657-21-701JB - Addendum 1_03_24_23.pdf
PDF 6 MB Posted
- Attached to
- Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks Federal contract opportunity
- Solicitation number
- 36C77623R0009
About this file
This federal contract opportunity solicitation seeks a general contractor to provide infrastructure upgrades at the St. Louis Jefferson Barracks VA Medical Center. Work will include electrical panel upgrades and power systems work, building management system integration, HVAC assessments and upgrades, data center renovations, communications infrastructure installation including upgrading outlets and cables to Cat6a, physical security enhancements, fiber optic backbone assessment and upgrades both within and between buildings, and hazardous material abatement. The locations include Buildings 1-3, 3T, 18, 23-25, 51, 51T, 52-53, 53T, 55-58, 59-61, 75 and associated site work. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.
View the file
Other files for this federal contract opportunity
Show all 50
Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AB
ABA
AC(T)
ACM
ACW
ADA
ADJ
A/E
AF
AFF
AGG
ALT
ALUM
APPROX
ARCH
ASPH
A/V
BARR
BATH
BB
BLDG
BLK
BLKG
BLW
BM
BMTU
BO
BOC
BOS
BRC
BRKT
BRNG
BTM
BTWN
CAB
CC
CD
CJ
CLG
CLR
CMU
CO
COL
COMP
CONC
CONN
CONST
CONT
COORD
COR
CORR
CS
CT
CTR
CV
AND
ANGLE
AT
CENTERLINE
DEGREES
NUMBER
ANCHOR BOLT
ARCHITECTURAL BARRIERS ACT
ACOUSTICAL CEILING (TILE)
ASBESTOS CONTAINING MATERIAL
ACOUSTICAL WALL
AMERICANS W/ DISABILITIES ACT
ADJACENT
ARCHITECT/ENGINEER
ACCESS FLOOR
ABOVE FINISH FLOOR
AGGREGATE
ALTERNATE
ALUMINUM
APPROXIMATELY
ARCHITECT(URAL)
ASPHALT
AUDIO / VIDEO
BARRIER
BATHROOM
BACKER BOARD
BUILDING
BLOCK
BLOCKING
BELOW
BEAM
BONE MARROW TRANSPLANT UNIT
BOTTOM OF
BOTTOM OF CURB
BOTTOM OF SLAB
BRACE, BRACING
BRACKET
BEARING
BOTTOM
BETWEEN
CABINET
CONTRACTOR FURN, CONTRACTOR INST
CONSTRUCTION/CONTRACT DOCUMENTS
CONTROL JOINT
CEILING
CLEAR(ANCE)
CONCRETE MASONRY UNIT
CONTRACTING OFFICER
COLUMN
COMPOSITION
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
COORDINATE
CONTRACTING OFFICER REPRESENTATIVE
CORRIDOR
CONCRETE SEALER
CERAMIC TILE
CENTER
CONTRACTOR FURNISHED, VA INSTALLED
HDR
HDWE
HM
HORZ
HPDL
HR
HT
HVAC
ICRA
ID
ILSM
INCL
INST
INSUL
INT
JT
KV
LAM
LAV
LCM
LT
MAT
MAX
MDF
MECH
MEP
MFR
MIN
MISC
MOD
MTL
N N/A
NEG
NO.
NOM
NTS
O.C.
OPNG
OPP
OPT
OVHD
P
PCONC
PCRA
PL
PLAM
PLY(WD)
PNL
PR
PRFB
PS
PT
PTN(S)
PVMT
QTY
HEADER
HARDWARE
HOLLOW METAL
HORIZONTAL
HIGH PRESSURE DECORATIVE LAM
HOUR
HEIGHT
HEATING, VENTILATION & AIR CONDITIONING
INFECTIOUS CONTROL RISK ASSESSMENT
INSIDE DIAMETER OR DIM
INTERIM LIFE SAFETY MEASURES
INCLUDE(D,ING)
INSTALL
INSULATION
INTERIOR
JOINT
KILOVOLT
LAMINATE(D)
LAVATORY
LEAD CONTAINING MATERIAL(S)
LIGHT
MATERIAL(S)
MAXIMUM
MEDIUM-DENSITY FIBREBOARD
MECHANIC(AL)
MECHANICAL, ELECTRICAL, PLUMBING
MANUFACTURE(R)
MINIMUM
MISCELLANEOUS
MODIFIED
METAL
NORTH
NOT APPLICABLE
NEGATIVE
NUMBER
NOMINAL
NOT TO SCALE
ON CENTER(S)
OPENING
OPPOSITE
OPTION(AL)
OVERHEAD
PAINT
PRECAST CONCRETE
PRE-CONSTRUCTION RISK ASSESSMENT
PLATE
PLASTIC LAMINATE
PLYWOOD
PANEL
PAIR
PREFABRICATED
PLASTIC
PRESSURE TREATED
PARTITION(S)
PAVEMENT
QUANTITY
RAD
RCP
REF
REINF
REP
REQ(s,(')D)
RESIL
REV
RF
RM
RMV
RO
S
SCHED
SD
SECT
SF
SFRM
SHG
SHT(G)
SIM
SM
SOW
SPEC
SQ
SS
ST
STDG
STL
STOR
STRUCT
SUSP
SV
SYS
TEMP
T&G
THK
THRESH
TOC
TOS
TPH
TRANS
TS
TYP
UON
VA
VAR
VB
VC
VERT
VIF
VV
W W/
WD
WDW
WGHT
W/O
WP
WR
RADIUS
REFLECTED CEILING PLAN
REFERENCE
REINFORCE(D,ING)
REPRESENTATIVE
REQUIRE(D,S,MENT(S))
RESILIENT
REVERSE
RADIO FREQUENCY / ROOF
ROOM
REMOVE
ROUGH OPENING
SOUTH
SCHEDULE
SCHEMATIC DESIGN
SECTION
SQUARE FEET
SPRAY APPLIED FIRE-RESISTIVE MATERIAL
SHINGLES
SHEET (SHEATHING)
SIMILAR
SEAM
SCOPE OF WORK
SPECIFICATION
SQUARE
STAINLESS STEEL
STAIN
STANDING
STEEL
STORAGE
STRUCTURAL
SUSPENDED
SHEET VINYL
SYSTEM
TEMPORARY
TONGUE AND GROOVE
THICK(NESS)
THRESHOLD
TABLE OF CONTENTS
TOP OF SLAB
TOILET PAPER HOLDER
TRANSITION
TUBE STEEL
TYPICAL
UNLESS OTHERWISE NOTED
VETERANS AFFAIRS
VARIES
VAPOR BARRIER
VA FURNISHED, CONTRACTOR INSTALLED
VERTICAL
VERIFY IN FIELD
VA FURNISHED, VA INSTALLED
WEST
WITH
WOOD
WINDOW
WEIGHT
WITHOUT
WATERPROOF(ING)
WATER RESISTANT
DBL
DC
DD
DEMO
DEPT
DG
DIA
DIM
DWN
DR
DTL
DWG
E
EA
EJ
ELEC
ELEV
ENG
EOC
EOP
EPDM
EQ
EQUIP
ES
ETS
EX(IST)
EXP
EXT
FA
FD
FE(C)
FF
FFB
FFL
FIN
FLASH
FLR
FLRSNT
FNDN
FOC
FOF
FOS
FP
FR
FRM
FT
FTG
FUR
FURN
GA
GALV
GE
G(W)B
GC
GL
GLB
GMU
GOV(T)
GYP
DOUBLE
DIRECT CURRENT
DESIGN DEVELOPMENT
DEMOLISH(ION)
DEPARTMENT
DESIGN GUIDE
DIAMETER
DIMENSION
DOWN
DOOR
DETAIL
DRAWING(S)
EAST
EACH
EXPANSION JOINT
ELECTRIC(AL)
ELEVATION OR ELEVATOR
ENGINEER(ING)
EDGE OF CURB
EDGE OF PAVEMENT
ETHYLENE PROPYLENE DIENE TERPOLYMER
EQUAL
EQUIPMENT
EACH SIDE
EXPOSED TO STRUCTURE
EXISTING
EXPANSION
EXTERIOR
FIRE ALARM
FLOOR DRAIN
FIRE EXTINGUISHER (CABINET)
FACTORY FINISH
FINISH FLOOR BREAK
FINISH FLOOR LINE
FINISH(ED)
FLASHING
FLOOR(ING)
FLORESCENT
FOUNDATION
FACE OF CONCRETE
FACE OF FINISH
FACE OF STUDS
FIRE PROOF
FIRE RATED
FRAME
FOOT, FEET
FOOTING
FURRING
FURNISHED
GAGE, GAUGE
GALVANIZED
GENERAL ELECTRIC
GYPSUM (WALL) BOARD
GENERAL CONTRACTOR
GRID LINE
GLUE LAMINATED BEAM
GLASS MASONRY UNIT
GOVERNMENT
GYPSUM BOARD
A101
1 TYP
101.1
A-101
SIM
EXTERIOR ELEVATION
INTERIOR ELEVATION
BUILDING SECTION FLAG
WALL SECTION FLAG
CALLOUT FLAG
VERTICAL GRID LINE
HORIZONTAL GRID LINE
TRUE NORTH ARROW
PROJECT NORTH ARROW
(TRUE NORTH DASHED)
ELEVATION MARKER
KEY NOTE
ROOM TAG (SF OPTIONAL)
CEILING HEIGHT TAG
ROOM NAME
150 SF
A
A-101
SIM
01A
TRUE
NORTH
W1
A-101
PROJECT
NORTH
WALL TAG
FLOOR TAG
ROOF TAG
DOOR TAG
WINDOW TAG
SPECIALTY EQUIPMENT TAG
SIGNAGE TAG
SIGNAGE KEY NOTE
(AW SHEETS ONLY)
SIGNAGE MATERIAL TAG
(AW SHEETS ONLY)
EXISTING TO REMAIN
NEW CONSTRUCTION
TO DEMOLISH
HIDDEN ABOVE OR BELOW
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
NEW DOOR
SMOKE ZONE
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
SMOKE RATED WALL
SMOKE & 1 HR FIRE RATED WALL
PATIENT NON-SLEEPING SUITE
AREA OF WORK / AREA SHOWN
CONSTRUCTION ZONE, ( - - )
PRESSURE
ANTE ROOM, ( - ) PRESSURE
TEMPORARY ICRA BARRIER
TEMPORARY ICRA DOOR
PATH OF TRAVEL
EMERGENCY EGRESS PATHWAY
SEISMIC JOINT
BATT INSULATION
RIGID INSULATION
GYPSUM BOARD, TYPE X
ACOUSTICAL CEILING TILE, 2' x 2'
CONCRETE
STEEL
PLYWOOD, FIRE RATED
EARTH
SUPPLY GRILLE PER MECHANICAL
(SIZE & PROPORTIONS MAY VARY)
RETURN GRILLE PER MECHANICAL
(SIZE & PROPORTIONS MAY VARY)
LIGHTING PER ELECTRICAL
(SIZE & PROPORTIONS MAY VARY)
FIRE EXTINGUISHER CABINET
A-101
A01
D88
A5175SOAP DISH
IN-04.02-01
AFF
GYP ON MTL STUD
9' - 0"
