Attachment 19 - Drawings Part-18.pdf

PDF 14 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks Federal contract opportunity
Solicitation number
36C77623R0009
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This solicitation is seeking a general contractor to provide infrastructure upgrades at the St. Louis Jefferson Barracks VA Medical Center. The scope of work includes electrical panel upgrades and power systems work, building management system integration, HVAC assessments and upgrades, interior renovations including demolition and new construction, data center renovations, physical security enhancements, fiber optic infrastructure assessment and upgrades between buildings, installation of a diversified wide area network path to the datacenter, and hazardous material abatement. The project involves construction and renovation activities in buildings 1, 2, 3, 3T, 18, 23, 24, 25, 51, 51T, 52, 53, 53T, 55, 56, 57, 58, 59, 60, 60T, 61, 75. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks, newest first.
File Type Posted
FOLLOW-UP Technical Questions - St. Louis 4-6-23.pdf PDF
36C77623R0009 0005.pdf PDF
Technical Questions - FINAL - St. Louis 3-28-23.pdf PDF
657-21-701JB - Addendum 1_03_24_23.pdf PDF
329000-5 - Sod Certificate.pdf PDF
Attachment 43 - Construction Wage Rates - St. Louis 3-24-23.pdf PDF
36C77623R0009 0004.pdf PDF
657-21-701JB - 100 PC - Basis of Design.pdf PDF
329000-05-R1 Sod Certificate.pdf PDF
Attachment 43 - Construction Wage Rates - St. Louis 3-3-23.pdf PDF
36C77623R0009 0003.pdf PDF
36C77623R0009 0002.pdf PDF
Site Visit Sign-in Sheet - St. Louis 2-28-23.pdf PDF
Attachment 45 - Site Visit Instructions Updated 2-16-23.pdf PDF
36C77623R0009 0001.pdf PDF
Attachment 2 - Drawings Part-1.pdf PDF
Attachment 3 - Drawings Part-2.pdf PDF
Attachment 8 - Drawings Part-7.pdf PDF
Attachment 15 - Drawings Part-14.pdf PDF
Attachment 17 - Drawings Part-16.pdf PDF
Attachment 23 - Drawings Part-22.pdf PDF
Attachment 27 - Drawings Part-26.pdf PDF
Attachment 30 - Drawings Part-29.pdf PDF
Attachment 33 - Drawings Part-32.pdf PDF
Attachment 34 - Envr. Report - Narrative.pdf PDF
Attachment 37 - Envr. Report - Appendix C.pdf PDF
Attachment 40 - NARA RM Contract Language Clause.pdf PDF
Attachment 43 - Construction Wage Rates - St. Louis 1-20-23.pdf PDF
36C77623R0009 - 2-16-23.pdf PDF
Attachment 7 - Drawings Part-6.pdf PDF
Attachment 11 - Drawings Part-10.pdf PDF
Attachment 12 - Drawings Part-11.pdf PDF
Attachment 13 - Drawings Part-12.pdf PDF
Attachment 18 - Drawings Part-17.pdf PDF
Attachment 31 - Drawings Part-30.pdf PDF
Attachment 35 - Envr. Report - Appendix A.pdf PDF
Attachment 38 - Envr. Report - Drawings.pdf PDF
Attachment 42 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 45 - Site Visit Instructions.pdf PDF
Attachment 4 - Drawings Part-3.pdf PDF
Attachment 10 - Drawings Part-9.pdf PDF
Attachment 14 - Drawings Part-13.pdf PDF
Attachment 20 - Drawings Part-19.pdf PDF
Attachment 21 - Drawings Part-20.pdf PDF
Attachment 25 - Drawings Part-24.pdf PDF
Attachment 26 - Drawings Part-25.pdf PDF
Attachment 28 - Drawings Part-27.pdf PDF
Attachment 29 - Drawings Part-28.pdf PDF
Attachment 32 - Drawings Part-31.pdf PDF
Attachment 39 - ICRA ILSM Tool - MCM 001S-03 Att B.zip ZIP file
Show all 50

Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES

FOUND SHALL BE REPORTED TO THE ENGINEER.

SG53-61-BUS

4160.0 V

0.0 A

FUSE-SG53-61-3

S&C

SMU-20, 200E

200.0 A

CBL-53-XF2 BLDG 53

95.0 ft

1 per phase

3/0 AWG

Copper

53-XF2-BLDG 53

750 kVA

Pri 4160 V

Sec 208 V

5.9300 %

CBL-53-GDP-53

70.0 ft

2 per phase

500 kcmil

Copper

PD53-GDP-53-MCB

CUTLER-HAMMER

ND

53-PANEL-MDP-53

208.0 V

2000.0 A

CBL-MDP-53

35.0 ft

6 per phase

400 kcmil

Copper

1200.0 A

PD53-ATS-53-N

CUTLER-HAMMER

MDL

800.0 A

CBL-ATS-53-N

23.0 ft

2 per phase

500 kcmil

Copper

PD-MDP-53-MCB

CUTLER-HAMMER

CRD

2000.0 A

PD53-ATS-EMP-N

CUTLER-HAMMER

DK

400.0 A

PD53-ATS-CDP-N

CUTLER-HAMMER

FD

200.0 A

PD53-ATS-ELGA-N

CUTLER-HAMMER

FD

100.0 A

CBL-53-ATS-53-E

26.0 ft

2 per phase

500 kcmil

Copper

CBL-53-ATS-ELGA-E

34.0 ft

1 per phase

1 AWG

Copper

CBL-53-ATS-CPD-E

23.0 ft

4/0 AWG

Copper

CBL-53-ATS-EMP-E

30.0 ft

2 per phase

350 kcmil

Copper

PD53-ATS-53-E

CUTLER-HAMMER

MDL

800.0 A

PD53-ATS-ELGA-E

CUTLER-HAMMER

FD

100.0 A

PD53-ATS-CDP-E

CUTLER-HAMMER

FD

200.0 A

PD53-ATS-EMP-E

CUTLER-HAMMER

DK

400.0 A

53-PANEL-GDP-53

208.0 V

1200.0 A

GEN87-BLDG 87

200 kVA

X"d 0.2 pu

E N

53-ATS-53

Amps Rating 800.0 A

AIC 50.00 kA

CBL-53-BLDG 53-SWBD

23.0 ft

3 per phase

350 kcmil

Copper

PD53- SP6

GE

AKR-30

800.0 A

PD53-SP5

GE

AKR-30

800.0 A

225A/3P

PD53-SP3

GE

AKR-30

800.0 A

PD53-SP2

GE

AKR-30

800.0 A

PD53-GB1-1

GE

AKR-30

800.0 A

CBL-53-GB1-1

229.0 ft

1 per phase

3/0 AWG

Copper

53-PANEL-GB1-1

208.0 V

200.0 A

PD53-2C

GE

AKR-30

800.0 A

CBL53-2C

333.0 ft

1/0 AWG

Copper

PD53-GA

GE

AKR-30

800.0 A

CBL-53-GA

77.0 ft

1/0 AWG

Copper

53-PANEL-GA

208.0 V

100.0 A

53-PANEL-2C

208.0 V

225.0 A

CBL-53-GB1-2

24.0 ft

3/0 AWG

Copper

CBL-53-2CA

7.0 ft

1/0 AWG

Copper

53-PANEL-GB1-2

208.0 V

200.0 A

53-PANEL-2CA

208.0 V

125.0 A

CBL-53-GC-1

307.0 ft

500 kcmil

Copper

53-PANEL-GC-1

208.0 V

225.0 A

CBL-53-GC-2

7.0 ft

500 kcmil

Copper

53-PANEL-GC-2

208.0 V

225.0 A

CBL-53-1C-1

103.0 ft

1 per phase

500 kcmil

Copper

53-PANEL-1C-1

208.0 V

225.0 A 53-PANEL-1B

208.0 V

225.0 A

CBL-53-1C-2

5.0 ft

1 per phase

500 kcmil

Copper

CBL-53-2B-1

31.0 ft

500 kcmil

Copper

53-PANEL-2B-1

208.0 V

400.0 A

53-PANEL-1C-2

208.0 V

225.0 A

CBL-53-2B-2

5.0 ft

1 per phase

500 kcmil

Copper

53-MTR53-ELEV S-17

NumMotors 1

Total 50 hp

CBL-53-ATS-ELEV1-E

4.0 ft

53-PANEL-2B-2

208.0 V

400.0 A

3/0 AWG

Copper

53-PANEL-EL2A

208.0 V

225.0 A

53-PANEL-EC2A

208.0 V

100.0 A

53-MTR53-ELEV P-18

NumMotors 1

Total 40 hp

53-PANEL-2A-2

208.0 V

225.0 A

53-PANEL-EL1A

208.0 V

125.0 A

CBL-53-EL2A

22.0 ft

1 AWG

Copper

PD53-GC-1

GE

AKR-30

800.0 A

PD53-RISER-B1

GE

AKR-30

800.0 A

CBL-53-RISER-B1-1

226.0 ft

500 kcmil

Copper

CBL-53-GB

0.1 ft

500 kcmil

Copper

53-PANEL-GB

208.0 V

400.0 A

CBL-53-RISER-B1-2

10.0 ft

500 kcmil Copper

CBL-53-1B

0.1 ft

1 per phase

500 kcmil

Copper

53-ATS53-ELEV1

Amps Rating 400.0 A

AIC 35.00 kA

CBL-53-ELEV 1

15.0 ft

3/0 AWG

Copper

PD53-MCC

GE

AKR-30

800.0 A

CBL-53-MCC

223.0 ft

2 per phase

4/0 AWG

Copper

53-PANEL-MCC

208.0 V

600.0 A

53-PANEL-GP

208.0 V

400.0 A

53-PANEL-KP

208.0 V

100.0 A

53-PANEL-P2

PD53-ATS-ELEV1-N

SQUARE D

KA

250.0 A

CBL-53-ATS-ELEV1-N

51.0 ft

3/0 AWG

Copper

PD53-ATS-ELEV2-N

SQUARE D

KA

250.0 A

CBL-53-ATS-ELEV2-N

51.0 ft

2/0 AWG

Copper

CBL-53-2A-1

152.0 ft

53-ATS53-ELEV2

Amps Rating 200.0 A

AIC 10.00 kA

CBL-53-ELEV 2

15.0 ft

2/0 AWG

Copper

CBL-53-2A-2

5.0 ft

500 kcmil Copper

500 kcmil

Copper

53-PANEL-2A-1

208.0 V

225.0 A

208.0 V

400.0 A

CBL-53-1A-2

16.0 ft

500 kcmil

Copper

53-PANEL-1A-2

208.0 V

225.0 A

PD53-GP

GE

AKR-30

800.0 A

CBL-53-GP

26.0 ft

1 per phase

250 kcmil

Copper

PD53-KP

GE

AKR-30

800.0 A

CBL-53-KP

233.0 ft

1 per phase

500 kcmil

Copper

PD53-P2

GE

AKR-30

800.0 A

CBL-53-P2

265.0 ft

1 per phase

500 kcmil

Copper

PD53-RISER-1A

GE

AKR-30

800.0 A

CBL-53-RISER-1A-1

138.0 ft

500 kcmil

Copper

CBL-53-1A-1

0.1 ft

500 kcmil

Copper

53-PANEL-1A-1

208.0 V

225.0 A

53-ATS53-EMP

Amps Rating 600.0 A

AIC 50.00 kA

CBL-53-EMP

27.0 ft

2 per phase

350 kcmil

Copper

PD53-EMCC

GE

THQDL

200.0 A

CBL-53-EMCC

219.0 ft

2 per phase

4/0 AWG

Copper

53-PANEL-EMCC

208.0 V

100.0 A

CBL-53-ELEV1

231.0 ft

1 per phase

3/0 AWG

Copper

1 per phase

1 AWG

Copper

CBL-53-EL1A

0.1 ft

1 per phase

1 AWG

Copper

PD53-ELEV1

GE

THQDL

200.0 A

53-PANEL-EMP

208.0 V

400.0 A

53-ATS53-ELGA

Amps Rating 100.0 A

AIC 22.00 kA

CBL-53-RISER-EL1-1

223.0 ft

1 per phase

1 AWG

Copper

CBL-53-ELGA

0.1 ft

1 per phase

1 AWG

Copper

53-PANEL-ELGA

208.0 V

200.0 A

CBL-53-RISER-EL1-2

37.0 ft

PD53-EC1A

GE

TEYD

125.0 A

CBL-53-EC1A-1

129.0 ft

1/0 AWG

Copper

CBL-53-EC1A-2

0.1 ft

1/0 AWG

Copper

PD53-CDP-MCB

GE

THQD

225.0 A

PD53-ECGA

GE

TEYD

60.0 A

CBL-53-ECGA

223.0 ft

4 AWG

Copper

53-PANEL-ECGA

208.0 V

60.0 A

CBL-53-EC1B

166.0 ft

53-PANEL-EC1A

208.0 V

100.0 A

53-CBL-EC2A

19.0 ft

1/0 AWG

Copper

53-PANEL-EC1B

208.0 V

225.0 A

4 AWG

Copper CBL-53-STR LTGS

20.0 ft

4 AWG

Copper

53-PANEL-ECGB

208.0 V

100.0 A

PD53-ECGB

GE

TEYD

50.0 A

CBL-53-ECGB

35.0 ft

6 AWG

Copper

PD53-STR LTGS

GE

TEYD

60.0 A

CBL-53-XF2-53-T

32.0 ft

4 AWG

Copper

PD53-STR

LTGS1

GE

SEDA

60.0 A

CBL53-0091

32.0 ft

350 kcmil

Copper

53-PANEL-CDP

208.0 V

225.0 A

PD53-SP1

GE

AKR-30

800.0 A

BLDG 53-SWBD

208.0 V

800 A

CBL-53-ATS-EMP-N

23.0 ft

1 per phase

500 kcmil

Copper

CBL-53-ATS-ELGA-N

27.0 ft

3/0 AWG

Copper

CBL-53-ATS-CDP-N

33.0 ft

1 per phase

3/0 AWG

Copper

53-ATS53-CDP

Amps Rating 225.0 A

AIC 35.00 kA

CBL-53-CDP

24.0 ft

1 per phase

3/0 AWG

Copper

53-XF2-53-T0

15 kVA

Pri 208 V

Sec 480 V

2.7789 %

440 V XFRM

208.0 V

100.0 A

BUS53-STR LTGS0

480.0 V

1 per phase 1 per phase

1 per phase 1 per phase 1 per phase

1 per phase

1 per phase

1 per phase 1 per phase

1 per phase

1 per phase

1 per phase

1 per phase

1 per phase

1 per phase 1 per phase

1 per phase

1 per phase 1 per phase

1 per phase

1 per phase

1 per phase

1 per phase

1 per phase

1 per phase

1 per phase

1 per phase

1 per phase 1 per phase 1 per phase

1 per phase

1 per phase

G

225A/3P

3"C-4#4/0, #4G

100A/3P 100A/3P 100A/3P 20A/3P 20A/3P

SPD DPM

1-1/4"C-4#3, #8G

53-DP-TRA

208V, 3PH

225A

53-GS10A

208V, 3PH

100A

53-GS02AA

208V, 3PH

100A

53-1S002A

208V, 3PH

100A

7 1 7

NSR251 (BLDG 53T)

208V, 1PH

400 A

SPD DPM

225A/3P

225A/3P

3"C-4#4/0, #4G

DISTRIBUTION PANEL

53-DP-TRB

120/208V,3PH, 225A

100A/3P 100A/3P 100A/3P 20A/3P 20A/3P

1-1/4"C-4#3,#8G

53-GS10B

120/208V

3PH

100A

53-1S002B 120/208V

3PH

100A

53-GS02AB

120/208V

3PH

100A

8 2 8

100A/3P

53-1S01A

208V, 3PH

100A

100A/3P

53-2S001A

208V, 3PH

100A

100A/3P

53-1S01B 120/208V

3PH

100A

100A/3P

53-2S001B 120/208V

3PH

100A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

53EP601

BLDG 53 AND 53T - ONE-LINE

DIAGRAMSPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL/WNM LLT/JPS

CONSTRUCTION

DOCUMENTS

Revisions: Date:

GENERAL NOTES

KEY NOTES

- 6" = 1'-0"

1 BLDG 53 AND 53T - ONE-LINE DIAGRAM

1 TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER

TR PANEL, TYPICAL - TYPE 1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER

TR PANEL, TYPICAL - TYPE 1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

EXISTING PANEL TO BE MODIFIED.

REFERENCE GEENRATOR LOAD CALCULATION SCHEDULE ON SHEET EP704 FOR

GENERATOR LOADING DATA.

TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER

TR PANEL, TYPICAL - TYPE 1.1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER

TR PANEL, TYPICAL - TYPE 1.1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER

TR PANEL, TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER

TR PANEL, TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

REPLACE EXISTING CIRCUIT BREAKER OR ADD CIRCUIT BREAKER AS SHOWN.

LRL/WNM LLT/JPS

MSB/55-1

3000A, 480/277V, 3PH, 4W,

100kAIC

2000kVA

4160-480Y/277V

3P,4W

MVSG

ATS/'55-LS1'

ISC=31,552A

ATS/'55-C1'

ISC=31,784A

ATS/'55-EQ1'

ISC=30,218A

ATS/'55-EQ2'

ISC=28,941A

DP/55-EQ2

ISC=25,062A

DP/'55-EQ1'

1200A, 480/277V, 3PH, 4W,

42kAIC, ISC=25,062A

MCC-'55-2E'

ISC=8,345A

MCC-'55-E'

ISC=24,214A

TR-55-EQ1

45kVA

TR-55-EQ4

30kVA

TR-55-EQ3

45kVA

TR-55-EQ2

30kVA

PANEL

'55-1EQ2-1'

ISC=2,170A

PANEL

'55-1EQ2-2'

ISC=1,996A

PANEL

'55-2EQ1-1'

ISC=1,699A

PANEL

'55-3EQ1-1'

ISC=1,374A

PANEL

'55-1EQ3-1'

ISC=1,843A

PANEL

'55-2EQ3-1'

ISC=1,268A

PANEL

'55-3EQ3-1'

ISC=1,007A

PANEL

'55-1EQ4-1'

ISC=1,858A

PANEL

'55-1EQ4-2'

ISC=1,724A

PANEL

'55-2EQ4-1'

ISC=1,519A

PANEL

'55-1EQ4-1'

ISC=1,247A

PANEL

'55-1EQ1-1'

ISC=2,540A

PANEL

'55-1EQ1-2'

ISC=2,511A

PANEL

'55-2EQ1-1'

ISC=1,699A

PANEL

'55-3EQ1-1'

ISC=1,374A

TR-55-1C3

30kVA

PANEL

'55-1C3'

ISC=4,192A

PANEL

'55-1C3P'

ISC=1,016A

PANEL

'55-2EQ1-1'

ISC=1,699A

PANEL

'55-3EQ1-1'

ISC=1,374A

TR-55-1C4

30kVA

TR-55-2C1

30kVA

PANEL

'55-2C1'

ISC=7,726A

PANEL

'55-2C1P'

ISC=1,085A

PANEL

'55-2C1P-1'

PANEL

'55-2C2P'

ISC=892A

TR-55-2C2

15kVA

TR-55-2C3

15kVA

PANEL

'55-2C3'

ISC=4,098A

PANEL

'55-2C3P'

ISC=1,017A

PANEL

'55-2C4P'

ISC=854A

PANEL

'55-2C4P-1'

TR-55-2C4

30kVA

TR-55-3C1

30kVA

PANEL

'55-3C1'

ISC=7,159A

PANEL

'55-3C1P'

ISC=1,077A

PANEL

'55-3C1P-1'

PANEL

'55-3C2P'

ISC=902A

TR-55-2C2

15kVA

TR-55-3C3

15kVA

PANEL

'55-3C3'

ISC=3,899A

PANEL

'55-3C3P'

ISC=988A

PANEL

'55-3C4P'

ISC=853A

PANEL

'55-3C4P-1'

TR-55-3C4

30kVA

DP/'55-C1'

400A, 480/277V, 3PH, 4W

42kAIC, ISC=25,062

TO 5kV PAD

MOUNTED SWITCH

1000A

GSB/'55-1'

1200A, 480/277V, 3PH, 4W,

10kAIC, ISC=4,859A

E N

L

E N

L

E N

L

E N

L

DP/'55-LS1'

225A, 480/277V, 3PH, 4W

42kAIC, ISC=25,622

PANEL

'55-3LS3P'

ISC=1,017A

TR-55-3LS3

15kVA

PANEL

'55-3LS3'

ISC=4,015A

PANEL

'55-3LS1P'

ISC=2,227A

TR-55-3LS1

30kVA

PANEL

'55-3LS1'

ISC=7,689A

PANEL

'55-3LS1P2'

ISC=1,074A

PANEL

'55-2LS3P'

ISC=1,036A

TR-55-2LS3

15kVA

PANEL

'55-2LS3'

ISC=7,988A

PANEL

'55-2LS1P'

ISC=1,032A

TR-55-2LS1

15kVA

PANEL

'55-2LS1'

ISC=7,718A

PANEL

'55-LSP-1'

ISC=1,077A

TR-55-LS1

15kVA

PANEL

'55-LS1'

ISC=7,806A

PANEL

'55-1LS3P'

ISC=1,006A

TR-55-1LS3

15kVA

PANEL

'55-1LS3'

ISC=4,208A

PANEL

'55-1LS1P'

ISC=1,078A

TR-55-1LS31

15kVA

PANEL

'55-1LS1'

ISC=9,320A

DP/'55-M'

1200A, 480/277V, 3PH, 4W,

42kAIC, ISC=31,933A

MCC-'55-1'

ISC=30,090A

MCC-'55-2'

ISC=4,183A

DP/'55-L'

400A, 480/277V, 3PH, 4W,

42kAIC, ISC=30,442A

PANEL

55-'1L3'

ISC=4,352A

PANEL

55-'2L3'

ISC=4,000A

PANEL

55-'3L3'

ISC=3,860A

PANEL

55-'1L1'

ISC=8,609A

PANEL

55-'2L1'

ISC=6,248A

PANEL

55-'3L1'

ISC=6,382A

DP/'55-R'

1200A, 480/277V, 3PH, 4W,

42kAIC, ISC=31,357A

TR-55-1N4

150kVA

DP/'55-1N4'

500A, 480/277V, 3PH, 42

22kAIC, ISC=7,325A

PANEL

'55-3N4-1'

ISC=5,568A

PANEL

'55-3N4-2'

ISC=5,660A

PANEL

'55-2N4-1'

ISC=6,303A

PANEL

'55-2N4-2'

ISC=6,092A

PANEL

'55-1N4-1'

ISC=7,105A

TR-55-1N3

150kVA

DP/'55-1N3'

500A, 208/120V, 3PH, 4W,

22kAIC, ISC=8,636A

PANEL

'55-3N3-1'

ISC=5,910A

PANEL

'55-3N3-2'

ISC=5,717A

PANEL

'55-2N3-1'

ISC=6,373A

PANEL

'55-2N3-2'

ISC=5,993A

PANEL

'55-1N3-1'

ISC=7,137A

PANEL

'55-1N3-2'

ISC=5,923A

TR-55-1N2

150kVA

DP/'55-1N2'

500A, 2080/120V, 3PH, 4W,

42kAIC, ISC=8,636A

PANEL

'55-3N2-1'

ISC=7,063A

PANEL

'55-3N2-2'

ISC=6,842A

PANEL

'55-2N2-1'

ISC=7,265A

PANEL

'55-2N2-2'

ISC=6,986A

PANEL

'55-1N2-2'

ISC=8,112A

PANEL

'55-1N2-1'

ISC=8,399A

DP/'55-1N1'

500A, 208/120V, 3PH, 4W,

42kAIC, ISC=8,694A

PANEL

'55-3N1-1'

ISC=6,795A

PANEL

'55-3N1-2'

ISC=6,552A

PANEL

'55-2N1-1'

ISC=7,306A

PANEL

'55-2N1-2'

ISC=7,024A

PANEL

'55-1N1-2'

ISC=8,001A

PANEL

'55-1N1-1'

ISC=8,333A

TR-55-1N1

150kVA

GEN-'55-1'

500kW/625kVA

480Y/277V, 3P,4W

G

225A/3P

400A/3P

2 SETS, 2"C-4#3/0, #3G

55-1A129A

208V, 3PH

100A

55-1B104A

208V, 3PH

100A

55-1C132A

208V, 3PH

100A

55-2A136A

208V, 3PH

100A

55-2C144A

208V, 3PH

100A

55-3A120A

208V, 3PH

100A

55-3C149A

208V, 3PH

100A

DISTRIBUTION PANEL

55-DP-TRA

400A, 208V, 3PH

100A/3P 100A/3P 100A/3P 100A/3P 100A/3P 100A/3P 100A/3P 20A/3P 20A/3P

1-1/4"C-4#3, #8G

SPD DPM

4"C-4#600 KCM, 1#3 GND

3"C-4#250, 1#4 GND

3"C-4#250, 1#4 GND

400A/3P 800A/3P 400A/3P 400A/3P 400A/3P 800A/3P 400A/3P 1000A/3P 1000A/3P 400A/3P

600A/3P 225A/3P 150A/3P 150A/3P

50A/3P50A/3P70A/3P50A/3P225A/3P225A/3P

100A/3P 100A/3P100A/3P 100A/3P 100A/3P

175A/3P 250A/3P 250A/3P 250A/3P

500A/3P

150A/3P 150A/3P 150A/3P 400A/3P

400A/3P

DISTRIBUTION PANEL

55-DP-TRB

400A, 208V, 3PH

100A/3P 100A/3P 100A/3P 100A/3P 100A/3P 100A/3P 100A/3P

55-1A129B

208V, 3PH

100A

55-1B104B

208V, 3PH

100A

55-1C132B

208V, 3PH

100A

55-2A136B

208V, 3PH

100A

55-2C144B

208V, 3PH

100A

55-3A120B

208V, 3PH

100A

55-3C149B

208V, 3PH

100A

20A/3P 20A/3P

SPD DPM

2 SETS, 2"C-4#3/0, #3G

1 1 4 1 1 1

2 2 5 2 2 2 2

1-1/4"C-4#3, #8G

200A/3P 150A/3P 200A/3P

200A/3P

500A/3P

150A/3P 200A/3P

200A/3P 200A/3P 200A/3P

500A/3P

125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P 125A/3P

2"C-3#4/0,#4G

TR-55-DP-TRA

150kVA

480-208/120V

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES

FOUND SHALL BE REPORTED TO THE ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

55EP601

BLDG 55 - ONE-LINE DIAGRAM

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL/WNM LLT/JPS

CONSTRUCTION

DOCUMENTS

Revisions: Date:

GENERAL NOTES

KEY NOTES

- 3/4" = 1'-0"

BLDG 55 - ONE-LINE DIAGRAM1

1 TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER

TR PANEL, TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER

TR PANEL, TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

REFERENCE GENERATOR LOAD CALCULATION SCHEDULE ON SHEET EP704 FOR

GENERATOR LOADING DATA.

TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER

TR PANEL, TYPICAL - TYPE 1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER

TR PANEL, TYPICAL - TYPE 1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

EXISTING EQUIPMENT TO BE MODIFIED; PROVIDE CIRCUIT BREAKER AS SHOWN.

1600A/3P

750kW/937.5kVA

480/277V, 3P, 4W G

GSB/56

1600A, 480/277V, 3PH, 4W,

22kAIC, ISC=7,318A

ATS/C

ISC=22,336A

E N

L

2000kVA

4160-480Y/277V

3P,4W

MVSG

TO 5kV PAD MOUNTED

SWITCH

TR-56-C

500kVA

PANEL

56-3CR

ISC=2,296A

PANEL

56-3CR1

PANEL

56-2CR

ISC=2,500A

PANEL

56-2CR1

PANEL

56-1CR

ISC=2,296A

PANEL

56-1CR1

56-SP1

PANEL

56-CR

ISC=2,500A

PANEL

56-CR1

300kVA

UPS

ISC-E

PANEL

56-3C1

ISC=592A

PANEL

56-1C1

ISC=599A

DP/56U

800A, 480/277V, 3PH, 4W,

10kAIC, ISC=623A

PANEL

56-C1

ISC=609A

PANEL

56-C2

ISC=622A

PANEL

56-C3

ISC=622A

PANEL

56-C4

ISC=619A

PANEL

56-C5

ISC=619A

PANEL

56-C6

ISC=618A

PANEL

56-C7

ISC=617A

PANEL

56-C8

ISC=593A

PANEL

56-C9

ISC=593A

ATS/EQ

ISC=22,824A

E N

L

MSB/56-1

2500A, 480/277V

3PH, 4W,

42kAIC

DP/56EQ

600A, 480/277V, 3PH, 4W,

42kAIC, ISC=23,244A

PANEL

56-3EQ1P

DS-100

TR-56-3EQ1

45kVA

PANEL

56-3EQ1

ISC=1,068A

PANEL

56-2EQ1P

DS-30

TR-56-2EQ1

15kVA

PANEL

56-2EQ1

ISC=1,087A

PANEL

56-1EQ1P

DS-30

TR-56-1EQ1

15kVA

PANEL

56-1EQ1

ISC=1,106A

PANEL

56-EQ1P

DS-30

TR-56-EQ1

30kVA

PANEL

56-EQ1

ISC=1,056A

MCC/56E-1

ISC=19,691A

ATS/LS

ISC=18,307A

E N

L

DP/56LS

225A, 480/277V, 3PH, 4W,

22kAIC, ISC=15,923A

DS-60

TR-56-LSGB

30kVA

PANEL

56-LSGB

ISC=2,408A

PANEL

56-3LS1

ISC=3,811A

PANEL

56-2LS1

ISC=4,060A

PANEL

56-1LS1

ISC=4,434A

PANEL

56-LS1

ISC=4,667A

DS-30

TR-56-LS1

15kVA

PANEL

56-LS1P

ISC=1,092A

PANEL

56-L1

ISC=6,196A

PANEL

56-1L1

ISC=5,642A

PANEL

56-1L1-MM

ISC=5,478A

PANEL

56-2L1

ISC=5,177A

PANEL

56-3L1

ISC=4,782A

PANEL

56-1L2-NCA

ISC=7,122AA

DP/56L

225A, 480/277V, 3PH, 4W,

42kAIC, ISC=22,510A

MCC/56-4

ISC=16,768A

DP/56M

800A, 480/277V, 3PH, 4W,

42kAIC, ISC-23,454A

MCC/56-3

ISC=17,727A

MCC/56-2

ISC=18,991A

MCC/56-1

ISC=22,515A

DS-100

TR-56-1N2-NCA

45kVA

PANEL

56-1N2-NCA

ISC=3,737A

DS-100

TR-56-2N2

45kVA

PANEL

56-2N2

ISC=2,652A

DS-100

TR-56-3N2

45kVA

PANEL

56-3N2

ISC=2,631A

DS-100

TR-56-3N1

45kVA

PANEL

56-3N1

ISC=4,676A

DS-100

TR-56-2N1

45kVA

PANEL

56-2N1

ISC=2,611A

DS-60

TR-56-1N1

30kVA

PANEL

56-1N1

ISC=2,324A

DS-60

TR-56-1N1-MM

30kVA

PANEL

56-1N1-MM

ISC=2,309A

DS-100

TR-56-N1

45kVA

PANEL

56-N1

ISC=2,702A

DS-100

TR-56-N2-1

45kVA

PANEL

56-N2-1

ISC=4,847A

DS-60

TR-56-N2-2

30kVA

PANEL

56-N2-2

ISC=2,401A

225A/3P

225A/3P

100A/3P 100A/3P 100A/3P 100A/3P 20A/3P 20A/3P

56-BA105A

208V, 3PH

100A

56-1A109A

208V, 3PH

100A

56-2A122A

208V, 3PH

100A

56-3A122A

208V, 3PH

100A

SPD

3"C-4#4/0, #4G

1-1/4"C-4#3, #8G

DISTRIBUTION PANEL

56-DP-TRA

225A, 208V, 3PH

DPM

100A/3P

3"C-4#4/0, #4G

56-BA105B

120/208V

3PH

100A

56-1A109B

120/208V

3PH

100A

56-2A122B

120/208V

3PH

100A

56-3A122B

120/208V

3PH

100A

100A/3P 100A/3P 100A/3P 20A/3P

DISTRIBUTION PANEL

56-DP-TRB

225A, 120/208V, 3PH

SPD DPM

150A/3P

1-1/4"C-4#3,#8G

225A/3P

2 2 2 2

1600A/3P

LSIG

500A/3P 500A/3P 100A/3P

2500A/3P

LSIG

600A/3P 800A2 /3P500A/3P 500A/3P

50A/3P 60A/3P 60A/3P 60A/3P 60A/3P

60A/3P 60A/3P 60A/3P 60A/3P 60A/3P 60A/3P

200A/3P 600A/3P200A/3P 200A/3P

80A/3P 30A/3P 30A/3P 30A/3P 400A/3P

100A/3P 100A/3P 225A/3P 225A/3P 225A/3P 225A/3P 225A/3P 225A/3P 225A/3P 60A/3P60A/3P

DP/56R

800A, 480/277V, 3PH, 4W,

42kAIC, ISC=22,831A

70A/3P 70A/3P 70A/3P 70A/3P 70A/3P 50A/3P 50A/3P 70A/3P 70A/3P 50A/3P

DP/56C

1600A, 208/120V, 3PH, 4W,

42kAIC, ISC=13,639A

60A/3P 60A/3P 60A/3P 60A/3P

20A/3P

500A/3P

60A/3P

2"C-3#2/0,#6G

TR-56-DP-TRB

75kVA

480-208/120V

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES

FOUND SHALL BE REPORTED TO THE ENGINEER.

TYPICAL 100A PANEL. REFERENCE TYPICAL SCHEDULE "SOURCE A POWER TR PANEL,

TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING INFORMATION.

TYPICAL 100A PANEL. REFERENCE TYPICAL SCHEDULE "SOURCE B POWER TR PANEL,

TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING INFORMATION.

REFERENCE GENERATOR LOAD CALCULATION SCHEDULE ON SHEET EP704 FOR

GENERATOR LOADING DATA.

EXISTING PANELBOARD TO BE MODIFIED; PROVIDE CIRCUIT BREAKER AS SHOWN.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

56EP601

BLDG. 56 - ONE-LINE DIAGRAM

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM - INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL/WNM LLT/JPS

CONSTRUCTION

DOCUMENTS

Revisions: Date:

GENERAL NOTES

KEY NOTES

- 1/2" = 1'-0"

1 BLDG. 56 - ONE-LINE DIAGRAM

XF2-BLDG-57

Size 2000 kVA Pri Delta Sec Wye-Ground %Z 5.7500 % X/R 8.0

57MSB-480V

480.0 V

1200.0 A

57-MOTOR LOADS

100 hp Load Factor 1.00 X"d 0.17 pu

57-LOADS

TO SG57

ISC=11258

57-1L1

DP/57L

400A, 480/277V, 3PH, 4W,

22kAIC, ISC=12809

100A/3P 225A/3P

ISC=3390

57-1L2

400A/3P 600A/3P

INVERTER

TO PV ON ROOF

MV

SWITCH

KVA

4160-480 /277V MSB/57 w/

METERING

DP/57R

800A, 480/277V, 3PH, 4W,

22kAIC, ISC=12428

800A/3P

DP/57M

600A, 480/277V, 3PH, 4W,

22kAIC, ISC=12428

600A/3P

MCC/57M

ISC=5428

MCC/57M-1

ISC=9058

400A/3P 200A/3P

200A

NF,N1

TR-57-1N1

75KVA

110A/3P

PANELPANEL

57-1T1-2

ISC=2000

57-1T1-1

ISC=2000

60A/3P60A/3P

PANEL

57-1N2

ISC=1826

PANEL

57-1N1 225A, 480/277V, 3PH, 4W,

10kAIC, ISC=2414

200A

NF,N1

TR-57-1N2

112.5KVA

175A/3P

PANEL

57-1N3

ISC=1933

200A

NF,N1

TR-57-1N3

112.5KVA

175A/3P

200A

NF,N1

TR-57-1N4

45KVA

70A/3P

PANEL

57-1N4 225A, 208/120V, 3PH, 4W,

10kAIC, ISC=3031

PANEL

57-1T4-1

ISC=2500

150A/3P

PANEL

57-1T4-1

ISC=2500

60A/3P

PANEL

57-1B139A

208V, 3PH

100A

100A/3P

PANEL

57-1B139B

208V, 3PH

100A

100A/3P

1-1/4"C-4#3, #8G

PANEL

57-1N5A

ISC=1889

PANEL

57-1N5B

ISC=1889

PANEL

57-1N5C

ISC=1889

PANEL

57-1N5 400A, 208/120V, 3PH, 4W,

10kAIC, ISC=3047

150A/3P150A/3P

200A

NF,N1

TR-57-1N5

150KVA

225A/3P

200A

NF,N1

TR-57-1N6

75KVA

110A/3P

PANEL

57-1N6 225A, 208/120V, 3PH, 4W,

10kAIC, ISC=1995

PANEL

57-1T6-1

ISC=1500

60A/3P

PANEL

57-1B120A

208V, 3PH

100A

PANEL

57-1B120B

208V, 3PH

100A

100A/3P 100A/3P

PANEL

57-1T6-2

ISC=1500

60A/3P

1-1/4"C-4#3, #8G

PANEL

57-1N7A

ISC=1889

150A/3P

TR-57-1N7

112.5KVA

PANEL

57-1N7 400A, 208/120V, 3PH, 4W,

10kAIC, ISC=1889

200A

NF,N1

175A/3P

3 4 3 4

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

57EP601

BLDG 57 - ONE-LINE DIAGRAM

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

JEFFERSON BARRACKS - 1 JEFFERSON BARRACKS

DRIVE - ST. LOUIS, MO 63125

657-21-701JB

03/31/2022 LRL/WNM LLT/JPS

CONSTRUCTION

DOCUMENTS

Revisions: Date:

GENERAL NOTES

KEY NOTES

- 3/4" = 1'-0"

1 BLDG 57 - ONE-LINE DIAGRAM

1 REPLACE EXISTING CIRCUIT BREAKER WITH 100A/3P CIRCUIT BREAKER TO

SUPPLY NEW LOAD.

2 DEMOLISH EXISTING PANELBOARD AND ASSOCIATED CONDUIT AND WIRE AS

INDICATED.

3 TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER

TR PANEL, TYPICAL - TYPE 3" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

4 TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER

TR PANEL, TYPICAL - TYPE 3" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

CONTINUED ON

SHEET

O-E-200

FUSE-SG52-58-1

S&C

SMU-20, 50E

50.0 A

58-XF2-BLDG 58

300 kVA Pri 4160 V

Sec 208 V

6.5000 %

SG52-58

4160.0 V

0.0 A

CBL-58-SWBD

50.0 ft

3 per phase

500 kcmil

Copper

PD58-SWBD-MCB

SQUARE D

RG

2500.0 A

PD58-SPD

SQUARE D

FH

60.0 A

Surge

Protective

Device

CBL-58-58L1

24.0 ft

1/0 AWG

Copper

58-PANEL-58L1

208.0 V

225.0 A

CBL-58-58P1

15.0 ft

3/0 AWG

Copper

58-PANEL-58P1

208.0 V

225.0 A

CBL-58-58L2

245.0 ft

1/0 AWG

Copper

58-PANEL-58L2

208.0 V

225.0 A

CBL-58-58P2

240.0 ft

600 kcmil

Copper

58-PANEL-58P2

208.0 V

400.0 A

PD58-58P3

SQUARE D

QJ

125.0 A CBL-58-58P3

17.0 ft

1 AWG

Copper

CBL-58-DP-1

20.0 ft

600 kcmil

Copper

58-PANEL-58P3

208.0 V

225.0 A

58-PANEL-DP-1

208.0 V

400.0 A

PD58-58SF-1

125.0 A

3P.

PD58-CWP-2

20.0 A

3P.

PD58-CWP-1

20.0 A

3P.

PD58-WH-1

25.0 A

2P.

PD58-WH-2

25.0 A

2P.

PD58-RF-1

50.0 A

3P.

PD58-HWP-1

20.0 A

3P.

PD58-EF-3

20.0 A

3P.

PD58-CRS-1

20.0 A

3P.

PD58-SP3

20.0 A

3P.

SPARE

PD58-SP4

20.0 A

1P.

SPARE

PD58-RECEPTS RM 117

20.0 A

1P.

RECEPTS

RM. 117

PD58-H-1 DAMPER

20.0 A

1P.

PD58-EF-1

20.0 A

1P.

PD58-EF-2

20.0 A

1P.

PD58-PHP-1

20.0 A

1P.

PD58-SP5

20.0 A

1P.

SPARE

PD58-HWP-2

20.0 A

3P.

PD58-FCU-1

20.0 A

3P.

