This document provides details of a federal contract solicitation for infrastructure upgrades at the St. Louis Jefferson Barracks VA Medical Center. The solicitation seeks a general contractor to provide electrical panel upgrades, power system work, bonding and grounding, UPS installations, building management system integration, HVAC assessments and work, building space reconfigurations, renovations and finishes, data center renovations, communication infrastructure upgrades including network cabling and outlets, physical security improvements, fiber infrastructure assessments and upgrades across campus buildings, and hazardous material abatement. The work locations include various campus buildings. Responses are due under Solicitation Number 36C77623R0009 issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.
View the file
Other files for this federal contract opportunity
Show all 50
Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EP703
ELECTRICAL SCHEDULES
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON
BARRACKS MO
657-21-701JB
03/31/2022 LRL/WNM WNM
CONSTRUCTION
DOCUMENTS
Revisions: Date:
LRL/WNM LLT/JPS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
EP704
ELECTRICAL SCHEDULE
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES
657-21-701JB
03/31/2022 Checker Author
CONSTRUCTION
DOCUMENTS
Revisions: Date:
LRL/WNM LLT/JPS
1. "GENERAL NOTES" APPLY TO ALL ELECTRICAL DRAWINGS. "SHEET NOTES" APPLY TO ONLY THE
SHEETS ON WHICH THEY OCCUR. "KEYNOTES" APPLY ONLY WHERE CALLED OUT.
2. ALL EQUIPMENT SHOWN IN BOLD IS TO BE PROVIDED, OR MODIFIED BY CONTRACTOR UNLESS
OTHERWISE NOTED.
3. CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FROM ALL CONTROL DEVICES TO
LUMINAIRES FOR CONTROL OF LUMINAIRES SHOWN.
4. LUMINAIRES SHOWN ON DRAWINGS FOR QUALITY AND CIRCUITING ONLY. SEE ARCHITECTURAL
DRAWINGS FOR EXACT LOCATIONS AND ELEVATIONS.
5. ALL FEEDERS AND BRANCH CIRCUITS SHALL CONTAIN AN EQUIPMENT GROUND CONDUCTOR
SIZED PER NEC TABLE 250.122. ALL WIRING IS BASED ON COPPER PER NEC TABLE
310.15(B),USING 75° C AMPACITIES FOR FEEDERS.
6. BRANCH CIRCUIT CONDUCTORS, NOT OTHERWISE IDENTIFIED SHALL BE A MINIMUM 12 AWG
FOR RUNS 70 FEET OR LESS AND A MINIMUM 10 AWG FOR RUNS GREATER THAN 70 FEET.
QUANTITY AND SIZE SHALL BE "AS REQUIRED" TO SERVE AND CONTROL DEVICE(S) OR
EQUIPMENT WITH A MAXIMUM VOLTAGE DROP OF THREE PERCENT. WHERE CONTRACTOR
CHOOSES TO RUN MORE THAN THREE CURRENT CARRYING CONDUCTORS WITHIN ONE
RACEWAY OR CABLE, CONDUCTORS SHALL BE INCREASED IN SIZE TO COMPENSATE FOR THE
DERATING REQUIRED PER NEC SECTION 310.15. CONDUCTOR AMPACITIES SHALL BE TAKEN
FROM THE 75° C COLUMN.
7. MINIMUM CONDUIT SIZE IN EXTERIOR AND UNDERGROUND LOCATIONS TO BE 1" UNLESS
NOTED OTHERWISE ON PLANS. CONDUITS FROM LUMINAIRES TO LOCAL USER CONTROL
DEVICES (SWITCHES, OCCUPANCY SENSORS, ETC.) MAY BE 3/4" OR AS INDICATED IN
SPECIFICATIONS. PROVIDE ADDITIONAL CONDUCTOR FOR UNSWITCHED "HOT" TO LIGHTING
LUMINAIRES WITH EMERGENCY POWER BATTERIES OR GENERATOR TRANSFER DEVICES.
8. WIRING FOR EMERGENCY LIGHTING CIRCUITS OR OTHER EMERGENCY EQUIPMENT SHALL BE
KEPT ENTIRELY INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT AND SHALL MEET ALL
REQUIREMENTS OF NEC SECTION 700.10.
9. CONTRACTORS SHALL PROVIDE CONDUIT AND WIRE FOR ALL CIRCUITS SHOWN ON DRAWINGS.
10. WHERE EQUIPMENT PART NUMBERS ARE SHOWN ON THESE PLANS THEY SHALL SUPERCEDE
THE REQUIREMENTS OF THE SPECIFICATIONS.
11. ALL CONDUITS SHALL BE CONCEALED UNLESS OTHERWISE NOTED.
12. COORDINATE EXACT LOCATION OF ALL OUTLETS, COMBINATION CLOCK/SPEAKERS, SPEAKER, FA DEVICES, ETC., WITH THE ARCHITECTURAL ELEVATIONS PRIOR TO COMMENCING WORK.
13. COORDINATE USE OF CEILING SPACE WITH ALL TRADES PRIOR TO COMMENCING WORK. MANY
AREAS ARE VERY CONGESTED AND REQUIRE CLOSE COORDINATION.
14. COORDINATE INSTALLATION REQUIREMENTS FOR OCCUPANCY SENSOR LIGHTING CONTROL
WITH THE MANUFACTURER. PROVIDE ALL APPURTENANCES AS REQUIRED BY THE
MANUFACTURER. PROVIDE ADDITIONAL SENSORS WHERE NECESSARY TO PROVIDE COMPLETE
COVERAGE IN EACH ROOM CONTROLLED BY OCCUPANCY SENSORS.
15. COORDINATE THE INSTALLATION OF ALL EXTERIOR OUTLET BOXES WITH THE TYPE OF
MASONRY IN EACH AREA. CUT ALL FLUTED BLOCKS SO THAT THE BOX IS INSTALLED FLUSH.
SEE ARCHITECTURAL DETAILS FOR MOUNTING REQUIREMENTS.
16. SEAL ALL CONDUIT PENETRATIONS OF FLOORS AND FIRE RATED ASSEMBLIES WITH U.L.
APPROVED MATERIALS AND METHODS TO MAINTAIN FIRE RATING. PROTECT ALL OPENINGS
FOR STEEL ELECTRICAL BOXES IN FIRE RATED WALLS WITH U.L. APPROVED MATERIALS AND
METHODS TO MAINTAIN THE FIRE INTEGRITY.
17. PROVIDE ADDITIONAL CONDUIT SLEEVES THROUGH WALLS WHERE REQUIRED FOR ROUTING
OF SIGNAL SYSTEM WIRING NOT REQUIRED TO BE RUN IN CONDUIT. EACH SLEEVE SHALL BE
DEDICATED TO EACH SIGNAL SYSTEMS. SLEEVES ROUTED THROUGH RATED WALLS SHALL BE
SEALED WITH U.L. MATERIALS AND METHODS TO MAINTAIN FIRE RATING OF WALL.
18. SEE MECHANICAL/PLUMBING DRAWINGS AND SUBMITTALS FOR EXACT LOCATIONS AND
ADDITIONAL ELECTRICAL REQUIREMENTS PRIOR TO INSTALLATION.
19. ALL LOW VOLTAGE SYSTEMS NOT RUN IN CONDUIT SHALL HAVE MINIMUM 3/4"C. ROUTED FROM
THE DEVICE THROUGH WALLS INTO THE ACCESSIBLE CEILING SPACE. NO CABLING SHALL BE
ROUTED IN THE WALLS OR INACCESSIBLE LOCATION WITHOUT CONDUIT.
20. GFCI RECEPTACLES ARE REQUIRED WITHIN 6 FT OF ALL SINKS, ON THE EXTERIOR BELOW 8FT
FROM THE FINISH FLOOR, AND ON ALL ROOFS.
21. UNLESS SPECIFICALLY SHOWN ON THESE PLANS NO STRUCTURAL MEMBER SHALL BE CUT,
NEITHER DRILLED NOR NOTCHED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM THE
STRUCTURAL ENGINEER AND THE COR.
22. CONTRATOR SHALL PROVIDE DUCT SEAL WHERE CONDUITS TRANSITION FROM AREAS THAT
CREATE TEMPERATURE DIFFERENTIAL PER NEC.