FEC
F-1
R-1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
A-001
ARCHITECTURAL SYMBOLS &
ABBREVIATIONSSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 EM AJ
CONSTRUCTION
DOCUMENTS
SYMBOLS ABBREVIATIONS
GENERAL NOTES
APPLICABLE PUBLICATIONS
1. MAINTAIN A SAFE, CLEAN CONSTRUCTION ZONE AT ALL TIMES.
2. DO NOT SCALE DRAWINGS.
3. DIMENSIONS ARE NOT ADJUSTABLE UNLESS NOTED WITH A +/- SYMBOL. ONLY NORMAL
INDUSTRY STANDARD TOLERANCES ARE ACCEPTABLE DEVIATIONS FROM DIMENSIONS
INDICATED.
4. ALL DIMENSIONS NOTED AS CLEAR SHALL MAINTAIN THE FULL SPACE INDICATED WITHOUT
ENCROACHMENTS.
5. FURNISH ALL MATERIALS & PRODUCTS TO COMPLY WITH THE CONTRACT DOCUMENTS.
6. ALL VERTICAL HEIGHTS INDICATED ARE FROM THE FINISH FLOOR ELEVATION, UON.
7. ANY AND ALL WALL MOUNTED EQUIPMENT SHALL HAVE BLOCKING IN WALL BEHIND, THIS
INCLUDES BACKING FOR WALL MOUNTED DOOR STOPS. ENSURE THAT ALL REQUIRED
BACKING IS INSTALLED IN WALLS PRIOR TO INSTALLING DRYWALL.
8. IN TOILET ROOMS PROVIDE STAINLESS STEEL FILLER BEHIND ANY MIRRORS AND OTHER
WALL MOUNTED ACCESSORIES WHEN ITEM IS INSTALLED PARTIALLY OVER CERAMIC TILE.
9. CONTRACTOR SHALL INSTALL FASCIA COVERS FOR HEADWALLS.
10. SEGREGATE ALL NURSE CALL, FIRE ALARM AND SECURITY SYSTEM ALARM WIRES FROM
THE DATA CABLES WHEN THEY ARE INTERMIXED. CONTRACTOR SHOULD EXPECT WIRES
TO BE INTERMIXED IN CERTAIN AREAS OF THE FACILITY TO INCLUDE BUT NOT LIMITED TO
CABLE TRAYS, J-HOOKS AND IN OPENINGS.
11. MOVE AND STORE ALL FURNITURE, FIXTURES, AND EQUIPMENT (FFE) AS NEEDED. FFE WILL
BE COVERED WITH PLASTIC BEFORE BEING MOVED. FFE WILL BE MOVED BACK TO THE SAME
LOCATION IT WAS ORIGINALLY LOCATED WHEN CONTRACTORS WORK IS COMPLETE. IF
EQUIPMENT NEEDS TO BE MOVED OUTSIDE THE ROOM IT IS THE CONTRACTOR'S
RESPONSIBILITY TO COVER ALL COSTS ASSOCIATED WITH MOVING, STORING, AND
REINSTALLING FFE.
12. WHEN THE CONTRACTOR MOVES FFE, THE CONTRACTOR IS RESPONSIBLE FOR UNPLUGGING
ALL EQUIPMENT FROM WALLS APPROPRIATELY. DURING REINSTALLATION OF FFE, IT IS THE
CONTRACTOR'S RESPONSIBILITY TO RECONNECT POWER PLUGS. THE VA WILL RECONNECT
ALL DATA TO THE NEW CAT 6A DATA PORTS.
APPLICABLE PUBLICATIONS GENERAL NOTES
AS AN AGENCY OF THE FEDERAL GOVERNMENT, THE VA IS NOT SUBJECT TO LOCAL IMPOSITIONS
OF CODE ENFORCEMENT PROCEDURES ( DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS,
FEES, ETC). THE VA SHALL FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ).
VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD
APPLICATION GUIDE AND OTHER GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL).
INTERNATIONAL BUILDING CODE (IBC) 2018.
INTERNATIONAL EXISTING BUILDING CODE (IEBC) 2018.
NATIONAL FIRE PROTECTION AGENCY (NFPA) 101 LIFE SAFETY CODE. NFPA 101 TAKES
PRECEDENCE OVER IBC.
NFPA NATIONAL FIRE CODES, WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900.
OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
VA SEISMIC DESIGN REQUIREMENTS, H-18-8.
NATIONAL ELECTRICAL CODE (NEC).
INTERNATIONAL PLUMBING CODE (IPC).
SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAL SOCIETY OF MECHANICAL
ENGINEERS (ASME) A 17.1.
ASME BOILER AND PRESSURE VESSEL CODE
ASME CODE FOR PRESSURE PIPING
ARCHITECTURAL BARRIER ACT ACCESSIBILITY STANDARDS (ABAAS), INCLUDING VA SUPPLEMENT
BARRIER FREE DESIGN GUIDE (PG-18-3)
BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE INSTITUTE
AND COMMENTARY (ACI 318)
MANUAL OF STEEL CONSTRUCTION , LOAD AND RESISTANCE FACTOR DESIGN SPECIFICATIONS FOR
STRUCTURAL STEEL BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
ENERGY POLICY ACT OF 2005 (EPACT)
DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL
AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-RESE RESIDENTIAL
BUILDINGS, 10 CFR PARTS 433,434 AND 435.
FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF
UNDERSTANDING (MOU)
EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY AND
TRANSPORTATION MANAGEMENT.
THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL
REQUIREMENTS SECTION 01 01 0 OF THE VA MASTER CONSTRUCTION SPECIFICATION.
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY - ASHRAE STANDARD 62.1 - 2004.
SAFETY STANDARD FOR REFRIGERATION SYSTEMS - ASHRAE STANDARD 15 - 2007.
VAMC APPROVED HARDWARE LOCKING STANDARDS
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM)
FEDERAL COMMUNICATIONS COMMISSION (FCC), ALL REGULATIONS, PROCEDURES AND
STANDARDS FOR TWO-WAY RADIO EQUIPMENT, SYSTEMS AND OPERATION
ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IESNA)
INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE)
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO), STANDARDS FOR PROTOCOLS AND
INTERFACES THAT INCLUDE OPEN SYSTEM INTERCONNECTIONS (OSI)
JOINT COMMISSION ON ACCREDITATION OF HEALTHCARE ORGANIZATIONS (JACHO),
ENVIRONMENT OF CARE GUIDELINES AND STANDARDS
FACILITIES GUIDELINES INSTITUTE (FGI): 2010 , OR MOST CURRENT ISSUE, GUIDELINES FOR THE
DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES
THE AMERICAN INSTITUTE OF ARCHITECTS (AIA) AND NATIONAL SOCIETY OF PROFESSIONAL
ENGINEERS(NSPE) RECENT ADDITIONS TO THEIR PROFESSIONAL CODES OF ETHICS ENCOURAGING
“ENVIRONMENTALLY RESPONSIBLE DESIGN”
Revisions: Date:
13. REMOVAL OF EXISTING CEILING AND TURNING UPRIGHT EXISTING SPRINKLER HEADS NEED
TO BE COORDINATED TO HAPPEN CONCURRENTLY.
14. REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.
15. IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE
WORK SHIFT DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRE STOPPING
COMPOSED OF MINERAL WOOL SHOULD BE INSTALLED IN THE PENETRATION TO PROVIDE
PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED PENETRATION.
16. CONTRACTOR TO REPLACE EXISTING FIRE EXTINGUISHER WITHIN 75' WITH A CLEAN AGENT
FIRE EXTINGUISHER IN ACCORDANCE TO THE FIRE PROTECTION MANUAL AT ALL TELECOM
ROOMS.
17. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING HANDRAILS TO INSTALL NEW OIT
TELECOM ROOM DOORS. CONTRACTORS SHALL REINSTALL AND/OR KICK RAILS ON BOTH
SIDES OF NEW DOOR AS NEEDED, ALL RAILS AND KICK RAILS WILL BE TO CODE.
18. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING DAMAGED FLOOR TILES AFTER NEW
OIT TELECOM DOORS ARE INSTALLED. CONTACT COR TO SEE IF EXTRA FLOORING IS
AVAILABLE FOR TO MATCH EXISTING, IF NOT, PROVIDE REPLACEMENT FLOORING THAT IS AS
CLOSE AS POSSIBLE TO MATCH EXISTING.
03/10/23General Notes Clarification
B.2
B.8
5 6
" 3
" 13
23A-100
B.2
B.8
105 SF
TR
G09B
107 SF
LOCK SHOP
G09
10' - 3"
G09
2' - 4 3/4"
G B
523 SF
CORRIDOR
H002
01a
2' - 10" 2' - 3 1/2"
12 SF
CLOSET
H002A
E X
IS
T
F
L O
O R
IN
G
N E
W
F L O
O R
IN
G
23A-100
B.2
B.8
10' - 0"
B.2
B.8
10' - 0"
EXPOSED
105 SF
TR
G09B
107 SF
LOCK SHOP
G09
195 SF
CARPENTER
STORAGE
G10
523 SF
CORRIDOR
H002
12 SF
CLOSET
H002A
211 SF
LOCK SHOP
G09
12 SF
CLOSET
H002A
523 SF
CORRIDOR
H002
TO DEMOLISH
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
NEW DOOR
EXISTING WALL TO DEMOLISH (NON-BEARING METAL STUD WALL)
EXISTING LIGHTS TO DEMOLISH
211 SF
LOCK SHOP
G09
12 SF
CLOSET
H002A
523 SF
CORRIDOR
H002
( + ) PRESSURE
CONSTRUCTION ZONE, ( - - ) PRESSURE
ANTE ROOM, ( - ) PRESSURE
TEMPORARY ICRA BARRIER
TEMPORARY ICRA DOOR
CONSTRUCTION TACKY MATT
NEGATIVE AIR MACHINE
EXISTING RESILIENT BASE:
CUT AS REQUIRED FOR
NEW DOOR AND PATCH
CLEANLY TO NEW FRAME.
EXISTING WINDOW TO BE DEMOLISHED.
WHERE DOOR OCCURS: CAREFULLY CUT EXISTING
KICK-RAIL. SALVAGE END CAPS FOR REUSE. REINSTALL
KICK-RAILAND INSTALL SALVAGED END CAPS. PROVIDE
ADDITIONAL BLOCKING AND SUPPORTS FOR NEW END
OF KICK-RAIL AS NEEDED.
INFILL WALL WITH GWB WHERE WINDOW WAS
DEMOLISHED, PATCH AND PAINT TO MATCH EXISTING.
3' - 0"
RM G09
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 23A-100
BLDG 23 - FLOOR 0 - DEMO,
FLOOR PLANS & RCPS 23
EM AJ/ST/KBIssue Date
KEY PLAN
PROJECT
NORTH
LEGEND
1/4" = 1'-0"
RM G09 - DEMO FLOOR PLAN
1/4" = 1'-0"
RM G09 - FLOOR PLAN
1/4" = 1'-0"
RM G09 - DEMO RCP
1/4" = 1'-0"
RM G09 - RCP
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
GENERAL NOTES
1. ALL PRODUCTS AND WALL FINISHES SHALL MATCH EXISTING OR ADJACENT
EXISTING UNLESS OTHERWISE NOTED.
2. PATCH AND REPAIR WALLS WHERE MECHANICAL, PLUMBING, AND ELECTRICAL
ITEMS DEMO'D.
3. PATCH AND REPAIR FLOOR WHERE CONDUITS, PIPING AND SIMILAR ARE DEMO'D.
4. PATCH AND REPAIR EXISTING CEILING GRID AND TILES WHERE NEW WALLS
INSTALLED.
5. PATCH AND REPAIR GWB WHERE DOORS ARE DEMO'D AND NEW DOORS ARE
INSTALLED.
6. PROTECT FINISHES IN ROOMS ADJACENT TO NEW TELECOMMUNICATION ROOMS
AND AREAS NOT SCHEDULED FOR NEW WORK.
KEYNOTES
CONSTRUCT NEW WALL AND PATCH/PAINT TO MATCH EXISTING ON ROOM G09
SIDE.
INSTALL NEW DOOR/FRAME. INFILL WALL AS NECESSARY ABOVE DOOR WHERE
DEMOLISHED WINDOW WAS LLOCATED. SEE DETAIL 1/23A-100.
DEMO EXISTING SINK. SALVAGE SINK FOR REUSE.
DEMO EXISTING WINDOW, SAWCUT TO FLOOR. PREP FOR NEW DOOR/FRAME.
DEMO EXISTING DOOR/FRAME.
DEMO EXISTING LVT FLOORING TO EXPOSED CONCRETE SLAB UNDERNEATH.
REMOVE EXISTING ADHESIVE AND PREP FOR NEW FLOORING.
APPLY ANTI-STATIC COATING TO EXPOSED CONCRETE FLOOR. PROVIDE VINYL
REDUCER STRIP AT EXISTING FLOORING TRANSITION.
DEMO EXISTING WALLS. SEE MECHANICAL SHEETS FOR COORDINATION ON
PLUMBING.
DEMO EXISTIGN ACT COMPLETELY INCLUDING ALL GRID, SUPPORTING WIRES,
CLIPS, AND PERIMETER WALL ANGLES IN ROOM TO EXPOSE UNDERSIDE OF
STRUCTURE ABOVE. PATCH WALLS WHERE CEILING IS REMOVED.
PATCH AND REPAINT WALL AS NECESSARY TO MATCH EXISTING ON CORRIDOR
SIDE.
NEW FRT PLYWOOD OVER WALLS PER DETAIL 4/AE421.
INSTALL PHYSICAL SECURITY AT INTERIOR AND EXTERIOR OF EXISTING WINDOW.
REFERENCE DETAIL 4/A-603.
PLACE ADHESIVE WALK OFF MATS AT ENTRANCE AND EXIT SIDE OF
CONSTRUCTION AREA, TYP.
DEMO EXISTING BASE, PREP FOR NEW BASE.
INSTALL NEW BASE ON ALL WALLS OF NEW TELECOM ROOM.
Revisions: Date:
ICRA LEGEND
1/2" = 1'-0"
H002 CORRIDOR - NORTH INTERIOR ELEVATION
CONSTRUCTION
DOCUMENTS
Building 23 Floor Plan Update 03/10/23
B.2
B.8
5 6
9' - 3 1/2"
/4
CONFIRM WITH DOOR
MANUFACTURER, TYP
3' - 4" 4' - 4"
23A-101
1Sim
B.2
B.8
5 6
11 SF
OI&T
115B
102 SF
TR
121A
107 SF
PROSTHETICS
RESTORATION
A
9' - 3"
0' - 6"
169 SF
CORRIDOR
C119
54 SF
PROSTHETICS
RESTORATION
OFFICE
36 SF
ALCOVE
122A
284 SF
LAB DUSTER
115A
01a
PATCH AND REPAIR WALLS AND
FLOOR TO MATCH EXISTING
WHERE CABINETS AND
PLUMBING ARE REMOVED.
