This solicitation is seeking a general contractor to provide infrastructure upgrades at the St. Louis Jefferson Barracks VA Medical Center. The scope of work includes electrical panel upgrades and power systems work, building management system integration, HVAC assessments and upgrades, interior renovations including demolition and new construction, data center renovations, physical security enhancements, fiber optic infrastructure assessment and upgrades, installation of a diversified wide area network path to the datacenter, and hazardous material abatement. The project involves buildings 1, 2, 3, 3T, 18, 23, 24, 25, 51, 51T, 52, 53, 53T, 55, 56, 57, 58, 59, 60, 60T, 61, 75 and surrounding site work. The Department of Veterans Affairs Technology Acquisition Center located in Austin is the contracting agency.
View the file
Other files for this federal contract opportunity
Show all 50
Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
4160 VO
LTS
DUST CO
LLECTO
R
LIQ UEFIED PETRO LEUM G AS
FLAM M ABLE G AS 2
TRASH COM
PACTO
R
P
SILVERBUILDING 1 23
VA PO
LICE
E
LECTRIC ACCESS
TRANSFO
RM
ER
TRANSFO
RM
ER
TRANSFO
RM
ER
HVAC UNIT
E
LECTRIC PANEL
HVAC UNIT
S&C PAD M
O
UNTED G
EAR
CATALO
G
# 55152-C3DGIG
2P1V M
O
DEL# PM
H-9
EE13299 SG
-52
13278
BUILDING
UPDN
DN DN
ROOF BELOW
ROOF BELOW
ROOF BELOW ROOF BELOW
ROOF BELOW
ROOF BELOW
ROOF
BELOW
UPDN
DN DN
ROOF BELOW
ROOF BELOW
ROOF BELOW ROOF BELOW
ROOF BELOW
ROOF BELOW
ROOF
BELOW
J2 J1
L
P2 IN PH
ABOVE
H
GA
G
YX
U.7S.2
U
S
Q
P.5
PNMK
11.9 11.9
12.8
8.7
3 3
M.1
J
H.2E.1
HGFEDCA
B.1
9.9
Z
4 4
52EP402b
52EP402b
OFFICE
2S20A
OFFICE
2N80
OFFICE
2N79
OFFICE
2N77
TOILET, MALE
2N78
OFFICE
2N76
TOILET, MALE
2N88
F.E. CLOSET
2N90
OFFICE
2N89
TR
2N91 OFFICE
2N92
OFFICE
2N93
STAIR 3
S203
STORAGE
2N109
STORAGE
2N108
STORAGE
2N107
CONFERENCE RM.
2N72A
CHAPEL
2N72
CHAPEL
2N73
TOILET, FEMALE
2N75
TOILET, STAFF
2N74
KITCHEN
2N71
OFFICE, OPEN
2N69
CORRIDOR
H206
TOILET, STAFF
2N70
LIBRARY
2N68
OFFICE
2N66
TOILET, MALE
2N67
OFFICE
2N65
HAC
2N64
OFFICE
2N63
OFFICE
2N60
OFFICE
2N59
OFFICE
2N59A
CLOSET
2N59B
OFFICE
2N112
WHEELCHAIR STORAGE
2N110
EXAM RM.
2S08EXAM
2N118
EXAM
2S01 TREAT. RM.
2S05
CONTROL RM.
2S06
VEST.
2S06A
EXAM
2S04
SCI SERVICE PAIN REHAB. CENTER
2N117A
TOILET
2N113A
TOILET, STAFF
2N115
ELEV 1
E1
SCI SERVICE PAIN REHAB. CENTER
2N117
TOILET
2N116
STAIR 2
S202
ELEVATOR LOBBY
2S57
PAIN REHAB. CENTER
2S56A
P.T. / O.T.
2N58
CORRIDOR
H205HALLWAY
2N113
WAITING RM.
2N112A
OFFICE
2S51
CORRIDOR
H208
HAC
2S10
ELEC. CLOSET
2S9
OFFICE
2S11
OFFICE
2S11A
EXAM
2S12B
HALLWAY
2S13
BATH / SHOWER
2S12
EXAM
2S12A
EXAM
2S13A
STORAGE
2S16
STORAGE
2S17
STORAGE
2S14
TOILET, FEMALE
2S43A
TOILET, MALE
2S41HALLWAY
2S45
CONFERENCE RM.
2S44
OFFICE
2S46
TOILET
2S47
OFFICE
2S48
OFFICE
2S49
TOILET
2S50
CRAFTS RM.
2S21
OFFICE
2S22B
HALLWAY
2S20
HALLWAY
2S22
OFFICE
2S22A
TOILET, FEMALE
2S23
OFFICE
2S20B
PIPE CHASE
2S24A
OFFICE
2S24
OFFICE
2S19B
OFFICE
2S18
STORAGE
2S26
OFFICE
2S25
STORAGE
2S28
STAIR 1
S201
VA CONSULT
2S29
OFFICE
2S30
HAC
2S31
OFFICE
2S32
OFFICE
2S33
OFFICE
2S36
OFFICE
2S38
OFFICE
2S37
CLOSET
2S37A
TOILET
2S39
ADMIN.
2S34
CORRIDOR
H202
CORRIDOR
H201
CORRIDOR
H203
OFFICE
2S35
OFFICE
2S45A
PIPE CHASE
2N77A
PIPE CHASE
2N76A
PIPE CHASE
2N90A
OFFICE
2S33A
F.E. CLOSET
2S40
F.E. CLOSET
2S27
STORAGE
2S15
WORK RM.
2N81
TELECOM
2N86A
CORRIDOR
H207
ELEV 3
E3
STORAGE
2S43
PIPE CHASE
2S41A
PIPE CHASE
2S38A
STORAGE
2S52
CHASE
CH-S-1
F.E. CLOSET
H208A
PIPE CHASE
2N75A
PIPE CHASE
2N81A
CHASE
CH-N-3 CHASE
CH-S-2
CHASE
CH-N-1
CHASE
CH-N-2
CHASE
CH-S-5
CHASE
CH-S-3
CLOSET
2N115A
CHASE
CH-N-4
CHASE
CH-S-4
CHASE
CH-S-6
UTILITY
2N103
TRAINING TOILET
2N104
TOOL BENCH/ WORK STATION
2N98
STPRAGE
2N97
MECH RM.