23. PRIMARY CONDUIT SWEEPS SHALL BE LONG RADIUS.
24. ALL "RMC" - RIGID METAL CONDUIT IN CONTACT WITH THE EARTH SHALL BE WRAPPED WITH
CORROSION PROTECTION TAPE PER NEC.
25. ALL J-BOXES SHALL BE MATKED WITH INDELIBLE MARKER INDICATING CONDUIT NUMBER AND
PANEL NUMBER.
26. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL 120 VOLT POWER FOR
THE MECHANICAL CONTROLS. COORDINATE EXACT REQUIREMENTS WITH THE CONTROL
CONTRACTOR.
27. ALL ELECTRICAL WORK SHALL BE COMPLETED WITH ALL PROXIMATE ELECTRICAL CIRCUITS DE-
ENERGIZED (I.E. A NEW BREAKER OR CIRCUIT CANNOT BE ADDED TO A PANEL UNLESS THE
PANEL IS COMPLETELY DE-ENERGIZED), OR THE CONTRACTOR MUST COMPLY WITH NFPA 70E
FOR WORK ON ENERGIZED SERVICE. THE VA WILL DETERMINE IF THE ELECTRICAL SERVICE
CAN BE SHUTDOWN OR IT WILL HAVE TO BE WORKED HOT DEPENDING ON THE CRITICALITY OF
THE AREA BEING AFFECTED. IF THE WORK MUST BE DONE WITH THE SERVICE LIVE, THE
CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL REQUIRED PROTECTIVE TOOLS,
EQUIPMENT AND CLOTHING, AND MUST FOLLOW THE JOB SPECIFIC WORK PLAN PREPARED BY
THE VA. WORK THAT REQUIRES SHUTTING DOWN ELECTRICAL SERVICE MAY HAVE TO BE
ACCOMPLISHED DURING OTHER THAN NORMAL DUTY HOURS.
28. WHENEVER FIRE ALARM WORK TAKES PLACE IN AN AREA THAT IS BEING REMODELED, AT THE
CONCLUSION OF THE WORK, THE FIRE ALARM CONTRACTOR SHALL TEST ALL FIRE ALARM
DEVICES WITHIN THE AREA OF REMODEL.
29. DEMOLITION PLAN/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD DRAWINGS. IF
DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY NOTIFY VA AND ENGINEER
OF SAID DISCREPANCY.
30. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF DEVICES SHALL
COMPLY WITH ALL APPROPRIATE CODES.
31. FIELD VERIFY RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO PERFORMING WORK.
32. ALL EQUIPMENT, CABLING, CONNECTORS AND APPURTENANCES SHALL BE LABELED PER THE
VA STANDARD "INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACE" VERSION 3.1
OR NEWER.
33. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER
OBSTRUCTIONS PRIOR TO INSTALLATION.
34. ALL ETHERNET CATEGORY CABLES SHALL FOLLOW THE FOLLOWING CABLE COLOR SCHEME:
DATA SHALL BLUE/TEAL, PHONES SHALL BE GRAY, AND (WIRELESS) ACCESS POINTS SHALL BE
YELLOW. COORDINATE WITH VA FOR ALL CABLING COLOR SCHEMES AS REQUIRED PRIOR TO
SUBMITTAL PROCESS.
35. TOTAL NUMBER OF DATA CONNECTIONS AND CABLING FOR WAOs AND WAPs SHALL BE
VERIFIED BY CONTRACTOR PRIOR TO ACQUISITION OF EQUIPMENT AND CABLING.
CONTRACTOR SHALL PROVIDE AN INITIAL SURVEY OF ALL AREAS TO HAVE UPGRADED WAOs
AND OTHER DATA CONNECTED EQUIPMENT IN ORDER TO VERIFY EXACT LOCATIONS AND
QUANTITIES PRIOR TO CONSTRUCTION.
36. CONTRACTOR MAY USE TEMPORARY CABLE HANGERS OR OTHER MEANS WHILE ROUTING
CABLE TO ITS INTENDED DESTINATION; HOWEVER, PRIOR TO FINAL INSTALLATION, CABLE
SHALL BE INSTALLED TO BE HOUSED WITHIN CABLE TRAY AND NOT ON TEMPORARY CABLE
HANGERS.
G E N E R A L N O T E S
THIS SHEET IS FOR REFERENCE ONLY AND ALL SYMBOLS, NOTES
AND ABBREVIATIONS MAY NOT APPLY TO THIS PROJECT
S H E E T I N D E X
ETG001 - TELECOMMUNICATIONS LEGEND, GENERAL NOTES, AND ABBREVIATIONS
01ET100 - BLDG 01 - FLOOR 0 - TELECOMMUNICATION PLANS
01ET101 - BLDG 01 - FLOOR 1 - TELECOMMUNICATION PLANS
01ET102 - BLDG 01 - FLOOR 2 - TELECOMMUNICATION PLANS
01ET103 - BLDG 01 - FLOOR 3 - TELECOMMUNICATION PLANS
02ET100 - BLDG 02 - FLOOR 0 - TELECOMMUNICATION PLANS
02ET101 - BLDG 02 - FLOOR 1 - TELECOMMUNICATION PLANS
02ET102 - BLDG 02 - FLOOR 2 - TELECOMMUNICATION PLANS
02ET103 - BLDG 02 - FLOOR 3 - TELECOMMUNICATION PLANS
03ET100 - BLDG 03 - FLOOR 0 - TELECOMMUNICATIONS PLAN
03ET101 - BLDG 03 - FLOOR 1 - TELECOMMUNICATIONS PLAN
03ET102 - BLDG 03 - FLOOR 2 - TELECOMMUNICATIONS PLAN
03TET101 - BLDG 03T - FLOOR 1 - TELECOMMUNICATIONS PLAN
18ET100 - BLDG 18 - FLOOR 0 - TELECOMMUNICATIONS PLAN
18ET101 - BLDG 18 - FLOOR 1 - TELECOMMUNICATIONS PLAN
18ET102 - BLDG 18 - FLOOR 2 - TELECOMMUNICATIONS PLAN
18ET103 - BLDG 18 - FLOOR 3 - TELECOMMUNICATIONS PLAN
23ET100 - BLDG 23 - FLOOR 0 - TELECOMMUNICATIONS PLAN
23ET101 - BLDG 23 - FLOOR 1 - TELECOMMUNICATIONS PLAN
24ET100 - BLDG 24 - FLOOR 0 - TELECOMMUNICATIONS PLAN
24ET101 - BLDG 24 - FLOOR 1 - TELECOMMUNICATIONS PLAN
24ET102 - BLDG 24 - FLOOR 2 - TELECOMMUNICATIONS PLAN
25ET100 - BLDG 25 - FLOOR 0 - TELECOMMUNICATIONS PLAN
25ET101 - BLDG 25 - FLOOR 1 - TELECOMMUNICATIONS PLAN
25ET102 - BLDG 25 - FLOOR 2 - TELECOMMUNICATIONS PLAN
25ET103 - BLDG 25 - FLOOR 3 - TELECOMMUNICATIONS PLAN
25ET104 - BLDG 25 - PENTHOUSE - TELECOMMUNICATIONS PLAN
51ET100a - BLDG 51 - FLOOR 0 - AREA A & C - TELECOMMUNICATIONS PLAN 51ET100b - BLDG 51 - FLOOR 0 - AREA E - TELECOMMUNICATIONS PLAN 51ET101a - BLDG 51 - FLOOR 1 - AREA A - TELECOMMUNICATIONS PLAN 51ET101b - BLDG 51 - FLOOR 1 - AREA B TELECOMMUNICATIONS PLAN 51ET101c - BLDG 51 - FLOOR 1 - AREA C TELECOMMUNICATIONS PLAN 51ET101d - BLDG 51 - FLOOR 1 - AREA D TELECOMMUNICATIONS PLAN 51ET101e- BLDG 51 - FLOOR 1 - AREA E TELECOMMUNICATIONS PLAN
51TET101 - BLDG 51T - FLOOR 1 - TELECOMMUNICATIONS PLAN
52ET100 - BLDG 52 - FLOOR 0 - TELECOMMUNICATIONS PLAN
52ET101 - BLDG 52 - FLOOR 1 - TELECOMMUNICATIONS PLAN
52ET102 - BLDG 52 - FLOOR 2 - TELECOMMUNICATIONS PLAN
53ET100 - BLDG 53 - FLOOR 0 - TELECOMMUNICATIONS PLAN
53ET101 - BLDG 53 - FLOOR 1 - TELECOMMUNICATIONS PLAN
53ET102 - BLDG 53 - FLOOR 2 - TELECOMMUNICATIONS PLAN
53ET103 - BLDG 53 - PENTHOUSE - TELECOMMUNICATIONS PLAN
53TET101 - BLDG 53T - FLOOR 1 - TELECOMMUNICATIONS PLAN
54ET100 - BLDG 54 - FLOOR 0 - TELECOMMUNICATIONS PLAN
54ET101 - BLDG 54 - FLOOR 1 - TELECOMMUNICATIONS PLAN
54ET102 - BLDG 54 - FLOOR 2 - TELECOMMUNICATIONS PLAN
55ET101a - BLDG 55 - FLOOR 1 - AREA A - TELECOMMUNICATIONS PLAN 55ET101b - BLDG 55 - FLOOR 1 - AREA B - TELECOMMUNICATIONS PLAN 55ET102a - BLDG 55 - FLOOR 2 - AREA A - TELECOMMUNICATIONS PLAN 55ET102b - BLDG 55 - FLOOR 2 - AREA B - TELECOMMUNICATIONS PLAN 55ET103a - BLDG 55 - FLOOR 3 - AREA A - TELECOMMUNICATIONS PLAN 55ET103b - BLDG 55 - FLOOR 3 - AREA B - TELECOMMUNICATIONS PLAN
56ET100 - BLDG 56 - FLOOR 0 - TELECOMMUNICATIONS PLAN
56ET101 - BLDG 56 - FLOOR 1 - TELECOMMUNICATIONS PLAN
56ET102 - BLDG 56 - FLOOR 2 - TELECOMMUNICATIONS PLAN
56ET103 - BLDG 56 - FLOOR 3 - TELECOMMUNICATIONS PLAN
57ET101 - BLDG 57 - FLOOR 1 - TELECOMMUNICATIONS PLAN
58ET101 - BLDG 58 - FLOOR 1 - TELECOMMUNICATIONS PLAN
60ET101 - BLDG 60 - FLOOR 1 - TELECOMMUNICATIONS PLAN
60TET101 - BLDG 60T - FLOOR 1 - TELECOMMUNICATIONS PLAN