E X
IS
T
F
L O
O R
IN
G
N E
W
F L O
O R
IN
G
10' - 0"
B.2
B.8
5 6
9' - 11"
DEMO EXISTING LIGHTS
B.2
B.8
5 6
10' - 0"
10' - 0"
EXPOSED
102 SF
TR
121A
107 SF
PROSTHETICS
RESTORATION
284 SF
LAB DUSTER
115A
169 SF
CORRIDOR
C119
11 SF
OI&T
115B
416 SF
LAB WORK
INSTALL NEW ACT PANELS,
TO MATCH EXISTING
214 SF
PROSTHETICS
RESTORATION
LAB
11 SF
OI&T
115B
169 SF
CORRIDOR
C119
284 SF
LAB DUSTER
115A
416 SF
LAB WORK
54 SF
PROSTHETICS
RESTORATION
OFFICE
36 SF
ALCOVE
122A
TO DEMOLISH
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
NEW DOOR
EXISTING WALL TO DEMOLISH (NON-BEARING METAL STUD WALL)
EXISTING LIGHTS TO DEMOLISH
214 SF
PROSTHETICS
RESTORATION
LAB
11 SF
OI&T
115B
54 SF
PROSTHETICS
RESTORATION
OFFICE
36 SF
ALCOVE
122A
169 SF
CORRIDOR
C119
284 SF
LAB DUSTER
115A
416 SF
LAB WORK
WHERE NEW DOOR OCCURS: CAREFULLY
CUT EXISTING RAILING AND KICK-RAIL.
SALVAGE END CAPS FOR REUSE. REINSTALL
RAILING AND KICK-RAIL AND INSTALL
SALVAGED END CAPS. PROVIDE ADDITIONAL
BLOCKING AND SUPPORTS FOR NEW END OF
RAILING AND KICK-RAIL AS NEEDED.
EXISTING RESILIENT BASE:
CUT AS REQUIRED FOR NEW
DOOR AND PATCH CLEANLY
TO NEW FRAME.
( + ) PRESSURE
CONSTRUCTION ZONE, ( - - ) PRESSURE
ANTE ROOM, ( - ) PRESSURE
TEMPORARY ICRA BARRIER
TEMPORARY ICRA DOOR
CONSTRUCTION TACKY MATT
NEGATIVE AIR MACHINE
RM 121
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 23A-101
BLDG 23 - FLOOR 1 - DEMO,
FLOOR PLANS & RCPS 23
EM AJ/ST/ KBIssue Date
KEY PLAN
PROJECT
NORTH
LEGEND
1/4" = 1'-0"
RM 121 - DEMO FLOOR PLAN
1/4" = 1'-0"
RM 121 - FLOOR PLAN
1/4" = 1'-0"
RM 121 - DEMO RCP
1/4" = 1'-0"
RM 121- RCP
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
Revisions: Date:
GENERAL NOTES
1. ALL PRODUCTS AND WALL FINISHES SHALL MATCH EXISTING OR ADJACENT
EXISTING UNLESS OTHERWISE NOTED.
2. PATCH AND REPAIR WALLS WHERE MECHANICAL, PLUMBING, AND ELECTRICAL
ITEMS DEMO'D.
3. PATCH AND REPAIR FLOOR WHERE CONDUITS, PIPING AND SIMILAR ARE DEMO'D.
4. PATCH AND REPAIR EXISTING CEILING GRID AND TILES WHERE NEW WALLS
INSTALLED.
5. PATCH AND REPAIR GWB WHERE DOORS ARE DEMO'D AND NEW DOORS ARE
INSTALLED.
6. PROTECT FINISHES IN ROOMS ADJACENT TO NEW TELECOMMUNICATION ROOMS
AND AREAS NOT SCHEDULED FOR NEW WORK.
7. PATCH CONCRETE FLOOR WHERE CONDUITS OCCUR AT EXISTING WALL
LOCATIONS.
KEYNOTES
1 CONSTRUCT NEW WALL AND PATCH/PAINT TO MATCH EXISTING IN ROOM 121
SIDE.
INSTALL NEW DOOR/FRAME.
DEMO EXISTING CABINETRY AND SINK.
DEMO EXISTING WALL AND RAILING. PREP FOR NEW DOOR/FRAME. SEE DETAIL
1/23A-101.
DEMO EXISTING VCT FLOORING TO EXPOSED CONCRETE SLAB UNDERNEATH.
REMOVE EXISTING ADHESIVE AND PREP FOR NEW FLOORING.
APPLY ANTI-STATIC COATING TO EXPOSED CONCRETE FLOOR. PROVIDE VINYL
REDUCER STRIP AT EXISTING FLOORING TRANSITION.
DEMO EXISTING ACT COMPLETELY INCLUDING ALL GRID, SUPPORTING WIRES,
CLIPS, AND PERIMETER WALL ANGLES IN ROOM TO EXPOSE UNDERSIDE OF
STRUCTURE ABOVE. PATCH WALLS WHERE CEILING IS REMOVED.
PATCH AND REPAINT WALL AS NECESSARY ON CORRIDOR SIDE TO MATCH
EXISTING.
NEW FRT PLYWOOD OVER WALLS PER DETAIL 4/AE421.
INSTALL PHYSICAL SECURITY AT INTERIOR AND EXTERIOR OF EXISTING
WINDOW. REFERENCE DETAIL 4/A-603.
PLACE ADHESIVE WALK OFF MATS AT ENTRANCE AND EXIT SIDE OF
CONSTRUCTION AREA, TYP.
DEMO EXISTING BASE, PREP FOR NEW BASE.
INSTALL NEW BASE ON ALL WALLS OF NEW TELECOM ROOM.
NTS
C119 - CORRIDOR
ICRA LEGEND
CONSTRUCTION
DOCUMENTS
Building 23 Floor Plan Update 03/10/23
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
EP704
ELECTRICAL SCHEDULE
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 Checker Author
CONSTRUCTION
DOCUMENTS
Revisions: Date:
REVISED SCHEDULES.1 03/10/2023
DN
UP
4160 VO
LTS
DUST CO
LLECTO
R
LIQ UEFIED PETRO LEUM G AS
FLAM M ABLE G AS 2
TRASH COM
PACTO
R
P
SILVERBUILDING 1 23
VA PO
LICE
E
LECTRIC ACCESS
TRANSFO
RM
ER
TRANSFO
RM
ER
TRANSFO
RM
ER
HVAC UNIT
E
LECTRIC PANEL
HVAC UNIT
S&C PAD M
O
UNTED G
EAR
CATALO
G
# 55152-C3DGIG
2P1V M
O
DEL# PM
H-9
EE13299 SG
-52
13278
BUILDING
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
TR
G09B
23ET400
23ET400
5 6
LOCK SHOP
G09
CARPENTER STORAGE
G10
CARPENTER SHOP OFFICE/ KEY
PICK-UP
G25
TRASH RM.
G13B
BREAK RM. / STORAGE
G23
CARPENTER SHOP
G26
LOCKER, MALE
G15
TOILET / SHOWER
G16
STORAGE
G14
STAIRWELL NO. 1
S1
CORRIDOR
H001
TOILET, MEN
G12
STORAGE
G13
LOCKER, MALE
G11
CHARGING STATION
G07
STORAGE
G08
KEY SHOP
G09A
BREAK RM.
G04 STORAGE
G05
OFFICE
G01A
ELEC RM.
G01
MECH. RM.
G02
ELEC RM.
G03
CORRIDOR
H002
BATTERY STORAGE
G13C
WASH RM.
G13A
STAIRWELL NO. 2
S2
MECH. RM.
G17
CORRIDOR
H000
ELEVATOR
E-1
B
C
D
E
F
G
A
B.2
B.8
C.6
D.4
E.2
E.8
1 2 3 4 7
3.4
E.5
D.5
C.5
B.5
E.6
23ET400
TYP
WAP 1
HAND HOLE
TYP.
SIDE-B FIBER-OPTIC BACKBONE:
REFERENCE COMMUNICATION
SHEETS FOR ADDITIONAL
INFORMATION REGARDING
HANDHOLE,CONDUIT, BUILDING
PENETRATIONS, FIBER-OPTIC
CABLING, AND RACEWAY
INFORMATION
TDU 5
TYP.
EXISTING SIDE-A FIBER-OPTIC BACKBONE
BUILDING ENTRY POINT (APPROXIMATE
LOCATION). ROUTE FIBER-OPTIC CABLES TO TRs
AS INDICATED ON COMMUNICATIONS DRAWINGS;
REFERENCE COMMUNICATIONS DRAWINGS FOR
ALL FIBER-OPTIC CABLING, RACEWAY TYPES,
SPECIFICATIONS, AND RATINGS. REFERENCE KEY
NOTES ON THIS SHEET REGARDING CABLE TRAY
AND VERTICAL/HORIZONTAL ROUTING FOR
ADDITIONAL FIBER BACKBONE CABLING
REQUIREMENTS.
DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE
SERVED FROM TELECOMMUNICATION ROOM G09B.
ALL BACKBONE CABLING ROUTES ARE
DIAGRAMMATICAL; CONTRACTOR SHALL ENSURE A-
SIDE AND B-SIDE ROUTING IS AS DIVERSE AS
PRACTICAL. REFERENCE COMMUNICATIONS
DRAWINGS FOR ALL REQUIRED FIBER-OPTIC
CABLING.
9.99.89.79.59.38.57.86.36.1
V
U
CORRIDOR
UTILITY
LOBBY
ELEVATOR LOBBY
EQUIPMENT
ELEVATOR
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO
BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE ACCEPTANCE OF THE
OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF REQUIRED.