2N106
CORRIDOR
2N95
VEST.
2N105
THERAPY
2N101
OFFICE
2S19A
HALLWAY
2S19
B
52EP402b
52EP402b
52EP402a
52EP402a
52EP402a
52EP402a
TR
2N86B
CONFERENCE RM.
2S56
BLDG 52
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR
SHALL FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT
TO BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
2. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS,
AND RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL
LOCATIONS WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER
INSTALLATION OF MILLWORK, UNLESS OTHERWISE NOTED.
3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY
POWER AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT.
POWER TO ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND
SHALL REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN
SHALL CONFORM WITH VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL
INFORMATION.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
52EP102
BLDG 52 - FLOOR 2 - ELECTRICAL
PLANSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM JPS/LTT
CONSTRUCTION
DOCUMENTS
- 1" = 20'-0"
1 BLDG 52 - FLOOR 2 - ELECTRICAL PLAN
GENERAL NOTES
KEY PLAN
KEY NOTES
Revisions: Date:
0' 10' 20' 40'
PROJECT
NORTH
PROJECT
NORTH
LRL/WNM LLT/JPS
JT
JT
JT
JT
JT
JT
JT
JT
4160 VO
LTS
DUST CO
LLECTO
R
LIQ UEFIED PETRO LEUM G AS
FLAM M ABLE G AS 2
TRASH COM
PACTO
R
P
SILVERBUILDING 1 23
VA PO
LICE
E
LECTRIC ACCESS
TRANSFO
RM
ER
TRANSFO
RM
ER
TRANSFO
RM
ER
HVAC UNIT
E
LECTRIC PANEL
HVAC UNIT
S&C PAD M
O
UNTED G
EAR
CATALO
G
# 55152-C3DGIG
2P1V M
O
DEL# PM
H-9
EE13299 SG
-52
13278
BUILDING
FEC
FEC
FEC
FEC
FEC
FEC FEC
FEFEC
GC2 GC - 1
GB
ECGA
GB1 - 1
GB1 - 2 ELGA
GA
GP
LOUNGE
GS16
MECH. RM.
GS12
MDS COORD.
GN38
STORAGE
GN44 OFFICE
GN43
EXAM
GN42OFFICE
GN39
OFFICE
GN48
OFFICE
GN41 OFFICE
GN45
OFFICE
GN45A
OFFICE
GN40
OFFICE
GN46
CORRIDOR
H008
SOILED LAUNDRY
GN50
TOILET, FEMALE
GN37
BREAK RM.
GN36
STORAGE
GS34A
CONFERENCE RM.
GS33
OFFICE
GS31OFFICE
GS32
OFFICE
GS29
OFFICE
GS26
OFFICE
GS23
CONTROL RM. 1
GS19A
SUITE 1
GS19B
SUITE 2
GS19C
CONTROL RM. 2
GS19D
TOILET, MALE
GS35
LAB.
GS28
OFFICE
GS24
OFFICE
GS22
CORRIDOR
H003
CORRIDOR
H005
CONTROL RM. 4
GS19E
SUITE 4
GS19F
SUITE 3
GS19GCONTROL RM. 3
GS19H
CORRIDOR
H004
ELEC. RM.
GS21
LOCKER RM.
GS17
CLOSET
GS16A
TOILET, MALE
GS14
CORRIDOR
H002
PIPE SPACE ACCESS
GS51
STAIRWELL NO. 2
S002
CORRIDOR
H001
LINEN CHUTE
GS04
HAC
GS05
STAIRWELL NO. 1
S001
OFFICE
GS07
LOADING DOCK
GS11
MECH. RM.
GS09
MECH. RM.
GS13
STORAGE
GS33A
LINEN CHUTE
GS08
LOCKER RM.
GS15
TOILET, FEMALE
GS18
ELEVATOR LOBBY
GS20
OFFICE
GS34
WAITING RM.
GS27
CORRIDOR
H006
CORRIDOR
H007
ELEVATOR LOBBY
GS01
ELEVATOR NO. 1
E1
PIPE CHASE
Z002
PIPE CHASE
Z003
PIPE CHASE
Z004
PIPE CHASE
Z005
PIPE CHASE
Z006
PIPE CHASE
Z007
CHASE
CH-GS-2
CHASE
CH-GS-3
CHASE
CH-GS-4
CHASE
CH-GS-5
CHASE
CH-GS-6
CHASE
CH-GN-1
CHASE
CH-GS-7
CHASE
CH-GS-8
CORRIDOR
H004
ELEVATOR NO. 2
E2
TV STORAGE
GS06
LOADING DOCK
GS11
TR
GS10
CHASE
CH-GS-7
CDP
3.43.4
A
A
C
C D.1 E H
E.1
E.1
E.2
E.2
H.2
H.2
6.56.5
M.1
M.1
P
P
W
WU
T.10
T.10
S.2
S.2 S.3
V.1
V.1
2.92.9
ATS#3
ATS - 53
PANEL GPD - 53
ATS#2
PANEL EMP
MAIN
SWITCHBOARD
MSB - 53
UP
ATS#1
MP53
53-DP-TRB
TR
GS02A
53EP400a
53EP400a
53EP400b
53EP400b
53EP400b
53EP400b
53EP400a
53EP400a
53-DP-TRA2
BLDG 53
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND LIGHTING DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE
NOTED.
2. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF
MILLWORK, UNLESS OTHERWISE NOTED.