75ET101 - BLDG 75 - FLOOR 1 - TELECOMMUNICATIONS PLAN
75ET102 - BLDG 75 - MEZZANINE - TELECOMMUNICATIONS PLAN
CET101 - BLDG 1-24 - FLOOR 0 - CORRIDOR WIRELESS ACCESS POINT
TELECOMMUNICATIONS PLAN
CET102 - BLDG 1-24 - FLOOR 1 - CORRIDOR WIRELESS ACCESS POINT
TELECOMMUNICATIONS PLAN
CET103 - BLDG 23-51-65 - FLOOR 1 - CORRIDOR WIRELESS ACCESS POINT
TELECOMMUNICATIONS PLAN
CET104 - BLDG 51-52-53-60-61 - FLOOR 1 - CORRIDOR WIRELESS ACCESS POINT
TELECOMMUNICATIONS PLAN
01ET400a - BLDG 01 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 01ET400b - BLDG 01 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 01ET401a - BLDG 01 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 01ET401b - BLDG 01 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
01ET402 - BLDG 01 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
01ET403a - BLDG 01 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS 01ET403b - BLDG 01 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS
02ET400 - BLDG 02 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
02ET401 - BLDG 02 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
02ET402 - BLDG 02 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
02ET403 - BLDG 02 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS
03ET400 - BLDG 03 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
03ET401 - BLDG 03 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
03ET402 - BLDG 03 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
03TET401 - BLDG 03T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
18ET400 - BLDG 18 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
18ET401 - BLDG 18 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
18ET402 - BLDG 18 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
18ET403 - BLDG 18 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS
23ET400 - BLDG 23 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
23ET401 - BLDG 23 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
24ET400 - BLDG 24 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
24ET401 - BLDG 24 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
24ET402 - BLDG 24 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
25ET401 - BLDG 25 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
25ET402 - BLDG 25 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
25ET403 - BLDG 25 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS
51ET400 - BLDG 51 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
51ET401a - BLDG 51 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 51ET401b - BLDG 51 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 51ET401c - BLDG 51 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
51TET401 - BLDG 51T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
52ET400 - BLDG 52 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
52ET401a - BLDG 52 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 52ET401b - BLDG 52 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 52ET401c - BLDG 52 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 52ET402a - BLDG 52 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 52ET402b - BLDG 52 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 53ET400a - BLDG 53 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 53ET400b - BLDG 53 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 53ET401a - BLDG 53 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 53ET401b - BLDG 53 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
53ET402 - BLDG 53 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
53TET401 - BLDG 53T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
55ET401a - BLDG 55 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 55ET401b - BLDG 55 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 55ET401c - BLDG 55 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 55ET402a - BLDG 55 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 55ET402b - BLDG 55 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 55ET403a - BLDG 55 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS 55ET403b - BLDG 55 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS
56ET400 - BLDG 56 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS
56ET401 - BLDG 56 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
56ET402 - BLDG 56 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS
56ET403 - BLDG 56 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS
57ET401a - BLDG 57 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 57ET401b - BLDG 57 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 58ET401a - BLDG 58 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 58ET401b - BLDG 58 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
60ET401 - BLDG 60 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
60TET401 - BLDG 60T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
75ET401 - BLDG 75 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS
ET501 - TELECOMMUNICATIONS DETAILS
ET502 - TELECOMMUNICATIONS DETAILS
ET503 - TELECOMMUNICATIONS DETAILS
ET601 - FIBER OPTIC NETWORK DIAGRAM
ET602 - FIBER OPTIC NETWORK DIAGRAM
ET603 - FIBER OPTIC NETWORK DIAGRAM
ET701 - TELECOMMUNICATIONS SCHEDULES
FLEXIBLE CONDUIT
CONDUIT TURNED UP OR TOWARD
CONDUIT TURNED DOWN OR AWAY
CONDUIT CAPPED
T E L E C O M M U N I C A T I O N S L E G E N D
COMMUNICATION OUTLETS
FLOOR MOUNTED TELECOMMUNICATIONS OUTLET.
# = INDICATES QUANTITY OF VOICE AND DATA JACKS
WALL MOUNTED TELECOMMUNICATIONS OUTLET. 18" AFF UON
# = INDICATES QUANTITY OF VOICE AND DATA JACKS
OUTLET; LETTER INDICATES AS FOLLOWS:
A=AUDIO V=VIDEO I=INTERCOM
OUTLET, TELEVISION
BLANK = 4 11/16" MASTER ANTENNA OUTLET BOX WITH BLANK
COVER, MTD. 18" AFF UNLESS OTHERWISE NOTED.
C = CAMERA (CCTV SYSTEM), MTD 18" AFF
M = MONITOR (CCTV SYSTEM).
TELECOMMUNICATIONS OUTLET, SPECIAL PURPOSE.
REFERENCE KEY NOTES ON PLANS FOR ADDITIONAL
INFORMATION.
S
WAP
A/V
S C
C
TGB
FNC
FIBEROPTICS LINE = FO
TELEPHONE LINE = T
SPEAKER, CEILING MOUNTED
SPEAKER, WALL MOUNTED, MTD. 7'-6" AFF UON.
RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" AFF UON.
M = SPEAKER PROGRAM SELECTOR SWITCH & VOLUME
CONTROL
3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD.
4'-6" AFF.
REMOTE DICTATING OUTLET MTD 1'-6" AFF. UON.
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL
OPERATION OF INSTRUMENT & TYPE REQUIRED).