COORDINATE WITH ARCHITECTURAL DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE UPGRADED WITH CAT6A PORTS AND CABLE
QUANTITIES INDICATED, UNLESS NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED BY EXISTING CABLING. PROVIDE
RACEWAYS TO EXTEND TO ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET
WITH THE PORT QUANTITY INDICATED.
7. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT 6A CABLING FROM EACH WAO (WORK AREA
OUTLET) TO ITS RESPECTIVE TR.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT CONDUIT RUNS, OR CONDUIT CONTAINING
BENDS TOTALING MORE THAN 180 DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF HORIZONTAL AND BACKBONE CABLING.
PROVIDE FIRE-STOP MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD; DOCUMENT VARIANCES ON AS-BUILT
DRAWINGS.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING TRANSPORTATION, FOR ALL WORK TO
DESIRED VA STORAGE LOCATION. COORDINATE WITH VA AS REQUIRED.
12. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN RACEWAY.
WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO SEGREGATE
SYSTEMS FROM ONE ANOTHER.
13. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS, ACRHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY
OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
AREA OF WORK
- 1/8" = 1'-0"
1 BLDG 23 - FLOOR 0 - TELECOMMUNICATIONS PLAN
0' 4' 8' 16'
PROJECT
NORTH
BLDG 23
KEY PLAN
GENERAL NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 23ET100
BLDG 23 - FLOOR 0 -
TELECOMMUNICATIONS PLAN 23
LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
03/31/2022
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE EXISTING TELECOMMUNICATIONS OUTLET;
EXISTING OUTLET CONDUIT SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE SHEET DETAIL '1' ON SHEET ET503 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET
PLACEMENT.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH CAT 6A CABLING.
REMOVE AND REPLACE EXISTING CABLE TRAY IN THE AREAS SHOWN AS REQUIRED; IF CABLE TRAY IS NON-EXISTENT, PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL '6' ON SHEET ET503 AND TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET ET701. WHERE WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO CONDUIT SLEEVES [(2) 4", MINIMUM] WITH APPROPRIATE FIRE-PROOFING AND CAULKING TO PASS THROUGH WALL. WHERE EXISTING CABLE TRAY AND/OR SLEEVES ARE DISCOVERED, EVALUATE CONDITION AND RACEWAY CAPACITY; IF CABLE TRAY AND/OR
SLEEVES APPEAR TO BE REUSABLE, NOTIFY COR FOR POSSIBLE REUSE.
FIBER-OPTIC CABLE HORIZONTAL ROUTING SHALL BE CONCEALED ABOVE DROP CEILING WHEREVER POSSIBLE. UTILIZE CABLE TRAY AS APPLICABLE. PROVIDE CONDUIT SLEEVE WITH FIREPROOFING AS REQUIRED WHERE WALL PENETRATIONS ARE
REQUIRED. REFERENCE DETAIL 2 ON SHEET ET503 FOR ADDITIONAL INFORMATION.
TUBE DISTRIBUTION UNIT (TDU). REFERENCE COMMUNICATION DRAWING FOR ADDITIONAL INFORMATION.
KEY NOTES
Revisions: Date:
03/10/2023
PROJECT
NORTH
1 REVISED ARCHITECTURAL BACKGROUND.
CONTINUE TO SHEET
CET103 FOR ADDITIONAL
BACKBONE ROUTING
CONTRACTOR SHALL DEMOLISH EXISTING FIBER-OPTIC
BACKBONE CABLING AND RACEWAY AFTER A-SIDE
FIBER-OPTIC BACKBONE IS COMPLETELY INSTALLED.
A-SIDE FIBER-OPTIC BACKBONE. ROUTE FIBER-OPTIC
CABLES TO TRs AS INDICATED ON COMMUNICATIONS
DRAWINGS; REFERENCE COMMUNICATIONS DRAWINGS
FOR ALL FIBER-OPTIC CABLING, RACEWAY TYPES,
SPECIFICATIONS, AND RATINGS. REFERENCE KEY
NOTES ON THIS SHEET REGARDING CABLE TRAY
AND VERTICAL/HORIZONTAL ROUTING FOR
ADDITIONAL FIBER BACKBONE CABLING
REQUIREMENTS.
1. "GENERAL NOTES" APPLY TO ALL ELECTRICAL DRAWINGS. "SHEET NOTES" APPLY TO ONLY THE
SHEETS ON WHICH THEY OCCUR. "KEYNOTES" APPLY ONLY WHERE CALLED OUT.
2. ALL EQUIPMENT SHOWN IN BOLD IS TO BE PROVIDED, OR MODIFIED BY CONTRACTOR UNLESS
OTHERWISE NOTED.
3. CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FROM ALL CONTROL DEVICES TO
LUMINAIRES FOR CONTROL OF LUMINAIRES SHOWN.
4. LUMINAIRES SHOWN ON DRAWINGS FOR QUALITY AND CIRCUITING ONLY. SEE ARCHITECTURAL
DRAWINGS FOR EXACT LOCATIONS AND ELEVATIONS.
5. ALL FEEDERS AND BRANCH CIRCUITS SHALL CONTAIN AN EQUIPMENT GROUND CONDUCTOR
SIZED PER NEC TABLE 250.122. ALL WIRING IS BASED ON COPPER PER NEC TABLE
310.15(B),USING 75° C AMPACITIES FOR FEEDERS.
6. BRANCH CIRCUIT CONDUCTORS, NOT OTHERWISE IDENTIFIED SHALL BE A MINIMUM 12 AWG
FOR RUNS 70 FEET OR LESS AND A MINIMUM 10 AWG FOR RUNS GREATER THAN 70 FEET.
QUANTITY AND SIZE SHALL BE "AS REQUIRED" TO SERVE AND CONTROL DEVICE(S) OR
EQUIPMENT WITH A MAXIMUM VOLTAGE DROP OF THREE PERCENT. WHERE CONTRACTOR
CHOOSES TO RUN MORE THAN THREE CURRENT CARRYING CONDUCTORS WITHIN ONE
RACEWAY OR CABLE, CONDUCTORS SHALL BE INCREASED IN SIZE TO COMPENSATE FOR THE
DERATING REQUIRED PER NEC SECTION 310.15. CONDUCTOR AMPACITIES SHALL BE TAKEN
FROM THE 75° C COLUMN.
7. MINIMUM CONDUIT SIZE IN EXTERIOR AND UNDERGROUND LOCATIONS TO BE 1" UNLESS
NOTED OTHERWISE ON PLANS. CONDUITS FROM LUMINAIRES TO LOCAL USER CONTROL
DEVICES (SWITCHES, OCCUPANCY SENSORS, ETC.) MAY BE 3/4" OR AS INDICATED IN
SPECIFICATIONS. PROVIDE ADDITIONAL CONDUCTOR FOR UNSWITCHED "HOT" TO LIGHTING
LUMINAIRES WITH EMERGENCY POWER BATTERIES OR GENERATOR TRANSFER DEVICES.
8. WIRING FOR EMERGENCY LIGHTING CIRCUITS OR OTHER EMERGENCY EQUIPMENT SHALL BE
KEPT ENTIRELY INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT AND SHALL MEET ALL
REQUIREMENTS OF NEC SECTION 700.10.
9. CONTRACTORS SHALL PROVIDE CONDUIT AND WIRE FOR ALL CIRCUITS SHOWN ON DRAWINGS.
10. WHERE EQUIPMENT PART NUMBERS ARE SHOWN ON THESE PLANS THEY SHALL SUPERCEDE
THE REQUIREMENTS OF THE SPECIFICATIONS.
11. ALL CONDUITS SHALL BE CONCEALED UNLESS OTHERWISE NOTED.
12. COORDINATE EXACT LOCATION OF ALL OUTLETS, COMBINATION CLOCK/SPEAKERS, SPEAKER, FA DEVICES, ETC., WITH THE ARCHITECTURAL ELEVATIONS PRIOR TO COMMENCING WORK.
13. COORDINATE USE OF CEILING SPACE WITH ALL TRADES PRIOR TO COMMENCING WORK. MANY
AREAS ARE VERY CONGESTED AND REQUIRE CLOSE COORDINATION.
14. COORDINATE INSTALLATION REQUIREMENTS FOR OCCUPANCY SENSOR LIGHTING CONTROL
WITH THE MANUFACTURER. PROVIDE ALL APPURTENANCES AS REQUIRED BY THE
MANUFACTURER. PROVIDE ADDITIONAL SENSORS WHERE NECESSARY TO PROVIDE COMPLETE
COVERAGE IN EACH ROOM CONTROLLED BY OCCUPANCY SENSORS.
15. COORDINATE THE INSTALLATION OF ALL EXTERIOR OUTLET BOXES WITH THE TYPE OF
MASONRY IN EACH AREA. CUT ALL FLUTED BLOCKS SO THAT THE BOX IS INSTALLED FLUSH.
SEE ARCHITECTURAL DETAILS FOR MOUNTING REQUIREMENTS.