3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN
ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL CONFORM WITH
VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
9. REFERENCE ONE-LINE DIAGRAM ON SHEET 53EP601 FOR CONDUIT AND WIRE SIZING.
AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
53EP100
BLDG 53 - FLOOR 0 - ELECTRICAL
PLANSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
- 1/16" = 1'-0"
1 BLDG 53 - FLOOR 0 - ELECTRICAL PLAN 0' 8' 16' 32'
GENERAL NOTES
KEY PLAN
KEY NOTES
Revisions: Date:
PROJECT
NORTH
1 EXISTING PANEL TO BE MODIFIED. REFERENCE ONE-LINE DIAGRAM ON SHEET
53EP601 FOR ADDITIONAL INFORMATION.
2 EQUIPMENT TO BE ADDED. REFERENCE ONE-LINE DIAGRAM ON SHEET 53EP601
FOR ADDITIONAL INFORMATION.
PROJECT
NORTH
UP
DN UP
DN
UP
DN
DN
DN
4160 VO
LTS
DUST CO
LLECTO
R
LIQ UEFIED PETRO LEUM G AS
FLAM M ABLE G AS 2
TRASH COM
PACTO
R
P
SILVERBUILDING 1 23
VA PO
LICE
E
LECTRIC ACCESS
TRANSFO
RM
ER
TRANSFO
RM
ER
TRANSFO
RM
ER
HVAC UNIT
E
LECTRIC PANEL
HVAC UNIT
S&C PAD M
O
UNTED G
EAR
CATALO
G
# 55152-C3DGIG
2P1V M
O
DEL# PM
H-9
EE13299 SG
-52
13278
BUILDING
1C - 1
1C - 2
EC1B
KP
1A2
1A1
EC1A
53EP401b
53EP401a
53EP401a
53EP401b
STORAGE
1S005
CORRIDOR
H104
Office
1S074
TR
1S011
TR
1S002
NURSE STATION
1N081
OPEN OFFICE
1N077
BED RM. - 1 BED
1N106
CLEAN STORAGE
1N086
BED RM. - 3 BED
1N099
DAY RM.
1N096
BATH / SHOWER RM.
1N098
BED RM. - 1 BED
1N095
TOILET
1N094
BED RM. - 1 BED
1N092
BED RM. - 3 BED
1N100
BATH / SHOWER RM.
1N101
BATH / SHOWER RM.
1N103
TOILET
1N102
CORRIDOR
H106
TOILET, STAFF
1N091
LINEN RM., CLEAN
1N104
STAIRWELL NO. 3
S103
DAY RM.
1N117
CHASE
CH-N-2
OI&T
1N115
CHASE
CH-N-1
BATH / SHOWER RM.
1N114
BED RM. - 1 BED
1N113
CORRIDOR
H108
BED RM. - 1 BED
1N107
BATH / SHOWER RM.
1N105
BED RM. - 1 BED
1N112
UTILITY RM., SOILED
1N089
KITCHEN
1N088
CONFERENCE RM.
1N082
BATH / SHOWER RM.
1N108
BED RM. - 2 BED
1N109
BED RM. - 2 BED
1N110
BATH / SHOWER RM.
1N111
BED RM.
1N119
ANTE RM.
1N118
LINEN CHUTE
1N120A
CHASE
CH-N-5
TOILET
1N121
MED PREP.
1N080
ALCOVE
1N078
DISHWASHING RM.
1S073
OFFICE
1S074
OFFICE
1S075
ACTIVITY RM.
1S004
STAIRWELL NO. 2
S102 ELEVATOR NO.1
E1
CHASE
CH-S-10ELEC. CLOSET
1S006
ELEC. CLOSET
H105C
HAC
H105B
MAIN LOBBY
H105
TOILET
1S014
CHASE
CH-S-6
ELEC. CLOSET
1S015
BED RM. - 1 BED
1S013
DINING RM.
1S069
BED RM. - 1 BED
1S016
ELEVATOR NO. 2
E2
LOBBY
1S071
KITCHEN
1S072
VEST.
1S008
STORAGE
H105A
TOILET, FEMALE
1S007
TOILET, MALE
1S009
BED RM.
1S018
ANTE RM.
1S017 DAY RM.
1S021
CHASE
CH-S-7
ENGINEERING RM.
1S022
TOILET
1S023
CHASE
CH-S-11
CORRIDOR
H103
BED RM. - 1 BED
1S024
BED RM. - 1 BED
1S025
HAC
1S066
STORAGE
1S064
LOCKER RM.
1S062
MEDICATION PREP.
1S061
CORRIDOR
H101
CHASE
CH-S-4
SOILED UTILITY
1S035
CHASE
CH-S-8
CHASE
CH-S-9
TOILET
1S032
BED RM. - 1 BED
1S031
BED RM. - 1 BED
1S030
BED RM. - 2 BED
1S027
BED RM. - 2 BED
1S028
TOILET
1S029
TOILET
1S026
LOUNGE
1S058
NURSE STATION
1S059
OFFICE
1S063
OFFICE
1S065
LINEN RM., CLEAN
1S054
CORRIDOR
H102
KITCHEN
1S053
UTILITY RM., SOILED
1S052
UTILITY RM., CLEAN
1S051
BED RM. - 2 BED
1S057
TOILET
1S056 BED RM. - 2 BED
1S055
BED RM. - 1 BED
1S050
TOILET
1S048
BED RM. - 1 BED
1S046
CHASE
CH-S-3
HAC
1S047
BED RM. - 3 BED
1S045
TOILET
1S044
TOILET
1S043
CHASE
CH-S-2
BED RM. - 3 BED
1S042
BED RM. - 2 BED
1S041
TOILET
1S038
CHASE
CH-S-1
OXYGEN STORAGE
1S040
TOILET
1S039
BATH / SHOWER RM.
1S037
STAIRWELL NO. 1
S101
TOILET, STAFF
1S019
TOILET
1S020
A B C D.1 E E.1
2.9
3.4
6.5
N.1 N.6
P
N.5N.3
WV.1VMJH.1HF F.1 S
T.6T.1
UTS.3 T.9
53EP401a
53EP401a
53EP401b
53EP401b
N.8
N.8
Activity Room
1S004
Activity Room
1S004
EL1A
1B
BLDG 53
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND LIGHTING DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE
NOTED.
2. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF
MILLWORK, UNLESS OTHERWISE NOTED.
3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN
ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL CONFORM WITH
VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
9. REFERENCE ONE-LINE DIAGRAM ON SHEET 53EP601 FOR CONDUIT AND WIRE SIZING.
AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
53EP101
BLDG 53 - FLOOR 1 - ELECTRICAL
PLANSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
- 1/16" = 1'-0"
1 BUILDING 53 - FLOOR 1 - ELECTRICAL PLAN 0' 8' 16' 32'
GENERAL NOTES
KEY PLAN
KEY NOTES
PROJECT
NORTH
Revisions: Date:
PROJECT
NORTH
DN
JT
JT
JT
JT
JTJT
JT
JT
JT
JT
JT
4160 VO
LTS
DUST CO
LLECTO
R
LIQ UEFIED PETRO LEUM G AS
FLAM M ABLE G AS 2
TRASH COM
PACTO
R
P
SILVERBUILDING 1 23
VA PO
LICE
E
LECTRIC ACCESS
TRANSFO
RM
ER
TRANSFO
RM
ER
TRANSFO
RM
ER
HVAC UNIT
E
LECTRIC PANEL
HVAC UNIT
S&C PAD M
O
UNTED G
EAR
CATALO
G
# 55152-C3DGIG
2P1V M
O
DEL# PM
H-9
EE13299 SG
-52
13278
BUILDING
RAD
FAP
FAS
2CA
2C
2B1
2B2
EL2A
2A1 2A2
EC2A
53EP402
53EP402
TR
2S001
O.T.
2N091
PT
2N096
PT
2N094
EQUIP. STORAGE
2N095
O.T. ADMIN.
2N092
STAIRWELL NO. 3
S203
TOILET, MALE
2N097
TOILET, FEMALE
2N098
OFFICE, OPEN
2N100A
EXAM
2N100B
EXAM
2N100D
EMG
2N100E
PT
2N100C
EXAM
2N102
ELEC. CLOSET
2N101
CHASE
CH-N-1
OFFICE
2N104
HAC
2N103
OFFICE, OPEN
2N106
CHASE
CH-N-2
LINEN CHUTE
2N105
WAITING RM.
2S003 OFFICE, OPEN
2S004
STAIRWELL NO. 2
S202
ELEVATOR NO. 1
E1
CHASE
CH-S-10
TOILET, FEMALE
2S014A
STORAGE
2S06
CHASE
CH-S-2
TREAT. RM.
2S007
OFFICE, OPEN
2S008
CHASE
CH-S-1
EXAM
2S009 STORAGE
2S015A
OFFICE
2S015
CONFERENCE RM.
2S017
OFFICE
2S10
OFFICE
2S011
OFFICE
2S012
OFFICE
2S013
EXAM
2S014
CORRIDOR
H206
OFFICE
2S016
COPY RM.
2S018
OFFICE
2S018A
BATH / SHOWER RM.
2S024TOILET, MALE
2S020
BED RM. - 3 BED
2S025
TOILET
2S027
CHASE
CH-S-9
CHASE
CH-S-12
BED- R. - 2 BED
2S028 BED RM.
2S030
ANTE RM.
2S029
ALCOVE
2S031
BATH / SHOWER RM.
2S032
CHASE
CH-S-4
ELEC. CLOSET
2S035
DAY RM.
2S034
BATH / SHOWER RM.
2S036 CHASE
CH-S-5
BED RM. - 1 BED
2S037
BED RM. - 1 BED
2S038
BATH / SHOWER RM.
2S039
BED RM. - 2 BED
2S040
BED RM. - 2 BED
2S041
TOILET
2S042
BED RM. - 1 BED
2S043
CORRIDOR
H203
BED RM. - 1 BED
2S044
BATH / SHOWER RM.
2S045
STAIRWELL NO. 1
S201
CHASE
CH-S-6 BATH / SHOWER RM.
2S049
ELEC. RM.
2S026
LINEN CHUTE
2S047
TOILET, STAFF
2S048
BED RM. - 2 BED
2S053
BED RM. - 3 BED
2S054
BATH / SHOWER RM.
2S055
TOILET
2S056
CHASE
CH-S-3
BED RM. - 3 BED
2S057
BED RM. - 1 BED
2S058
HAC
2S059
TOILET
2S060
BED RM. - 1 BED
2S061
UTILITY RM., CLEAN
2S062
LINEN RM., CLEAN
2S063
SOILED UTILITY
2S64
NURSE STATION
2S072
BED RM. - 2 BED
2S073
MEDICATION PREP.
2S069 KITCHEN
2S070
OFFICE
2S065
PATIENT RM. - 1 BED
2S066
BATH / SHOWER RM.
2S067
BREAK RM.
2S68
CORRIDOR
H202BED RM. - 3 BED
2S76
BED RM. - 3 BED
2S77
SERVICE LOBBY
2S081
ELEVATOR NO. 2
E2
LOCKER RM.
2S078
TOILET
2S079
CHASE
CH-S-11
STORAGE
2S080
OFFICE
2S082
OFFICE, OPEN
2S083
OFFICE
2S085
WHEELCHAIR STORAGE
2N086WAITING RM.
2N088RECEPTION
2N089
STORAGE
2N091C
CORRIDOR
H207
5.65.6
5.4
5.9
P P.1L.1LK
53EP402
53EP402
N.8
BLDG 53
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND LIGHTING DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE
NOTED.
2. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF
MILLWORK, UNLESS OTHERWISE NOTED.