S = STAFF STATION
WIRELESS ACCESS PORT
WALL MOUNTED SPEAKER/CLOCK COMBINATION
WALL CLOCK
CABLE TRAY
RECESSED AUDIO FLOOR BACK BOX, OUTLET AND CONDUIT
TELECOMMUNICATIONS SYSTEMS BONDING BUSBAR
FIBER OPTIC NETWORK CARD
COMMUNICATION
SECTION A
XXX
SECTION LETTER
SHEET WHERE
SECTION IS TAKEN
FROM
A
XXX
SECTION LETTER
SHEET WHERE
SECTION IS TAKEN
FROM
XXX
DETAIL NUMBER
SHEET ON WHICH
DETAIL APPEARS
DETAIL AREA
SCALE
XXXNG
CONDUIT & WIRE TAG
(REFER TO CONDUIT
AND WIRE SCHEDULE)
XX FAULT CURRENT TAG
(3 PH, SYM AMPS)
1 KEY NOTE
XXX
FIGURE OR PHOTO
DETAIL NUMBER
IF PHOTO, ARROW
DENOTES DIRECTION
TAKEN
SHEET WHERE DETAIL
IS TAKEN FROM
DETAIL/PLAN
DETAIL/PLAN NUMBER
G E N E R A L S Y M B O L S
AFC
AFG
AF
AFCI
AFF
AIC
AHJ
ATS
C
CATV
CB
CCTV
CL
CO
DDC
DP
EC
EL
EMER
EN
EMT
ER
EX
FAAP
FACP
FCIO
FOIC
GFCI
GFP
GND
HTR
IG
IMC
J-BOX
LCP
MCA
MCB
MCC
MDP
MLO
MS
MTD
NAC
NEC
NFC
NIC
NL
NTS
OC
OH
OS
PIV
PNL
PS
PVC
R
RECPT
RMC
SAC
SB, SWBDm
SG
SM
SPD
TEL
TR
TYP
UON
UL
UG
VD
VFD
W
WP
XFMR
ABOVE FINISHED COUNTER
ABOVE FINISHED GRADE
AMP FRAME
ARC FLASH CIRCUIT INTERRUPTER
ABOVE FINISHED FLOOR
AMPERE INTERRUPTING CAPACITY
AUTHORITY HAVING JURISDICTION
AUTOMATIC TRANSFER SWITCH
CONDUIT OR CEILING
COMMUNITY ANTENNA TELEVISION
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CONNECTOR LIGHTING
CONDUIT ONLY
DIRECT DIGITAL CONTROLS
DISTRIBUTION PANELBOARD
EMPTY CONDUIT
ELEVATION
EMERGENCY
EXISTING IN NEW LOCATION
ELECTRICAL METALLIC TUBING
EXISTING TO REMAIN
EXISTING
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FURNISHED BY CONTRACTOR, INSTALLED
BY OWNER
FURNISHED BY OWNER, INSTALLED BY
CONTRACTOR
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT PROTECTION
GROUND
HEATER
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
JUNCTION BOX
LIGHTING CONTROL PANEL
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
MAIN LUGS ONLY
MOTOR STARTER
MOUNTED
NOTIFICATION APPLIANCE CABINET
NATIONAL ELECTRICAL CODE
NOT FOR CONSTRUCTION
NOT IN CONTRACT
NIGHT LIGHT
NOT TO SCALE
ON CENTER
OVERHEAD
OCCUPANCY SENSOR
POST INDICATOR VALVE
PANEL
POWER SUPPLY
POLYVINYL CHLORIDE
EXISTING TO BE REMOVED
RECEPTACLE
RIGID METAL CONDUIT
SMALL APPLIANCE CIRCUIT
SWITCHBOARD
SWITCHGEAR
SMART METER
SURGE PROTECTIVE DEVICE
TELEPHONE
TAMPER RESISTANT
TYPICAL
UNLESS OTHERWISE NOTED
UNDERWRITERS LABORATORIES
UNDERGROUND
VOLTAGE DROP
VARIABLE FREQUENCY DRIVE
WEATHERPROOF (WHILE IN USE)
WEATHERPROOF
TRANSFORMER
A B B R E V I A T I O N S
AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL C-CHIME H-HORN K-KLAXON
L-LISTEN M-MICROPHONE S-SOUNDER S-SPEAKER Z-BUZZER
KEYPAD DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR WALL CALL
M-MAG STRIP P-PROXIMITY S-SMART CARD T-TOKEN
D DOOR CONTACT
ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DEADBOLT H-HYBRID L-LATCH SET S-STRIKE
INTERCOM; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
M-MASTER S-SUBSTATION
MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC
PUSH BUTTON; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL PUSH D-DURESS P-PANIC R-DOOR OPENER X-REQUEST FOR EXIT
SECURITY ACCESS, ANNUNCIATOR PANEL
SECURITY ACCESS, VIDEO CAMERA WITH LENS
SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW
SECURITY ACCESS, PANNING CAMERA TRAVERSE ANGLE
SAFETY AND SECURITY
M = MOUNTING FOR ALL SAFETY AND SECURITY SYMBOLS:
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
NURSE CALL
FIRE ALARM
PS
WG
NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER TOP UNLESS
OTHERWISE NOTED.
NURSE CALL TERMINAL CABINET.
NURSE CALL STATION.
D E
P S
U
= DUPLICATE PATIENT STATIONS (SEPARATE INDICATORS AT
MASTER STATION) MTD 5'-0" AFF UNLESS OTHERWISE NOTED
= DUTY STATION. MTD 5'-0" AFF UNLESS OTHERWISE NOTED
= STATION MTD 6'-0" AFF FOR SHOWER LOCATION, MTD 4'-6" AFF
FOR TUB LOCATION, & MTD 3'-0" AFF FOR TOILET LOCATION,UON
= PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH
= AUDIO VISUAL WALL STATION (STAFF) MTD 5'-0" AFF UNLESS
OTHERWISE NOTED
= UTILITY CALL STATION, MTD 5'-0" AFF UNLESS OTHERWISE NOTED
NURSE CALL STATION.
D I
= NURSE'S CALL DOME LIGHT (SUFFIX INDICATES NO. OF LAMP)
MTD 6" ABOVE DOOR
= CORRIDOOR DOME LIGHT.
= AUXILIARY INTERSECTIONAL DOME LIGHT.
NIGHT LIGHT
PATIENT BED OUTLETB
POWER SUPPLY WITH BATTERY BACKUP
WANDER GUARD
R
C
C
F
K
A
ADDRESSABLE RELAY
ALARM, FIRE, COMMUNICATOR
ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:
FACC = CENTRAL CONSOLE FACP = CONTROL PANEL
MFACP = MASTER CONTROL PANEL FAAP = ANNUNCIATOR PANEL
ALARM, FIRE; LETTERS INDICATE AS FOLLOWS:
BATT = BATTERIES CHR = CHARGER FAR = RECORDER
ALARM, FIRE, VALVE SUPERVISORY SWITCH.
ALARM, FIRE, TERMINAL CABINET.
ALARM, FIRE, POST INDICATOR VALVE.
ALARM, TRANSPONDER OR TRANSMITTER.
ALARM, FIRE, MANUAL PULL STATION
C = WITH CLEAR PLASTIC COVER
ALARM, HORN/LIGHT, ONE ASSEMBLY
C = WITH CHIME
ALARM, HORN/LIGHT, SEPARATE ASSEMBLY
ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE
ALARM, MANUAL CONTROL
ALARM, MINI HORN
ALARM, SPRINKLER SYSTEM WATER FLOW BELL
ALARM, VOICE COMMUNICATION PANEL
ALARM, TAMPER SWITCH
DETECTION, GAS
C = CARBON DIOXIDE TRANSMITTER
DETECTOR, FLOW SWITCH
DETECTOR, HEAT
DETECTOR, SMOKE
DETECTOR, SMOKE, FOR DUCT
ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET
CITY FIRE ALARM MASTER STATION MTD 5'-6" AFF UNLESS NOTED.
FIRE ALARM TRANSMITTER (BASE LOOP) NUMERALS DENOTE CODE.
FIRE ALARM TROUBLE TRANSMITTER (BASE LOOP) NUMERALS
DENOTE CODE.