CBL-58-58P4

242.0 ft

1/0 AWG

Copper

58-PANEL-58P4

208.0 V

100.0 A

PD58-DP-1

SQUARE D

LX

400.0 A

PD58-58L1

SQUARE D

QJ

150.0 A

PD58-58P1

SQUARE D

QG

200.0 A

PD58-58L2

SQUARE D

QG

150.0 A

PD58-58P2

SQUARE D

LX

400.0 A

PD58-58P4

SQUARE D

FH

100.0 A

100A/3P 100A/3P

58-PANEL-MDP-58

208.0 V

1000.0 A

58SF-1

NumMotors 1 Total 0 hp

58-CWP-2

NumMotors 1 Total 0 hp

58-CWP-1

NumMotors 1 Total 0 hp

58-WH-1

3.6KW

58-WH-2

3.6KW

58RF-1

NumMotors 1 Total 0 hp

58HWP-1

NumMotors 1 Total 0 hp

58-EF-3

NumMotors 1 Total 0 hp

58-CRS-1

NumMotors 1 Total 0 hp

58-H-1 DAMPER

NumMotors 1 Total 0 hp

58EF-1

NumMotors 1 Total 0 hp

58EF-2

NumMotors 1 Total 0 hp

58-PHP-1

NumMotors 1 Total 0 hp

58-HWP-2

NumMotors 1 Total 0 hp

58-FCU-1

NumMotors 1 Total 0 hp

1 per phase 1 per phase 1 per phase 1 per phase 1 per phase

1 per phase

1 per phase

1-1/4"C-4#3, #8G

58-104B

208V, 3PH

100A

58-104A

208V, 3PH

100A

TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER TR

PANEL, TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER TR

PANEL, TYPICAL - TYPE 2" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

EXISTING PANEL TO BE MODIFIED; PROVIDE CIRCUIT BREAKERS AS INDICATED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

58EP601

BLDG 58 - ONE-LINE DIAGRAM

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL/WNM LLT/JPS

CONSTRUCTION

DOCUMENTS

GENERAL NOTES

KEY NOTES

- 6" = 1'-0"

1 BLDG 58 - ONE-LINE DIAGRAM

Revisions: Date:

1 2

3 3

SG51-60

4160.0 V

600.0 A

51-PD-XF2-BLDG 51

S&C

SMU-20, 100E

100.0 A

CBL-51-XF2-BLDG 51

260.0 ft

1 per phase

3/0 AWG

Copper

SHEET 51-E-201

FUSE-SG51-60-3

S&C

SMU-20, 200E

200.0 A

CBL-60-XF2 BLDG 60

100.0 ft

1 per phase

3/0 AWG

Copper

60-XF2-BLDG 60

300 kVA

Pri 4160 V Sec 208 V

5.3000 %

PD90-90P

CUTLER-HAMMER

CND

CBL-60-MDP-60

4.0 ft

4 per phase

350 kcmil

Copper

PD60-MDP-60-MCB

CUTLER-HAMMER

CRD

1600.0 A

PD60-SP1

CUTLER-HAMMER

BAB

20.0 A

SPARE

PD60-SP2

CUTLER-HAMMER

ED

100.0 A

SPARE

PD60-SP3

CUTLER-HAMMER

ED

100.0 A

SPARE

PD60-SP4

CUTLER-HAMMER

ED

100.0 A

SPARE

PD60-SP5

CUTLER-HAMMER

ED

100.0 A

SPARE

PD60-SP6

CUTLER-HAMMER

CA

225.0 A

SPARE

PD60-SP7

CUTLER-HAMMER

CA

225.0 A

SPARE

PD60-SP8

CUTLER-HAMMER

DA

400.0 A

SPARE

PD60-SP9

CUTLER-HAMMER

DA

400.0 A

SPARE

90-ATS 90-2 Amps

Rating 800.0 A AIC

50.00 kA

PD90-ATS 90-1-N

CUTLER-HAMMER

DA

400.0 A

PD90-ATS 90-2-N

CUTLER-HAMMER

MDL

800.0 A

60-PANEL-MDP-60

208.0 V

1600.0 A

PD90-ATS 90-2-E

CUTLER-HAMMER

MDL

800.0 A

PD90-ATS 90-1-E

CUTLER-HAMMER

DA

400.0 A

PD90-SPACE

CUTLER-HAMMER

DA

400.0 A

1200.0 A

CBL-90-90P

12.0 ft

4 per phase

350 kcmil Copper

90-PANEL-90P

208.0 V

1200.0 A

GEN90P

389 kVA

X"d 0.2 pu

90-ATS 90-1 Amps

Rating 400.0 A AIC

35.00 kA

PD60-DP-60EM-MCB

CUTLER-HAMMER

MDL

800.0 A

90-CBL-AC 90 TON

50.0 ft

2 per phase

250 kcmil

Copper

PD60-REF PNL-B

CUTLER-HAMMER

DK

400.0 A

PD60-P2

CUTLER-HAMMER

HLB

400.0 A

90-AC 90 TON

NumMotors 1

Total 100 hp

60-PANEL-B

208.0 V

400.0 A

60-PANEL-REF PNL-B

PD60-A

CUTLER-HAMMER

ED

CBL-60-A

5.0 ft

1 per phase

1 AWG

Copper

CBL-60-BA

2.0 ft 1 per phase

350 kcmil Copper

100.0 A

BUS-0373

208.0 V

0.0 A

CBL-60-P2-2

16.0 ft

1 per phase

350 kcmil

Copper

60-PANEL-60-BA

208.0 V

225.0 A

PNL-60-P2

208.0 V

225.0 A

208.0 V

400.0 A

CBL-60-P2-1

99.0 ft

1 per phase

350 kcmil

Copper

90-PANEL-GB BLDG.90

208.0 V

225.0 A

TO BLDG.90

60-PANEL-60-B1

208.0 V

225.0 A

60-PANEL-60-B2

208.0 V

225.0 A

PD90-GB

CUTLER-HAMMER

CA

225.0 A

PD60-EXHAUST HOODS

CUTLER-HAMMER

ED

100.0 A

EXHAUST

HOODS

CBL-60-REF PNL-B

131.0 ft

2 per phase

250 kcmil

Copper

CBL-90-GB

50.0 ft

1 per phase

350 kcmil

Copper

CBL-60T-MDP 60T

126.0 ft

2 per phase

250 kcmil

Copper

60-PANEL-MDP-60T

208V, 3PH

400A

(BLDG 60T)

CBL-60-B1

5.0 ft 1 per phase

350 kcmil

Copper

CBL-60-B2

0.1 ft

1 per phase

350 kcmil

Copper

EM

LIGHTS

CBL-60-RISER-B1

138.0 ft

1 per phase

350 kcmil

Copper

CBL-60-P4

27.0 ft

1 per phase

1 AWG

Copper

60-PANEL-P4

208.0 V

225.0 A

CBL-60-P4A

16.0 ft

1 per phase

1 AWG

Copper

60-PANEL-P4A

208.0 V

225.0 A

PD60-EM LIGHTS

CUTLER-HAMMER

GB

100.0 A

PD60T-MDP 60T

CUTLER-HAMMER

DK

400.0 A

PD60-RISER-B1

CUTLER-HAMMER

CA

225.0 A

60-PANEL-DP-60EM

PD60-P4

CUTLER-HAMMER

GB

100.0 A

208.0 V

1200.0 A

PD60-SP10

CUTLER-HAMMER

GB

100.0 A

G

60-102A 120/208V

3PH

100A

60-102B

208V, 3PH

100A

1-1/4"C-4#3, #8G

1-1/4"C-4#3,#8G

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

60EP601

BLDG 60 AND 60T - ONE-LINE

DIAGRAMSPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL/WNM LLT/JPS

CONSTRUCTION

DOCUMENTS

GENERAL NOTES

KEY NOTES

- 6" = 1'-0"

1 BLDG 60 AND 60T - ONE-LINE DIAGRAM

Revisions: Date:

TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER

TR PANEL, TYPICAL - TYPE 1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE B POWER

TR PANEL, TYPICAL - TYPE 1" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

EXISTING PANEL TO BE MODIFIED.

REFERENCE GENERATOR LOAD CALCULATION SCHEDULE ON SHEET EP704 FOR

GENERATOR LOADING DATA.

XISTING PANEL TO BE MODIFIED; UTILIZE EXISTING CIRCUIT BREAKERS AS

INDICATED.

TO UNIT SUBSTATION UNS 75

CBL-TR-MDP75-1-4160V

Cable Size 600 AWG/kcmil

Length 10.0 ft

QtyPerPhase 1

Installation Non-Segregated

TR-MDP75-1-4160V

System Nominal Voltage 4160.0 V 13464 Amps 3P

X/R Pos 10.91 12459 Amps SLG

X/R SLG 10.5532

S

P

TR-MDP75-1

Nominal kVA 2500.0 kVA Z% 5.7500 %

X/R 10.4739

Pri RatedVoltage 4160 V

Pri FLA 347.0 A

Sec RatedVoltage 480 V Sec FLA 3007.0 A

TR-MDP75-1-480V

System Nominal Voltage 480.0 V

50311 Amps 3P

X/R Pos 9.55

50686 Amps SLG

X/R SLG 9.8386

CBL-0030

Cable Size 3000 AWG/kcmil

Length 10.0 ft

QtyPerPhase 1

Installation

(MDP/75- 1)

Frame/Rating 3000.0 A

Frame/Model KTU

(MDP/75-1)

System Nominal Voltage 480.0 V 50211 Amps 3P

X/R Pos 9.29 50097 Amps SLG

X/R SLG 8.3585

(MDP/75-1)-1 (MDP/75-1)-3

Frame/Rating 1600.0 A

Frame/Model PA

Settings

Thermal Curve

INST LO (4960A)

(MDP/75-1)-2

Frame/Rating 800.0 A

Frame/Model PA

Settings

Thermal Curve

INST LO (3200A)

CBL-0036

Cable Size 500 AWG/kcmil

Length 145.0 ft

QtyPerPhase 5

Installation

CBL-0037

Cable Size 300 AWG/kcmil

Length 87.0 ft

QtyPerPhase 3

Installation

(MCC/75-2)

PD-0184

Frame/Rating 0.0 A Frame/Model

Settings

PD-0185

Frame/Rating 0.0 A Frame/Model

Settings

PD-0186

Frame/Rating 0.0 A Frame/Model

Settings

PD-0187

Frame/Rating 0.0 A Frame/Model

Settings

PD-0188

Frame/Rating 0.0 A Frame/Model

Settings

PD-0189

Frame/Rating 0.0 A Frame/Model

Settings

PD-0190

Frame/Rating 0.0 A Frame/Model

Settings

PD-0191

Frame/Rating 0.0 A Frame/Model

Settings

PD-0192

Frame/Rating 0.0 A Frame/Model

Settings

System Nominal Voltage 480.0 V

39128 Amps 3P

X/R Pos 3.71

34080 Amps SLG

X/R SLG 2.5903

Frame/Rating 1000.0 A

Frame/Model PA

Settings

Thermal Curve

INST LO (3500A)

(MDP/75-1)-4

Frame/Rating 225.0 A

Frame/Model KC

Settings

Thermal Curve

INST LO (1125A)

(MDP/75-1)-5

Frame/Rating 250.0 A

Frame/Model KA

Settings

Thermal Curve

INST LO (875A)

