAL CONDUIT

JUNCTION BOX

LIGHTING CONTROL PANEL

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN DISTRIBUTION PANEL

MAIN LUGS ONLY

MOTOR STARTER

MOUNTED

NOTIFICATION APPLIANCE CABINET

NATIONAL ELECTRICAL CODE

NOT FOR CONSTRUCTION

NOT IN CONTRACT

NIGHT LIGHT

NOT TO SCALE

ON CENTER

OVERHEAD

OCCUPANCY SENSOR

POST INDICATOR VALVE

PANEL

POWER SUPPLY

POLYVINYL CHLORIDE

EXISTING TO BE REMOVED

RECEPTACLE

RIGID METAL CONDUIT

SMALL APPLIANCE CIRCUIT

SWITCHBOARD

SWITCHGEAR

SMART METER

SURGE PROTECTIVE DEVICE

TELEPHONE

TAMPER RESISTANT

TYPICAL

UNLESS OTHERWISE NOTED

UNDERWRITERS LABORATORIES

UNDERGROUND

VOLTAGE DROP

VARIABLE FREQUENCY DRIVE

WEATHERPROOF (WHILE IN USE)

WEATHERPROOF

TRANSFORMER

A B B R E V I A T I O N S

AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BELL C-CHIME H-HORN K-KLAXON

L-LISTEN M-MICROPHONE S-SOUNDER S-SPEAKER Z-BUZZER

KEYPAD DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR WALL CALL

M-MAG STRIP P-PROXIMITY S-SMART CARD T-TOKEN

D DOOR CONTACT

ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DEADBOLT H-HYBRID L-LATCH SET S-STRIKE

INTERCOM; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

M-MASTER S-SUBSTATION

MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC

PUSH BUTTON; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BELL PUSH D-DURESS P-PANIC R-DOOR OPENER X-REQUEST FOR EXIT

SECURITY ACCESS, ANNUNCIATOR PANEL

SECURITY ACCESS, VIDEO CAMERA WITH LENS

SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW

SECURITY ACCESS, PANNING CAMERA TRAVERSE ANGLE

SAFETY AND SECURITY

M = MOUNTING FOR ALL SAFETY AND SECURITY SYMBOLS:

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

NURSE CALL

FIRE ALARM

PS

WG

NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER TOP UNLESS

OTHERWISE NOTED.

NURSE CALL TERMINAL CABINET.

NURSE CALL STATION.

D E

P S

U

= DUPLICATE PATIENT STATIONS (SEPARATE INDICATORS AT

MASTER STATION) MTD 5'-0" AFF UNLESS OTHERWISE NOTED

= DUTY STATION. MTD 5'-0" AFF UNLESS OTHERWISE NOTED

= STATION MTD 6'-0" AFF FOR SHOWER LOCATION, MTD 4'-6" AFF

FOR TUB LOCATION, & MTD 3'-0" AFF FOR TOILET LOCATION,UON

= PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH

= AUDIO VISUAL WALL STATION (STAFF) MTD 5'-0" AFF UNLESS

OTHERWISE NOTED

= UTILITY CALL STATION, MTD 5'-0" AFF UNLESS OTHERWISE NOTED

NURSE CALL STATION.

D I

= NURSE'S CALL DOME LIGHT (SUFFIX INDICATES NO. OF LAMP)

MTD 6" ABOVE DOOR

= CORRIDOOR DOME LIGHT.

= AUXILIARY INTERSECTIONAL DOME LIGHT.

NIGHT LIGHT

PATIENT BED OUTLETB

POWER SUPPLY WITH BATTERY BACKUP

WANDER GUARD

R

C

C

F

K

A

ADDRESSABLE RELAY

ALARM, FIRE, COMMUNICATOR

ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:

FACC = CENTRAL CONSOLE FACP = CONTROL PANEL

MFACP = MASTER CONTROL PANEL FAAP = ANNUNCIATOR PANEL

ALARM, FIRE; LETTERS INDICATE AS FOLLOWS:

BATT = BATTERIES CHR = CHARGER FAR = RECORDER

ALARM, FIRE, VALVE SUPERVISORY SWITCH.

ALARM, FIRE, TERMINAL CABINET.

ALARM, FIRE, POST INDICATOR VALVE.

ALARM, TRANSPONDER OR TRANSMITTER.

ALARM, FIRE, MANUAL PULL STATION

C = WITH CLEAR PLASTIC COVER

ALARM, HORN/LIGHT, ONE ASSEMBLY

C = WITH CHIME

ALARM, HORN/LIGHT, SEPARATE ASSEMBLY

ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE

ALARM, MANUAL CONTROL

ALARM, MINI HORN

ALARM, SPRINKLER SYSTEM WATER FLOW BELL

ALARM, VOICE COMMUNICATION PANEL

ALARM, TAMPER SWITCH

DETECTION, GAS

C = CARBON DIOXIDE TRANSMITTER

DETECTOR, FLOW SWITCH

DETECTOR, HEAT

DETECTOR, SMOKE

DETECTOR, SMOKE, FOR DUCT

ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET

CITY FIRE ALARM MASTER STATION MTD 5'-6" AFF UNLESS NOTED.

FIRE ALARM TRANSMITTER (BASE LOOP) NUMERALS DENOTE CODE.

FIRE ALARM TROUBLE TRANSMITTER (BASE LOOP) NUMERALS

DENOTE CODE.

FIRE SPRINKLE WATER FLOW SWITCH

KITCHEN HOOD FIRE SUPPRESSION SYSTEM

REMOTE ANNUNCIATOR

SPECIAL SYSTEMS

P

AUDIO CONTROLLER

PRESSURE BEACON

PRESSUR…