16. SEAL ALL CONDUIT PENETRATIONS OF FLOORS AND FIRE RATED ASSEMBLIES WITH U.L.
APPROVED MATERIALS AND METHODS TO MAINTAIN FIRE RATING. PROTECT ALL OPENINGS
FOR STEEL ELECTRICAL BOXES IN FIRE RATED WALLS WITH U.L. APPROVED MATERIALS AND
METHODS TO MAINTAIN THE FIRE INTEGRITY.
17. PROVIDE ADDITIONAL CONDUIT SLEEVES THROUGH WALLS WHERE REQUIRED FOR ROUTING
OF SIGNAL SYSTEM WIRING NOT REQUIRED TO BE RUN IN CONDUIT. EACH SLEEVE SHALL BE
DEDICATED TO EACH SIGNAL SYSTEMS. SLEEVES ROUTED THROUGH RATED WALLS SHALL BE
SEALED WITH U.L. MATERIALS AND METHODS TO MAINTAIN FIRE RATING OF WALL.
18. SEE MECHANICAL/PLUMBING DRAWINGS AND SUBMITTALS FOR EXACT LOCATIONS AND
ADDITIONAL ELECTRICAL REQUIREMENTS PRIOR TO INSTALLATION.
19. ALL LOW VOLTAGE SYSTEMS NOT RUN IN CONDUIT SHALL HAVE MINIMUM 3/4"C. ROUTED FROM
THE DEVICE THROUGH WALLS INTO THE ACCESSIBLE CEILING SPACE. NO CABLING SHALL BE
ROUTED IN THE WALLS OR INACCESSIBLE LOCATION WITHOUT CONDUIT.
20. GFCI RECEPTACLES ARE REQUIRED WITHIN 6 FT OF ALL SINKS, ON THE EXTERIOR BELOW 8FT
FROM THE FINISH FLOOR, AND ON ALL ROOFS.
21. UNLESS SPECIFICALLY SHOWN ON THESE PLANS NO STRUCTURAL MEMBER SHALL BE CUT,
NEITHER DRILLED NOR NOTCHED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM THE
STRUCTURAL ENGINEER AND THE COR.
22. CONTRATOR SHALL PROVIDE DUCT SEAL WHERE CONDUITS TRANSITION FROM AREAS THAT
CREATE TEMPERATURE DIFFERENTIAL PER NEC.
23. PRIMARY CONDUIT SWEEPS SHALL BE LONG RADIUS.
24. ALL "RMC" - RIGID METAL CONDUIT IN CONTACT WITH THE EARTH SHALL BE WRAPPED WITH
CORROSION PROTECTION TAPE PER NEC.
25. ALL J-BOXES SHALL BE MATKED WITH INDELIBLE MARKER INDICATING CONDUIT NUMBER AND
PANEL NUMBER.
26. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL 120 VOLT POWER FOR
THE MECHANICAL CONTROLS. COORDINATE EXACT REQUIREMENTS WITH THE CONTROL
CONTRACTOR.
27. ALL ELECTRICAL WORK SHALL BE COMPLETED WITH ALL PROXIMATE ELECTRICAL CIRCUITS DE-
ENERGIZED (I.E. A NEW BREAKER OR CIRCUIT CANNOT BE ADDED TO A PANEL UNLESS THE
PANEL IS COMPLETELY DE-ENERGIZED), OR THE CONTRACTOR MUST COMPLY WITH NFPA 70E
FOR WORK ON ENERGIZED SERVICE. THE VA WILL DETERMINE IF THE ELECTRICAL SERVICE
CAN BE SHUTDOWN OR IT WILL HAVE TO BE WORKED HOT DEPENDING ON THE CRITICALITY OF
THE AREA BEING AFFECTED. IF THE WORK MUST BE DONE WITH THE SERVICE LIVE, THE
CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL REQUIRED PROTECTIVE TOOLS,
EQUIPMENT AND CLOTHING, AND MUST FOLLOW THE JOB SPECIFIC WORK PLAN PREPARED BY
THE VA. WORK THAT REQUIRES SHUTTING DOWN ELECTRICAL SERVICE MAY HAVE TO BE
ACCOMPLISHED DURING OTHER THAN NORMAL DUTY HOURS.
28. WHENEVER FIRE ALARM WORK TAKES PLACE IN AN AREA THAT IS BEING REMODELED, AT THE
CONCLUSION OF THE WORK, THE FIRE ALARM CONTRACTOR SHALL TEST ALL FIRE ALARM
DEVICES WITHIN THE AREA OF REMODEL.
29. DEMOLITION PLAN/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD DRAWINGS. IF
DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY NOTIFY VA AND ENGINEER
OF SAID DISCREPANCY.
30. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF DEVICES SHALL
COMPLY WITH ALL APPROPRIATE CODES.
31. FIELD VERIFY RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO PERFORMING WORK.
32. ALL EQUIPMENT, CABLING, CONNECTORS AND APPURTENANCES SHALL BE LABELED PER THE
VA STANDARD "INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACE" VERSION 3.1
OR NEWER.
33. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER
OBSTRUCTIONS PRIOR TO INSTALLATION.
34. ALL ETHERNET CATEGORY CABLES SHALL FOLLOW THE FOLLOWING CABLE COLOR SCHEME:
DATA SHALL BLUE/TEAL, PHONES SHALL BE GRAY, AND (WIRELESS) ACCESS POINTS SHALL BE
YELLOW. COORDINATE WITH VA FOR ALL CABLING COLOR SCHEMES AS REQUIRED PRIOR TO
SUBMITTAL PROCESS.
35. TOTAL NUMBER OF DATA CONNECTIONS AND CABLING FOR WAOs AND WAPs SHALL BE
VERIFIED BY CONTRACTOR PRIOR TO ACQUISITION OF EQUIPMENT AND CABLING.
CONTRACTOR SHALL PROVIDE AN INITIAL SURVEY OF ALL AREAS TO HAVE UPGRADED WAOs
AND OTHER DATA CONNECTED EQUIPMENT IN ORDER TO VERIFY EXACT LOCATIONS AND
QUANTITIES PRIOR TO CONSTRUCTION.
36. CONTRACTOR MAY USE TEMPORARY CABLE HANGERS OR OTHER MEANS WHILE ROUTING
CABLE TO ITS INTENDED DESTINATION; HOWEVER, PRIOR TO FINAL INSTALLATION, CABLE
SHALL BE INSTALLED TO BE HOUSED WITHIN CABLE TRAY AND NOT ON TEMPORARY CABLE
HANGERS.
37. SEGREGATE ALL NURSE CALL, FIRE ALARM, AND SECURITY SYSTEM ALARM WIRES FROM THE
DATA CABLES WHEN THEY SHARE A CABLE TRAY OR ARE INTERMIXED. CONTRACTOR SHALL
EXPECT WIRES TO BE INTERMIXED IN CERTAIN AREAS OF THE FACILITY TO INCLUDE BUT NOT
LIMITED TO CABLE TRAYS, J-HOOKS, AND IN OPENINGS.
G E N E R A L N O T E S
THIS SHEET IS FOR REFERENCE ONLY AND ALL SYMBOLS, NOTES
AND ABBREVIATIONS MAY NOT APPLY TO THIS PROJECT
S H E E T I N D E X
ETG001 - TELECOMMUNICATIONS LEGEND, GENERAL NOTES, AND ABBREVIATIONS
01ET100 - BLDG 01 - FLOOR 0 - TELECOMMUNICATION PLANS
01ET101 - BLDG 01 - FLOOR 1 - TELECOMMUNICATION PLANS
01ET102 - BLDG 01 - FLOOR 2 - TELECOMMUNICATION PLANS
01ET103 - BLDG 01 - FLOOR 3 - TELECOMMUNICATION PLANS
02ET100 - BLDG 02 - FLOOR 0 - TELECOMMUNICATION PLANS
02ET101 - BLDG 02 - FLOOR 1 - TELECOMMUNICATION PLANS
02ET102 - BLDG 02 - FLOOR 2 - TELECOMMUNICATION PLANS
02ET103 - BLDG 02 - FLOOR 3 - TELECOMMUNICATION PLANS
03ET100 - BLDG 03 - FLOOR 0 - TELECOMMUNICATIONS PLAN
03ET101 - BLDG 03 - FLOOR 1 - TELECOMMUNICATIONS PLAN
03ET102 - BLDG 03 - FLOOR 2 - TELECOMMUNICATIONS PLAN
03TET101 - BLDG 03T - FLOOR 1 - TELECOMMUNICATIONS PLAN
18ET100 - BLDG 18 - FLOOR 0 - TELECOMMUNICATIONS PLAN
18ET101 - BLDG 18 - FLOOR 1 - TELECOMMUNICATIONS PLAN
18ET102 - BLDG 18 - FLOOR 2 - TELECOMMUNICATIONS PLAN
18ET103 - BLDG 18 - FLOOR 3 - TELECOMMUNICATIONS PLAN
23ET100 - BLDG 23 - FLOOR 0 - TELECOMMUNICATIONS PLAN
23ET101 - BLDG 23 - FLOOR 1 - TELECOMMUNICATIONS PLAN
24ET100 - BLDG 24 - FLOOR 0 - TELECOMMUNICATIONS PLAN
24ET101 - BLDG 24 - FLOOR 1 - TELECOMMUNICATIONS PLAN
24ET102 - BLDG 24 - FLOOR 2 - TELECOMMUNICATIONS PLAN
25ET100 - BLDG 25 - FLOOR 0 - TELECOMMUNICATIONS PLAN
25ET101 - BLDG 25 - FLOOR 1 - TELECOMMUNICATIONS PLAN
25ET102 - BLDG 25 - FLOOR 2 - TELECOMMUNICATIONS PLAN
25ET103 - BLDG 25 - FLOOR 3 - TELECOMMUNICATIONS PLAN
25ET104 - BLDG 25 - PENTHOUSE - TELECOMMUNICATIONS PLAN
51ET100a - BLDG 51 - FLOOR 0 - AREA A & C - TELECOMMUNICATIONS PLAN 51ET100b - BLDG 51 - FLOOR 0 - AREA E - TELECOMMUNICATIONS PLAN 51ET101a - BLDG 51 - FLOOR 1 - AREA A - TELECOMMUNICATIONS PLAN 51ET101b - BLDG 51 - FLOOR 1 - AREA B TELECOMMUNICATIONS PLAN 51ET101c - BLDG 51 - FLOOR 1 - AREA C TELECOMMUNICATIONS PLAN 51ET101d - BLDG 51 - FLOOR 1 - AREA D TELECOMMUNICATIONS PLAN 51ET101e- BLDG 51 - FLOOR 1 - AREA E TELECOMMUNICATIONS PLAN
51TET101 - BLDG 51T - FLOOR 1 - TELECOMMUNICATIONS PLAN
52ET100 - BLDG 52 - FLOOR 0 - TELECOMMUNICATIONS PLAN
52ET101 - BLDG 52 - FLOOR 1 - TELECOMMUNICATIONS PLAN
52ET102 - BLDG 52 - FLOOR 2 - TELECOMMUNICATIONS PLAN
53ET100 - BLDG 53 - FLOOR 0 - TELECOMMUNICATIONS PLAN
53ET101 - BLDG 53 - FLOOR 1 - TELECOMMUNICATIONS PLAN
53ET102 - BLDG 53 - FLOOR 2 - TELECOMMUNICATIONS PLAN
53ET103 - BLDG 53 - PENTHOUSE - TELECOMMUNICATIONS PLAN
53TET101 - BLDG 53T - FLOOR 1 - TELECOMMUNICATIONS PLAN
54ET100 - BLDG 54 - FLOOR 0 - TELECOMMUNICATIONS PLAN
54ET101 - BLDG 54 - FLOOR 1 - TELECOMMUNICATIONS PLAN
54ET102 - BLDG 54 - FLOOR 2 - TELECOMMUNICATIONS PLAN
55ET101a - BLDG 55 - FLOOR 1 - AREA A - TELECOMMUNICATIONS PLAN 55ET101b - BLDG 55 - FLOOR 1 - AREA B - TELECOMMUNICATIONS PLAN 55ET102a - BLDG 55 - FLOOR 2 - AREA A - TELECOMMUNICATIONS PLAN 55ET102b - BLDG 55 - FLOOR 2 - AREA B - TELECOMMUNICATIONS PLAN 55ET103a - BLDG 55 - FLOOR 3 - AREA A - TELECOMMUNICATIONS PLAN 55ET103b - BLDG 55 - FLOOR 3 - AREA B - TELECOMMUNICATIONS PLAN
56ET100 - BLDG 56 - FLOOR 0 - TELECOMMUNICATIONS PLAN
56ET101 - BLDG 56 - FLOOR 1 - TELECOMMUNICATIONS PLAN
56ET102 - BLDG 56 - FLOOR 2 - TELECOMMUNICATIONS PLAN
56ET103 - BLDG 56 - FLOOR 3 - TELECOMMUNICATIONS PLAN
57ET101 - BLDG 57 - FLOOR 1 - TELECOMMUNICATIONS PLAN
58ET101 - BLDG 58 - FLOOR 1 - TELECOMMUNICATIONS PLAN
60ET101 - BLDG 60 - FLOOR 1 - TELECOMMUNICATIONS PLAN
60TET101 - BLDG 60T - FLOOR 1 - TELECOMMUNICATIONS PLAN
75ET101 - BLDG 75 - FLOOR 1 - TELECOMMUNICATIONS PLAN
75ET102 - BLDG 75 - MEZZANINE - TELECOMMUNICATIONS PLAN
CET101 - BLDG 1-24 - FLOOR 0 - CORRIDOR WIRELESS ACCESS POINT
TELECOMMUNICATIONS PLAN
CET102 - BLDG 1-24 - FLOOR 1 - CORRIDOR WIRELESS ACCESS POINT
TELECOMMUNICATIONS PLAN
CET103 - BLDG 23-51-65 - FLOOR 1 - CORRIDOR WIRELESS ACCESS POINT
TELECOMMUNICATIONS PLAN
CET104 - BLDG 51-52-53-60 - FLOOR 1 - CORRIDOR WIRELESS ACCESS POINT
TELECOMMUNICATIONS PLAN
01ET400a - BLDG 01 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 01ET400b - BLDG 01 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 01ET401a - BLDG 01 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 01ET401b - BLDG 01 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
01ET402 - BLDG 01 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
01ET403a - BLDG 01 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS 01ET403b - BLDG 01 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS
02ET400 - BLDG 02 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
02ET401 - BLDG 02 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
02ET402 - BLDG 02 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
02ET403 - BLDG 02 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS
03ET400 - BLDG 03 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
03ET401 - BLDG 03 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
03ET402 - BLDG 03 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
03TET401 - BLDG 03T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
18ET400 - BLDG 18 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
18ET401 - BLDG 18 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
18ET402 - BLDG 18 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
18ET403 - BLDG 18 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS
23ET400 - BLDG 23 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
23ET401 - BLDG 23 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
24ET400 - BLDG 24 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
24ET401 - BLDG 24 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
24ET402 - BLDG 24 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
25ET401 - BLDG 25 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
25ET402 - BLDG 25 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
25ET403 - BLDG 25 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS
51ET400 - BLDG 51 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
51ET401a - BLDG 51 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 51ET401b - BLDG 51 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 51ET401c - BLDG 51 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
51TET401 - BLDG 51T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
52ET400 - BLDG 52 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
52ET401a - BLDG 52 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 52ET401b - BLDG 52 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 52ET401c - BLDG 52 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 52ET402a - BLDG 52 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 52ET402b - BLDG 52 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 53ET400a - BLDG 53 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 53ET400b - BLDG 53 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 53ET401a - BLDG 53 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 53ET401b - BLDG 53 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
53ET402 - BLDG 53 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
53TET401 - BLDG 53T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
55ET401a - BLDG 55 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 55ET401b - BLDG 55 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 55ET401c - BLDG 55 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 55ET402a - BLDG 55 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 55ET402b - BLDG 55 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 55ET403a - BLDG 55 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS 55ET403b - BLDG 55 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS
56ET400 - BLDG 56 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
56ET401 - BLDG 56 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
56ET402 - BLDG 56 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
56ET403 - BLDG 56 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS
57ET401a - BLDG 57 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 57ET401b - BLDG 57 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 58ET401a - BLDG 58 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 58ET401b - BLDG 58 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
60ET401 - BLDG 60 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
60TET401 - BLDG 60T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
75ET401 - BLDG 75 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
ET501 - TELECOMMUNICATIONS DETAILS
ET502 - TELECOMMUNICATIONS DETAILS
ET503 - TELECOMMUNICATIONS DETAILS
ET601 - FIBER OPTIC NETWORK DIAGRAM
ET602 - FIBER OPTIC NETWORK DIAGRAM
ET603 - FIBER OPTIC NETWORK DIAGRAM
ET701 - TELECOMMUNICATIONS SCHEDULES
FLEXIBLE CONDUIT
CONDUIT TURNED UP OR TOWARD
CONDUIT TURNED DOWN OR AWAY
CONDUIT CAPPED
T E L E C O M M U N I C A T I O N S L E G E N D
COMMUNICATION OUTLETS
FLOOR MOUNTED TELECOMMUNICATIONS OUTLET.
# = INDICATES QUANTITY OF VOICE AND DATA JACKS
WALL MOUNTED TELECOMMUNICATIONS OUTLET. 18" AFF UON
# = INDICATES QUANTITY OF VOICE AND DATA JACKS
OUTLET; LETTER INDICATES AS FOLLOWS:
A=AUDIO V=VIDEO I=INTERCOM
OUTLET, TELEVISION
BLANK = 4 11/16" MASTER ANTENNA OUTLET BOX WITH BLANK
COVER, MTD. 18" AFF UNLESS OTHERWISE NOTED.
C = CAMERA (CCTV SYSTEM), MTD 18" AFF
M = MONITOR (CCTV SYSTEM).
TELECOMMUNICATIONS OUTLET, SPECIAL PURPOSE.
REFERENCE KEY NOTES ON PLANS FOR ADDITIONAL
INFORMATION.
S
WAP
A/V
S C
C
TGB
FNC
FIBEROPTICS LINE = FO
TELEPHONE LINE = T
SPEAKER, CEILING MOUNTED
SPEAKER, WALL MOUNTED, MTD. 7'-6" AFF UON.
RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" AFF UON.
M = SPEAKER PROGRAM SELECTOR SWITCH & VOLUME
CONTROL
3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD.
4'-6" AFF.
REMOTE DICTATING OUTLET MTD 1'-6" AFF. UON.
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL
OPERATION OF INSTRUMENT & TYPE REQUIRED).
S = STAFF STATION
WIRELESS ACCESS PORT
WALL MOUNTED SPEAKER/CLOCK COMBINATION
WALL CLOCK
CABLE TRAY
RECESSED AUDIO FLOOR BACK BOX, OUTLET AND CONDUIT
TELECOMMUNICATIONS SYSTEMS BONDING BUSBAR
FIBER OPTIC NETWORK CARD
COMMUNICATION
SECTION A
XXX
SECTION LETTER
SHEET WHERE
SECTION IS TAKEN
FROM
A
XXX
SECTION LETTER
SHEET WHERE
SECTION IS TAKEN
FROM
XXX
DETAIL NUMBER
SHEET ON WHICH
DETAIL APPEARS
DETAIL AREA
SCALE
XXXNG
CONDUIT & WIRE TAG
(REFER TO CONDUIT
AND WIRE SCHEDULE)
XX FAULT CURRENT TAG
(3 PH, SYM AMPS)
1 KEY NOTE
XXX
FIGURE OR PHOTO
DETAIL NUMBER
IF PHOTO, ARROW
DENOTES DIRECTION
TAKEN
SHEET WHERE DETAIL
IS TAKEN FROM
DETAIL/PLAN
DETAIL/PLAN NUMBER
G E N E R A L S Y M B O L S
AFC
AFG
AF
AFCI
AFF
AIC
AHJ
ATS
C
CATV
CB
CCTV
CL
CO
DDC
DP
EC
EL
EMER
EN
EMT
ER
EX
FAAP
FACP
FCIO
FOIC
GFCI
GFP
GND
HTR
IG
IMC
J-BOX
LCP
MCA
MCB
MCC
MDP
MLO
MS
MTD
NAC
NEC
NFC
NIC
NL
NTS
OC
OH
OS
PIV
PNL
PS
PVC
R
RECPT
RMC
SAC
SB, SWBDm
SG
SM
SPD
TEL
TR
TYP
UON
UL
UG
VD
VFD
W
WP
XFMR
ABOVE FINISHED COUNTER
ABOVE FINISHED GRADE
AMP FRAME
ARC FLASH CIRCUIT INTERRUPTER
ABOVE FINISHED FLOOR
AMPERE INTERRUPTING CAPACITY
AUTHORITY HAVING JURISDICTION
AUTOMATIC TRANSFER SWITCH
CONDUIT OR CEILING
COMMUNITY ANTENNA TELEVISION
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CONNECTOR LIGHTING
CONDUIT ONLY
DIRECT DIGITAL CONTROLS
DISTRIBUTION PANELBOARD
EMPTY CONDUIT
ELEVATION
EMERGENCY
EXISTING IN NEW LOCATION
ELECTRICAL METALLIC TUBING
EXISTING TO REMAIN
EXISTING
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FURNISHED BY CONTRACTOR, INSTALLED
BY OWNER
FURNISHED BY OWNER, INSTALLED BY
CONTRACTOR
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT PROTECTION
GROUND
HEATER
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
JUNCTION BOX
LIGHTING CONTROL PANEL
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
MAIN LUGS ONLY
MOTOR STARTER
MOUNTED
NOTIFICATION APPLIANCE CABINET
NATIONAL ELECTRICAL CODE
NOT FOR CONSTRUCTION
NOT IN CONTRACT
NIGHT LIGHT
NOT TO SCALE
ON CENTER
OVERHEAD
OCCUPANCY SENSOR
POST INDICATOR VALVE
PANEL
POWER SUPPLY
POLYVINYL CHLORIDE
EXISTING TO BE REMOVED
RECEPTACLE
RIGID METAL CONDUIT
SMALL APPLIANCE CIRCUIT
SWITCHBOARD
SWITCHGEAR
SMART METER
SURGE PROTECTIVE DEVICE
TELEPHONE
TAMPER RESISTANT
TYPICAL
UNLESS OTHERWISE NOTED
UNDERWRITERS LABORATORIES
UNDERGROUND
VOLTAGE DROP
VARIABLE FREQUENCY DRIVE
WEATHERPROOF (WHILE IN USE)
WEATHERPROOF
TRANSFORMER
A B B R E V I A T I O N S
AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL C-CHIME H-HORN K-KLAXON
L-LISTEN M-MICROPHONE S-SOUNDER S-SPEAKER Z-BUZZER
KEYPAD DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR WALL CALL
M-MAG STRIP P-PROXIMITY S-SMART CARD T-TOKEN
D DOOR CONTACT
ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DEADBOLT H-HYBRID L-LATCH SET S-STRIKE
INTERCOM; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
M-MASTER S-SUBSTATION
MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC
PUSH BUTTON; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL PUSH D-DURESS P-PANIC R-DOOR OPENER X-REQUEST FOR EXIT
SECURITY ACCESS, ANNUNCIATOR PANEL
SECURITY ACCESS, VIDEO CAMERA WITH LENS
SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW
SECURITY ACCESS, PANNING CAMERA TRAVERSE ANGLE
SAFETY AND SECURITY
M = MOUNTING FOR ALL SAFETY AND SECURITY SYMBOLS:
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
NURSE CALL
FIRE ALARM
PS
WG
NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER TOP UNLESS
OTHERWISE NOTED.
NURSE CALL TERMINAL CABINET.
NURSE CALL STATION.
D E
P S
U
= DUPLICATE PATIENT STATIONS (SEPARATE INDICATORS AT
MASTER STATION) MTD 5'-0" AFF UNLESS OTHERWISE NOTED
= DUTY STATION. MTD 5'-0" AFF UNLESS OTHERWISE NOTED
= STATION MTD 6'-0" AFF FOR SHOWER LOCATION, MTD 4'-6" AFF
FOR TUB LOCATION, & MTD 3'-0" AFF FOR TOILET LOCATION,UON
= PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH
= AUDIO VISUAL WALL STATION (STAFF) MTD 5'-0" AFF UNLESS
OTHERWISE NOTED
= UTILITY CALL STATION, MTD 5'-0" AFF UNLESS OTHERWISE NOTED
NURSE CALL STATION.
D I
= NURSE'S CALL DOME LIGHT (SUFFIX INDICATES NO. OF LAMP)
MTD 6" ABOVE DOOR
= CORRIDOOR DOME LIGHT.
= AUXILIARY INTERSECTIONAL DOME LIGHT.
NIGHT LIGHT
PATIENT BED OUTLETB
POWER SUPPLY WITH BATTERY BACKUP
WANDER GUARD
R
C
C
F
K
A
ADDRESSABLE RELAY
ALARM, FIRE, COMMUNICATOR
ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:
FACC = CENTRAL CONSOLE FACP = CONTROL PANEL
MFACP = MASTER CONTROL PANEL FAAP = ANNUNCIATOR PANEL
ALARM, FIRE; LETTERS INDICATE AS FOLLOWS:
BATT = BATTERIES CHR = CHARGER FAR = RECORDER
ALARM, FIRE, VALVE SUPERVISORY SWITCH.
ALARM, FIRE, TERMINAL CABINET.
ALARM, FIRE, POST INDICATOR VALVE.
ALARM, TRANSPONDER OR TRANSMITTER.
ALARM, FIRE, MANUAL PULL STATION
C = WITH CLEAR PLASTIC COVER
ALARM, HORN/LIGHT, ONE ASSEMBLY
C = WITH CHIME
ALARM, HORN/LIGHT, SEPARATE ASSEMBLY
ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE
ALARM, MANUAL CONTROL
ALARM, MINI HORN
ALARM, SPRINKLER SYSTEM WATER FLOW BELL
ALARM, VOICE COMMUNICATION PANEL
ALARM, TAMPER SWITCH
DETECTION, GAS
C = CARBON DIOXIDE TRANSMITTER
DETECTOR, FLOW SWITCH
DETECTOR, HEAT
DETECTOR, SMOKE
DETECTOR, SMOKE, FOR DUCT
ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET
CITY FIRE ALARM MASTER STATION MTD 5'-6" AFF UNLESS NOTED.
FIRE ALARM TRANSMITTER (BASE LOOP) NUMERALS DENOTE CODE.
FIRE ALARM TROUBLE TRANSMITTER (BASE LOOP) NUMERALS
DENOTE CODE.
FIRE SPRINKLE WATER FLOW SWITCH
KITCHEN HOOD FIRE SUPPRESSION SYSTEM
REMOTE ANNUNCIATOR
SPECIAL SYSTEMS
P
AUDIO CONTROLLER
PRESSURE BEACON
PRESSUR…