FIRE SPRINKLE WATER FLOW SWITCH
KITCHEN HOOD FIRE SUPPRESSION SYSTEM
REMOTE ANNUNCIATOR
SPECIAL SYSTEMS
P
AUDIO CONTROLLER
PRESSURE BEACON
PRESSURE DEVICE
SLEEVE WITH BUSHING FIRESTOP AND INNERDUCT FOR
FIBER
SLEEVE OR CONDUIT WITH BUSHING FIRESTOP AND
INNERDUCT FOR FIBER
A
FAC
BATT
FACC
OSY
FATC
PIV
FTR
P
C
M
WB
CP
TS
HD
DH
FAT
2-4-6
2-4-6
FTT
FO
T
S X
S X
R M
R M
NCS
NCT
N
N
M
T
M
M
M
T
M
T
M
T
M
T
M
T
AP
180o
60o
ALARM, CHECK VALVE
ALARM, GONG
ALARM, HORN/LIGHT, ONE ASSEMBLY
SCCP DETECTION, SMOKE CONTROL AND PRESSURE PANEL
EPO
DETECTION SWITCH, ABORT
DETECTION SWITCH, VALVE TAMPER
DETECTOR, FLAME FLICKER
R/T
HD
DETECTOR, HEAT; LETTER INDICATED AS FOLLOWS:
R/T= COMBINATION F= FIXED TEMPERATURE
R/C= RATE COMPENSATION R= RATE OF RISE
H
DETECTOR; LETTER INDICATED AS FOLLOWS:
BLANK= SMOKE DETECTOR
H= HEAT SMOKE
I= IONIZATION SMOKE
P=PHOTOELECTRIC SMOKE
IH= IONIZATION AND HEAT SMOKE
IP= IONIZATION AND PHOTOELECTRIC SMOKE
PH= PHOTOELECTRIC AND HEAT SMOKE
IPH= IONIZATION, PHOTOELECTRIC HEAT
DETECTOR, SWITCH LEVEL
FS FIRE ALARM STATION, MANUAL PULL
FA FIRE ALARM LINE = FA
BI-STATIC BEAM SENSOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T= TECHNOLOGY/TYPE
I-INFRARED M-MICROWAVE
F=FUNCTION
RX=RECEIVE TX-TRANSMIT
M
TF
BIOMETRICS ACCESS CONTROL DEVICE; LETTER IDNICATED AS FOLLOWS:
M=MOUNT
C-CEILING
T= TECHNOLOGY/TYPE
F-FINGER PRINT H-HAND GEOMETRY I-EYE IRIS
R-EYE RETINA V-VOICE
M
T
CARD READER WITH TIME AND ATTENDANCE; LETTER INDICAED AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
M
CENTRAL PROCESSING UNIT
CONTROL PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BURGLAR D-DOOR F-FIRE P-PERIMETER
M
T
EXIT DEVICE; LETTER INDICATED AS FOLLOWS:
T=TECHNOLOGY/TYPE
D-DELAYED EGRESS E-ELECTRIFIED M-MECHANICAL X-HIGH SECURITY
T
FIBER OPTIC MODULE; LETTER INDICATED AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
R-RECIEVER T-TRANSCEIVER TX-TRANSMITTER
M
T
FIELD PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
M
T
GLASS BREAKAGE SENSOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-AUDIO S-SHOCK
M
T
MONITOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DATA G-GRAPHIC M-MULTISCREEN V-VIDEO
M
T
RECORDER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-AUDIO D-DIGITAL V-VIDEO
M
T
SECURITY ACCESS, BUZZER. MTD 1'-6" {457mm} AFF UNLESS OTHERWISE NOTED
SECURITY ACCESS, "X" INDICATES THE TYPE, PROVIDE SCHEDULE OR LEGENDX
SECURITY ACCESS, HORN OR SIREN
SECURITY ACCESS, OUTDOOR MICROWAVE TRANSMISSION UNIT
SECURITY ACCESS, PANIC ALARM
O
X
SECURITY ACCESS, VIDEO CAMERA WITH LENS
M = MOTION DETECTOR
PZ = MOTION DETECTOR WITH PAN AND ZOOM
PTZ = MOTION DETECTOR WITH PAN, TILT, AND ZOOM
M PTZ
SECURITY ACCESS, VOLUMETRIC SENSOR
SECURITY SCREEN WITH ALARM; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYPE
B-BIND S-SHADE
T
SECURITY WINDOW SCREEN; LETTER INDICATED AS FOLLOWS:
T=TECHNOLOGY/TYPE
B-BLIND
T
VIDEO CONTROL KEYBOARD
VIDEO MOTION DETECTOR
SECURITY ACCESS, SENSOR, BURIED VEHICULAR
SECURITY ACCESS, SWITCH, BALANCED MAGNETIC CONTROL
CODE ONE CONTROL AND ALARM STATION. MTD 5'-0" [1524mm] AFF UNLESS
OTHERWISE NOTED.
NIP
CODE ONE TERMINAL CABINET.NIT
CODE ONE ANNUNCIATOR PANEL.NIA
CODE ONE BEDSIDE STATION.NI
CODE ONE DUTY STATION, MTD 5'-0" [1524mm] AFF UNLESS OTHERWISE NOTED.NID
X
V I
H
CONDUIT OR EQUIPMENT TO BE REMOVED
CONDUIT ROUTED UNDERGROUND OR
UNDERFLOOR
CONDUIT CONCEILED IN WALL, CEILING,
OR UNDER FLOOR WHERE POSSIBLE,
OTHERWISE EXPOSED
EXISTING CONDUIT EXPOSED, EXISTING
TO REMAIN UNLESS OTHERWISE NOTED
EXISTING CONDUIT ROUTED UNDERGROUND,
EXISTING TO REMAIN UNLESS OTHERWISE
NOTED
EXTRA-HARD USAGE FLEXIBLE CORD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES ETG001
LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
03/31/2022
TELECOMMUNICATIONS LEGEND, GENERAL
NOTES, AND ABBREVIATIONS
Revisions: Date: 301 OF 435
DN
UP
DN
2 2
2 2
2 2
4160 VO
LTS
DUST CO
LLECTO
R
LIQ UEFIED PETRO LEUM G AS
FLAM M ABLE G AS 2
TRASH COM
PACTO
R
P
SILVERBUILDING 1 23
VA PO
LICE
E
LECTRIC ACCESS
TRANSFO
RM
ER
TRANSFO
RM
ER
TRANSFO
RM
ER
HVAC UNIT
E
LECTRIC PANEL
HVAC UNIT
S&C PAD M
O
UNTED G
EAR
CATALO
G
# 55152-C3DGIG
2P1V M
O
DEL# PM
H-9
EE13299 SG
-52
13278
BUILDING
A
A
A.1
A.1 A.3A.2 B C.1
D.2
D.2C
D.1
D.1D
E.1
E
F
F
G
G
H
H
J.1
J
H.2 J.2
K
L M
M
N
N
O
O
P
P Q
R.3
R.1
R.1 R.2 S U
V.3
V.3T V.2V V.1
A.4 B.1 B.2 C.2 R.4 T.1 T.2 U.1
G.1 H.1 K.2
N.1
N.1
R
01ET400a
01ET400a
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1 WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
DUPLICATION
GE09A
OFFICE
GE10A
STORAGE
GE10
OI&T
GE11
MAIL RM.
GE09
CORRIDOR
H001
STORAGE
GE07
STORAGE
GE12
OI&T
GE13
TOILET
GE05
STORAGE
GE04
STORAGE
GE03
VEST.
GE02
STORAGE
GE01
STAIRWELL #1
S001
LINEN CHUTE
GE15
CORRIDOR
H002
STORAGE
GE16
CORRIDOR
H003
STORAGE
GE18
STORAGE
GE18A
STORAGE
GE18B
ELEVATOR #2
E2
HAC
GE35
HAC
GE34
RECEIVING
GE17
STORAGE
GE19
CORRIDOR
H004
OFFICE
GE21
OFFICE
GE20
PREP. RM.
GE32
TOILET
GE22
TOILET
GE23
CORRIDOR
GE31
CORRIDOR
H005
DECONTAMINATION AREA
GE29
MECH. RM.
GE26
HAC
GC09
COOLER
GC10A
MECH. RM.
GC10B
TOILET, MEN
GC08
HAC
GC07A
CORRIDOR
H008
FILE RM.
GC03
STORAGE
GC02
UTILITY RM.
GC01
TRANSFORMER RM.
GC16A
MECH. RM.
GC13
OI&T
GC12
FACILITIES ENGINEERING
GC17C
CORRIDOR
H007
STORAGE
GC17BELECTRIC CARTS
GC17E
SERVICE RM.
GC22
STORAGE
GC21
STORAGE
GC20
STORAGE
GC19
HAC
GC17G
PATRIOT CAFE
GC17
PUMP RM.
GC18
IV RM.
