This solicitation is seeking a general contractor to provide infrastructure upgrades at the St. Louis Jefferson Barracks VA Medical Center. The scope of work includes electrical panel upgrades and power systems work, building management system integration, HVAC assessments and upgrades, interior renovations including demolition and new construction, data center renovations, physical security enhancements, fiber optic infrastructure assessment and upgrades between buildings, installation of a diversified wide area network path to the datacenter, and hazardous material abatement. The project involves construction and renovation activities in buildings 1, 2, 3, 3T, 18, 23, 24, 25, 51, 51T, 52, 53, 53T, 55, 56, 57, 58, 59, 60, 60T, 61, 75. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.
View the file
Other files for this federal contract opportunity
Show all 50
Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
SG53-61-BUS
4160.0 V
0.0 A
FUSE-SG53-61-3
S&C
SMU-20, 200E
200.0 A
CBL-53-XF2 BLDG 53
95.0 ft
1 per phase
3/0 AWG
Copper
53-XF2-BLDG 53
750 kVA
Pri 4160 V
Sec 208 V
5.9300 %
CBL-53-GDP-53
70.0 ft
2 per phase
500 kcmil
Copper
PD53-GDP-53-MCB
CUTLER-HAMMER
ND
53-PANEL-MDP-53
208.0 V
2000.0 A
CBL-MDP-53
35.0 ft
6 per phase
400 kcmil
Copper
1200.0 A
PD53-ATS-53-N
CUTLER-HAMMER
MDL
800.0 A
CBL-ATS-53-N
23.0 ft
2 per phase
500 kcmil
Copper
PD-MDP-53-MCB
CUTLER-HAMMER
CRD
2000.0 A
PD53-ATS-EMP-N
CUTLER-HAMMER
DK
400.0 A
PD53-ATS-CDP-N
CUTLER-HAMMER
FD
200.0 A
PD53-ATS-ELGA-N
CUTLER-HAMMER
FD
100.0 A
CBL-53-ATS-53-E
26.0 ft
2 per phase
500 kcmil
Copper
CBL-53-ATS-ELGA-E
34.0 ft
1 per phase
1 AWG
Copper
CBL-53-ATS-CPD-E
23.0 ft
4/0 AWG
Copper
CBL-53-ATS-EMP-E
30.0 ft
2 per phase
350 kcmil
Copper
PD53-ATS-53-E
CUTLER-HAMMER
MDL
800.0 A
PD53-ATS-ELGA-E
CUTLER-HAMMER
FD
100.0 A
PD53-ATS-CDP-E
CUTLER-HAMMER
FD
200.0 A
PD53-ATS-EMP-E
CUTLER-HAMMER
DK
400.0 A
53-PANEL-GDP-53
208.0 V
1200.0 A
GEN87-BLDG 87
200 kVA
X"d 0.2 pu
E N
53-ATS-53
Amps Rating 800.0 A
AIC 50.00 kA
CBL-53-BLDG 53-SWBD
23.0 ft
3 per phase
350 kcmil
Copper
PD53- SP6
GE
AKR-30
800.0 A
PD53-SP5
GE
AKR-30
800.0 A
225A/3P
PD53-SP3
GE
AKR-30
800.0 A
PD53-SP2
GE
AKR-30
800.0 A
PD53-GB1-1
GE
AKR-30
800.0 A
CBL-53-GB1-1
229.0 ft
1 per phase
3/0 AWG
Copper
53-PANEL-GB1-1
208.0 V
200.0 A
PD53-2C
GE
AKR-30
800.0 A
CBL53-2C
333.0 ft
1/0 AWG
Copper
PD53-GA
GE
AKR-30
800.0 A
CBL-53-GA
77.0 ft
1/0 AWG
Copper
53-PANEL-GA
208.0 V
100.0 A
53-PANEL-2C
208.0 V
225.0 A
CBL-53-GB1-2
24.0 ft
3/0 AWG
Copper
CBL-53-2CA
7.0 ft
1/0 AWG
Copper
53-PANEL-GB1-2
208.0 V
200.0 A
53-PANEL-2CA
208.0 V
125.0 A
CBL-53-GC-1
307.0 ft
500 kcmil
Copper
53-PANEL-GC-1
208.0 V
225.0 A
CBL-53-GC-2
7.0 ft
500 kcmil
Copper
53-PANEL-GC-2
208.0 V
225.0 A
CBL-53-1C-1
103.0 ft
1 per phase
500 kcmil
Copper
53-PANEL-1C-1
208.0 V
225.0 A 53-PANEL-1B
208.0 V
225.0 A
CBL-53-1C-2
5.0 ft
1 per phase
500 kcmil
Copper
CBL-53-2B-1
31.0 ft
500 kcmil
Copper
53-PANEL-2B-1
208.0 V
400.0 A
53-PANEL-1C-2
208.0 V
225.0 A
CBL-53-2B-2
5.0 ft
1 per phase
500 kcmil
Copper
53-MTR53-ELEV S-17
NumMotors 1
Total 50 hp
CBL-53-ATS-ELEV1-E
4.0 ft
53-PANEL-2B-2
208.0 V
400.0 A
3/0 AWG
Copper
53-PANEL-EL2A
208.0 V
225.0 A
53-PANEL-EC2A
208.0 V
100.0 A
53-MTR53-ELEV P-18
NumMotors 1
Total 40 hp
53-PANEL-2A-2
208.0 V
225.0 A
53-PANEL-EL1A
208.0 V
125.0 A
CBL-53-EL2A
22.0 ft
1 AWG
Copper
PD53-GC-1
GE
AKR-30
800.0 A
PD53-RISER-B1
GE
AKR-30
800.0 A
CBL-53-RISER-B1-1
226.0 ft
500 kcmil
Copper
CBL-53-GB
0.1 ft
500 kcmil
Copper
53-PANEL-GB
208.0 V
400.0 A
CBL-53-RISER-B1-2
10.0 ft
500 kcmil Copper
CBL-53-1B
0.1 ft
1 per phase
500 kcmil
Copper
53-ATS53-ELEV1
Amps Rating 400.0 A
AIC 35.00 kA
CBL-53-ELEV 1
15.0 ft
3/0 AWG
Copper
PD53-MCC
GE
AKR-30
800.0 A
CBL-53-MCC
223.0 ft
2 per phase
4/0 AWG
Copper
53-PANEL-MCC
208.0 V
600.0 A
53-PANEL-GP
208.0 V
400.0 A
53-PANEL-KP
208.0 V
100.0 A
53-PANEL-P2
PD53-ATS-ELEV1-N
SQUARE D
KA
250.0 A
CBL-53-ATS-ELEV1-N
51.0 ft
3/0 AWG
Copper
PD53-ATS-ELEV2-N
SQUARE D
KA
250.0 A
CBL-53-ATS-ELEV2-N
51.0 ft
2/0 AWG
Copper
CBL-53-2A-1
152.0 ft
53-ATS53-ELEV2
Amps Rating 200.0 A
AIC 10.00 kA
CBL-53-ELEV 2
15.0 ft
2/0 AWG
Copper
CBL-53-2A-2
5.0 ft
500 kcmil Copper
500 kcmil
Copper
53-PANEL-2A-1
208.0 V
225.0 A
208.0 V
400.0 A
CBL-53-1A-2
16.0 ft
500 kcmil
Copper
53-PANEL-1A-2
208.0 V
225.0 A
PD53-GP
GE
AKR-30
800.0 A
CBL-53-GP
26.0 ft
1 per phase
250 kcmil
Copper
PD53-KP
GE
AKR-30
800.0 A
CBL-53-KP
233.0 ft
1 per phase
500 kcmil
Copper
PD53-P2
GE
AKR-30
800.0 A
CBL-53-P2
265.0 ft
1 per phase
500 kcmil
Copper
PD53-RISER-1A
GE
AKR-30
800.0 A
CBL-53-RISER-1A-1
138.0 ft
500 kcmil
Copper
CBL-53-1A-1
0.1 ft
500 kcmil
Copper
53-PANEL-1A-1
208.0 V
225.0 A
53-ATS53-EMP
Amps Rating 600.0 A
AIC 50.00 kA
CBL-53-EMP
27.0 ft
2 per phase
350 kcmil
Copper
PD53-EMCC
GE
THQDL
200.0 A
CBL-53-EMCC
219.0 ft
2 per phase
4/0 AWG
Copper
53-PANEL-EMCC
208.0 V
100.0 A
CBL-53-ELEV1
231.0 ft
1 per phase
3/0 AWG
Copper
1 per phase
1 AWG
Copper
CBL-53-EL1A
0.1 ft
1 per phase
1 AWG
Copper
PD53-ELEV1
GE
THQDL
200.0 A
53-PANEL-EMP
208.0 V
400.0 A
53-ATS53-ELGA
Amps Rating 100.0 A
AIC 22.00 kA
CBL-53-RISER-EL1-1
223.0 ft
1 per phase
1 AWG
Copper
CBL-53-ELGA
0.1 ft
1 per phase
1 AWG
Copper
53-PANEL-ELGA
208.0 V
200.0 A
CBL-53-RISER-EL1-2
37.0 ft
PD53-EC1A
GE
TEYD
125.0 A
CBL-53-EC1A-1
129.0 ft
1/0 AWG
Copper
CBL-53-EC1A-2
0.1 ft
1/0 AWG
Copper
PD53-CDP-MCB
GE
THQD
225.0 A
PD53-ECGA
GE
TEYD
60.0 A
CBL-53-ECGA
223.0 ft
4 AWG
Copper
53-PANEL-ECGA
208.0 V
60.0 A
CBL-53-EC1B
166.0 ft
53-PANEL-EC1A
208.0 V
100.0 A
53-CBL-EC2A
19.0 ft
1/0 AWG
Copper
53-PANEL-EC1B
208.0 V
225.0 A
4 AWG
Copper CBL-53-STR LTGS
20.0 ft
4 AWG
Copper
53-PANEL-ECGB
208.0 V
100.0 A
PD53-ECGB
GE
TEYD
50.0 A
CBL-53-ECGB
35.0 ft
6 AWG
Copper
PD53-STR LTGS
GE
TEYD
60.0 A
CBL-53-XF2-53-T
32.0 ft
4 AWG
Copper
PD53-STR
LTGS1
GE
SEDA