CBL-0038 CBL-0039

Cable Size 300 AWG/kcmil

Length 134.0 ft

Qty Per Phase 3

Installation

Cable Size 2 AWG/kcmil

Length 113.0 ft

Qty Per Phase 1

Installation

PANEL '75L'

System Nominal Voltage 480.0 V

10364 Amps 3P

X/R Pos 0.51 6392 Amps SLG

X/R SLG 0.3824

S

P

CBL-0040

Cable Size 2/0 AWG/kcmil

Length 12.0 ft

Qty Per Phase 1

Installation

(TR/75N)

Nominal kVA 112.5 kVA Z% 5.0000 %

X/R 3.1562

Pri Rated Voltage 480 V

Pri FLA 135.3 A

CBL-BLR-1

Cable Size 4 AWG/kcmil

Length 10.0 ft

QtyPerPhase 1

Installation

BUS-BLR-1

System Nominal Voltage 480.0 V 31209 Amps 3P

X/R Pos 1.48

25862 Amps SLG

X/R SLG 1.2513

MTRI-BLR-1

Init Sym RMS 3P 279.13 A

Init Sym RMS SLG 154.20 A

Rated HP 40.0 hp

Rated Voltage 480 V

Rated Amps 48.2 A

CBL-BLR-2

Cable Size 4 AWG/kcmil

Length 10.0 ft

QtyPerPhase 1

Installation

BUS-BLR-2

System Nominal Voltage 480.0 V 31209 Amps 3P

X/R Pos 1.48

25862 Amps SLG

X/R SLG 1.2513

MTRI-BLR-2

Init Sym RMS 3P 279.13 A

Init Sym RMS SLG 154.20 A

Rated HP 40.0 hp Rated Voltage 480 V

Rated Amps 48.2 A

CBL-BLR-3

Cable Size 4 AWG/kcmil

Length 10.0 ft

QtyPerPhase 1

Installation

BUS-BLR-3

System Nominal Voltage 480.0 V 31209 Amps 3P

X/R Pos 1.48

25862 Amps SLG

X/R SLG 1.2513

MTRI-BLR-3

Init Sym RMS 3P 279.13 A

Init Sym RMS SLG 154.20 A

Rated HP 40.0 hp

Rated Voltage 480 V

Rated Amps 48.2 A

CBL-AC-1

Cable Size 8 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1

Installation

BUS-AC-1

System Nominal Voltage 480.0 V 22154 Amps 3P

X/R Pos 0.75

18062 Amps SLG

X/R SLG 0.6699

MTRI-AC-1

Init Sym RMS 3P 139.57 A

Init Sym RMS SLG 75.86 A

Rated HP 20.0 hp

Rated Voltage 480 V

Rated Amps 24.1 A

CBL-ROP-1 & 2

CableSize 12 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1

Installation

BUS-ROP-1 & 2

System Nominal Voltage 480.0 V 12475 Amps 3P

X/R Pos 0.38

10200 Amps SLG

X/R SLG 0.3510

MTRI-ROP-1 & 2

Init Sym RMS 3P 41.87 A

Init Sym RMS SLG 22.82 A

Rated HP 6.0 hp

Rated Voltage 480 V

Rated Amps 7.2 A

CBL-FOP-1 & 2

Cable Size 12 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1

Installation

BUS-FOP-1 & 2

System Nominal Voltage 480.0 V 12470 Amps 3P

X/R Pos 0.37

10197 Amps SLG

X/R SLG 0.3503

MTRI-FOP-1 & 2

Init Sym RMS 3P 27.91 A

Init Sym RMS SLG 15.22 A

Rated HP 4.0 hp

Rated Voltage 480 V

Rated Amps 4.8 A

CBL-BFP-1 & 2

Cable Size 4 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1

Installation

BUS-BFP-1 & 2

System Nominal Voltage 480.0 V 31209 Amps 3P

X/R Pos 1.48

25862 Amps SLG

X/R SLG 1.2513

MTRI-BFP-1 & 2

InitSymRMS 3P 279.13 A

InitSymRMS SLG 154.20 A

Rated HP 40.0 hp

RatedVoltage 480 V

RatedAmps 48.2 A

CBL-BFP-3 & 4

Cable Size 4 AWG/kcmil

Length 10.0 ft

QtyPerPhase 1

Installation

BUS-BFP-3 & 4

System Nominal Voltage 480.0 V 31209 Amps 3P

X/R Pos 1.48

25862 Amps SLG

X/R SLG 1.2513

MTRI-BFP-3 & 4

Init Sym RMS 3P 279.13 A

Init Sym RMS SLG 154.20 A

Rated HP 40.0 hp Rated Voltage 480 V

Rated Amps 48.2 A

CBL-TP-1 & 2

Cable Size 10 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1

Installation

BUS-TP-1 & 2

System Nominal Voltage 480.0 V

17558 Amps 3P

X/R Pos 0.56

14294 Amps SLG

X/R SLG 0.5161

MTRI-TP-1 & 2

Init Sym RMS 3P 104.67 A

Init Sym RMS SLG 56.81 A

Rated HP 15.0 hp

Rated Voltage 480 V

Rated Amps 18.1 A

PANEL '75N'

System Nominal Voltage 208.0 V

5716 Amps 3P

X/R Pos 3.14

5788 Amps SLG

X/R SLG 3.1068

Sec Rated Voltage 208 V Sec FLA 312.3 A

CBL-0041

Cable Size 600 AWG/kcmil

Length 5.0 ft

QtyPerPhase 1

Installation

(MCC/75-3)

PD-0193

Frame/Rating 0.0 A Frame/Model

Settings

PD-0194

Frame/Rating 0.0 A Frame/Model

Settings

PD-0195

Frame/Rating 0.0 A Frame/Model

Settings

PD-0196

Frame/Rating 0.0 A Frame/Model

Settings

PD-0197

Frame/Rating 0.0 A Frame/Model

Settings

PD-0198

Frame/Rating 0.0 A Frame/Model

Settings

PD-0199

Frame/Rating 0.0 A Frame/Model

Settings

PD-0200

Frame/Rating 0.0 A Frame/Model

Settings

PD-0201

Frame/Rating 0.0 A Frame/Model

Settings

PD-0202

Frame/Rating 0.0 A Frame/Model

Settings

PD-0203

Frame/Rating 0.0 A Frame/Model

Settings

PD-0204

System Nominal Voltage 480.0 V

35897 Amps 3P

X/R Pos 3.23

29255 Amps SLG

X/R SLG 2.1473

Frame/Rating 0.0 A Frame/Model

Settings

CBL-CT/1A CBL-CT/1B

Cable Size 2 AWG/kcmil

Length 10.0 ft

QtyPerPhase 1 Installation

BUS-CT/1A

System Nominal Voltage 480.0 V 30965 Amps 3P

X/R Pos 1.83 24500 Amps SLG

X/R SLG 1.4485

MTRI-CT/1A

Init Sym RMS 3P 348.92 A

Init Sym RMS SLG 184.05 A

Rated HP 50.0 hp

Rated Voltage 480 V

Rated Amps 60.3 A

Cable Size 2 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1 Installation

BUS-CT/1B

System Nominal Voltage 480.0 V 30965 Amps 3P

X/R Pos 1.83 24500 Amps SLG

X/R SLG 1.4485

MTRI-CT/1B

Init Sym RMS 3P 348.92 A

Init Sym RMS SLG 184.05 A

Rated HP 50.0 hp

Rated Voltage 480 V

Rated Amps 60.3 A

CBL-CT/2A

Cable Size 2 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1 Installation

BUS-CT/2A

System Nominal Voltage 480.0 V 30965 Amps 3P

X/R Pos 1.83 24500 Amps SLG

X/R SLG 1.4485

MTRI-CT/2A

Init Sym RMS 3P 348.92 A

Init Sym RMS SLG 184.05 A

Rated HP 50.0 hp

Rated Voltage 480 V

Rated Amps 60.3 A

CBL-CT/2B

Cable Size 2 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1 Installation

BUS-CT/2B

System Nominal Voltage 480.0 V 30965 Amps 3P

X/R Pos 1.83 24500 Amps SLG

X/R SLG 1.4485

MTRI-CT/2B

Init Sym RMS 3P 348.92 A

Init Sym RMS SLG 184.05 A

Rated HP 50.0 hp

Rated Voltage 480 V

Rated Amps 60.3 A

CBL-CT/3A

CableSize 2 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1 Installation

BUS-CT/3A

System Nominal Voltage 480.0 V 30965 Amps 3P

X/R Pos 1.83 24500 Amps SLG

X/R SLG 1.4485

MTRI-CT/3A

Init Sym RMS 3P 348.92 A

Init Sym RMS SLG 184.05 A

Rated HP 50.0 hp

Rated Voltage 480 V

Rated Amps 60.3 A

CBL-CT/3B

Cable Size 2 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1 Installation

BUS-CT/3B

System Nominal Voltage 480.0 V 30965 Amps 3P

X/R Pos 1.83 24500 Amps SLG

X/R SLG 1.4485

MTRI-CT/3B

Init Sym RMS 3P 348.92 A

Init Sym RMS SLG 184.05 A

Rated HP 50.0 hp

Rated Voltage 480 V

Rated Amps 60.3 A

CBL-CT/4A

Cable Size 2 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1 Installation

BUS-CT/4A

System Nominal Voltage 480.0 V 30965 Amps 3P

X/R Pos 1.83 24500 Amps SLG

X/R SLG 1.4485

MTRI-CT/4A

Init Sym RMS 3P 348.92 A

Init Sym RMS SLG 184.05 A

Rated HP 50.0 hp

Rated Voltage 480 V

Rated Amps 60.3 A

CBL-CT/4B

Cable Size 2 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1 Installation

BUS-CT/4B

System Nominal Voltage 480.0 V 30965 Amps 3P

X/R Pos 1.83 24500 Amps SLG

X/R SLG 1.4485

MTRI-CT/4B

Init Sym RMS 3P 348.92 A

Init Sym RMS SLG 184.05 A

Rated HP 50.0 hp

Rated Voltage 480 V

Rated Amps 60.3 A

CBL-MUA-1 & 2 &3

Cable Size 6 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1 Installation

BUS-MUA-1 & 2 & 3

System Nominal Voltage 480.0 V 25487 Amps 3P

X/R Pos 1.07 19966 Amps SLG

X/R SLG 0.9291

MTRI-MUA-1 & 2 & 3

Init Sym RMS 3P 209.35 A

Init Sym RMS SLG 109.33 A

Rated HP 30.0 hp

Rated Voltage 480 V

Rated Amps 36.2 A

CBL-AHU-1 & 2 & 3

Cable Size 2 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1 Installation

BUS-AHU-1 & 2 & 3

System Nominal Voltage 480.0 V 30953 Amps 3P

X/R Pos 1.82 24494 Amps SLG

X/R SLG 1.4472

MTRI-AHU-1 & 2 & 3

Init Sym RMS 3P 282.62 A

Init Sym RMS SLG 149.10 A

Rated HP 40.5 hp

Rated Voltage 480 V

Rated Amps 48.8 A

CBL-SF-1 & 2, EF-1 & 2 & 3

Cable Size 2 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1 Installation

BUS-SF-1 & 2, EF-1 & 2 & 3

System Nominal Voltage 480.0 V 30958 Amps 3P

X/R Pos 1.83 24497 Amps SLG

X/R SLG 1.4478

MTRI-SF-1 & 2, EF-1 & 2 & 3

Init Sym RMS 3P 314.02 A

Init Sym RMS SLG 165.65 A

Rated HP 45.0 hp

Rated Voltage 480 V

Rated Amps 54.3 A

CBL-SF-3, EF-4 & 5, FCU-1 & 2

Cable Size 8 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1 Installation

BUS-SF-3, EF-4 & 5, FCU-1 & 2

System Nominal Voltage 480.0 V 21033 Amps 3P

X/R Pos 0.77 16511 Amps SLG

X/R SLG 0.6917

MTRI-SF-3, EF-4 & 5, FCU-1 & 2

Init Sym RMS 3P 167.48 A

Init Sym RMS SLG 87.64 A

Rated HP 24.0 hp

Rated Voltage 480 V

Rated Amps 28.9 A

(MCC/75-1)

PD-0174

Frame/Rating 0.0 A

Frame/Model

Settings

PD-0175

Frame/Rating 0.0 A

Frame/Model

Settings

PD-0176

Frame/Rating 0.0 A

Frame/Model

Settings

PD-0177

Frame/Rating 0.0 A

Frame/Model

Settings

PD-0178

Frame/Rating 0.0 A

Frame/Model

Settings

PD-0179

Frame/Rating 0.0 A

Frame/Model

Settings

PD-0180

Frame/Rating 0.0 A

Frame/Model

Settings

PD-0181

Frame/Rating 0.0 A

Frame/Model

Settings

PD-0182

Frame/Rating 0.0 A

Frame/Model

Settings

PD-0183

Frame/Rating 0.0 A

Frame/Model

Settings

PD-0205

Frame/Rating 0.0 A

Frame/Model

Settings

PD-0206

Frame/Rating 0.0 A

Frame/Model

Settings

PD-0207

Frame/Rating 0.0 A

Frame/Model

Settings

System Nominal Voltage 480.0 V

43845 Amps 3P

X/R Pos 5.99

37663 Amps SLG

X/R SLG 3.8134

CBL-SCWP-1 CBL-SCWP-2

Cable Size 3/0 AWG/kcmil

Length 10.0 ft

Qty Per Phase 2

Installation

BUS-SCWP-1

System Nominal Voltage 480.0 V 42110 Amps 3P

X/R Pos 4.60 35628 Amps SLG

X/R SLG 3.2151

MTRI-SCWP-1

Init Sym RMS 3P 1744.58 A

Init Sym RMS SLG 984.03 A

Rated HP 250.0 hp

Rated Voltage 480 V

Rated Amps 301.5 A

Cable Size 3/0 AWG/kcmil

Length 10.0 ft

Qty Per Phase 2

Installation

BUS-SCWP-2

System Nominal Voltage 480.0 V 42110 Amps 3P

X/R Pos 4.60 35628 Amps SLG

X/R SLG 3.2151

MTRI-SCWP-2

Init Sym RMS 3P 1744.58 A

Init Sym RMS SLG 984.03 A

Rated HP 250.0 hp

Rated Voltage 480 V

Rated Amps 301.5 A

CBL-SCWP-3

Cable Size 3/0 AWG/kcmil

Length 10.0 ft

Qty Per Phase 2

Installation

BUS-SCWP-3

System Nominal Voltage 480.0 V 42110 Amps 3P

X/R Pos 4.60 35628 Amps SLG

X/R SLG 3.2151

MTRI-SCWP-3

Init Sym RMS 3P 1744.58 A

Init Sym RMS SLG 984.03 A

Rated HP 250.0 hp

Rated Voltage 480 V

Rated Amps 301.5 A

CBL-CWP-1

Cable Size 2 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1

Installation

BUS-CWP-1

System Nominal Voltage 480.0 V 37591 Amps 3P

X/R Pos 2.19 31007 Amps SLG

X/R SLG 1.8227

MTRI-CWP-1

Init Sym RMS 3P 348.92 A

Init Sym RMS SLG 191.87 A

Rated HP 50.0 hp

Rated Voltage 480 V

Rated Amps 60.3 A

CBL-CWP-2

Cable Size 2 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1

Installation

BUS-CWP-2

System Nominal Voltage 480.0 V 37591 Amps 3P

X/R Pos 2.19 31007 Amps SLG

X/R SLG 1.8227

MTRI-CWP-2

Init Sym RMS 3P 348.92 A

Init Sym RMS SLG 191.87 A

Rated HP 50.0 hp

Rated Voltage 480 V

Rated Amps 60.3 A

CBL-CWP-3

Cable Size 2 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1

Installation

BUS-CWP-3

System Nominal Voltage 480.0 V 37591 Amps 3P

X/R Pos 2.19 31007 Amps SLG

X/R SLG 1.8227

MTRI-CWP-3

Init Sym RMS 3P 348.92 A

Init Sym RMS SLG 191.87 A

Rated HP 50.0 hp

Rated Voltage 480 V

Rated Amps 60.3 A

CBL-CWP-4

Cable Size 2 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1

Installation

BUS-CWP-4

System Nominal Voltage 480.0 V 37591 Amps 3P

X/R Pos 2.19 31007 Amps SLG

X/R SLG 1.8227

MTRI-CWP-4

Init Sym RMS 3P 348.92 A

Init Sym RMS SLG 191.87 A

Rated HP 50.0 hp

Rated Voltage 480 V

Rated Amps 60.3 A

CBL-CWP-5

Cable Size 3/0 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1

Installation

BUS-CWP-5

System Nominal Voltage 480.0 V 40291 Amps 3P

X/R Pos 3.72 33677 Amps SLG

X/R SLG 2.7917

MTRI-CWP-5

Init Sym RMS 3P 872.29 A

Init Sym RMS SLG 486.06 A

Rated HP 125.0 hp

Rated Voltage 480 V

Rated Amps 150.8 A

CBL-CWP-6

Cable Size 3/0 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1

Installation

BUS-CWP-6

System Nominal Voltage 480.0 V 40291 Amps 3P

X/R Pos 3.72 33677 Amps SLG

X/R SLG 2.7917

MTRI-CWP-6

Init Sym RMS 3P 872.29 A

Init Sym RMS SLG 486.06 A

Rated HP 125.0 hp

Rated Voltage 480 V

Rated Amps 150.8 A

CBL-CP-1

CableSize 2/0 AWG/kcmil

Length 10.0 ft

QtyPerPhase 1

Installation

BUS-CP-1

SystemNominalVoltage 480.0 V 39814 Amps 3P

X/R Pos 3.28 33183 Amps SLG

X/R SLG 2.5293

MTRI-CP-1

Init Sym RMS 3P 697.83 A

Init Sym RMS SLG 387.74 A

Rated HP 100.0 hp

Rated Voltage 480 V

Rated Amps 120.6 A

CBL-CP-2

Cable Size 2/0 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1

Installation

BUS-CP-2

System Nominal Voltage 480.0 V 39814 Amps 3P

X/R Pos 3.28 33183 Amps SLG

X/R SLG 2.5293

MTRI-CP-2

Init Sym RMS 3P 697.83 A

Init Sym RMS SLG 387.74 A

Rated HP 100.0 hp

Rated Voltage 480 V

Rated Amps 120.6 A

CBL-CP-3

Cable Size 2/0 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1

Installation

BUS-CP-3

System Nominal Voltage 480.0 V 39814 Amps 3P

X/R Pos 3.28 33183 Amps SLG

X/R SLG 2.5293

MTRI-CP-3

Init Sym RMS 3P 697.83 A

Init Sym RMS SLG 387.74 A

Rated HP 100.0 hp

Rated Voltage 480 V

Rated Amps 120.6 A

CBL-CP-4

Cable Size 2/0 AWG/kcmil

Length 10.0 ft

Qty Per Phase 1

Installation

BUS-CP-4

System Nominal Voltage 480.0 V 39814 Amps 3P

X/R Pos 3.28 33183 Amps SLG

X/R SLG 2.5293

MTRI-CP-4

Init Sym RMS 3P 697.83 A

Init Sym RMS SLG 387.74 A

Rated HP 100.0 hp

Rated Voltage 480 V

Rated Amps 120.6 A

75-DP-TRAB

208V, 3PH

200A

200A/3P

20A/3P20A/3P100A/3P100A/3P

DPMSPD

1/4"C-4#3, #8G

75-1B105A

208V, 3PH

100A

75-1B105B

208V, 3PH

100A

2 3

2"C-4#3/0, #6G

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES

FOUND SHALL BE REPORTED TO THE ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

75EP601

BLDG 75 - ONE-LINE DIAGRAM

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL/WNM LLT/JPS

CONSTRUCTION

DOCUMENTS

Revisions: Date:

KEY NOTES

GENERAL NOTES

- Scale: NTS

1 BLDG 75 - ONE-LINE DIAGRAM

PROVIDE TAPS AS REQUIRED TO INSTALL FEEDER TO PANEL 75-DP-TRAB; IF

REQUIRED, PROVIDE JUNCTION BOX TO HOUSE INSULATED TAPS AS REQUIRED.

TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER

TR PANEL, TYPICAL - TYPE 3" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

TYPICAL 100A PANEL. REFERENCE TYPICAL PANEL SCHEDULE "SOURCE A POWER

TR PANEL, TYPICAL - TYPE 3" ON SHEET 00EP701 FOR ADDITIONAL CIRCUITING

INFORMATION.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

01EP701

BLDG 01 - ELECTRICAL SCHEDULES

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

ST. LOUIS VA MEDICAL CENTER - JEFFERSON

BARRACKS MO

657-21-701JB

03/31/2022 LRL/WNM JBB

CONSTRUCTION

DOCUMENTS

Revisions: Date:

GENERAL NOTES

KEY NOTES

Notes:

Total Est. Demand: 80 A

Total Conn.: 126 A

Total Est. Demand: 28840 VA

Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 45280 VA

Other 2400 VA 100.00% 2400 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 132 A 118 A 132 A

Total Load: 15573 VA 14133 VA 15573 VA

71 -- -- -- 0 VA 72

69 -- -- -- 0 VA 70

67 1-24-B (LIGHTS) 400 A 3 0 VA 68

65 -- -- -- 0 VA 1557... -- -- -- 66

63 -- -- -- 0 VA 1413... -- -- -- 64

61 PANEL P-4 400 A 3 0 VA 1557... 3 400 A 1-DP-TRB 62

59 -- -- -- 0 VA 0 VA -- -- -- 60

57 -- -- -- 0 VA 0 VA -- -- -- 58

55 ATS1-CDP 600 A 3 0 VA 0 VA 3 400 A PANEL 1PPC 56

53 -- -- -- 0 VA 0 VA -- -- -- 54

51 -- -- -- 0 VA 0 VA -- -- -- 52

49 ATS1-EMDP 700 A 3 0 VA 0 VA 3 225 A PANEL 1E-15H 50

47 -- -- -- 0 VA 0 VA -- -- -- 48

45 -- -- -- 0 VA 0 VA -- -- -- 46

43 PANEL X1 (VIA 1-XF2-PANEL-X1) 800 A 3 0 VA 0 VA 3 225 A PANEL 1-L15 44

41 -- -- -- 0 VA 0 VA -- -- -- 42

39 -- -- -- 0 VA 0 VA -- -- -- 40

37 PANEL SERV. ROM 6614 200 A 3 0 VA 0 VA 3 400 A PANEL L34 38

35 -- -- -- 0 VA 0 VA -- -- -- 36

33 -- -- -- 0 VA 0 VA -- -- -- 34

31 PANEL GC17 200 A 3 0 VA 0 VA 3 300 A PANEL N1 32

29 -- -- -- 0 VA 0 VA -- -- -- 30

27 -- -- -- 0 VA 0 VA -- -- -- 28

25 PANEL 1P2 250 A 3 0 VA 0 VA 3 400 A RISER-1P-1 (PANELS 1P5, GC18, 1P3) 26

23 -- -- -- 0 VA 0 VA -- -- -- 24

21 -- -- -- 0 VA 0 VA -- -- -- 22

19 ATS1-EDP25 250 A 3 0 VA 0 VA 3 400 A L2-RISER-1 (PANELS L02L, 1-L12L, L22R, L32L) 20

17 -- -- -- 0 VA 0 VA -- -- -- 18

15 -- -- -- 0 VA 0 VA -- -- -- 16

13 PANEL L13A 250 A 3 0 VA 0 VA 3 400 A PANEL E3 LAB 14

11 -- -- -- 0 VA 0 VA -- -- -- 12

9 -- -- -- 0 VA 0 VA -- -- -- 10

7 PANEL H1 100 A 3 0 VA 0 VA 3 400 A L1-RISER-1 (PANEL L01, PANEL 1-L11R, PANE... 8

5 -- -- -- 0 VA 0 VA -- -- -- 6

3 -- -- -- 0 VA 0 VA -- -- -- 4

1 ATS1-LSA 100 A 3 0 VA 0 VA 3 400 A L3-RISER-1 (PANEL L03, PANEL L13L, PANEL... 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: N/A Wires: 4 Mains: 2500A / 3P

Supply From: 1-XF2-BLDG-1-MSB Phases: 3 Mains Rating: 2500 A

Location: GC16 Volts: 120/208 Wye A.I.C. Rating:

Switchboard: MSB

REMOVE EXISTING SPARE CIRCUIT BREAKER AND INSTALL NEW CIRCUIT

BREAKER TO SUPPLY NEW LOAD.

PROVIDE NEW CIRCUIT BREAKER TO SUPPLY NEW LOAD.2

EXISTING POWER DISTRIBUTION EQUIPMENT TO BE MODIFIED AS SHOWN.

REFERENCE ONE-LINE DIAGRAM ON SHEET 01EP601 FOR ADDITIONAL

INFORMATION. ALL CIRCUITS SHALL BE EXISTING UNLESS OTHERWISE NOTED.

THIS SCHEDULE IS PROVIDED TO SHOW BRANCH CIRCUITING ONLY AND IS NOT

PROVIDED TO SHOW OVERALL LOAD OF PANEL.

Notes:

Total Est. Demand: 82 A

Total Conn.: 128 A

Lighting 808 VA 100.00% 808 VA Total Est. Demand: 29648 VA

Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 46088 VA

Other 2400 VA 100.00% 2400 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 134 A 121 A 131 A

Total Load: 15977 VA 14537 VA 15573 VA

29 -- -- -- 1557... -- -- -- -- 30

27 -- -- -- 1453... -- -- -- -- 28

25 1-DP-TRA 400 A 3 1597... -- 3 -- Space 26

23 -- -- -- 0 VA 0 VA -- -- -- 24

21 -- -- -- 0 VA 0 VA -- -- -- 22

19 ECGB 100 A 3 0 VA 0 VA 3 100 A ECGA 20

17 -- -- -- 0 VA 0 VA -- -- -- 18

15 -- -- -- 0 VA 0 VA -- -- -- 16

13 EC1 175 A 3 0 VA 0 VA 3 225 A 2CEC, 3CEC 14

11 -- -- -- 0 VA 0 VA -- -- -- 12

9 -- -- -- 0 VA 0 VA -- -- -- 10

7 GC14 200 A 3 0 VA 0 VA 3 225 A EP, 2C3 8

5 -- -- -- 0 VA 0 VA -- -- -- 6

3 -- -- -- 0 VA 0 VA -- -- -- 4

1 EP3L 400 A 3 0 VA 0 VA 3 225 A 60kW UPS 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains: 600A

Supply From: 1-ATS1-CDP Phases: 3 Mains Rating: 100 A

Location: GC16A Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: CDP

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY

AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

01EP702

BLDG 01 - ELECTRICAL SCHEDULES

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

ST. LOUIS VA MEDICAL CENTER - JEFFERSON

BARRACKS MO

657-21-701JB

03/31/2022 Checker Author

CONSTRUCTION

DOCUMENTS

Revisions: Date:

Notes:

Total Est. Demand: 82 A

Total Conn.: 128 A

Lighting 808 VA 100.00% 808 VA Total Est. Demand: 29648 VA

Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 46088 VA

Other 2400 VA 100.00% 2400 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 134 A 121 A 131 A

Total Load: 15977 VA 14537 VA 15573 VA

29 SPARE 20 A 1 0 VA 0 VA -- -- -- 30

27 SPARE 20 A 1 0 VA 0 VA -- -- -- 28

25 SPARE 20 A 1 0 VA 0 VA 3 20 A SPD 26

23 SPARE 20 A 1 0 VA 0 VA -- -- -- 24

21 SPARE 20 A 1 0 VA 0 VA -- -- -- 22

19 SPARE 20 A 1 0 VA 0 VA 3 20 A DIGITAL POWER METER 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 -- -- -- 3533... 0 VA 1 20 A SPARE 16

13 -- -- -- 3735... 0 VA 1 20 A SPARE 14

11 PANEL 1-1E15A 100 A 3 4253... 3533... -- -- -- 12

9 -- -- -- 3533... 3735... -- -- -- 10

7 -- -- -- 3735... 4253... 3 20 A PANEL 1-3C13A 8

5 PANEL 1-2C10A 20 A 3 4253... 3533... -- -- -- 6

3 SPARE 20 A 1 0 VA 3735... -- -- -- 4

1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 1-C102DA 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: SURFACE Wires: 4 Mains: 400A/3P

Supply From: 1-PANEL-CDP Phases: 3 Mains Rating: 400 A

Location: GC-15 Volts: 120/208 Wye A.I.C. Rating: 65k

Branch Panel: 1-DP-TRA

Notes:

Total Est. Demand: 80 A

Total Conn.: 126 A

Total Est. Demand: 28840 VA

Receptacle 42880 VA 61.66% 26440 VA Total Conn. Load: 45280 VA

Other 2400 VA 100.00% 2400 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 132 A 118 A 132 A

Total Load: 15573 VA 14133 VA 15573 VA

29 SPARE 20 A 1 0 VA 0 VA -- -- -- 30

27 SPARE 20 A 1 0 VA 0 VA -- -- -- 28

25 SPARE 20 A 1 0 VA 0 VA 3 20 A SPD 26

23 SPARE 20 A 1 0 VA 0 VA -- -- -- 24

21 SPARE 20 A 1 0 VA 0 VA -- -- -- 22

19 SPARE 20 A 1 0 VA 0 VA 3 20 A DIGITAL POWER METER 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 -- -- -- 3533... 0 VA 1 20 A SPARE 16

13 -- -- -- 3533... 0 VA 1 20 A SPARE 14

11 PANEL 1-2C10AB 100 A 3 4253... 3533... -- -- -- 12

9 -- -- -- 3533... 3533... -- -- -- 10

7 -- -- -- 3533... 4253... 3 100 A PANEL 1-3C13B 8

5 PANEL 1-1E15B 100 A 3 4253... 3533... -- -- -- 6

3 SPARE 20 A 1 0 VA 3533... -- -- -- 4

1 SPARE 20 A 1 0 VA 4253... 3 100 A PANEL 1-C102DB 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: SURFACE Wires: 4 Mains: 400A / 3P

Supply From: 1-SWBD-MSB-01 Phases: 3 Mains Rating: 400 A

Location: GC-15 Volts: 120/208 Wye A.I.C. Rating: 65k

Branch Panel: 1-DP-TRB

GENERAL NOTES

KEY NOTES

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE ANY

AND ALL CHANGES; ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL TR SOURCE-A AND

SOURCE-B PANEL SCHEDULES.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

02EP701

BLDG 02 - ELECTRICAL

SCHEDULESSPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 LRL/WNM JBB

CONSTRUCTION

DOCUMENTS

Revisions: Date:

GENERAL NOTES

KEY NOTES

Notes:

Total Est. Demand: 103 A

Total Conn.: 144 A

Power 6568 VA 100.00% 6568 VA Total Est. Demand: 36968 VA

Receptacle 40000 VA 62.50% 25000 VA Total Conn. Load: 51968 VA

Other 5400 VA 100.00% 5400 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 155 A 126 A 160 A

Total Load: 18101 VA 15133 VA 18733 VA

41 SPARE 20 A 1 0 VA 100 VA -- -- -- 42

39 SPARE 20 A 1 0 VA 100…