GW05A
UNLOADING AREA
GW04A
PHARMACY
GW04
OFFICE
GW06
PHARMACY
GW07
DISPENSING
GW08
MECH. RM.
GW03
WAITING RM.
GW02
CORRIDOR
H010
PRESCRIPTION INTAKE
GW09
WAITING RM.
GW09A
CHECK-IN
GW10B
HAC
GW10A
STAIRWELL #3
S003
STORAGE
GW19
OFFICE
GW10
MECH. RM.
GW11
LOCKER RM., FEMALE
GW17
OFFICE
GW12
OFFICE
GW12A
OFFICE
GW12B
OFFICE
GW12C
FLUID STORAGE
GW16
TELEMED
GW15
STORAGE
GW13
TOILET
GE14
PHARMACY SUPPLIES
GW05
ELEVATOR #1
E02
CORRIDOR
H011
STORAGE
GW19A
CORRIDOR
H009
PHARMACY VAULT
GW14
TOILET, FEMALE
GW18
MECH.
GC17A
STORAGE
GC17D
ELEC. CLOSET
GC15
ELEC. SUPPLY
GC15A
OI&T
GC12A
OI&T
GC11B
OI&T
GC11A
CORRIDOR
H006
UTILITY RM.
GE06
HAC
GE24
STEAM RM.
GE28
STORAGE
GE32A
CANTEEN
GC17F
D.W.
E3
CHASE
CH-C-1
CHASE
CH-W-1
UNDER CONSTRUCTION
GW17A
STAIRWELL #4
S004
WAP 1
WAP 1
WAP 1
2 2
WAP 1
WAP 1
2 2
10.1
8.1
TYP
STORAGE
GE19
01ET400b
01ET400b
Hand Hole
SIDE-B FIBER-
OPTIC BACKBONE:
REFERENCE
COMMUNICATION
SHEETS FOR
ADDITIONAL
INFORMATION
REGARDING
HANDHOLE,
CONDUIT, FIBER-
OPTIC CABLING,
AND RACEWAY
INFORMATION
B-SIDE:
TO TR 1E15
FROM GC12 TDU
TYP
B-SIDE:
TO TR 2C10A,
E303, AND 3C13
FROM GC12 TDU
B-SIDE:
TO TR C102D
FROM GC12 TDU
EXISTING SIDE-A FIBER-OPTIC BACKBONE
BUILDING ENTRY POINT (APPROXIMATE
LOCATION). ROUTE FIBER-OPTIC CABLES TO TRs
AS INDICATED ON COMMUNICATIONS DRAWINGS;
REFERENCE COMMUNICATIONS DRAWINGS FOR
ALL FIBER-OPTIC CABLING, RACEWAY TYPES,
SPECIFICATIONS, AND RATINGS. REFERENCE KEY
NOTES ON THIS SHEET REGARDING CABLE TRAY
AND VERTICAL/HORIZONTAL ROUTING FOR
ADDITIONAL FIBER BACKBONE CABLING
REQUIREMENTS.
DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE
SERVED FROM TELECOMMUNICATION ROOM GC12.
ALL BACKBONE CABLING ROUTES ARE
DIAGRAMMATICAL; CONTRACTOR SHALL ENSURE A-
SIDE AND B-SIDE ROUTING IS AS DIVERSE AS
PRACTICAL. REFERENCE COMMUNICATIONS
DRAWINGS FOR ALL REQUIRED FIBER-OPTIC
CABLING.
TYP
BLDG 01
AREA OF WORK
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED SHALL
BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF REQUIRED.
COORDINATE WITH ARCHITECTURAL DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE UPGRADED WITH CAT6A PORTS AND CABLE QUANTITIES
INDICATED, UNLESS NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED BY EXISTING CABLING AS CONDUIT FILL ALLOWS.
PROVIDE ADDITIONAL RACEWAYS TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY
INDICATED.
7. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT6A CABLING FROM EACH WAO (WORK AREA OUTLET) TO ITS
RESPECTIVE TR.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT CONDUIT RUNS, OR CONDUIT CONTAINING BENDS
TOTALING MORE THAN 180 DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR PARTITION TYPES
AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD; DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING TRANSPORTATION, FOR ALL WORK TO DESIRED VA
STORAGE LOCATION. COORDINATE WITH VA AS REQUIRED.
12. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
13. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE DIAGRAMMATICAL.
COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS, ARCHITECTURAL FEATURES,
MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER OBSTRUCTIONS PRIOR TO
INSTALLATION.
- 1/16" = 1'-0"
1 BLDG 01 - FLOOR 0 - TELECOMMUNICATIONS PLAN
PROJECT
NORTH
0' 8' 16' 32'
KEY PLAN
PROJECT
NORTH
KEY NOTES
GENERAL NOTES
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE EXISTING TELECOMMUNICATIONS OUTLET;
EXISTING OUTLET CONDUIT SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE SHEET DETAIL '1' ON SHEET ET503 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH CAT6A CABLING.
REMOVE AND REPLACE EXISTING CABLE TRAY IN THE AREAS SHOWN AS REQUIRED; IF CABLE TRAY IS NON-EXISTENT, PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL ‘6’ ON SHEET ET503 AND TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET ET701. WHERE WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO CONDUIT SLEEVES [(2) 4”, MINIMUM] WITH APPROPRIATE FIRE-PROOFING AND CAULKING TO PASS THROUGH WALL WHERE EXISTING CABLE TRAY AND/OR SLEEVES ARE DISCOVERED, EVALUATE CONDITION AND RACEWAY CAPACITY; IF CABLE TRAY AND/OR SLEEVES APPEAR TO BE REUSABLE, NOTIFY
COR FOR POSSIBLE REUSE.
FIBER-OPTIC CABLE VERTICAL ROUTING; COORDINATE EXACT LOCATIONS PRIOR TO INSTALLATION. UTILIZE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AND ALL REQUIRED APPURTENANCES AS REQUIRED. REFERENCE DETAIL 2 ON SHEET ET503 FOR ADDITIONAL
INFORMATION.
FIBER-OPTIC CABLE HORIZONTAL ROUTING SHALL BE CONCEALED ABOVE DROP CEILING WHEREVER POSSIBLE. UTILIZE CABLE TRAY AS APPLICABLE. PROVIDE CONDUIT SLEEVE WITH FIREPROOFING AS REQUIRED WHERE WALL PENETRATIONS ARE REQUIRED.
REFERENCE DETAIL 2 ON SHEET ET503 FOR ADDITIONAL INFORMATION.
UTILIZE EXISTING PACS SECURITY HEAD END LOCATION FOR NEW OR RELOCATED PACS SECURITY TR EQUIPMENT. UPGRADE OR MODIFY EXISTING HEAD END LOCATION AS REQUIRED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL TR PACS SECURITY SYSTEM.
PROVIDE EQUIPMENT, RACEWAYS, AND CABLING AS REQUIRED. COORDINATE WITH VA PRIOR TO CONSTRUCTION. CONTRACTOR SHALL
VERIFY EXACT HEAD END LOCATION AS REQUIRED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 01ET100
BLDG 01 - FLOOR 0 -
TELECOMMUNICATIONS PLAN 01
LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
03/31/2022
Revisions: Date:
2 2
2 2
2 2
4160 VO
LTS
DUST CO
LLECTO
R
LIQ UEFIED PETRO LEUM G AS
FLAM M ABLE G AS 2
TRASH COM
PACTO
R
P
SILVERBUILDING 1 23
VA PO
LICE
E
LECTRIC ACCESS
TRANSFO
RM
ER
TRANSFO
RM
ER
TRANSFO
RM
ER
HVAC UNIT
E
LECTRIC PANEL
HVAC UNIT
S&C PAD M
O
UNTED G
EAR
CATALO
G
# 55152-C3DGIG
2P1V M
O
DEL# PM
H-9
EE13299 SG
-52
13278
BUILDING
CONNECTING CORRIDORS
TO BUILDING 23
CONNECTING CORRIDORS
TO BUILDING 24
UP
UP
UP
UP
EXTERIOR
SURFACE
BASEMENT
LEVEL
TRENCH
STAIRS TO
BASEMENT
LEVEL
ROOF
BELOW
A
A
A.1
A.1 A.3A.2 B C.1
D.2
D.2C
D.1
D.1D
E.1
E
F
F
G
G
H
H
J.1
J
H.2 J.2
K
L M
M
N
N
O
O
P
P Q
R.3
R.1
R.1 R.2
S U
V.3
V.3T V.2V V.1
A.4 B.1 B.2 C.2 R.4 T.1 T.2 U.1
4.7
8.1
10.1
G.1
G.1 K.2
N.1
N.1
R
01ET401a
01ET401b
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 4
WAP 1
WAP 4
01ET401a
01ET401a
OFFICE
C105
EXISTING DISPATCH
1E11A
GROUP ROOM
1W08B
GROUP ROOM
1W08A
OFFICE
1W09
VEST.