60.0 A
CBL53-0091
32.0 ft
350 kcmil
Copper
53-PANEL-CDP
208.0 V
225.0 A
PD53-SP1
GE
AKR-30
800.0 A
BLDG 53-SWBD
208.0 V
800 A
CBL-53-ATS-EMP-N
23.0 ft
1 per phase
500 kcmil
Copper
CBL-53-ATS-ELGA-N
27.0 ft
3/0 AWG
Copper
CBL-53-ATS-CDP-N
33.0 ft
1 per phase
3/0 AWG
Copper
53-ATS53-CDP
Amps Rating 225.0 A
AIC 35.00 kA
CBL-53-CDP
24.0 ft
1 per phase
3/0 AWG
Copper
53-XF2-53-T0
15 kVA
Pri 208 V
Sec 480 V
2.7789 %
440 V XFRM
208.0 V
100.0 A
BUS53-STR LTGS0
480.0 V
1 per phase 1 per phase
1 per phase 1 per phase 1 per phase
1 per phase
1 per phase
1 per phase 1 per phase
1 per phase
1 per phase
1 per phase
1 per phase
1 per phase
1 per phase 1 per phase
1 per phase
1 per phase 1 per phase
1 per phase
1 per phase
1 per phase
1 per phase
1 per phase
1 per phase
1 per phase
1 per phase
1 per phase 1 per phase 1 per phase
1 per phase
1 per phase
G
225A/3P
3"C-4#4/0, #4G
100A/3P 100A/3P 100A/3P 20A/3P 20A/3P
SPD DPM
1-1/4"C-4#3, #8G
53-DP-TRA
208V, 3PH
225A
53-GS10A
208V, 3PH
100A
53-GS02AA
208V, 3PH
100A
53-1S002A
208V, 3PH
100A
7 1 7
NSR251 (BLDG 53T)
208V, 1PH
400 A
SPD DPM
225A/3P
225A/3P
3"C-4#4/0, #4G
DISTRIBUTION PANEL
53-DP-TRB
120/208V,3PH, 225A
100A/3P 100A/3P 100A/3P 20A/3P 20A/3P
1-1/4"C-4#3,#8G
53-GS10B
120/208V
3PH
100A
53-1S002B 120/208V
3PH
100A
53-GS02AB
120/208V
3PH
100A
8 2 8
100A/3P
53-1S01A
208V, 3PH
100A
100A/3P
53-2S001A
208V, 3PH
100A
100A/3P
53-1S01B 120/208V
3PH
100A
100A/3P
53-2S001B 120/208V
3PH
100A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
53EP601
BLDG 53 AND 53T - ONE-LINE
DIAGRAMSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM LLT/JPS
CONSTRUCTION
DOCUMENTS
Revisions: Date:
GENERAL NOTES
KEY NOTES
- 6" = 1'-0"
1 BLDG 53 AND 53T - ONE-LINE DIAGRAM
1 TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER
TR PANEL, TYPICAL - TYPE 1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER
TR PANEL, TYPICAL - TYPE 1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
EXISTING PANEL TO BE MODIFIED.
REFERENCE GEENRATOR LOAD CALCULATION SCHEDULE ON SHEET EP704 FOR
GENERATOR LOADING DATA.
TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER
TR PANEL, TYPICAL - TYPE 1.1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER
TR PANEL, TYPICAL - TYPE 1.1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER
TR PANEL, TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER
TR PANEL, TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
REPLACE EXISTING CIRCUIT BREAKER OR ADD CIRCUIT BREAKER AS SHOWN.
LRL/WNM LLT/JPS
MSB/55-1
3000A, 480/277V, 3PH, 4W,
100kAIC
2000kVA
4160-480Y/277V
3P,4W
MVSG
ATS/'55-LS1'
ISC=31,552A
ATS/'55-C1'
ISC=31,784A
ATS/'55-EQ1'
ISC=30,218A
ATS/'55-EQ2'
ISC=28,941A
DP/55-EQ2
ISC=25,062A
DP/'55-EQ1'
1200A, 480/277V, 3PH, 4W,
42kAIC, ISC=25,062A
MCC-'55-2E'
ISC=8,345A
MCC-'55-E'
ISC=24,214A
TR-55-EQ1
45kVA
TR-55-EQ4
30kVA
TR-55-EQ3
45kVA
TR-55-EQ2
30kVA
PANEL
'55-1EQ2-1'
ISC=2,170A
PANEL
'55-1EQ2-2'
ISC=1,996A
PANEL
'55-2EQ1-1'
ISC=1,699A
PANEL
'55-3EQ1-1'
ISC=1,374A
PANEL
'55-1EQ3-1'
ISC=1,843A
PANEL
'55-2EQ3-1'
ISC=1,268A
PANEL
'55-3EQ3-1'
ISC=1,007A
PANEL
'55-1EQ4-1'
ISC=1,858A
PANEL
'55-1EQ4-2'
ISC=1,724A
PANEL
'55-2EQ4-1'
ISC=1,519A
PANEL
'55-1EQ4-1'
ISC=1,247A
PANEL
'55-1EQ1-1'
ISC=2,540A
PANEL
'55-1EQ1-2'
ISC=2,511A
PANEL
'55-2EQ1-1'
ISC=1,699A
PANEL
'55-3EQ1-1'
ISC=1,374A
TR-55-1C3
30kVA
PANEL
'55-1C3'
ISC=4,192A
PANEL
'55-1C3P'
ISC=1,016A
PANEL
'55-2EQ1-1'
ISC=1,699A
PANEL
'55-3EQ1-1'
ISC=1,374A
TR-55-1C4
30kVA
TR-55-2C1
30kVA
PANEL
'55-2C1'
ISC=7,726A
PANEL
'55-2C1P'
ISC=1,085A
PANEL
'55-2C1P-1'
PANEL
'55-2C2P'
ISC=892A
TR-55-2C2
15kVA
TR-55-2C3
15kVA
PANEL
'55-2C3'
ISC=4,098A
PANEL
'55-2C3P'
ISC=1,017A
PANEL
'55-2C4P'
ISC=854A
PANEL
'55-2C4P-1'
TR-55-2C4
30kVA
TR-55-3C1
30kVA
PANEL
'55-3C1'
ISC=7,159A
PANEL
'55-3C1P'
ISC=1,077A
PANEL
'55-3C1P-1'
PANEL
'55-3C2P'
ISC=902A
TR-55-2C2
15kVA
TR-55-3C3
15kVA
PANEL
'55-3C3'
ISC=3,899A
PANEL
'55-3C3P'
ISC=988A
PANEL
'55-3C4P'
ISC=853A
PANEL
'55-3C4P-1'
TR-55-3C4
30kVA
DP/'55-C1'
400A, 480/277V, 3PH, 4W
42kAIC, ISC=25,062
TO 5kV PAD
MOUNTED SWITCH
1000A
GSB/'55-1'
1200A, 480/277V, 3PH, 4W,
10kAIC, ISC=4,859A
E N
L
E N
L
E N
L
E N
L
DP/'55-LS1'
225A, 480/277V, 3PH, 4W
42kAIC, ISC=25,622
PANEL
'55-3LS3P'
ISC=1,017A
TR-55-3LS3
15kVA
PANEL
'55-3LS3'
ISC=4,015A
PANEL
'55-3LS1P'
ISC=2,227A
TR-55-3LS1
30kVA
PANEL
'55-3LS1'
ISC=7,689A
PANEL
'55-3LS1P2'
ISC=1,074A
PANEL
'55-2LS3P'
ISC=1,036A
TR-55-2LS3
15kVA
PANEL
'55-2LS3'
ISC=7,988A
PANEL
'55-2LS1P'
ISC=1,032A
TR-55-2LS1
15kVA
PANEL
'55-2LS1'
ISC=7,718A
PANEL
'55-LSP-1'
ISC=1,077A
TR-55-LS1
15kVA
PANEL
'55-LS1'
ISC=7,806A
PANEL
'55-1LS3P'
ISC=1,006A
TR-55-1LS3
15kVA
PANEL
'55-1LS3'
ISC=4,208A
PANEL
'55-1LS1P'
ISC=1,078A
TR-55-1LS31
15kVA
PANEL
'55-1LS1'
ISC=9,320A
DP/'55-M'
1200A, 480/277V, 3PH, 4W,
42kAIC, ISC=31,933A
MCC-'55-1'
ISC=30,090A
MCC-'55-2'
ISC=4,183A
DP/'55-L'
400A, 480/277V, 3PH, 4W,
42kAIC, ISC=30,442A
PANEL
55-'1L3'
ISC=4,352A
PANEL
55-'2L3'
ISC=4,000A
PANEL
55-'3L3'
ISC=3,860A
PANEL
55-'1L1'
ISC=8,609A
PANEL
55-'2L1'
ISC=6,248A
PANEL
55-'3L1'
ISC=6,382A
DP/'55-R'
1200A, 480/277V, 3PH, 4W,
42kAIC, ISC=31,357A
TR-55-1N4
150kVA
DP/'55-1N4'
500A, 480/277V, 3PH, 42
22kAIC, ISC=7,325A
PANEL
'55-3N4-1'
ISC=5,568A
PANEL
'55-3N4-2'
ISC=5,660A
PANEL
'55-2N4-1'
ISC=6,303A
PANEL
'55-2N4-2'
ISC=6,092A
PANEL
'55-1N4-1'
ISC=7,105A
TR-55-1N3
150kVA
DP/'55-1N3'
500A, 208/120V, 3PH, 4W,
22kAIC, ISC=8,636A
PANEL
'55-3N3-1'
ISC=5,910A
PANEL
'55-3N3-2'
ISC=5,717A
PANEL
'55-2N3-1'
ISC=6,373A
PANEL
'55-2N3-2'
ISC=5,993A
PANEL
'55-1N3-1'
ISC=7,137A
PANEL
'55-1N3-2'
ISC=5,923A
TR-55-1N2
150kVA
DP/'55-1N2'
500A, 2080/120V, 3PH, 4W,
42kAIC, ISC=8,636A
PANEL
'55-3N2-1'
ISC=7,063A
PANEL
'55-3N2-2'
ISC=6,842A
PANEL
'55-2N2-1'
ISC=7,265A
PANEL
'55-2N2-2'
ISC=6,986A
PANEL
'55-1N2-2'
ISC=8,112A
PANEL
'55-1N2-1'
ISC=8,399A
DP/'55-1N1'
500A, 208/120V, 3PH, 4W,
42kAIC, ISC=8,694A
PANEL
'55-3N1-1'
ISC=6,795A
PANEL
'55-3N1-2'
ISC=6,552A
PANEL
'55-2N1-1'
ISC=7,306A
PANEL
'55-2N1-2'
ISC=7,024A
PANEL
'55-1N1-2'
ISC=8,001A
PANEL
'55-1N1-1'
ISC=8,333A
TR-55-1N1
150kVA
GEN-'55-1'
500kW/625kVA
480Y/277V, 3P,4W
G
225A/3P
400A/3P
2 SETS, 2"C-4#3/0, #3G
55-1A129A
208V, 3PH
100A
55-1B104A
208V, 3PH
100A
55-1C132A
208V, 3PH
100A
55-2A136A
208V, 3PH
100A
55-2C144A
208V, 3PH
100A
55-3A120A
208V, 3PH
100A
55-3C149A
208V, 3PH
100A
DISTRIBUTION PANEL
55-DP-TRA
400A, 208V, 3PH
100A/3P 100A/3P 100A/3P 100A/3P 100A/3P 100A/3P 100A/3P 20A/3P 20A/3P
1-1/4"C-4#3, #8G
SPD DPM
4"C-4#600 KCM, 1#3 GND
3"C-4#250, 1#4 GND
3"C-4#250, 1#4 GND
400A/3P 800A/3P 400A/3P 400A/3P 400A/3P 800A/3P 400A/3P 1000A/3P 1000A/3P 400A/3P
600A/3P 225A/3P 150A/3P 150A/3P
50A/3P50A/3P70A/3P50A/3P225A/3P225A/3P
100A/3P 100A/3P100A/3P 100A/3P 100A/3P
175A/3P 250A/3P 250A/3P 250A/3P
500A/3P
150A/3P 150A/3P 150A/3P 400A/3P
400A/3P
DISTRIBUTION PANEL
55-DP-TRB
400A, 208V, 3PH
100A/3P 100A/3P 100A/3P 100A/3P 100A/3P 100A/3P 100A/3P
55-1A129B
208V, 3PH
100A
55-1B104B
208V, 3PH
100A
55-1C132B
208V, 3PH
100A
55-2A136B
208V, 3PH
100A
55-2C144B
208V, 3PH
100A
55-3A120B
208V, 3PH
100A
55-3C149B
208V, 3PH
100A
20A/3P 20A/3P
SPD DPM
2 SETS, 2"C-4#3/0, #3G
1 1 4 1 1 1
2 2 5 2 2 2 2
1-1/4"C-4#3, #8G
200A/3P 150A/3P 200A/3P
200A/3P
500A/3P
150A/3P 200A/3P
200A/3P 200A/3P 200A/3P
500A/3P
125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P
2"C-3#4/0,#4G
TR-55-DP-TRA
150kVA
480-208/120V
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
55EP601
BLDG 55 - ONE-LINE DIAGRAM
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM LLT/JPS
CONSTRUCTION
DOCUMENTS
Revisions: Date:
GENERAL NOTES
KEY NOTES
- 3/4" = 1'-0"
BLDG 55 - ONE-LINE DIAGRAM1
1 TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER
TR PANEL, TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER
TR PANEL, TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
REFERENCE GENERATOR LOAD CALCULATION SCHEDULE ON SHEET EP704 FOR
GENERATOR LOADING DATA.
TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER
TR PANEL, TYPICAL - TYPE 1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER
TR PANEL, TYPICAL - TYPE 1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
EXISTING EQUIPMENT TO BE MODIFIED; PROVIDE CIRCUIT BREAKER AS SHOWN.
1600A/3P
750kW/937.5kVA
480/277V, 3P, 4W G
GSB/56
1600A, 480/277V, 3PH, 4W,
22kAIC, ISC=7,318A
ATS/C
ISC=22,336A
E N
L
2000kVA
4160-480Y/277V
3P,4W
MVSG
TO 5kV PAD MOUNTED
SWITCH
TR-56-C
500kVA
PANEL
56-3CR
ISC=2,296A
PANEL
56-3CR1
PANEL
56-2CR
ISC=2,500A
PANEL
56-2CR1
PANEL
56-1CR
ISC=2,296A
PANEL
56-1CR1
56-SP1
PANEL
56-CR
ISC=2,500A
PANEL
56-CR1
300kVA
UPS
ISC-E
PANEL
56-3C1
ISC=592A
PANEL
56-1C1
ISC=599A
DP/56U
800A, 480/277V, 3PH, 4W,
10kAIC, ISC=623A
PANEL
56-C1
ISC=609A
PANEL
56-C2
ISC=622A
PANEL
56-C3
ISC=622A
PANEL
56-C4
ISC=619A
PANEL
56-C5
ISC=619A
PANEL
56-C6
ISC=618A
PANEL
56-C7
ISC=617A
PANEL
56-C8
ISC=593A
PANEL
56-C9
ISC=593A
ATS/EQ
ISC=22,824A
E N
L
MSB/56-1
2500A, 480/277V
3PH, 4W,
42kAIC
DP/56EQ
600A, 480/277V, 3PH, 4W,
42kAIC, ISC=23,244A
PANEL
56-3EQ1P
DS-100
TR-56-3EQ1
45kVA
PANEL
56-3EQ1
ISC=1,068A
PANEL
56-2EQ1P
DS-30
TR-56-2EQ1
15kVA
PANEL
56-2EQ1
ISC=1,087A
PANEL
56-1EQ1P
DS-30
TR-56-1EQ1
15kVA
PANEL
56-1EQ1
ISC=1,106A
PANEL
56-EQ1P
DS-30
TR-56-EQ1
30kVA
PANEL
56-EQ1
ISC=1,056A
MCC/56E-1
ISC=19,691A
ATS/LS
ISC=18,307A
E N
L
DP/56LS
225A, 480/277V, 3PH, 4W,
22kAIC, ISC=15,923A
DS-60
TR-56-LSGB
30kVA
PANEL
56-LSGB
ISC=2,408A
PANEL
56-3LS1
ISC=3,811A
PANEL
56-2LS1
ISC=4,060A
PANEL
56-1LS1
ISC=4,434A
PANEL
56-LS1
ISC=4,667A
DS-30
TR-56-LS1
15kVA
PANEL
56-LS1P
ISC=1,092A
PANEL
56-L1
ISC=6,196A
PANEL
56-1L1
ISC=5,642A
PANEL
56-1L1-MM
ISC=5,478A
PANEL
56-2L1
ISC=5,177A
PANEL
56-3L1
ISC=4,782A
PANEL
56-1L2-NCA
ISC=7,122AA
DP/56L
225A, 480/277V, 3PH, 4W,
42kAIC, ISC=22,510A
MCC/56-4
ISC=16,768A
DP/56M
800A, 480/277V, 3PH, 4W,
42kAIC, ISC-23,454A
MCC/56-3
ISC=17,727A
MCC/56-2
ISC=18,991A
MCC/56-1
ISC=22,515A
DS-100
TR-56-1N2-NCA
45kVA
PANEL
56-1N2-NCA
ISC=3,737A
DS-100
TR-56-2N2
45kVA
PANEL
56-2N2
ISC=2,652A
DS-100
TR-56-3N2
45kVA
PANEL
56-3N2
ISC=2,631A
DS-100
TR-56-3N1
45kVA
PANEL
56-3N1
ISC=4,676A
DS-100
TR-56-2N1
45kVA
PANEL
56-2N1
ISC=2,611A
DS-60
TR-56-1N1
30kVA
PANEL
56-1N1
ISC=2,324A
DS-60
TR-56-1N1-MM
30kVA
PANEL
56-1N1-MM
ISC=2,309A
DS-100
TR-56-N1
45kVA
PANEL
56-N1
ISC=2,702A
DS-100
TR-56-N2-1
45kVA
PANEL
56-N2-1
ISC=4,847A
DS-60
TR-56-N2-2
30kVA
PANEL
56-N2-2
ISC=2,401A
225A/3P
225A/3P
100A/3P 100A/3P 100A/3P 100A/3P 20A/3P 20A/3P
56-BA105A
208V, 3PH
100A
56-1A109A
208V, 3PH
100A
56-2A122A
208V, 3PH
100A
56-3A122A
208V, 3PH
100A
SPD
3"C-4#4/0, #4G
1-1/4"C-4#3, #8G
DISTRIBUTION PANEL
56-DP-TRA
225A, 208V, 3PH
DPM
100A/3P
3"C-4#4/0, #4G
56-BA105B
120/208V
3PH
100A
56-1A109B
120/208V
3PH
100A
56-2A122B
120/208V
3PH
100A
56-3A122B
120/208V
3PH
100A
100A/3P 100A/3P 100A/3P 20A/3P
DISTRIBUTION PANEL
56-DP-TRB
225A, 120/208V, 3PH
SPD DPM
150A/3P
1-1/4"C-4#3,#8G
225A/3P
2 2 2 2
1600A/3P
LSIG
500A/3P 500A/3P 100A/3P
2500A/3P
LSIG
600A/3P 800A2 /3P500A/3P 500A/3P
50A/3P 60A/3P 60A/3P 60A/3P 60A/3P
60A/3P 60A/3P 60A/3P 60A/3P 60A/3P 60A/3P
200A/3P 600A/3P200A/3P 200A/3P
80A/3P 30A/3P 30A/3P 30A/3P 400A/3P
100A/3P 100A/3P 225A/3P 225A/3P 225A/3P 225A/3P 225A/3P 225A/3P 225A/3P 60A/3P60A/3P
DP/56R
800A, 480/277V, 3PH, 4W,
42kAIC, ISC=22,831A
70A/3P 70A/3P 70A/3P 70A/3P 70A/3P 50A/3P 50A/3P 70A/3P 70A/3P 50A/3P
DP/56C
1600A, 208/120V, 3PH, 4W,
42kAIC, ISC=13,639A
60A/3P 60A/3P 60A/3P 60A/3P
20A/3P
500A/3P
60A/3P
2"C-3#2/0,#6G
TR-56-DP-TRB
75kVA
480-208/120V
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
TYPICAL 100A PANEL. REFERENCE TYPICAL SCHEDULE "SOURCE A POWER TR PANEL,
TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING INFORMATION.
TYPICAL 100A PANEL. REFERENCE TYPICAL SCHEDULE "SOURCE B POWER TR PANEL,
TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING INFORMATION.
REFERENCE GENERATOR LOAD CALCULATION SCHEDULE ON SHEET EP704 FOR
GENERATOR LOADING DATA.
EXISTING PANELBOARD TO BE MODIFIED; PROVIDE CIRCUIT BREAKER AS SHOWN.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
56EP601
BLDG. 56 - ONE-LINE DIAGRAM
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM - INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM LLT/JPS
CONSTRUCTION
DOCUMENTS
Revisions: Date:
GENERAL NOTES
KEY NOTES
- 1/2" = 1'-0"
1 BLDG. 56 - ONE-LINE DIAGRAM
XF2-BLDG-57
Size 2000 kVA Pri Delta Sec Wye-Ground %Z 5.7500 % X/R 8.0
57MSB-480V
480.0 V
1200.0 A
57-MOTOR LOADS
100 hp Load Factor 1.00 X"d 0.17 pu
57-LOADS
TO SG57
ISC=11258
57-1L1
DP/57L
400A, 480/277V, 3PH, 4W,
22kAIC, ISC=12809
100A/3P 225A/3P
ISC=3390
57-1L2
400A/3P 600A/3P
INVERTER
TO PV ON ROOF
MV
SWITCH
KVA
4160-480 /277V MSB/57 w/
METERING
DP/57R
800A, 480/277V, 3PH, 4W,
22kAIC, ISC=12428
800A/3P
DP/57M
600A, 480/277V, 3PH, 4W,
22kAIC, ISC=12428
600A/3P
MCC/57M
ISC=5428
MCC/57M-1
ISC=9058
400A/3P 200A/3P
200A
NF,N1
TR-57-1N1
75KVA
110A/3P
PANELPANEL
57-1T1-2
ISC=2000
57-1T1-1
ISC=2000
60A/3P60A/3P
PANEL
57-1N2
ISC=1826
PANEL
57-1N1 225A, 480/277V, 3PH, 4W,
10kAIC, ISC=2414
200A
NF,N1
TR-57-1N2
112.5KVA
175A/3P
PANEL
57-1N3
ISC=1933
200A
NF,N1
TR-57-1N3
112.5KVA
175A/3P
200A
NF,N1
TR-57-1N4
45KVA
70A/3P
PANEL
57-1N4 225A, 208/120V, 3PH, 4W,
10kAIC, ISC=3031
PANEL
57-1T4-1
ISC=2500
150A/3P
PANEL
57-1T4-1
ISC=2500
60A/3P
PANEL
57-1B139A
208V, 3PH
100A
100A/3P
PANEL
57-1B139B
208V, 3PH
100A
100A/3P
1-1/4"C-4#3, #8G
PANEL
57-1N5A
ISC=1889
PANEL
57-1N5B
ISC=1889
PANEL
57-1N5C
ISC=1889
PANEL
57-1N5 400A, 208/120V, 3PH, 4W,
10kAIC, ISC=3047
150A/3P150A/3P
200A
NF,N1
TR-57-1N5
150KVA
225A/3P
200A
NF,N1
TR-57-1N6
75KVA
110A/3P
PANEL
57-1N6 225A, 208/120V, 3PH, 4W,
10kAIC, ISC=1995
PANEL
57-1T6-1
ISC=1500
60A/3P
PANEL
57-1B120A
208V, 3PH
100A
PANEL
57-1B120B
208V, 3PH
100A
100A/3P 100A/3P
PANEL
57-1T6-2
ISC=1500
60A/3P
1-1/4"C-4#3, #8G
PANEL
57-1N7A
ISC=1889
150A/3P
TR-57-1N7
112.5KVA
PANEL
57-1N7 400A, 208/120V, 3PH, 4W,
10kAIC, ISC=1889
200A
NF,N1
175A/3P
3 4 3 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
57EP601
BLDG 57 - ONE-LINE DIAGRAM
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
JEFFERSON BARRACKS - 1 JEFFERSON BARRACKS
DRIVE - ST. LOUIS, MO 63125
657-21-701JB
03/31/2022 LRL/WNM LLT/JPS
CONSTRUCTION
DOCUMENTS
Revisions: Date:
GENERAL NOTES
KEY NOTES
- 3/4" = 1'-0"
1 BLDG 57 - ONE-LINE DIAGRAM
1 REPLACE EXISTING CIRCUIT BREAKER WITH 100A/3P CIRCUIT BREAKER TO
SUPPLY NEW LOAD.
2 DEMOLISH EXISTING PANELBOARD AND ASSOCIATED CONDUIT AND WIRE AS
INDICATED.
3 TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER
TR PANEL, TYPICAL - TYPE 3" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
4 TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER
TR PANEL, TYPICAL - TYPE 3" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
CONTINUED ON
SHEET
O-E-200
FUSE-SG52-58-1
S&C
SMU-20, 50E
50.0 A
58-XF2-BLDG 58
300 kVA Pri 4160 V
Sec 208 V
6.5000 %
SG52-58
4160.0 V
0.0 A
CBL-58-SWBD
50.0 ft
3 per phase
500 kcmil
Copper
PD58-SWBD-MCB
SQUARE D
RG
2500.0 A
PD58-SPD
SQUARE D
FH
60.0 A
Surge
Protective
Device
CBL-58-58L1
24.0 ft
1/0 AWG
Copper
58-PANEL-58L1
208.0 V
225.0 A
CBL-58-58P1
15.0 ft
3/0 AWG
Copper
58-PANEL-58P1
208.0 V
225.0 A
CBL-58-58L2
245.0 ft
1/0 AWG
Copper
58-PANEL-58L2
208.0 V
225.0 A
CBL-58-58P2
240.0 ft
600 kcmil
Copper
58-PANEL-58P2
208.0 V
400.0 A
PD58-58P3
SQUARE D
QJ
125.0 A CBL-58-58P3
17.0 ft
1 AWG
Copper
CBL-58-DP-1
20.0 ft
600 kcmil
Copper
58-PANEL-58P3
208.0 V
225.0 A
58-PANEL-DP-1
208.0 V
400.0 A
PD58-58SF-1
125.0 A
3P.
PD58-CWP-2
20.0 A
3P.
PD58-CWP-1
20.0 A
3P.
PD58-WH-1
25.0 A
2P.
PD58-WH-2
25.0 A
2P.
PD58-RF-1
50.0 A
3P.
PD58-HWP-1
20.0 A
3P.
PD58-EF-3
20.0 A
3P.
PD58-CRS-1
20.0 A
3P.
PD58-SP3
20.0 A
3P.
SPARE
PD58-SP4
20.0 A
1P.
SPARE
PD58-RECEPTS RM 117
20.0 A
1P.
RECEPTS
RM. 117
PD58-H-1 DAMPER
20.0 A
1P.
PD58-EF-1
20.0 A
1P.
PD58-EF-2
20.0 A
1P.
PD58-PHP-1
20.0 A
1P.
PD58-SP5
20.0 A
1P.
SPARE
PD58-HWP-2
20.0 A
3P.
PD58-FCU-1
20.0 A
3P.
CBL-58-58P4
242.0 ft
1/0 AWG
Copper
58-PANEL-58P4
208.0 V
100.0 A
PD58-DP-1
SQUARE D
LX
400.0 A
PD58-58L1
SQUARE D
QJ
150.0 A
PD58-58P1
SQUARE D
QG
200.0 A
PD58-58L2
SQUARE D
QG
150.0 A
PD58-58P2
SQUARE D
LX
400.0 A
PD58-58P4
SQUARE D
FH
100.0 A
100A/3P 100A/3P
58-PANEL-MDP-58
208.0 V
1000.0 A
58SF-1
NumMotors 1 Total 0 hp
58-CWP-2
NumMotors 1 Total 0 hp
58-CWP-1
NumMotors 1 Total 0 hp
58-WH-1
3.6KW
58-WH-2
3.6KW
58RF-1
NumMotors 1 Total 0 hp
58HWP-1
NumMotors 1 Total 0 hp
58-EF-3
NumMotors 1 Total 0 hp
58-CRS-1
NumMotors 1 Total 0 hp
58-H-1 DAMPER
NumMotors 1 Total 0 hp
58EF-1
NumMotors 1 Total 0 hp
58EF-2
NumMotors 1 Total 0 hp
58-PHP-1
NumMotors 1 Total 0 hp
58-HWP-2
NumMotors 1 Total 0 hp
58-FCU-1
NumMotors 1 Total 0 hp
1 per phase 1 per phase 1 per phase 1 per phase 1 per phase
1 per phase
1 per phase
1-1/4"C-4#3, #8G
58-104B
208V, 3PH
100A
58-104A
208V, 3PH
100A
TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER TR
PANEL, TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER TR
PANEL, TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
EXISTING PANEL TO BE MODIFIED; PROVIDE CIRCUIT BREAKERS AS INDICATED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
58EP601
BLDG 58 - ONE-LINE DIAGRAM
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM LLT/JPS
CONSTRUCTION
DOCUMENTS
GENERAL NOTES
KEY NOTES
- 6" = 1'-0"
1 BLDG 58 - ONE-LINE DIAGRAM
Revisions: Date:
1 2
3 3
SG51-60
4160.0 V
600.0 A
51-PD-XF2-BLDG 51
S&C
SMU-20, 100E
100.0 A
CBL-51-XF2-BLDG 51
260.0 ft
1 per phase
3/0 AWG
Copper
SHEET 51-E-201
FUSE-SG51-60-3
S&C
SMU-20, 200E
200.0 A
CBL-60-XF2 BLDG 60
100.0 ft
1 per phase
3/0 AWG
Copper
60-XF2-BLDG 60
300 kVA
Pri 4160 V Sec 208 V
5.3000 %
PD90-90P
CUTLER-HAMMER
CND
CBL-60-MDP-60
4.0 ft
4 per phase
350 kcmil
Copper
PD60-MDP-60-MCB
CUTLER-HAMMER
CRD
1600.0 A
PD60-SP1
CUTLER-HAMMER
BAB
20.0 A
SPARE
PD60-SP2
CUTLER-HAMMER
ED
100.0 A
SPARE
PD60-SP3
CUTLER-HAMMER
ED
100.0 A
SPARE
PD60-SP4
CUTLER-HAMMER
ED
100.0 A
SPARE
PD60-SP5
CUTLER-HAMMER
ED
100.0 A
SPARE
PD60-SP6
CUTLER-HAMMER
CA
225.0 A
SPARE
PD60-SP7
CUTLER-HAMMER
CA
225.0 A
SPARE
PD60-SP8
CUTLER-HAMMER
DA
400.0 A
SPARE
PD60-SP9
CUTLER-HAMMER
DA
400.0 A
SPARE
90-ATS 90-2 Amps
Rating 800.0 A AIC
50.00 kA
PD90-ATS 90-1-N
CUTLER-HAMMER
DA
400.0 A
PD90-ATS 90-2-N
CUTLER-HAMMER
MDL
800.0 A
60-PANEL-MDP-60
208.0 V
1600.0 A
PD90-ATS 90-2-E
CUTLER-HAMMER
MDL
800.0 A
PD90-ATS 90-1-E
CUTLER-HAMMER
DA
400.0 A
PD90-SPACE
CUTLER-HAMMER
DA
400.0 A
1200.0 A
CBL-90-90P
12.0 ft
4 per phase
350 kcmil Copper
90-PANEL-90P
208.0 V
1200.0 A
GEN90P
389 kVA
X"d 0.2 pu
90-ATS 90-1 Amps
Rating 400.0 A AIC
35.00 kA
PD60-DP-60EM-MCB
CUTLER-HAMMER
MDL
800.0 A
90-CBL-AC 90 TON
50.0 ft
2 per phase
250 kcmil
Copper
PD60-REF PNL-B
CUTLER-HAMMER
DK
400.0 A
PD60-P2
CUTLER-HAMMER
HLB
400.0 A
90-AC 90 TON
NumMotors 1
Total 100 hp
60-PANEL-B
208.0 V
400.0 A
60-PANEL-REF PNL-B
PD60-A
CUTLER-HAMMER
ED
CBL-60-A
5.0 ft
1 per phase
1 AWG
Copper
CBL-60-BA
2.0 ft 1 per phase
350 kcmil Copper
100.0 A
BUS-0373
208.0 V
0.0 A
CBL-60-P2-2
16.0 ft
1 per phase
350 kcmil
Copper
60-PANEL-60-BA
208.0 V
225.0 A
PNL-60-P2
208.0 V
225.0 A
208.0 V
400.0 A
CBL-60-P2-1
99.0 ft
1 per phase
350 kcmil
Copper
90-PANEL-GB BLDG.90
208.0 V
225.0 A
TO BLDG.90
60-PANEL-60-B1
208.0 V
225.0 A
60-PANEL-60-B2
208.0 V
225.0 A
PD90-GB
CUTLER-HAMMER
CA
225.0 A
PD60-EXHAUST HOODS
CUTLER-HAMMER
ED
100.0 A
EXHAUST
HOODS
CBL-60-REF PNL-B
131.0 ft
2 per phase
250 kcmil
Copper
CBL-90-GB
50.0 ft
1 per phase
350 kcmil
Copper
CBL-60T-MDP 60T
126.0 ft
2 per phase
250 kcmil
Copper
60-PANEL-MDP-60T
208V, 3PH
400A
(BLDG 60T)
CBL-60-B1
5.0 ft 1 per phase
350 kcmil
Copper
CBL-60-B2
0.1 ft
1 per phase
350 kcmil
Copper
EM
LIGHTS
CBL-60-RISER-B1
138.0 ft
1 per phase
350 kcmil
Copper
CBL-60-P4
27.0 ft
1 per phase
1 AWG
Copper
60-PANEL-P4
208.0 V
225.0 A
CBL-60-P4A
16.0 ft
1 per phase
1 AWG
Copper
60-PANEL-P4A
208.0 V
225.0 A
PD60-EM LIGHTS
CUTLER-HAMMER
GB
100.0 A
PD60T-MDP 60T
CUTLER-HAMMER
DK
400.0 A
PD60-RISER-B1
CUTLER-HAMMER
CA
225.0 A
60-PANEL-DP-60EM
PD60-P4
CUTLER-HAMMER
GB
100.0 A
208.0 V
1200.0 A
PD60-SP10
CUTLER-HAMMER
GB
100.0 A
G
60-102A 120/208V
3PH
100A
60-102B
208V, 3PH
100A
1-1/4"C-4#3, #8G
1-1/4"C-4#3,#8G
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
60EP601
BLDG 60 AND 60T - ONE-LINE
DIAGRAMSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM LLT/JPS
CONSTRUCTION
DOCUMENTS
GENERAL NOTES
KEY NOTES
- 6" = 1'-0"
1 BLDG 60 AND 60T - ONE-LINE DIAGRAM
Revisions: Date:
TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER
TR PANEL, TYPICAL - TYPE 1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER
TR PANEL, TYPICAL - TYPE 1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
EXISTING PANEL TO BE MODIFIED.
REFERENCE GENERATOR LOAD CALCULATION SCHEDULE ON SHEET EP704 FOR
GENERATOR LOADING DATA.
XISTING PANEL TO BE MODIFIED; UTILIZE EXISTING CIRCUIT BREAKERS AS
INDICATED.
TO UNIT SUBSTATION UNS 75
CBL-TR-MDP75-1-4160V
Cable Size 600 AWG/kcmil
Length 10.0 ft
QtyPerPhase 1
Installation Non-Segregated
TR-MDP75-1-4160V
System Nominal Voltage 4160.0 V 13464 Amps 3P
X/R Pos 10.91 12459 Amps SLG
X/R SLG 10.5532
S
P
TR-MDP75-1
Nominal kVA 2500.0 kVA Z% 5.7500 %
X/R 10.4739
Pri RatedVoltage 4160 V
Pri FLA 347.0 A
Sec RatedVoltage 480 V Sec FLA 3007.0 A
TR-MDP75-1-480V
System Nominal Voltage 480.0 V
50311 Amps 3P
X/R Pos 9.55
50686 Amps SLG
X/R SLG 9.8386
CBL-0030
Cable Size 3000 AWG/kcmil
Length 10.0 ft
QtyPerPhase 1
Installation
(MDP/75- 1)
Frame/Rating 3000.0 A
Frame/Model KTU
(MDP/75-1)
System Nominal Voltage 480.0 V 50211 Amps 3P
X/R Pos 9.29 50097 Amps SLG
X/R SLG 8.3585
(MDP/75-1)-1 (MDP/75-1)-3
Frame/Rating 1600.0 A
Frame/Model PA
Settings
Thermal Curve
INST LO (4960A)
(MDP/75-1)-2
Frame/Rating 800.0 A
Frame/Model PA
Settings
Thermal Curve
INST LO (3200A)
CBL-0036
Cable Size 500 AWG/kcmil
Length 145.0 ft
QtyPerPhase 5
Installation
CBL-0037
Cable Size 300 AWG/kcmil
Length 87.0 ft
QtyPerPhase 3
Installation
(MCC/75-2)
PD-0184
Frame/Rating 0.0 A Frame/Model
Settings
PD-0185
Frame/Rating 0.0 A Frame/Model
Settings
PD-0186
Frame/Rating 0.0 A Frame/Model
Settings
PD-0187
Frame/Rating 0.0 A Frame/Model
Settings
PD-0188
Frame/Rating 0.0 A Frame/Model
Settings
PD-0189
Frame/Rating 0.0 A Frame/Model
Settings
PD-0190
Frame/Rating 0.0 A Frame/Model
Settings
PD-0191
Frame/Rating 0.0 A Frame/Model
Settings
PD-0192
Frame/Rating 0.0 A Frame/Model
Settings
System Nominal Voltage 480.0 V
39128 Amps 3P
X/R Pos 3.71
34080 Amps SLG
X/R SLG 2.5903
Frame/Rating 1000.0 A
Frame/Model PA
Settings
Thermal Curve
INST LO (3500A)
(MDP/75-1)-4
Frame/Rating 225.0 A
Frame/Model KC
Settings
Thermal Curve
INST LO (1125A)
(MDP/75-1)-5
Frame/Rating 250.0 A
Frame/Model KA
Settings
Thermal Curve
INST LO (875A)
CBL-0038 CBL-0039
Cable Size 300 AWG/kcmil
Length 134.0 ft
Qty Per Phase 3
Installation
Cable Size 2 AWG/kcmil
Length 113.0 ft
Qty Per Phase 1
Installation
PANEL '75L'
System Nominal Voltage 480.0 V
10364 Amps 3P
X/R Pos 0.51 6392 Amps SLG
X/R SLG 0.3824
S
P
CBL-0040
Cable Size 2/0 AWG/kcmil
Length 12.0 ft
Qty Per Phase 1
Installation
(TR/75N)
Nominal kVA 112.5 kVA Z% 5.0000 %
X/R 3.1562
Pri Rated Voltage 480 V
Pri FLA 135.3 A
CBL-BLR-1
Cable Size 4 AWG/kcmil
Length 10.0 ft
QtyPerPhase 1
Installation
BUS-BLR-1
System Nominal Voltage 480.0 V 31209 Amps 3P
X/R Pos 1.48
25862 Amps SLG
X/R SLG 1.2513
MTRI-BLR-1
Init Sym RMS 3P 279.13 A
Init Sym RMS SLG 154.20 A
Rated HP 40.0 hp
Rated Voltage 480 V
Rated Amps 48.2 A
CBL-BLR-2
Cable Size 4 AWG/kcmil
Length 10.0 ft
QtyPerPhase 1
Installation
BUS-BLR-2
System Nominal Voltage 480.0 V 31209 Amps 3P
X/R Pos 1.48
25862 Amps SLG
X/R SLG 1.2513
MTRI-BLR-2
Init Sym RMS 3P 279.13 A
Init Sym RMS SLG 154.20 A
Rated HP 40.0 hp Rated Voltage 480 V
Rated Amps 48.2 A
CBL-BLR-3
Cable Size 4 AWG/kcmil
Length 10.0 ft
QtyPerPhase 1
Installation
BUS-BLR-3
System Nominal Voltage 480.0 V 31209 Amps 3P
X/R Pos 1.48
25862 Amps SLG
X/R SLG 1.2513
MTRI-BLR-3
Init Sym RMS 3P 279.13 A
Init Sym RMS SLG 154.20 A
Rated HP 40.0 hp
Rated Voltage 480 V
Rated Amps 48.2 A
CBL-AC-1
Cable Size 8 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1
Installation
BUS-AC-1
System Nominal Voltage 480.0 V 22154 Amps 3P
X/R Pos 0.75
18062 Amps SLG
X/R SLG 0.6699
MTRI-AC-1
Init Sym RMS 3P 139.57 A
Init Sym RMS SLG 75.86 A
Rated HP 20.0 hp
Rated Voltage 480 V
Rated Amps 24.1 A
CBL-ROP-1 & 2
CableSize 12 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1
Installation
BUS-ROP-1 & 2
System Nominal Voltage 480.0 V 12475 Amps 3P
X/R Pos 0.38
10200 Amps SLG
X/R SLG 0.3510
MTRI-ROP-1 & 2
Init Sym RMS 3P 41.87 A
Init Sym RMS SLG 22.82 A
Rated HP 6.0 hp
Rated Voltage 480 V
Rated Amps 7.2 A
CBL-FOP-1 & 2
Cable Size 12 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1
Installation
BUS-FOP-1 & 2
System Nominal Voltage 480.0 V 12470 Amps 3P
X/R Pos 0.37
10197 Amps SLG
X/R SLG 0.3503
MTRI-FOP-1 & 2
Init Sym RMS 3P 27.91 A
Init Sym RMS SLG 15.22 A
Rated HP 4.0 hp
Rated Voltage 480 V
Rated Amps 4.8 A
CBL-BFP-1 & 2
Cable Size 4 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1
Installation
BUS-BFP-1 & 2
System Nominal Voltage 480.0 V 31209 Amps 3P
X/R Pos 1.48
25862 Amps SLG
X/R SLG 1.2513
MTRI-BFP-1 & 2
InitSymRMS 3P 279.13 A
InitSymRMS SLG 154.20 A
Rated HP 40.0 hp
RatedVoltage 480 V
RatedAmps 48.2 A
CBL-BFP-3 & 4
Cable Size 4 AWG/kcmil
Length 10.0 ft
QtyPerPhase 1
Installation
BUS-BFP-3 & 4
System Nominal Voltage 480.0 V 31209 Amps 3P
X/R Pos 1.48
25862 Amps SLG
X/R SLG 1.2513
MTRI-BFP-3 & 4
Init Sym RMS 3P 279.13 A
Init Sym RMS SLG 154.20 A
Rated HP 40.0 hp Rated Voltage 480 V
Rated Amps 48.2 A
CBL-TP-1 & 2
Cable Size 10 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1
Installation
BUS-TP-1 & 2
System Nominal Voltage 480.0 V
17558 Amps 3P
X/R Pos 0.56
14294 Amps SLG
X/R SLG 0.5161
MTRI-TP-1 & 2
Init Sym RMS 3P 104.67 A
Init Sym RMS SLG 56.81 A
Rated HP 15.0 hp
Rated Voltage 480 V
Rated Amps 18.1 A
PANEL '75N'
System Nominal Voltage 208.0 V
5716 Amps 3P
X/R Pos 3.14
5788 Amps SLG
X/R SLG 3.1068
Sec Rated Voltage 208 V Sec FLA 312.3 A
CBL-0041
Cable Size 600 AWG/kcmil
Length 5.0 ft
QtyPerPhase 1
Installation
(MCC/75-3)
PD-0193
Frame/Rating 0.0 A Frame/Model
Settings
PD-0194
Frame/Rating 0.0 A Frame/Model
Settings
PD-0195
Frame/Rating 0.0 A Frame/Model
Settings
PD-0196
Frame/Rating 0.0 A Frame/Model
Settings
PD-0197
Frame/Rating 0.0 A Frame/Model
Settings
PD-0198
Frame/Rating 0.0 A Frame/Model
Settings
PD-0199
Frame/Rating 0.0 A Frame/Model
Settings
PD-0200
Frame/Rating 0.0 A Frame/Model
Settings
PD-0201
Frame/Rating 0.0 A Frame/Model
Settings
PD-0202
Frame/Rating 0.0 A Frame/Model
Settings
PD-0203
Frame/Rating 0.0 A Frame/Model
Settings
PD-0204
System Nominal Voltage 480.0 V
35897 Amps 3P
X/R Pos 3.23
29255 Amps SLG
X/R SLG 2.1473
Frame/Rating 0.0 A Frame/Model
Settings
CBL-CT/1A CBL-CT/1B
Cable Size 2 AWG/kcmil
Length 10.0 ft
QtyPerPhase 1 Installation
BUS-CT/1A
System Nominal Voltage 480.0 V 30965 Amps 3P
X/R Pos 1.83 24500 Amps SLG
X/R SLG 1.4485
MTRI-CT/1A
Init Sym RMS 3P 348.92 A
Init Sym RMS SLG 184.05 A
Rated HP 50.0 hp
Rated Voltage 480 V
Rated Amps 60.3 A
Cable Size 2 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1 Installation
BUS-CT/1B
System Nominal Voltage 480.0 V 30965 Amps 3P
X/R Pos 1.83 24500 Amps SLG
X/R SLG 1.4485
MTRI-CT/1B
Init Sym RMS 3P 348.92 A
Init Sym RMS SLG 184.05 A
Rated HP 50.0 hp
Rated Voltage 480 V
Rated Amps 60.3 A
CBL-CT/2A
Cable Size 2 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1 Installation
BUS-CT/2A
System Nominal Voltage 480.0 V 30965 Amps 3P
X/R Pos 1.83 24500 Amps SLG
X/R SLG 1.4485
MTRI-CT/2A
Init Sym RMS 3P 348.92 A
Init Sym RMS SLG 184.05 A
Rated HP 50.0 hp
Rated Voltage 480 V
Rated Amps 60.3 A
CBL-CT/2B
Cable Size 2 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1 Installation
BUS-CT/2B
System Nominal Voltage 480.0 V 30965 Amps 3P
X/R Pos 1.83 24500 Amps SLG
X/R SLG 1.4485
MTRI-CT/2B
Init Sym RMS 3P 348.92 A
Init Sym RMS SLG 184.05 A
Rated HP 50.0 hp
Rated Voltage 480 V
Rated Amps 60.3 A
CBL-CT/3A
CableSize 2 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1 Installation
BUS-CT/3A
System Nominal Voltage 480.0 V 30965 Amps 3P
X/R Pos 1.83 24500 Amps SLG
X/R SLG 1.4485
MTRI-CT/3A
Init Sym RMS 3P 348.92 A
Init Sym RMS SLG 184.05 A
Rated HP 50.0 hp
Rated Voltage 480 V
Rated Amps 60.3 A
CBL-CT/3B
Cable Size 2 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1 Installation
BUS-CT/3B
System Nominal Voltage 480.0 V 30965 Amps 3P
X/R Pos 1.83 24500 Amps SLG
X/R SLG 1.4485
MTRI-CT/3B
Init Sym RMS 3P 348.92 A
Init Sym RMS SLG 184.05 A
Rated HP 50.0 hp
Rated Voltage 480 V
Rated Amps 60.3 A
CBL-CT/4A
Cable Size 2 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1 Installation
BUS-CT/4A
System Nominal Voltage 480.0 V 30965 Amps 3P
X/R Pos 1.83 24500 Amps SLG
X/R SLG 1.4485
MTRI-CT/4A
Init Sym RMS 3P 348.92 A
Init Sym RMS SLG 184.05 A
Rated HP 50.0 hp
Rated Voltage 480 V
Rated Amps 60.3 A
CBL-CT/4B
Cable Size 2 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1 Installation
BUS-CT/4B
System Nominal Voltage 480.0 V 30965 Amps 3P
X/R Pos 1.83 24500 Amps SLG
X/R SLG 1.4485
MTRI-CT/4B
Init Sym RMS 3P 348.92 A
Init Sym RMS SLG 184.05 A
Rated HP 50.0 hp
Rated Voltage 480 V
Rated Amps 60.3 A
CBL-MUA-1 & 2 &3
Cable Size 6 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1 Installation
BUS-MUA-1 & 2 & 3
System Nominal Voltage 480.0 V 25487 Amps 3P
X/R Pos 1.07 19966 Amps SLG
X/R SLG 0.9291
MTRI-MUA-1 & 2 & 3
Init Sym RMS 3P 209.35 A
Init Sym RMS SLG 109.33 A
Rated HP 30.0 hp
Rated Voltage 480 V
Rated Amps 36.2 A
CBL-AHU-1 & 2 & 3
Cable Size 2 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1 Installation
BUS-AHU-1 & 2 & 3
System Nominal Voltage 480.0 V 30953 Amps 3P
X/R Pos 1.82 24494 Amps SLG
X/R SLG 1.4472
MTRI-AHU-1 & 2 & 3
Init Sym RMS 3P 282.62 A
Init Sym RMS SLG 149.10 A
Rated HP 40.5 hp
Rated Voltage 480 V
Rated Amps 48.8 A
CBL-SF-1 & 2, EF-1 & 2 & 3
Cable Size 2 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1 Installation
BUS-SF-1 & 2, EF-1 & 2 & 3
System Nominal Voltage 480.0 V 30958 Amps 3P
X/R Pos 1.83 24497 Amps SLG
X/R SLG 1.4478
MTRI-SF-1 & 2, EF-1 & 2 & 3
Init Sym RMS 3P 314.02 A
Init Sym RMS SLG 165.65 A
Rated HP 45.0 hp
Rated Voltage 480 V
Rated Amps 54.3 A
CBL-SF-3, EF-4 & 5, FCU-1 & 2
Cable Size 8 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1 Installation
BUS-SF-3, EF-4 & 5, FCU-1 & 2
System Nominal Voltage 480.0 V 21033 Amps 3P
X/R Pos 0.77 16511 Amps SLG
X/R SLG 0.6917
MTRI-SF-3, EF-4 & 5, FCU-1 & 2
Init Sym RMS 3P 167.48 A
Init Sym RMS SLG 87.64 A
Rated HP 24.0 hp
Rated Voltage 480 V
Rated Amps 28.9 A
(MCC/75-1)
PD-0174
Frame/Rating 0.0 A
Frame/Model
Settings
PD-0175
Frame/Rating 0.0 A
Frame/Model
Settings
PD-0176
Frame/Rating 0.0 A
Frame/Model
Settings
PD-0177
Frame/Rating 0.0 A
Frame/Model
Settings
PD-0178
Frame/Rating 0.0 A
Frame/Model
Settings
PD-0179
Frame/Rating 0.0 A
Frame/Model
Settings
PD-0180
Frame/Rating 0.0 A
Frame/Model
Settings
PD-0181
Frame/Rating 0.0 A
Frame/Model
Settings
PD-0182
Frame/Rating 0.0 A
Frame/Model
Settings
PD-0183
Frame/Rating 0.0 A
Frame/Model
Settings
PD-0205
Frame/Rating 0.0 A
Frame/Model
Settings
PD-0206
Frame/Rating 0.0 A
Frame/Model
Settings
PD-0207
Frame/Rating 0.0 A
Frame/Model
Settings
System Nominal Voltage 480.0 V
43845 Amps 3P
X/R Pos 5.99
37663 Amps SLG
X/R SLG 3.8134
CBL-SCWP-1 CBL-SCWP-2
Cable Size 3/0 AWG/kcmil
Length 10.0 ft
Qty Per Phase 2
Installation
BUS-SCWP-1
System Nominal Voltage 480.0 V 42110 Amps 3P
X/R Pos 4.60 35628 Amps SLG
X/R SLG 3.2151
MTRI-SCWP-1
Init Sym RMS 3P 1744.58 A
Init Sym RMS SLG 984.03 A
Rated HP 250.0 hp
Rated Voltage 480 V
Rated Amps 301.5 A
Cable Size 3/0 AWG/kcmil
Length 10.0 ft
Qty Per Phase 2
Installation
BUS-SCWP-2
System Nominal Voltage 480.0 V 42110 Amps 3P
X/R Pos 4.60 35628 Amps SLG
X/R SLG 3.2151
MTRI-SCWP-2
Init Sym RMS 3P 1744.58 A
Init Sym RMS SLG 984.03 A
Rated HP 250.0 hp
Rated Voltage 480 V
Rated Amps 301.5 A
CBL-SCWP-3
Cable Size 3/0 AWG/kcmil
Length 10.0 ft
Qty Per Phase 2
Installation
BUS-SCWP-3
System Nominal Voltage 480.0 V 42110 Amps 3P
X/R Pos 4.60 35628 Amps SLG
X/R SLG 3.2151
MTRI-SCWP-3
Init Sym RMS 3P 1744.58 A
Init Sym RMS SLG 984.03 A
Rated HP 250.0 hp
Rated Voltage 480 V
Rated Amps 301.5 A
CBL-CWP-1
Cable Size 2 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1
Installation
BUS-CWP-1
System Nominal Voltage 480.0 V 37591 Amps 3P
X/R Pos 2.19 31007 Amps SLG
X/R SLG 1.8227
MTRI-CWP-1
Init Sym RMS 3P 348.92 A
Init Sym RMS SLG 191.87 A
Rated HP 50.0 hp
Rated Voltage 480 V
Rated Amps 60.3 A
CBL-CWP-2
Cable Size 2 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1
Installation
BUS-CWP-2
System Nominal Voltage 480.0 V 37591 Amps 3P
X/R Pos 2.19 31007 Amps SLG
X/R SLG 1.8227
MTRI-CWP-2
Init Sym RMS 3P 348.92 A
Init Sym RMS SLG 191.87 A
Rated HP 50.0 hp
Rated Voltage 480 V
Rated Amps 60.3 A
CBL-CWP-3
Cable Size 2 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1
Installation
BUS-CWP-3
System Nominal Voltage 480.0 V 37591 Amps 3P
X/R Pos 2.19 31007 Amps SLG
X/R SLG 1.8227
MTRI-CWP-3
Init Sym RMS 3P 348.92 A
Init Sym RMS SLG 191.87 A
Rated HP 50.0 hp
Rated Voltage 480 V
Rated Amps 60.3 A
CBL-CWP-4
Cable Size 2 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1
Installation
BUS-CWP-4
System Nominal Voltage 480.0 V 37591 Amps 3P
X/R Pos 2.19 31007 Amps SLG
X/R SLG 1.8227
MTRI-CWP-4
Init Sym RMS 3P 348.92 A
Init Sym RMS SLG 191.87 A
Rated HP 50.0 hp
Rated Voltage 480 V
Rated Amps 60.3 A
CBL-CWP-5
Cable Size 3/0 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1
Installation
BUS-CWP-5
System Nominal Voltage 480.0 V 40291 Amps 3P
X/R Pos 3.72 33677 Amps SLG
X/R SLG 2.7917
MTRI-CWP-5
Init Sym RMS 3P 872.29 A
Init Sym RMS SLG 486.06 A
Rated HP 125.0 hp
Rated Voltage 480 V
Rated Amps 150.8 A
CBL-CWP-6
Cable Size 3/0 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1
Installation
BUS-CWP-6
System Nominal Voltage 480.0 V 40291 Amps 3P
X/R Pos 3.72 33677 Amps SLG
X/R SLG 2.7917
MTRI-CWP-6
Init Sym RMS 3P 872.29 A
Init Sym RMS SLG 486.06 A
Rated HP 125.0 hp
Rated Voltage 480 V
Rated Amps 150.8 A
CBL-CP-1
CableSize 2/0 AWG/kcmil
Length 10.0 ft
QtyPerPhase 1
Installation
BUS-CP-1
SystemNominalVoltage 480.0 V 39814 Amps 3P
X/R Pos 3.28 33183 Amps SLG
X/R SLG 2.5293
MTRI-CP-1
Init Sym RMS 3P 697.83 A
Init Sym RMS SLG 387.74 A
Rated HP 100.0 hp
Rated Voltage 480 V
Rated Amps 120.6 A
CBL-CP-2
Cable Size 2/0 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1
Installation
BUS-CP-2
System Nominal Voltage 480.0 V 39814 Amps 3P
X/R Pos 3.28 33183 Amps SLG
X/R SLG 2.5293
MTRI-CP-2
Init Sym RMS 3P 697.83 A
Init Sym RMS SLG 387.74 A
Rated HP 100.0 hp
Rated Voltage 480 V
Rated Amps 120.6 A
CBL-CP-3
Cable Size 2/0 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1
Installation
BUS-CP-3
System Nominal Voltage 480.0 V 39814 Amps 3P
X/R Pos 3.28 33183 Amps SLG
X/R SLG 2.5293
MTRI-CP-3
Init Sym RMS 3P 697.83 A
Init Sym RMS SLG 387.74 A
Rated HP 100.0 hp
Rated Voltage 480 V
Rated Amps 120.6 A
CBL-CP-4
Cable Size 2/0 AWG/kcmil
Length 10.0 ft
Qty Per Phase 1
Installation
BUS-CP-4
System Nominal Voltage 480.0 V 39814 Amps 3P
X/R Pos 3.28 33183 Amps SLG
X/R SLG 2.5293
MTRI-CP-4
Init Sym RMS 3P 697.83 A
Init Sym RMS SLG 387.74 A
Rated HP 100.0 hp
Rated Voltage 480 V
Rated Amps 120.6 A
75-DP-TRAB
208V, 3PH
200A
200A/3P
20A/3P20A/3P100A/3P100A/3P
DPMSPD
1/4"C-4#3, #8G
75-1B105A
208V, 3PH
100A
75-1B105B
208V, 3PH
100A
2 3
2"C-4#3/0, #6G
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
75EP601
BLDG 75 - ONE-LINE DIAGRAM
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM LLT/JPS
CONSTRUCTION
DOCUMENTS
Revisions: Date:
KEY NOTES
GENERAL NOTES
- Scale: NTS
1 BLDG 75 - ONE-LINE DIAGRAM
PROVIDE TAPS AS REQUIRED TO INSTALL FEEDER TO PANEL 75-DP-TRAB; IF
REQUIRED, PROVIDE JUNCTION BOX TO HOUSE INSULATED TAPS AS REQUIRED.
TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER
TR PANEL, TYPICAL - TYPE 3" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER
TR PANEL, TYPICAL - TYPE 3" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING
INFORMATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
01EP701
BLDG 01 - ELECTRICAL SCHEDULES
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON
BARRACKS MO
657-21-701JB
03/31/2022 LRL/WNM JBB
CONSTRUCTION
DOCUMENTS
Revisions: Date:
GENERAL NOTES
KEY NOTES
Notes:
Total Est. Demand: 80 A
Total Conn.: 126 A
Total Est. Demand: 28840 VA
Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 45280 VA
Other 2400 VA 100.00% 2400 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 132 A 118 A 132 A
Total Load: 15573 VA 14133 VA 15573 VA
71 -- -- -- 0 VA 72
69 -- -- -- 0 VA 70
67 1-24-B (LIGHTS) 400 A 3 0 VA 68
65 -- -- -- 0 VA 1557... -- -- -- 66
63 -- -- -- 0 VA 1413... -- -- -- 64
61 PANEL P-4 400 A 3 0 VA 1557... 3 400 A 1-DP-TRB 62
59 -- -- -- 0 VA 0 VA -- -- -- 60
57 -- -- -- 0 VA 0 VA -- -- -- 58
55 ATS1-CDP 600 A 3 0 VA 0 VA 3 400 A PANEL 1PPC 56
53 -- -- -- 0 VA 0 VA -- -- -- 54
51 -- -- -- 0 VA 0 VA -- -- -- 52
49 ATS1-EMDP 700 A 3 0 VA 0 VA 3 225 A PANEL 1E-15H 50
47 -- -- -- 0 VA 0 VA -- -- -- 48
45 -- -- -- 0 VA 0 VA -- -- -- 46
43 PANEL X1 (VIA 1-XF2-PANEL-X1) 800 A 3 0 VA 0 VA 3 225 A PANEL 1-L15 44
41 -- -- -- 0 VA 0 VA -- -- -- 42
39 -- -- -- 0 VA 0 VA -- -- -- 40
37 PANEL SERV. ROM 6614 200 A 3 0 VA 0 VA 3 400 A PANEL L34 38
35 -- -- -- 0 VA 0 VA -- -- -- 36
33 -- -- -- 0 VA 0 VA -- -- -- 34
31 PANEL GC17 200 A 3 0 VA 0 VA 3 300 A PANEL N1 32
29 -- -- -- 0 VA 0 VA -- -- -- 30
27 -- -- -- 0 VA 0 VA -- -- -- 28
25 PANEL 1P2 250 A 3 0 VA 0 VA 3 400 A RISER-1P-1 (PANELS 1P5, GC18, 1P3) 26
23 -- -- -- 0 VA 0 VA -- -- -- 24
21 -- -- -- 0 VA 0 VA -- -- -- 22
19 ATS1-EDP25 250 A 3 0 VA 0 VA 3 400 A L2-RISER-1 (PANELS L02L, 1-L12L, L22R, L32L) 20
17 -- -- -- 0 VA 0 VA -- -- -- 18
15 -- -- -- 0 VA 0 VA -- -- -- 16
13 PANEL L13A 250 A 3 0 VA 0 VA 3 400 A PANEL E3 LAB 14
11 -- -- -- 0 VA 0 VA -- -- -- 12
9 -- -- -- 0 VA 0 VA -- -- -- 10
7 PANEL H1 100 A 3 0 VA 0 VA 3 400 A L1-RISER-1 (PANEL L01, PANEL 1-L11R, PANE... 8
5 -- -- -- 0 VA 0 VA -- -- -- 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 ATS1-LSA 100 A 3 0 VA 0 VA 3 400 A L3-RISER-1 (PANEL L03, PANEL L13L, PANEL... 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: N/A Wires: 4 Mains: 2500A / 3P
Supply From: 1-XF2-BLDG-1-MSB Phases: 3 Mains Rating: 2500 A
Location: GC16 Volts: 120/208 Wye A.I.C. Rating:
Switchboard: MSB
REMOVE EXISTING SPARE CIRCUIT BREAKER AND INSTALL NEW CIRCUIT
BREAKER TO SUPPLY NEW LOAD.
PROVIDE NEW CIRCUIT BREAKER TO SUPPLY NEW LOAD.2
EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.
REFERENCE ONE-LINE DIAGRAM ON SHEET 01EP601 FOR ADDITIONAL
INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.
THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT
PROVIDED TO SHOW OVERALL LOAD OF PANEL.
Notes:
Total Est. Demand: 82 A
Total Conn.: 128 A
Lighting 808 VA 100.00% 808 VA Total Est. Demand: 29648 VA
Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 46088 VA
Other 2400 VA 100.00% 2400 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 134 A 121 A 131 A
Total Load: 15977 VA 14537 VA 15573 VA
29 -- -- -- 1557... -- -- -- -- 30
27 -- -- -- 1453... -- -- -- -- 28
25 1-DP-TRA 400 A 3 1597... -- 3 -- Space 26
23 -- -- -- 0 VA 0 VA -- -- -- 24
21 -- -- -- 0 VA 0 VA -- -- -- 22
19 ECGB 100 A 3 0 VA 0 VA 3 100 A ECGA 20
17 -- -- -- 0 VA 0 VA -- -- -- 18
15 -- -- -- 0 VA 0 VA -- -- -- 16
13 EC1 175 A 3 0 VA 0 VA 3 225 A 2CEC, 3CEC 14
11 -- -- -- 0 VA 0 VA -- -- -- 12
9 -- -- -- 0 VA 0 VA -- -- -- 10
7 GC14 200 A 3 0 VA 0 VA 3 225 A EP, 2C3 8
5 -- -- -- 0 VA 0 VA -- -- -- 6
3 -- -- -- 0 VA 0 VA -- -- -- 4
1 EP3L 400 A 3 0 VA 0 VA 3 225 A 60kW UPS 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains: 600A
Supply From: 1-ATS1-CDP Phases: 3 Mains Rating: 100 A
Location: GC16A Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: CDP
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY
AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND
SOURCE-B PANEL SCHEDULES.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
01EP702
BLDG 01 - ELECTRICAL SCHEDULES
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON
BARRACKS MO
657-21-701JB
03/31/2022 Checker Author
CONSTRUCTION
DOCUMENTS
Revisions: Date:
Notes:
Total Est. Demand: 82 A
Total Conn.: 128 A
Lighting 808 VA 100.00% 808 VA Total Est. Demand: 29648 VA
Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 46088 VA
Other 2400 VA 100.00% 2400 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 134 A 121 A 131 A
Total Load: 15977 VA 14537 VA 15573 VA
29 SPARE 20 A 1 0 VA 0 VA -- -- -- 30
27 SPARE 20 A 1 0 VA 0 VA -- -- -- 28
25 SPARE 20 A 1 0 VA 0 VA 3 20 A SPD 26
23 SPARE 20 A 1 0 VA 0 VA -- -- -- 24
21 SPARE 20 A 1 0 VA 0 VA -- -- -- 22
19 SPARE 20 A 1 0 VA 0 VA 3 20 A DIGITAL POWER METER 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 -- -- -- 3533... 0 VA 1 20 A SPARE 16
13 -- -- -- 3735... 0 VA 1 20 A SPARE 14
11 PANEL 1-1E15A 100 A 3 4253... 3533... -- -- -- 12
9 -- -- -- 3533... 3735... -- -- -- 10
7 -- -- -- 3735... 4253... 3 20 A PANEL 1-3C13A 8
5 PANEL 1-2C10A 20 A 3 4253... 3533... -- -- -- 6
3 SPARE 20 A 1 0 VA 3735... -- -- -- 4
1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 1-C102DA 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: SURFACE Wires: 4 Mains: 400A/3P
Supply From: 1-PANEL-CDP Phases: 3 Mains Rating: 400 A
Location: GC-15 Volts: 120/208 Wye A.I.C. Rating: 65k
Branch Panel: 1-DP-TRA
Notes:
Total Est. Demand: 80 A
Total Conn.: 126 A
Total Est. Demand: 28840 VA
Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 45280 VA
Other 2400 VA 100.00% 2400 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 132 A 118 A 132 A
Total Load: 15573 VA 14133 VA 15573 VA
29 SPARE 20 A 1 0 VA 0 VA -- -- -- 30
27 SPARE 20 A 1 0 VA 0 VA -- -- -- 28
25 SPARE 20 A 1 0 VA 0 VA 3 20 A SPD 26
23 SPARE 20 A 1 0 VA 0 VA -- -- -- 24
21 SPARE 20 A 1 0 VA 0 VA -- -- -- 22
19 SPARE 20 A 1 0 VA 0 VA 3 20 A DIGITAL POWER METER 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 -- -- -- 3533... 0 VA 1 20 A SPARE 16
13 -- -- -- 3533... 0 VA 1 20 A SPARE 14
11 PANEL 1-2C10AB 100 A 3 4253... 3533... -- -- -- 12
9 -- -- -- 3533... 3533... -- -- -- 10
7 -- -- -- 3533... 4253... 3 100 A PANEL 1-3C13B 8
5 PANEL 1-1E15B 100 A 3 4253... 3533... -- -- -- 6
3 SPARE 20 A 1 0 VA 3533... -- -- -- 4
1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 1-C102DB 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1
Mounting: SURFACE Wires: 4 Mains: 400A / 3P
Supply From: 1-SWBD-MSB-01 Phases: 3 Mains Rating: 400 A
Location: GC-15 Volts: 120/208 Wye A.I.C. Rating: 65k
Branch Panel: 1-DP-TRB
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY
AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND
SOURCE-B PANEL SCHEDULES.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
02EP701
BLDG 02 - ELECTRICAL
SCHEDULESSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM JBB
CONSTRUCTION
DOCUMENTS
Revisions: Date:
GENERAL NOTES
KEY NOTES
Notes:
Total Est. Demand: 103 A
Total Conn.: 144 A
Power 6568 VA 100.00% 6568 VA Total Est. Demand: 36968 VA
Receptacle 40000 VA 62.50% 25000 VA Total Conn. Load: 51968 VA
Other 5400 VA 100.00% 5400 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 155 A 126 A 160 A
Total Load: 18101 VA 15133 VA 18733 VA
41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42
39 SPARE 20 A 1 0 VA 100…