3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN
ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL CONFORM WITH
VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
9. REFERENCE ONE-LINE DIAGRAM ON SHEET 53EP601 FOR CONDUIT AND WIRE SIZING.
AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
53EP102
BLDG 53 - FLOOR 2 - ELECTRICAL
PLANSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
- 1/16" = 1'-0"
1 BLDG 53 - FLOOR 2 - ELECTRICAL PLAN 0' 8' 16' 32'
PROJECT
NORTH
GENERAL NOTES
KEY PLAN
KEY NOTES
Revisions: Date:
PROJECT
NORTH
DN
4160 VO
LTS
DUST CO
LLECTO
R
LIQ UEFIED PETRO LEUM G AS
FLAM M ABLE G AS 2
TRASH COM
PACTO
R
P
SILVERBUILDING 1 23
VA PO
LICE
E
LECTRIC ACCESS
TRANSFO
RM
ER
TRANSFO
RM
ER
TRANSFO
RM
ER
HVAC UNIT
E
LECTRIC PANEL
HVAC UNIT
S&C PAD M
O
UNTED G
EAR
CATALO
G
# 55152-C3DGIG
2P1V M
O
DEL# PM
H-9
EE13299 SG
-52
13278
BUILDING
FEC
FEC
53TEP401
53TEP401
CONFERENCE
RM.
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
TOILET, FEMALE
TOILET, MALE
HAC
OFFICE
OFFICE
CORRIDOR
C105
FOYER
C101
TR
CORRIDOR
C103
CORRIDOR
C104
E F
A B C D G H I J
BLDG 53T
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR
SHALL FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT
TO BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
2. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS,
AND RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL
LOCATIONS WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER
INSTALLATION OF MILLWORK, UNLESS OTHERWISE NOTED.
3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY
POWER AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT.
POWER TO ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND
SHALL REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN
SHALL CONFORM WITH VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL
INFORMATION.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
AREA OF WORK
- 1/4" = 1'-0"
1 BLDG 53T - FLOOR 1 - ELECTRICAL PLAN
KEY PLAN
GENERAL NOTES
0' 2' 4' 8'
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
53TEP101
BLDG 53T - FLOOR 1 -
ELECTRICAL PLANSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
JEFFERSON BARRACKS - 1 JEFFERSON BARRACKS
DRIVE - ST. LOUIS, MO 63125
657-21-701JB
53T
03/31/2022 LRL/WNM JPS/LLT
CONSTRUCTION
DOCUMENTS
Revisions: Date:
PROJECT
NORTH
PROJECT
NORTH
Tectonic Copyright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
UP
DN
FEC
FEC
F E
C
DATA
SYSTEMS
1C132
DATA
TECH
1C133
CORRIDOR
C1-57
BREAKDOWN,VERIFICATION
INVENTORY
1C135
55EP401a
55EP401a
A
55EP401a
55EP401a
DATA, SYSTEM
1A130
TR
1A129
CORE LAB AREA
1A126
Staff Lockers & Lounge
1A 139 Corridor
C1-30
Staff Toilet 1A
Storage 1A
Mobile X-Ray 1A
137a
PAC Office 1A
Path. Office 1A
Sup. Office 1A
Staff Lounge/ Lockers
1A
Training- Low Vision/ Poly
Trauma 1A
Exam- Low Vision 1A
Office, Eyecare Provider-L.V.
Multipurpose
1A
Optometry Exam- Large
1A
Staff Lounge 1A
Corridor
C1-18a
Agent Cashier 1B
Corridor
C1-15
Elec.
1A 111 Resident Exam
1A
Soiled Utility 1A
Crash Cart
C1-16 Optometry Exam 1A
Corridor
C1-12 Equipment/ Clean Supply
1A
Closet 1A
110a Staff Toilet
1A
Tele- Retinal Reading
1A
Photography Room
1A
Pre- Testing 2 1A
Pre- Testing 1 1A
Open Office 1A
Visual Field 1A
Dilation Waiting
C1-13
Waiting 1A
Eyeglass Fitting & Display
1A 100c
Storage, Wheelchair &
Stretcher 1B
House Keeping 1A
Office (Disposition)
1B
Pat. Toilet 1A
100b
Pat. Toilet 1A
Optometry Exam 1A
Office (Disposition)
1B 103b Office
(Disposition) 1B
Specimen Toilet 1A
124c
Specimen Toilet 1A
124b
Blood Collection 1A
Lab Reception 1A
124a
Elec.
1A
Waiting
C1-24
Corridor
C1-19
Kiosk
C1-23
Public Toilet 1A
Public Toilet 1A
Radiology Room 1 1A
Control 1A
153a
Control 1A
152a
Radiology Room 2 1A
Stair #1-1 Stair
#1
Corridor
C1-22
House Keeping 1A
IP Holding
C1-28
Sub- Waiting
C1-27 Dressing, ADA
1A
Patient Toilet 1A
Corridor
C1-25
Clean Supply 1A
Crash Cart 1A
147a
Soiled Utility 1A
PACS/Digital Control/
Tele-Radiology 1A
Bulk Storage 1A
Microbiology 1A
Ultrasound Room 1A
Housekeeping 1A
Office 1A
Office 1A
Corridor
C1-29
Office 1A
Office 1A
Mechanical 1M 1a
Generator Building
GB100
COURTYARD-
LOW VISION
SITE
C
F
H
B
E
G
J
K
8 8.2
MSB
ATS 55-C1
ATS 55-EQ1
GSB 55-1
55-DP-TRA 1
TR-55-DP-TRA 1
DP 55-LSI
DP 55-C1
DP 55-EQ1
DP 55-EQ2
MCC GG-1E
ATS 55-EQ2
MCC GG-1
ATS 55-LS1
A R
E A
A
A R
E A
B
S E
E S
H E
E T
E
P b
AREA A
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER,SIGNAL, LIGHTING DEVICES AND ASSOCIATED CIRCUITRY
AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH DEMOLISHED
BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF
MILLWORK, UNLESS OTHERWISE NOTED.
3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
4. CONTRACTOR TO COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN
ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL CONFORM WITH
VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
9. REFERENCE ONE-LINE DIAGRAM ON SHEET 55EP601 FOR CONDUIT AND WIRE SIZING.
- AREA OF WORK
KEY PLAN
GENERAL NOTES
KEY PLAN
KEY NOTES
GENERAL NOTES
- 1" = 10'-0"
1 BLDG 55 - FLOOR 1 - AREA A - ELECTRICAL PLAN
1 EQUIPMENT TO BE ADDED. REFERENCE ONE-LINE DIAGRAM ON SHEET 55EP601 FOR
ADDITIONAL INFORMATION.
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE DIAGRAM ON SHEET
55EP601 FOR ADITIONAL INFORMATION.
0' 5' 10' 20'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
55EP101a
BLDG 55 - FLOOR 1 - AREA A -
ELECTRICAL PLANSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM JPS/LLT
CONSTRUCTION
DOCUMENTS
Revisions: Date:
PROJECT
NORTH
PROJECT
NORTH
Tectonic Copyright 2007
Tectonic Copyright 2007
F E
C F
E C
FEC
F E
C
F E
C
F E
C
F E
C
FEC
55EP401b
55EP401b
55EP401c
55EP401c
55EP401c
55EP401c
8.3 8.5 8.7 8.9
J.1
H.4
55EP401b
TR
1B104
AGENT CASHIER
WAITING
1B102
CORRIDOR
C1-4
TR
1B104
AGENT CASHIER
WAITING
1B102
TR
1C132
55EP401b
Staff Lounge 1A
Agent Cashier 1B
Eyeglass Fitting & Display
1A 100c
Storage, Wheelchair &
Stretcher 1B
House Keeping 1A
Office (Disposition)
1B
Office (Disposition)
1B 103b Office
(Disposition) 1B
DATA TECH
1C133
CORRIDOR
C1-57
BREAKDOWN,
VERIFICATION &
INVENTORY
1C135
Women's Toilet 1B
Elevator Lobby
C1-8
Cache 1C
Lockers 1C
130a
Lounge 1C
OP (Shared) Storage - Med
Supplies 1C
127a OP (Shared)
Storage Prepack.
Meds
1C
Vault Controlled Sub.
1C
124b
IP Storage, Active 1C
Aseptic Transfer, IV Admixture
1C 126a
Anteroom, IV Admixture
1C
Cubicle, Inventory Clerk
C1-45
Cubicle, Swing 1C
125h
IV Admix Freezer
C1-55
Dispensing, Controlled Sub
1C 124a
Cubicle, IP Process
1C 125d
Cubicle, IP Process
1C 125b
Cubicle, IP Process
1C 125c
Cubicle, IP Process
1C 125a
Cubicle, OP Spec.
1C
125f
Cubicle, OP Spec.
1C
125e
Invest. Drug Work Area & Stor.
1C
Pharm Teach Lab / Conf 1C
Storage, Sterile Fluids and Admixture
1C
IP Freezer
C1-54
Consult 1C
100a Consult
1C 100b
Consult 1C
100c
Consult 1C
100d
OP Waiting 1C
Dispensing
C1-40
Dispensing
C1-39
Drug Information Area
C1-47
OP Refrigerator
C1-52
Storage - Cart 1C
Mail Out 1C
P.C.
C1-53
Elec.
1C
Clinical Pharm Teaching
1C
Cubicle, Resident 1C
110a
Cubicle, Phone 1C
119e
Cubicle, Phone 1C
119b
Cubicle, Phone 1C
119a Cubicle, Pain
1C 118a
Cubicle, Phone & Telemed
1C 119f
Cubicle, Phone 1C
119c
Cubicle, Phone 1C
119d Office, Secretary /
Wait 1C
Office, Assistant Chief
1C
Cubicle, Resident 1C
110b
Office, Pharmacist 1C
Office, Pharmacist 1C
Office, Pharmacist 1C
Office, Pharmacist 1C
Office, Chief 1C
Office, Pharmacist 1C
Cubicle, Ancil.
1C
118e
Workstation, Tech- Lead
1C 125g
Workstation, Tech
C1-46
Mechanical 1M
Men's Toilet 1B
Electrical 1C
Staff Toilet 1C
Recycling 1B
Housekeeping Storage (Future Public Elev. #4)
1B
Stair #2-1 Stair
#2
Service Elev. #3
S-1
Elevator Lobby
C1-3
Stair #3-1 Stair
#3
Corridor
C1-7
Corridor
C1-9
Corridor
C1-5
Lobby
C1-2
Radiology Data Room
1B 109a
Corridor
C1-35
Corridor
C1-36
Corridor
C1-38
Corridor
C1-51 Corridor
C1-50
Corridor
C1-56
Stat. Counter
C1-43Med Assignment
C1-42
Repackaging, Extemp.
C1-44
Active Filling
C1-41
Prescription Filling and Assembly
C1-49
Gen Tech Work
C1-48
Staff Toilet 1C
H.K.
1C
Cubicle, Psych 1C
118d
Cubicle, LTC 1C
118c
Cubicle, LTC 1C
118b
Staff Toilet 1C
Corridor
C1-37
Reception 1B
Corridor
C1-6
Corridor
C1-58
COURTYARD-
LOW VISION
SITE
Public Elev. #1
2C148
Public Elev. #2
2C149
Service Elev. #3
2C150
Lobby
2C153
Service Elev. #3
2C158
C
F
H
B
E
G
J
K
L
1311109
8 8.2
8.8
L.9
LCP-2
TR-55-1C3
TR-55-EQ3
DP-551N3
PANEL 55-1EQ3-1
PANEL 55-1C3P
PANEL 55-1N3-2
TR-55-1N3
PANEL 55-1L3
55-DP-TRB2
A R
E A
A
A R
E A
B
S E
E S
H E
E T
E
P b
PANEL 55-1N3-1
PANEL 55-1C3
AREA B
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER,SIGNAL, LIGHTING DEVICES AND ASSOCIATED CIRCUITRY
AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH DEMOLISHED
BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF
MILLWORK, UNLESS OTHERWISE NOTED.
3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
4. CONTRACTOR TO COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN
ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL CONFORM WITH
VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
9. REFERENCE ONE-LINE DIAGRAM ON SHEET 55EP601 FOR CONDUIT AND WIRE SIZING.
- AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
55EP101b
BLDG 55 - FLOOR 1 - AREA B
ELECTRICAL PLANSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM JPS/LLT
CONSTRUCTION
DOCUMENTS
- 1" = 10'-0"
1 BLDG 55 - FLOOR 1 - AREA B - ELECTRICAL PLAN 0' 5' 10' 20'
KEY PLAN
GENERAL NOTES
KEY PLAN
KEY NOTES
GENERAL NOTES
Revisions: Date:
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE DIAGRAM ON SHEET 55EP601
FOR ADDITIONAL INFORMATION.
EQUIPMENT TO BE ADDED. REFERENCE ONE-LINE DIAGRAM ON SHEET 55EP601 FOR
ADDITIONAL INFORMATION.
PROJECT
NORTH
PROJECT
NORTH
Tectonic Copyright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
UP
DN
FEC
FEC
F E
C
DATA
SYSTEMS
1C132
DATA
TECH
1C133
CORRIDOR
C1-57
BREAKDOWN,VERIFICATION
INVENTORY
1C135
C
F
H
B
E
G
J
8765432 8.2
3.7
H.4
6.4
D.4
5.8
A
55EP402a
55EP402a
TR
2A136
CORRIDOR
C2-12
DATA SYSTEM
2A135
INTAKE/EXIT
2A137
A R
E A
B
S E
E S
H E
E T
E P b
55EP402a
55EP402a
A R
E A
A
J Exam 2A
Soiled Utility 2A
Staff Toilet 2A
I & J Intake / Exit Interview
2A
I Exam 2A
Office, Dietician 2A
Nurse Work 2A
103a
F Exam 2A
H Exam 2A
Procedure Room 2A
C Exam 2A
Clean Supply 2A
B Exam 2A
G Exam 2A
I Exam 2A
B Exam 2A
C Exam 2A
Soiled Utility 2A
Nurse Station, Communication
2A
Mechanical 2M
H Exam 2A
F Exam 2A
G Exam 2A
Staff Toilet 2A
E Exam 2A
Waiting, General 2A
D Exam 2A
A Exam 2A
Patient Toilet 2A
D Office, Provider 2A
A Office, Provider 2A
J Office, Provider 2A
E Office, Provider 2A
F Office, Provider 2A
G Office, Provider 2A
H Office, Provider 2A
Lab 2A
J Exam - Isolation 2A
Immunization 2A
Office, Psych.
2A
C Office, Provider 2A
Clean Supply 2A
Medicine 2A
B Office, Provider 2A
A Exam 2A
Office, Social Worker
2A
Classroom/Office Diabetic
Education 2A
D Exam 2A
Storage, Wheelchair
2B
Toilet, Isolation 2A
161a
Patient Toilet 2A
Office, Psych.
2A
Office, Pharmacist 2A
Patient Toilet 2A
Staff Toilet 2A
Storage, Equipment
2B 100a
Toilet, Female 2A
Toilet, Male 2A
House Keeping 2A
Education Kiosk 2A
102a
Crash Cart
C2-13
Women's Toilet 2B
Elec.
2A
Elec.
2A
Stair #1-2
2C151
I Office, Provider 2A
Lobby
2C153
Corridor
C2-4
Corridor
C2-9
Corridor
C2-10
Corridor
C2-11 Corridor
C2-15
Corridor
C2-16
Corridor
C2-17
Corridor
C2-8
Corridor
C2-6
E Exam 2A
Nurse Work 2A
103b
Nurse Work 2A
A Intake/Exit Interview
2A
D Intake/Exit Interview
2A
C Intake/Exit Interview
2A
B Intake/Exit Interview
2A
E Intake/Exit Interview
2A
F Intake/Exit Interview
2A
H Intake/Exit Interview
2A
Scales
C2-14
Housekeeping Storage (Future) Public Elev. #4
2B
AREA A
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER,SIGNAL, LIGHTING DEVICES AND ASSOCIATED CIRCUITRY
AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH DEMOLISHED
BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF
MILLWORK, UNLESS OTHERWISE NOTED.
3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
4. CONTRACTOR TO COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN
ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL CONFORM WITH
VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
- AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
55EP102a
BLDG 55 - FLOOR 2 - AREA A
ELECTRICAL PLANSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM JPS/LLT
CONSTRUCTION
DOCUMENTS
- 1" = 10'-0"
1 BLDG 55 - FLOOR 2 - AREA A - ELECTRICAL PLAN 0' 5' 10' 20'
KEY PLAN
GENERAL NOTES
KEY PLAN
KEY NOTES
GENERAL NOTES
Revisions: Date:
PROJECT
NORTH
PROJECT
NORTH
UP
DN
Tectonic Copyright 2007
Tectonic Copyright 2007
D
F
H
B
E
G
J
K
L
M
111098.2 8.8
K.6
K.3
D.4
55EP402b
55EP402b
A R
E A
A
S E
E S
H E
E T
E P a
A R
E A
B
DATA TECH
2C145
TR
2C144
55EP402b
55EP402b
Service Elev. #3
S-1 Procedure Room
2A
Classroom/Office Diabetic
Education 2A
Storage, Wheelchair
2B
Toilet, Isolation 2A
161a
Storage, Equipment
2B 100a
House Keeping 2A
Women's Toilet 2B
Service Elev. #3
2C150
Elevator Lobby
C2-1
Corridor
C2-4
Stair #2-2
2C155
Housekeeping Storage (Future) Public Elev. #4
2B
Service Elev. #3
2C158
Vending Area 2B
Stair #2-2
2C155
Public Elev. #1
P-2
Public Elev. #2
P-3
Exam, Gastro.
2C
Procedure Room 2C
Exam, Podiatry 2C
Exam/ Office, Employee Health
2C
Staff Toilet 2C
Exam, C/P 2C
Exam, Resident 2C
Nurse Work 2C
Exam, Resident 2C
Equipment Storage
2C 131a
Office, ACOS 2C
Elec.
2C
House Keeping 2C
Medicine 2C
Office, Head Nurse 2C
Exam, Resident 2C
Exam, Resident 2C
Exam, Resident 2C
Waiting, Resident Clinic/ C&P
2C
Reception/ Module Control Unit
2C 100a
Patient Toilet 2C
Staff Toilet 2C
Office, Supervisor HAS Admin.
2C
EKG Room 2C
Exam, Resident 2C
Exam, Resident 2C
Exam, Resident 2C
Clean Supply 2C
Cast Room 2C
Exam, Cardiology 2C
Elec.
2C
Exam, Gastro.
2C
Exam, Ortho.
2C
Patient Toilet 2C
Exam, Podiatry 2C
Laboratory 2C
Staff Toilet 2C
Exam, C/P 2C
Staff Lounge 2C
Lockers 2C
153a
Secretary
C2-23
Exam, Cardiology 2C
Nurse Work 2C
Soiled Utility 2C
Exam, Ortho.
2C
Exam/ Office, Employee Health
2C
Employee Health and C/P Clerk
2C
Storage, Forms 2C
Exam, Urology 2C
Resident Clinic Reception
2C
Waiting, Specialty Clinic
2C
Staff Toilet 2C
Records 2C
151a
Mechanical 2M
Men's Toilet 2B
Waiting
C2-26
Public Elev. #1
2C148
Public Elev. #2
2C149
Stair #3-2
2C152
Corridor
C2-2
Corridor
C2-5
Elevator Lobby
C2-3
CORRIDOR
C2-24
Corridor
C2-22
Corridor
C2-20
Corridor
C2-21
Corridor
C2-18
Work Alcove
C2-19
Exam, Resident 2C
Conference Room 2C
Education 2C
Nurse Work 2C
Urology Patient Toilet
2C 120a
Exam, Urology 2C
Corridor
C2-25
Public Elev. #1
2C156
Public Elev. #2
2C157
AREA B
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER,SIGNAL, LIGHTING DEVICES AND ASSOCIATED CIRCUITRY
AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH DEMOLISHED
BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF
MILLWORK, UNLESS OTHERWISE NOTED.
3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
4. CONTRACTOR TO COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN
ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL CONFORM WITH
VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
- AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
55EP102b
BLDG 55 - FLOOR 2 - AREA B
ELECTRICAL PLANSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM JPS/LLT
CONSTRUCTION
DOCUMENTS
- 1" = 10'-0"
1 BLDG 55 - FLOOR 2 - AREA B - ELECTRICAL PLAN 0' 5' 10' 20'
KEY PLAN
KEY NOTES
GENERAL NOTES
KEY PLAN
KEY NOTES
GENERAL NOTES
Revisions: Date:
PROJECT
NORTH
PROJECT
NORTH
Tectonic Copyright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
UP
DN
FEC
FEC
F E
C
DATA
SYSTEMS
1C132
DATA
TECH
1C133
CORRIDOR
C1-57
BREAKDOWN,VERIFICATION
INVENTORY
1C135
C
F
H
B
E
G
J
876543 8.2
3.7
6.4
D.4
5.8
A
55EP403a
55EP403a
A R
E A
A
A R
E A
B
S E
E S
H E
E T
E P b
TR
3A120
PROGRAM
MANAGER
3A121
55EP403a
55EP403a
Group Room 3A
Work Area & Storage
3A
Waiting 3A
Group Room 3A
Reception 3A
Group Room 3A
Counseling A 3A
Counseling A 3A
Counseling A 3A
Counseling B 3A
Counseling B 3A
Counseling A 3A
SP
3A
SP
3A
Counseling B 3A
Counseling B 3A
Counseling B 3A
Counseling B 3A
Secretary GER 3A
Print Room 3A
Elec.
3A
Print Room 3A
Counseling, Student
3A
Counseling, Student
3A
Counseling B 3A
Counseling B 3A
Ger. Counseling 3A
Elec.
3A
Counseling A 3A
Counseling A 3A
Program Manager
GER
3A
Counseling A 3A
Patient Toilet 3A
Ger. Counseling 3A
Ger. Counseling 3A
Ger. Counseling 3A
Ger. Counseling 3A
Ger. Counseling 3A
Ger. Counseling 3A
Ger. Counseling 3A
Counseling A 3A
Counseling A 3A
Counseling B 3A
Counseling B 3A
Counseling B 3A
Counseling B 3A
Counseling A 3A
Patient Toilet 3A
Staff Toilet 3A
Lounge 3A
Patient Toilet 3A
Staff Toilet 3A
Counseling A 3A
SP
3A
P. Toilet 3A
Injection 3A
Intake 3A
Pharmacist Office 3A
Intake 3A
Counseling A 3A
Computer Kiosk 3A
DATA SYSTEM
3A
Women's Toilet 3B
Stair #1-3
2C159 Elevator Lobby
C3-1
Corridor
C3-4
Corridor
C3-6
Corridor
C3-7
Corridor
C3-8
Corridor
C3-9
Corridor
C3-11
Corridor
C3-12
Corridor
C3-13
Group Room, Large
3A
Secretary A & B 3A
Counseling B 3A
Counseling A 3A
PC Exam 3A
Counseling B 3A
P. Toilet 3A
Housekeeping 3A
Group Room Storage (Future Public Elev.) #4
3B
Oxygen 3M 1A
Corridor
C3-6
Corridor
C3-13
Corridor
C3-6
Corridor
C3-13
AREA A
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER,SIGNAL, LIGHTING DEVICES AND ASSOCIATED CIRCUITRY
AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH DEMOLISHED
BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF
MILLWORK, UNLESS OTHERWISE NOTED.
3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
4. CONTRACTOR TO COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN
ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL CONFORM WITH
VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
- AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
55EP103a
BLDG 55 - FLOOR 3 - AREA A -
ELECTRICAL PLANSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 LRL/WNM JPS/LLT
CONSTRUCTION
DOCUMENTS
- 1" = 10'-0"
1 BLDG. 55 - FLOOR 3 - AREA A - ELECTRICAL PLAN 0' 5' 10' 20'
KEY PLAN
GENERAL NOTES
KEY PLAN
KEY NOTES
GENERAL NOTES
Revisions: Date:
PROJECT
NORTH
PROJECT
NORTH