1W08
TOILET
1W07A
WAITING ROOM
1W07OFFICE
1W10
OFFICE
1W11A
CORRIDOR
H119
OFFICE
1W06
TOILET
1W05
VEST.
1W06A
OFFICE
1W11B
CONSULT
1W12
OFFICE
1W04
CORRIDOR
1W13
CONSULT
1W03
MECH. RM.
1W02
CONSULT
1W14
OFFICE
1W15
ELEV 1
E1
MECH
1W01
CORRIDOR
H116
OFFICE
1W16
STAIR 3
S103
TOILET
1W31
CONSULT
1W17
STORAGE
1W18
WAITING
1W30AOFFICE
1W18A
OFFICE
1W20
OFFICE
1W21
OFFICE
1W22A
OFFICE
1W30
OFFICE
1W29
TOILET
1W28
WAITING RM.
1W27
OFFICE
1W22
HALLWAY
1W24
TOILET
1W25
STORAGE
1W23
SHARED OFFICE
C106A OFFICE
C106
OFFICE
C108
LACTATION
C108A
CORRIDOR
H111
OT GROUP ROOM
C104
CONTROL
C102E
FES UTILITY
C101
STAIR 2
S102
VEST.
H109
CLEAN UTILITY
C102J
CORRIDOR
H113
OFFICE
C110
COPY RM.
C109
OFFICE
C111
OFFICE
C112
OFFICE
C113
OFFICE
C114
OFFICE
C115OFFICE
C116
OFFICE
C117
OFFICE
C115A
OFFICE
C115B
AGENT CASHIER
C119
OFFICE
C122A
OFFICE
C122
VACANT
C120
HAC
C121
VACANT
C123C
OFFICE
C123B
OFFICE
C123A
LOBBY
C124
HALLWAY
C123
CORRIDOR
H106
TOILET, MALE
C127
TOILET, FEMALE
C126
OFFICE
C125
CLOSET
C126A
MEDICAL PROVIDERS
PREP
STAIRWELL NO. 1
S101
CLEAN LINEN RM.
1E136
COPY/STORAGE
1W13A
STORAGE
C129
WAITING RM.
C131
ALCOVE
H113A
CORRIDOR
H118
CORRIDOR
H117
CORRIDOR
1W28A
ALCOVE
H117A
CORRIDOR
H114
RECEPTION
C118
CORRIDOR
H110
CORRIDOR
H108
CORRIDOR
H107
WAITING RM.
C128
CORRIDOR
H115
TOILET
C103
CLOSET
1W06B
CHASE
CH-C-1
ELEVATOR NO. 2
E2
CHASE
CH-1W-4
CHASE
CH-1W-3
CHASE
CH-1W-2
CHASE
CH-C-2
CHASE
CH-C-3
CHASE
CH-1W-1
D.W.
E3
UTILITY
E4
WAITING RM.
H115A
MAIL RM.
C115C
AGENT CASHIER
C119B
TOILET
C127
STAIR 4
S104
CHASE
CH-E-2
CHASE
CH-E-1
CHASE
CH-C-5
CHASE
CH-1W-6
CHASE
CH-C-4COMMUNITY BREAK ROOM
1W32
TR
C102D
MVP
C102A
TRAINING
MENS RESTROOM/LOCKER ROOM
STORAGE
106A
CORRIDOR
KITCHENETTE
HOLDING
ARMS
WOMENS RESTROOM/LOCKER
ROOM
STORAGE
1E13
INTERVIEW
STORAGE
1E02
STORAGE
1E01
STORAGE
1E14
DATA OUTLETS AND
DEVICES IN THIS AREA
SHALL BE SERVED
FROM
TELECOMMUNICATION
ROOM C102D
DATA OUTLETS AND
DEVICES IN THIS AREA
SHALL BE SERVED
FROM
TELECOMMUNICATION
ROOM 1E15
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
01ET401a
01ET401b
01ET401a
01ET401b
TR
1E15
MEDICATION/LOGISTICS
EXAM
EXAM
EXAM
SOILED UTILITY
EXAM
EXAM
DOCTOR OFFICE
IMAGING
RESTROOM
EXAM
EXAM
EXAM
LPN/VITALS
WAITING
RECEPTION
SERVER RM
1E07
B-SIDE:
TO TR 2C10A, E303,
AND 3C13 FROM
GC12 TDU, FROM
FLR 00 TO 01
B-SIDE:
TO TR 2C10A, E303,
AND 3C13 FROM
GC12 TDU, FROM
FLR 01 TO 02
TYP
B-SIDE:
TO TR 1E15 FROM
GC12 TDU
B-SIDE:
TO TR C102D
FROM GC12 TDU
ALL BACKBONE CABLING ROUTES ARE
DIAGRAMMATICAL; CONTRACTOR SHALL ENSURE A-SIDE
AND B-SIDE ROUTING IS AS DIVERSE AS PRACTICAL.
REFERENCE COMMUNICATIONS DRAWINGS FOR ALL
REQUIRED FIBER-OPTIC CABLING.
TYP
5 6
BLDG 01
AREA OF WORK
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF
REQUIRED. COORDINATE WITH ARCHITECTURAL DRAWINGS AS REQUIRED.
3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE UPGRADED WITH CAT6A PORTS AND CABLE
QUANTITIES INDICATED, UNLESS NOTED OTHERWISE.
4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS TO EXTEND TO ASSOCIATED TR AS REQUIRED.
5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A
FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
6. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT 6A CABLING FROM EACH WAO (WORK
AREA OUTLET) TO ITS RESPECTIVE TR.
7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT CONDUIT RUNS, OR CONDUIT
CONTAINING BENDS TOTALING MORE THAN 180 DEGREES.
8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL
DRAWINGS FOR PARTITION TYPES AND WALL HEIGHTS.
9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD; DOCUMENT VARIANCES ON AS-
BUILT DRAWINGS.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING TRANSPORTATION, FOR ALL WORK
TO DESIRED VA STORAGE LOCATION. COORDINATE WITH VA AS REQUIRED.
11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY
DIVIDERS AS REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.
13. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE DIAGRAMMATICAL.
COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS, ARCHITECTURAL FEATURES,
MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER OBSTRUCTIONS PRIOR TO
INSTALLATION.
- 1/16" = 1'-0"
1 BLDG 01 - FLOOR 1 - TELECOMMUNICATIONS PLAN
PROJECT
NORTH
0' 8' 16' 32'
KEY PLAN
KEY NOTES
GENERAL NOTES
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE EXISTING
TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE SHEET DETAIL '1' ON SHEET ET503 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL
INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH CAT6A CABLING.
REMOVE AND REPLACE EXISTING CABLE TRAY IN THE AREAS SHOWN AS REQUIRED; IF CABLE TRAY IS NON- EXISTENT, PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL ‘6’ ON SHEET ET503 AND TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET ET701. WHERE WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO CONDUIT SLEEVES [(2) 4”, MINIMUM] WITH APPROPRIATE FIRE-PROOFING AND CAULKING TO PASS THROUGH WALL WHERE EXISTING CABLE TRAY AND/OR SLEEVES ARE DISCOVERED, EVALUATE CONDITION AND RACEWAY CAPACITY; IF CABLE TRAY AND/OR SLEEVES APPEAR TO BE REUSABLE, NOTIFY COR FOR POSSIBLE
REUSE
FIBER-OPTIC CABLE VERTICAL ROUTING; COORDINATE EXACT LOCATIONS PRIOR TO INSTALLATION. UTILIZE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AND ALL REQUIRED APPURTENANCES AS REQUIRED. REFERENCE DETAIL 2
ON SHEET ET503 FOR ADDITIONAL INFORMATION.
UTILIZE EXISTING PACS SECURITY HEAD END LOCATION FOR NEW OR RELOCATED PACS SECURITY TR EQUIPMENT.
UPGRADE OR MODIFY EXISTING HEAD END LOCATION AS REQUIRED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL TR PACS SECURITY SYSTEM. PROVIDE EQUIPMENT, RACEWAYS, AND CABLING AS REQUIRED.
COORDINATE WITH VA PRIOR TO CONSTRUCTION. CONTRACTOR SHALL VERIFY EXACT HEAD END LOCATION AS
REQUIRED.
SECURITY SYSTEMS CAMPUS WIDE HEADEND EQUIPMENT LOCATED IN 1E11. COORDINATE EXACT LOCATION WITH VA. PROVIDE NEW FIBER-OPTIC CONNECTION AS REQUIRED TO ASSIMILATE WITH THE NEW FIBER-OPTIC BACKBONE UPGRADE; REPLACE EXISTING HARDWARE AS REQUIRED. REFERENCE SHEET 01ET401b FOR ADDITIONAL
INFORMATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO
657-21-701JB
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES 01ET101
BLDG 01 - FLOOR 1 -
TELECOMMUNICATIONS PLAN 01
LRL/WNM JGE/JBB
CONSTRUCTION
DOCUMENTS
03/31/2022
Revisions: Date:
PROJECT
NORTH
2 2
2 2
2 2
2 22
4160 VO
LTS
DUST CO
LLECTO
R
LIQ UEFIED PETRO LEUM G AS
FLAM M ABLE G AS 2
TRASH COM
PACTO
R
P
SILVERBUILDING 1 23
VA PO
LICE
E
LECTRIC ACCESS
TRANSFO
RM
ER
TRANSFO
RM
ER
TRANSFO
RM
ER
HVAC UNIT
E
LECTRIC PANEL
HVAC UNIT
S&C PAD M
O
UNTED G
EAR
CATALO
G
# 55152-C3DGIG
2P1V M
O
DEL# PM
H-9
EE13299 SG
-52
13278
BUILDING
ROOF BELOW
ROOF BELOW
DNUP
DN
UP
SHRED
REF
1 2
REF
MICRO
A
A
A.1
A.1 A.3A.2 B C.1
D.2
D.2C
D.1
D.1D
E.1
E F G H
J.1
J
H.2 J.2
K
L
M N O P Q
R.2
R
R
R.1
R.1
S U
V.3
V.3T
V.2
V.2V V.1
A.4 B.1 B.2 C.2 R.3 T.1 T.2 U.1
10.1
8.1
01ET402
01ET402
WAP 1
WAP 1 WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 4
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 4
WAP 1 WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1
WAP 1 WAP 1
WAP 1
WAP 1
WAP 1
WAP 4
WAP 1
WAP 1 WAP 1
OFFICE
2W29B
WAP 1 WAP 1
WAP 1
WAP 1
WAP 4
TYP
LAB.
2C07
LAB.
2C08UNDER CONSTRUCTION
2C09
CORRIDOR
H204
OFFICE
2C04
VETERAN HEALTH EDUCATION
2C03
LOW VISION THERAPY
2C02
OFFICE
2C01A
LOW VISION CLINIC
2C01
RECEPTION
2C01B
WAITING RM.
2E27
TOILET
2E28
OXYGEN STORAGE
2E30
EXAM
2E29
TOILET, STAFF
2E31
OFFICE
2C05
HAC
2C06
CORRIDOR
H210 STORAGE
2E16A
EXAM
2E21
EXAM
2E20
TOILET
2E22A
CORRIDOR
H203
OFFICE
2E22
STAIR 1
S201
EXAM
2E26
TOILET
2E25B
EXAM
2E25A
OFFICE
2E23
TOILET
2E24
EXAM
2E25
HIMS WORK ROOM
2C19
CORRIDOR
H206
EXAM
2W22C
TOILET
2W23
OFFICE
2W26
OFFICE
2W24
MECH
2W25
CORRIDOR
H207
OFFICE
2W27
OFFICE
2W28
OFFICE
2W28A
OFFICE
2W29
OFFICE
2W28C
TELEHEALTH
2W28B
CLEAN SUPPLY
2W29A
STORAGE
SW29C
TOILET, STAFF
2W29F
VEST.
2W29E
TELEHEALTH
2W29D
OFFICE
2W33
EXAM
2W32
OFFICE
2W30
HAC
2W36
TOILET
2W34
SHARED OFFICE
2W35
STAIR 3
S203
STORAGE
2C22
TOILET
2C24
STORAGE
2C21
LAB.
2C20
OFFICE
2C29
STAIR 2
S202LAB.
2C23
TOILET, FEMALE
2C27
HAC
2C28
EXAM
2C25
EXAM
2C11
OPTICAL SHOP
2C12
NURSE STATION
2C13
EXAM
2C14
ELEC RM.
2C18
KITCHENETTE
2C17
SHARED OFFICE
2C15
TOILET, MALE
2C16
CORRIDOR
H205
CLOSET
2C20A
TOILET
2W03
MED. PREP.
2W04
STORAGE
2W05
BREAK RM.
2W06
TOILET
2W08
EXAM
2W07
TOILET
2W11
EXAM
2W10
EXAM
2W09
EXAM
2W12
RECEPTION
2W01
CORRIDOR
H208
CORRIDOR
H209
OFFICE
2W21
PATIENT NOUR.
2W22
OFFICE
2W22A
CLEAN LINEN / STORAGE
2W22B
CORRIDOR
2W19
TOILET, STAFF
2W20
SHARED OFFICE
2W18
TOILET
2W17
TOILET
2W14
EXAM
2W15
EXAM
2W16
EXAM
2W13
FAX RM.
2W02
ELEV 1
E1
CHASE
CH-C-6
CHASE
CH-C-3
CHASE
CH-C-1
ELEC. CLOSET
2C03A
CHASE
CH-E-3
CHASE
CH-W-2
CHASE
CH-W-4
CHASE
CH-W-3
CHASE
CH-W-5
ELEVATOR NO. 2
E2
CHASE
CH-C-4
D.W.
E3
CHASE
CH-W-8
CHASE
CH-E-8
STAIR 4
S204
2 2
WAP 1
2 2
WAP 1
WAP 1
WAP 1
2 2 2
WAP 1
01ET402
TR
2C10A
LAB.
2C10
RECEPTION
2E18
VITAL SIGN RM
2E19
KITCHENETTE
2E17
EXAM
2E16
LACTATION RM
2E15
STORAGE
2E03
HAC
2E01
STORAGE
2E02
TREAT RM
2E13
OFFICE
2E12
ELEC RM
2E04
TOILET
2E05A
OFFICE
2E05
TELERETINAL IMAGING
2E11
TOILET
2E10
OFFICE
2E09
FAX RM
2E05B
OFFICE
2E06
OFFICE
2E08
TOILET
2E06A
TOILET
2E07B
OFFICE
2E07
TOILET
2E07C
OFFICE
2E07A
CORRIDOR
H201
B-SIDE:
TO TR 2C10A, E303,
AND 3C13 FROM
GC12 TDU, FROM
FLR 01 TO 02
TYP
DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE
SERVED FROM TELECOMMUNICATION ROOM 2C10A.
ALL BACKBONE CABLING ROUTES ARE
DIAGRAMMATICAL; CONTRACTOR SHALL ENSURE A-
SIDE AND B-SIDE ROUTING IS AS DIVERSE AS
PRACTICAL. REFERENCE COMMUNICATIONS
DRAWINGS FOR ALL REQUIRED FIBER-OPTIC CABLING.
BLDG 01
AREA OF WORK
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL FIELD VERIFY
ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS REQUIRED. ALL RACEWAYS
AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED SHALL BE DEMOLISHED
BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY DAMAGED
MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE REPAIRED OR REPLACED AT
THE EXPENSE OF THE CONTRACTOR TO THE ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE RATING OR NEW
FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE UPGRADED WITH CAT6A
PORTS AND CABLE QUANTITIES INDICATED, UNLESS NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS TO EXTEND TO ASSOCIATED
TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT
QUANTITY INDICATED.
7. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT6A CABLING FROM
EACH WAO (WORK AREA OUTLET) TO ITS RESPECTIVE TR.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180 DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND…