Attachment 21 - Drawings Part-20.pdf

PDF 15 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks Federal contract opportunity
Solicitation number
36C77623R0009
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document provides details of a federal contract solicitation for infrastructure upgrades at the St. Louis Jefferson Barracks VA Medical Center. The solicitation seeks a general contractor to provide electrical panel upgrades, power system work, bonding and grounding, UPS installations, building management system integration, HVAC assessments and work, building space reconfigurations, renovations and finishes, data center renovations, communication infrastructure upgrades including network cabling and outlets, physical security improvements, fiber infrastructure assessments and upgrades across campus buildings, and hazardous material abatement. The work locations include various campus buildings. Responses are due under Solicitation Number 36C77623R0009 issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks, newest first.
File Type Posted
FOLLOW-UP Technical Questions - St. Louis 4-6-23.pdf PDF
Technical Questions - FINAL - St. Louis 3-28-23.pdf PDF
657-21-701JB - Addendum 1_03_24_23.pdf PDF
329000-5 - Sod Certificate.pdf PDF
Attachment 43 - Construction Wage Rates - St. Louis 3-24-23.pdf PDF
36C77623R0009 0004.pdf PDF
657-21-701JB - 100 PC - Basis of Design.pdf PDF
32 32 23 01R1 - Mechanically Stabilized Earth Wall System RESPONSE.pdf PDF
Attachment 43 - Construction Wage Rates - St. Louis 3-3-23.pdf PDF
36C77623R0009 0002.pdf PDF
Site Visit Sign-in Sheet - St. Louis 2-28-23.pdf PDF
Attachment 45 - Site Visit Instructions Updated 2-16-23.pdf PDF
Attachment 2 - Drawings Part-1.pdf PDF
Attachment 3 - Drawings Part-2.pdf PDF
Attachment 8 - Drawings Part-7.pdf PDF
Attachment 15 - Drawings Part-14.pdf PDF
Attachment 17 - Drawings Part-16.pdf PDF
Attachment 19 - Drawings Part-18.pdf PDF
Attachment 23 - Drawings Part-22.pdf PDF
Attachment 27 - Drawings Part-26.pdf PDF
Attachment 30 - Drawings Part-29.pdf PDF
Attachment 33 - Drawings Part-32.pdf PDF
Attachment 34 - Envr. Report - Narrative.pdf PDF
Attachment 37 - Envr. Report - Appendix C.pdf PDF
Attachment 40 - NARA RM Contract Language Clause.pdf PDF
Attachment 43 - Construction Wage Rates - St. Louis 1-20-23.pdf PDF
36C77623R0009 - 2-16-23.pdf PDF
Attachment 7 - Drawings Part-6.pdf PDF
Attachment 11 - Drawings Part-10.pdf PDF
Attachment 12 - Drawings Part-11.pdf PDF
Attachment 13 - Drawings Part-12.pdf PDF
Attachment 18 - Drawings Part-17.pdf PDF
Attachment 31 - Drawings Part-30.pdf PDF
Attachment 35 - Envr. Report - Appendix A.pdf PDF
Attachment 38 - Envr. Report - Drawings.pdf PDF
Attachment 42 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 45 - Site Visit Instructions.pdf PDF
Attachment 1 - Specifications.pdf PDF
Attachment 5 - Drawings Part-4.pdf PDF
Attachment 6 - Drawings Part-5.pdf PDF
Attachment 9 - Drawings Part-8.pdf PDF
Attachment 16 - Drawings Part-15.pdf PDF
Attachment 22 - Drawings Part-21.pdf PDF
Attachment 24 - Drawings Part-23.pdf PDF
Attachment 36 - Envr. Report - Appendix B.pdf PDF
Attachment 41 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Attachment 44 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 4 - Drawings Part-3.pdf PDF
Attachment 10 - Drawings Part-9.pdf PDF
Attachment 14 - Drawings Part-13.pdf PDF
Show all 50

Y1DA--EHRM Infrastructure Upgrades Construction Jefferson Barracks has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EP703

ELECTRICAL SCHEDULES

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

ST. LOUIS VA MEDICAL CENTER - JEFFERSON

BARRACKS MO

657-21-701JB

03/31/2022 LRL/WNM WNM

CONSTRUCTION

DOCUMENTS

Revisions: Date:

LRL/WNM LLT/JPS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

EP704

ELECTRICAL SCHEDULE

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

EHRM INFRASTRUCTURE

UPGRADES

657-21-701JB

03/31/2022 Checker Author

CONSTRUCTION

DOCUMENTS

Revisions: Date:

LRL/WNM LLT/JPS

1. "GENERAL NOTES" APPLY TO ALL ELECTRICAL DRAWINGS. "SHEET NOTES" APPLY TO ONLY THE

SHEETS ON WHICH THEY OCCUR. "KEYNOTES" APPLY ONLY WHERE CALLED OUT.

2. ALL EQUIPMENT SHOWN IN BOLD IS TO BE PROVIDED, OR MODIFIED BY CONTRACTOR UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FROM ALL CONTROL DEVICES TO

LUMINAIRES FOR CONTROL OF LUMINAIRES SHOWN.

4. LUMINAIRES SHOWN ON DRAWINGS FOR QUALITY AND CIRCUITING ONLY. SEE ARCHITECTURAL

DRAWINGS FOR EXACT LOCATIONS AND ELEVATIONS.

5. ALL FEEDERS AND BRANCH CIRCUITS SHALL CONTAIN AN EQUIPMENT GROUND CONDUCTOR

SIZED PER NEC TABLE 250.122. ALL WIRING IS BASED ON COPPER PER NEC TABLE

310.15(B),USING 75° C AMPACITIES FOR FEEDERS.

6. BRANCH CIRCUIT CONDUCTORS, NOT OTHERWISE IDENTIFIED SHALL BE A MINIMUM 12 AWG

FOR RUNS 70 FEET OR LESS AND A MINIMUM 10 AWG FOR RUNS GREATER THAN 70 FEET.

QUANTITY AND SIZE SHALL BE "AS REQUIRED" TO SERVE AND CONTROL DEVICE(S) OR

EQUIPMENT WITH A MAXIMUM VOLTAGE DROP OF THREE PERCENT. WHERE CONTRACTOR

CHOOSES TO RUN MORE THAN THREE CURRENT CARRYING CONDUCTORS WITHIN ONE

RACEWAY OR CABLE, CONDUCTORS SHALL BE INCREASED IN SIZE TO COMPENSATE FOR THE

DERATING REQUIRED PER NEC SECTION 310.15. CONDUCTOR AMPACITIES SHALL BE TAKEN

FROM THE 75° C COLUMN.

7. MINIMUM CONDUIT SIZE IN EXTERIOR AND UNDERGROUND LOCATIONS TO BE 1" UNLESS

NOTED OTHERWISE ON PLANS. CONDUITS FROM LUMINAIRES TO LOCAL USER CONTROL

DEVICES (SWITCHES, OCCUPANCY SENSORS, ETC.) MAY BE 3/4" OR AS INDICATED IN

SPECIFICATIONS. PROVIDE ADDITIONAL CONDUCTOR FOR UNSWITCHED "HOT" TO LIGHTING

LUMINAIRES WITH EMERGENCY POWER BATTERIES OR GENERATOR TRANSFER DEVICES.

8. WIRING FOR EMERGENCY LIGHTING CIRCUITS OR OTHER EMERGENCY EQUIPMENT SHALL BE

KEPT ENTIRELY INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT AND SHALL MEET ALL

REQUIREMENTS OF NEC SECTION 700.10.

9. CONTRACTORS SHALL PROVIDE CONDUIT AND WIRE FOR ALL CIRCUITS SHOWN ON DRAWINGS.

10. WHERE EQUIPMENT PART NUMBERS ARE SHOWN ON THESE PLANS THEY SHALL SUPERCEDE

THE REQUIREMENTS OF THE SPECIFICATIONS.

11. ALL CONDUITS SHALL BE CONCEALED UNLESS OTHERWISE NOTED.

12. COORDINATE EXACT LOCATION OF ALL OUTLETS, COMBINATION CLOCK/SPEAKERS, SPEAKER, FA DEVICES, ETC., WITH THE ARCHITECTURAL ELEVATIONS PRIOR TO COMMENCING WORK.

13. COORDINATE USE OF CEILING SPACE WITH ALL TRADES PRIOR TO COMMENCING WORK. MANY

AREAS ARE VERY CONGESTED AND REQUIRE CLOSE COORDINATION.

14. COORDINATE INSTALLATION REQUIREMENTS FOR OCCUPANCY SENSOR LIGHTING CONTROL

WITH THE MANUFACTURER. PROVIDE ALL APPURTENANCES AS REQUIRED BY THE

MANUFACTURER. PROVIDE ADDITIONAL SENSORS WHERE NECESSARY TO PROVIDE COMPLETE

COVERAGE IN EACH ROOM CONTROLLED BY OCCUPANCY SENSORS.

15. COORDINATE THE INSTALLATION OF ALL EXTERIOR OUTLET BOXES WITH THE TYPE OF

MASONRY IN EACH AREA. CUT ALL FLUTED BLOCKS SO THAT THE BOX IS INSTALLED FLUSH.

SEE ARCHITECTURAL DETAILS FOR MOUNTING REQUIREMENTS.

16. SEAL ALL CONDUIT PENETRATIONS OF FLOORS AND FIRE RATED ASSEMBLIES WITH U.L.

APPROVED MATERIALS AND METHODS TO MAINTAIN FIRE RATING. PROTECT ALL OPENINGS

FOR STEEL ELECTRICAL BOXES IN FIRE RATED WALLS WITH U.L. APPROVED MATERIALS AND

METHODS TO MAINTAIN THE FIRE INTEGRITY.

17. PROVIDE ADDITIONAL CONDUIT SLEEVES THROUGH WALLS WHERE REQUIRED FOR ROUTING

OF SIGNAL SYSTEM WIRING NOT REQUIRED TO BE RUN IN CONDUIT. EACH SLEEVE SHALL BE

DEDICATED TO EACH SIGNAL SYSTEMS. SLEEVES ROUTED THROUGH RATED WALLS SHALL BE

SEALED WITH U.L. MATERIALS AND METHODS TO MAINTAIN FIRE RATING OF WALL.

18. SEE MECHANICAL/PLUMBING DRAWINGS AND SUBMITTALS FOR EXACT LOCATIONS AND

ADDITIONAL ELECTRICAL REQUIREMENTS PRIOR TO INSTALLATION.

19. ALL LOW VOLTAGE SYSTEMS NOT RUN IN CONDUIT SHALL HAVE MINIMUM 3/4"C. ROUTED FROM

THE DEVICE THROUGH WALLS INTO THE ACCESSIBLE CEILING SPACE. NO CABLING SHALL BE

ROUTED IN THE WALLS OR INACCESSIBLE LOCATION WITHOUT CONDUIT.

20. GFCI RECEPTACLES ARE REQUIRED WITHIN 6 FT OF ALL SINKS, ON THE EXTERIOR BELOW 8FT

FROM THE FINISH FLOOR, AND ON ALL ROOFS.

21. UNLESS SPECIFICALLY SHOWN ON THESE PLANS NO STRUCTURAL MEMBER SHALL BE CUT,

NEITHER DRILLED NOR NOTCHED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM THE

STRUCTURAL ENGINEER AND THE COR.

22. CONTRATOR SHALL PROVIDE DUCT SEAL WHERE CONDUITS TRANSITION FROM AREAS THAT

CREATE TEMPERATURE DIFFERENTIAL PER NEC.

23. PRIMARY CONDUIT SWEEPS SHALL BE LONG RADIUS.

24. ALL "RMC" - RIGID METAL CONDUIT IN CONTACT WITH THE EARTH SHALL BE WRAPPED WITH

CORROSION PROTECTION TAPE PER NEC.

25. ALL J-BOXES SHALL BE MATKED WITH INDELIBLE MARKER INDICATING CONDUIT NUMBER AND

PANEL NUMBER.

26. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL 120 VOLT POWER FOR

THE MECHANICAL CONTROLS. COORDINATE EXACT REQUIREMENTS WITH THE CONTROL

CONTRACTOR.

27. ALL ELECTRICAL WORK SHALL BE COMPLETED WITH ALL PROXIMATE ELECTRICAL CIRCUITS DE-

ENERGIZED (I.E. A NEW BREAKER OR CIRCUIT CANNOT BE ADDED TO A PANEL UNLESS THE

PANEL IS COMPLETELY DE-ENERGIZED), OR THE CONTRACTOR MUST COMPLY WITH NFPA 70E

FOR WORK ON ENERGIZED SERVICE. THE VA WILL DETERMINE IF THE ELECTRICAL SERVICE

CAN BE SHUTDOWN OR IT WILL HAVE TO BE WORKED HOT DEPENDING ON THE CRITICALITY OF

THE AREA BEING AFFECTED. IF THE WORK MUST BE DONE WITH THE SERVICE LIVE, THE

CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL REQUIRED PROTECTIVE TOOLS,

EQUIPMENT AND CLOTHING, AND MUST FOLLOW THE JOB SPECIFIC WORK PLAN PREPARED BY

THE VA. WORK THAT REQUIRES SHUTTING DOWN ELECTRICAL SERVICE MAY HAVE TO BE

ACCOMPLISHED DURING OTHER THAN NORMAL DUTY HOURS.

28. WHENEVER FIRE ALARM WORK TAKES PLACE IN AN AREA THAT IS BEING REMODELED, AT THE

CONCLUSION OF THE WORK, THE FIRE ALARM CONTRACTOR SHALL TEST ALL FIRE ALARM

DEVICES WITHIN THE AREA OF REMODEL.

29. DEMOLITION PLAN/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD DRAWINGS. IF

DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY NOTIFY VA AND ENGINEER

OF SAID DISCREPANCY.

30. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF DEVICES SHALL

COMPLY WITH ALL APPROPRIATE CODES.

31. FIELD VERIFY RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO PERFORMING WORK.

32. ALL EQUIPMENT, CABLING, CONNECTORS AND APPURTENANCES SHALL BE LABELED PER THE

VA STANDARD "INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACE" VERSION 3.1

OR NEWER.

33. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER

OBSTRUCTIONS PRIOR TO INSTALLATION.

34. ALL ETHERNET CATEGORY CABLES SHALL FOLLOW THE FOLLOWING CABLE COLOR SCHEME:

DATA SHALL BLUE/TEAL, PHONES SHALL BE GRAY, AND (WIRELESS) ACCESS POINTS SHALL BE

YELLOW. COORDINATE WITH VA FOR ALL CABLING COLOR SCHEMES AS REQUIRED PRIOR TO

SUBMITTAL PROCESS.

35. TOTAL NUMBER OF DATA CONNECTIONS AND CABLING FOR WAOs AND WAPs SHALL BE

VERIFIED BY CONTRACTOR PRIOR TO ACQUISITION OF EQUIPMENT AND CABLING.

CONTRACTOR SHALL PROVIDE AN INITIAL SURVEY OF ALL AREAS TO HAVE UPGRADED WAOs

AND OTHER DATA CONNECTED EQUIPMENT IN ORDER TO VERIFY EXACT LOCATIONS AND

QUANTITIES PRIOR TO CONSTRUCTION.

36. CONTRACTOR MAY USE TEMPORARY CABLE HANGERS OR OTHER MEANS WHILE ROUTING

CABLE TO ITS INTENDED DESTINATION; HOWEVER, PRIOR TO FINAL INSTALLATION, CABLE

SHALL BE INSTALLED TO BE HOUSED WITHIN CABLE TRAY AND NOT ON TEMPORARY CABLE

HANGERS.

G E N E R A L N O T E S

THIS SHEET IS FOR REFERENCE ONLY AND ALL SYMBOLS, NOTES

AND ABBREVIATIONS MAY NOT APPLY TO THIS PROJECT

S H E E T I N D E X

ETG001 - TELECOMMUNICATIONS LEGEND, GENERAL NOTES, AND ABBREVIATIONS

01ET100 - BLDG 01 - FLOOR 0 - TELECOMMUNICATION PLANS

01ET101 - BLDG 01 - FLOOR 1 - TELECOMMUNICATION PLANS

01ET102 - BLDG 01 - FLOOR 2 - TELECOMMUNICATION PLANS

01ET103 - BLDG 01 - FLOOR 3 - TELECOMMUNICATION PLANS

02ET100 - BLDG 02 - FLOOR 0 - TELECOMMUNICATION PLANS

02ET101 - BLDG 02 - FLOOR 1 - TELECOMMUNICATION PLANS

02ET102 - BLDG 02 - FLOOR 2 - TELECOMMUNICATION PLANS

02ET103 - BLDG 02 - FLOOR 3 - TELECOMMUNICATION PLANS

03ET100 - BLDG 03 - FLOOR 0 - TELECOMMUNICATIONS PLAN

03ET101 - BLDG 03 - FLOOR 1 - TELECOMMUNICATIONS PLAN

03ET102 - BLDG 03 - FLOOR 2 - TELECOMMUNICATIONS PLAN

03TET101 - BLDG 03T - FLOOR 1 - TELECOMMUNICATIONS PLAN

18ET100 - BLDG 18 - FLOOR 0 - TELECOMMUNICATIONS PLAN

18ET101 - BLDG 18 - FLOOR 1 - TELECOMMUNICATIONS PLAN

18ET102 - BLDG 18 - FLOOR 2 - TELECOMMUNICATIONS PLAN

18ET103 - BLDG 18 - FLOOR 3 - TELECOMMUNICATIONS PLAN

23ET100 - BLDG 23 - FLOOR 0 - TELECOMMUNICATIONS PLAN

23ET101 - BLDG 23 - FLOOR 1 - TELECOMMUNICATIONS PLAN

24ET100 - BLDG 24 - FLOOR 0 - TELECOMMUNICATIONS PLAN

24ET101 - BLDG 24 - FLOOR 1 - TELECOMMUNICATIONS PLAN

24ET102 - BLDG 24 - FLOOR 2 - TELECOMMUNICATIONS PLAN

25ET100 - BLDG 25 - FLOOR 0 - TELECOMMUNICATIONS PLAN

25ET101 - BLDG 25 - FLOOR 1 - TELECOMMUNICATIONS PLAN

25ET102 - BLDG 25 - FLOOR 2 - TELECOMMUNICATIONS PLAN

25ET103 - BLDG 25 - FLOOR 3 - TELECOMMUNICATIONS PLAN

25ET104 - BLDG 25 - PENTHOUSE - TELECOMMUNICATIONS PLAN

51ET100a - BLDG 51 - FLOOR 0 - AREA A & C - TELECOMMUNICATIONS PLAN 51ET100b - BLDG 51 - FLOOR 0 - AREA E - TELECOMMUNICATIONS PLAN 51ET101a - BLDG 51 - FLOOR 1 - AREA A - TELECOMMUNICATIONS PLAN 51ET101b - BLDG 51 - FLOOR 1 - AREA B TELECOMMUNICATIONS PLAN 51ET101c - BLDG 51 - FLOOR 1 - AREA C TELECOMMUNICATIONS PLAN 51ET101d - BLDG 51 - FLOOR 1 - AREA D TELECOMMUNICATIONS PLAN 51ET101e- BLDG 51 - FLOOR 1 - AREA E TELECOMMUNICATIONS PLAN

51TET101 - BLDG 51T - FLOOR 1 - TELECOMMUNICATIONS PLAN

52ET100 - BLDG 52 - FLOOR 0 - TELECOMMUNICATIONS PLAN

52ET101 - BLDG 52 - FLOOR 1 - TELECOMMUNICATIONS PLAN

52ET102 - BLDG 52 - FLOOR 2 - TELECOMMUNICATIONS PLAN

53ET100 - BLDG 53 - FLOOR 0 - TELECOMMUNICATIONS PLAN

53ET101 - BLDG 53 - FLOOR 1 - TELECOMMUNICATIONS PLAN

53ET102 - BLDG 53 - FLOOR 2 - TELECOMMUNICATIONS PLAN

53ET103 - BLDG 53 - PENTHOUSE - TELECOMMUNICATIONS PLAN

53TET101 - BLDG 53T - FLOOR 1 - TELECOMMUNICATIONS PLAN

54ET100 - BLDG 54 - FLOOR 0 - TELECOMMUNICATIONS PLAN

54ET101 - BLDG 54 - FLOOR 1 - TELECOMMUNICATIONS PLAN

54ET102 - BLDG 54 - FLOOR 2 - TELECOMMUNICATIONS PLAN

55ET101a - BLDG 55 - FLOOR 1 - AREA A - TELECOMMUNICATIONS PLAN 55ET101b - BLDG 55 - FLOOR 1 - AREA B - TELECOMMUNICATIONS PLAN 55ET102a - BLDG 55 - FLOOR 2 - AREA A - TELECOMMUNICATIONS PLAN 55ET102b - BLDG 55 - FLOOR 2 - AREA B - TELECOMMUNICATIONS PLAN 55ET103a - BLDG 55 - FLOOR 3 - AREA A - TELECOMMUNICATIONS PLAN 55ET103b - BLDG 55 - FLOOR 3 - AREA B - TELECOMMUNICATIONS PLAN

56ET100 - BLDG 56 - FLOOR 0 - TELECOMMUNICATIONS PLAN

56ET101 - BLDG 56 - FLOOR 1 - TELECOMMUNICATIONS PLAN

56ET102 - BLDG 56 - FLOOR 2 - TELECOMMUNICATIONS PLAN

56ET103 - BLDG 56 - FLOOR 3 - TELECOMMUNICATIONS PLAN

57ET101 - BLDG 57 - FLOOR 1 - TELECOMMUNICATIONS PLAN

58ET101 - BLDG 58 - FLOOR 1 - TELECOMMUNICATIONS PLAN

60ET101 - BLDG 60 - FLOOR 1 - TELECOMMUNICATIONS PLAN

60TET101 - BLDG 60T - FLOOR 1 - TELECOMMUNICATIONS PLAN

75ET101 - BLDG 75 - FLOOR 1 - TELECOMMUNICATIONS PLAN

75ET102 - BLDG 75 - MEZZANINE - TELECOMMUNICATIONS PLAN

CET101 - BLDG 1-24 - FLOOR 0 - CORRIDOR WIRELESS ACCESS POINT

TELECOMMUNICATIONS PLAN

CET102 - BLDG 1-24 - FLOOR 1 - CORRIDOR WIRELESS ACCESS POINT

TELECOMMUNICATIONS PLAN

CET103 - BLDG 23-51-65 - FLOOR 1 - CORRIDOR WIRELESS ACCESS POINT

TELECOMMUNICATIONS PLAN

CET104 - BLDG 51-52-53-60-61 - FLOOR 1 - CORRIDOR WIRELESS ACCESS POINT

TELECOMMUNICATIONS PLAN

01ET400a - BLDG 01 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 01ET400b - BLDG 01 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 01ET401a - BLDG 01 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 01ET401b - BLDG 01 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

01ET402 - BLDG 01 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

01ET403a - BLDG 01 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS 01ET403b - BLDG 01 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS

02ET400 - BLDG 02 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

02ET401 - BLDG 02 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

02ET402 - BLDG 02 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

02ET403 - BLDG 02 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS

03ET400 - BLDG 03 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

03ET401 - BLDG 03 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

03ET402 - BLDG 03 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

03TET401 - BLDG 03T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

18ET400 - BLDG 18 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

18ET401 - BLDG 18 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

18ET402 - BLDG 18 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

18ET403 - BLDG 18 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS

23ET400 - BLDG 23 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

23ET401 - BLDG 23 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

24ET400 - BLDG 24 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

24ET401 - BLDG 24 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

24ET402 - BLDG 24 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

25ET401 - BLDG 25 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

25ET402 - BLDG 25 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

25ET403 - BLDG 25 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS

51ET400 - BLDG 51 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

51ET401a - BLDG 51 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 51ET401b - BLDG 51 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 51ET401c - BLDG 51 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

51TET401 - BLDG 51T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

52ET400 - BLDG 52 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

52ET401a - BLDG 52 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 52ET401b - BLDG 52 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 52ET401c - BLDG 52 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 52ET402a - BLDG 52 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 52ET402b - BLDG 52 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 53ET400a - BLDG 53 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 53ET400b - BLDG 53 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS 53ET401a - BLDG 53 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 53ET401b - BLDG 53 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

53ET402 - BLDG 53 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

53TET401 - BLDG 53T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

55ET401a - BLDG 55 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 55ET401b - BLDG 55 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 55ET401c - BLDG 55 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 55ET402a - BLDG 55 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 55ET402b - BLDG 55 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS 55ET403a - BLDG 55 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS 55ET403b - BLDG 55 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS

56ET400 - BLDG 56 - FLOOR 0 - ENLARGED TELECOMMUNICATIONS PLANS

56ET401 - BLDG 56 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

56ET402 - BLDG 56 - FLOOR 2 - ENLARGED TELECOMMUNICATIONS PLANS

56ET403 - BLDG 56 - FLOOR 3 - ENLARGED TELECOMMUNICATIONS PLANS

57ET401a - BLDG 57 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 57ET401b - BLDG 57 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 58ET401a - BLDG 58 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS 58ET401b - BLDG 58 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

60ET401 - BLDG 60 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

60TET401 - BLDG 60T - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

75ET401 - BLDG 75 - FLOOR 1 - ENLARGED TELECOMMUNICATIONS PLANS

ET501 - TELECOMMUNICATIONS DETAILS

ET502 - TELECOMMUNICATIONS DETAILS

ET503 - TELECOMMUNICATIONS DETAILS

ET601 - FIBER OPTIC NETWORK DIAGRAM

ET602 - FIBER OPTIC NETWORK DIAGRAM

ET603 - FIBER OPTIC NETWORK DIAGRAM

ET701 - TELECOMMUNICATIONS SCHEDULES

FLEXIBLE CONDUIT

CONDUIT TURNED UP OR TOWARD

CONDUIT TURNED DOWN OR AWAY

CONDUIT CAPPED

T E L E C O M M U N I C A T I O N S L E G E N D

COMMUNICATION OUTLETS

FLOOR MOUNTED TELECOMMUNICATIONS OUTLET.

# = INDICATES QUANTITY OF VOICE AND DATA JACKS

WALL MOUNTED TELECOMMUNICATIONS OUTLET. 18" AFF UON

# = INDICATES QUANTITY OF VOICE AND DATA JACKS

OUTLET; LETTER INDICATES AS FOLLOWS:

A=AUDIO V=VIDEO I=INTERCOM

OUTLET, TELEVISION

BLANK = 4 11/16" MASTER ANTENNA OUTLET BOX WITH BLANK

COVER, MTD. 18" AFF UNLESS OTHERWISE NOTED.

C = CAMERA (CCTV SYSTEM), MTD 18" AFF

M = MONITOR (CCTV SYSTEM).

TELECOMMUNICATIONS OUTLET, SPECIAL PURPOSE.

REFERENCE KEY NOTES ON PLANS FOR ADDITIONAL

INFORMATION.

S

WAP

A/V

S C

C

TGB

FNC

FIBEROPTICS LINE = FO

TELEPHONE LINE = T

SPEAKER, CEILING MOUNTED

SPEAKER, WALL MOUNTED, MTD. 7'-6" AFF UON.

RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" AFF UON.

M = SPEAKER PROGRAM SELECTOR SWITCH & VOLUME

CONTROL

3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD.

4'-6" AFF.

REMOTE DICTATING OUTLET MTD 1'-6" AFF. UON.

INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL

OPERATION OF INSTRUMENT & TYPE REQUIRED).

S = STAFF STATION

WIRELESS ACCESS PORT

WALL MOUNTED SPEAKER/CLOCK COMBINATION

WALL CLOCK

CABLE TRAY

RECESSED AUDIO FLOOR BACK BOX, OUTLET AND CONDUIT

TELECOMMUNICATIONS SYSTEMS BONDING BUSBAR

FIBER OPTIC NETWORK CARD

COMMUNICATION

SECTION A

XXX

SECTION LETTER

SHEET WHERE

SECTION IS TAKEN

FROM

A

XXX

SECTION LETTER

SHEET WHERE

SECTION IS TAKEN

FROM

XXX

DETAIL NUMBER

SHEET ON WHICH

DETAIL APPEARS

DETAIL AREA

SCALE

XXXNG

CONDUIT & WIRE TAG

(REFER TO CONDUIT

AND WIRE SCHEDULE)

XX FAULT CURRENT TAG

(3 PH, SYM AMPS)

1 KEY NOTE

XXX

FIGURE OR PHOTO

DETAIL NUMBER

IF PHOTO, ARROW

DENOTES DIRECTION

TAKEN

SHEET WHERE DETAIL

IS TAKEN FROM

DETAIL/PLAN

DETAIL/PLAN NUMBER

G E N E R A L S Y M B O L S

AFC

AFG

AF

AFCI

AFF

AIC

AHJ

ATS

C

CATV

CB

CCTV

CL

CO

DDC

DP

EC

EL

EMER

EN

EMT

ER

EX

FAAP

FACP

FCIO

FOIC

GFCI

GFP

GND

HTR

IG

IMC

J-BOX

LCP

MCA

MCB

MCC

MDP

MLO

MS

MTD

NAC

NEC

NFC

NIC

NL

NTS

OC

OH

OS

PIV

PNL

PS

PVC

R

RECPT

RMC

SAC

SB, SWBDm

SG

SM

SPD

TEL

TR

TYP

UON

UL

UG

VD

VFD

W

WP

XFMR

ABOVE FINISHED COUNTER

ABOVE FINISHED GRADE

AMP FRAME

ARC FLASH CIRCUIT INTERRUPTER

ABOVE FINISHED FLOOR

AMPERE INTERRUPTING CAPACITY

AUTHORITY HAVING JURISDICTION

AUTOMATIC TRANSFER SWITCH

CONDUIT OR CEILING

COMMUNITY ANTENNA TELEVISION

CIRCUIT BREAKER

CLOSED CIRCUIT TELEVISION

CONNECTOR LIGHTING

CONDUIT ONLY

DIRECT DIGITAL CONTROLS

DISTRIBUTION PANELBOARD

EMPTY CONDUIT

ELEVATION

EMERGENCY

EXISTING IN NEW LOCATION

ELECTRICAL METALLIC TUBING

EXISTING TO REMAIN

EXISTING

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

FURNISHED BY CONTRACTOR, INSTALLED

BY OWNER

FURNISHED BY OWNER, INSTALLED BY

CONTRACTOR

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT PROTECTION

GROUND

HEATER

ISOLATED GROUND

INTERMEDIATE METAL CONDUIT

JUNCTION BOX

LIGHTING CONTROL PANEL

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN DISTRIBUTION PANEL

MAIN LUGS ONLY

MOTOR STARTER

MOUNTED

NOTIFICATION APPLIANCE CABINET

NATIONAL ELECTRICAL CODE

NOT FOR CONSTRUCTION

NOT IN CONTRACT

NIGHT LIGHT

NOT TO SCALE

ON CENTER

OVERHEAD

OCCUPANCY SENSOR

POST INDICATOR VALVE

PANEL

POWER SUPPLY

POLYVINYL CHLORIDE

EXISTING TO BE REMOVED

RECEPTACLE

RIGID METAL CONDUIT

SMALL APPLIANCE CIRCUIT

SWITCHBOARD

SWITCHGEAR

SMART METER

SURGE PROTECTIVE DEVICE

TELEPHONE

TAMPER RESISTANT

TYPICAL

UNLESS OTHERWISE NOTED

UNDERWRITERS LABORATORIES

UNDERGROUND

VOLTAGE DROP

VARIABLE FREQUENCY DRIVE

WEATHERPROOF (WHILE IN USE)

WEATHERPROOF

TRANSFORMER

A B B R E V I A T I O N S

AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BELL C-CHIME H-HORN K-KLAXON

L-LISTEN M-MICROPHONE S-SOUNDER S-SPEAKER Z-BUZZER

KEYPAD DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR WALL CALL

M-MAG STRIP P-PROXIMITY S-SMART CARD T-TOKEN

D DOOR CONTACT

ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DEADBOLT H-HYBRID L-LATCH SET S-STRIKE

INTERCOM; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

M-MASTER S-SUBSTATION

MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC

PUSH BUTTON; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BELL PUSH D-DURESS P-PANIC R-DOOR OPENER X-REQUEST FOR EXIT

SECURITY ACCESS, ANNUNCIATOR PANEL

SECURITY ACCESS, VIDEO CAMERA WITH LENS

SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW

SECURITY ACCESS, PANNING CAMERA TRAVERSE ANGLE

SAFETY AND SECURITY

M = MOUNTING FOR ALL SAFETY AND SECURITY SYMBOLS:

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

NURSE CALL

FIRE ALARM

PS

WG

NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER TOP UNLESS

OTHERWISE NOTED.

NURSE CALL TERMINAL CABINET.

NURSE CALL STATION.

D E

P S

U

= DUPLICATE PATIENT STATIONS (SEPARATE INDICATORS AT

MASTER STATION) MTD 5'-0" AFF UNLESS OTHERWISE NOTED

= DUTY STATION. MTD 5'-0" AFF UNLESS OTHERWISE NOTED

= STATION MTD 6'-0" AFF FOR SHOWER LOCATION, MTD 4'-6" AFF

FOR TUB LOCATION, & MTD 3'-0" AFF FOR TOILET LOCATION,UON

= PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH

= AUDIO VISUAL WALL STATION (STAFF) MTD 5'-0" AFF UNLESS

OTHERWISE NOTED

= UTILITY CALL STATION, MTD 5'-0" AFF UNLESS OTHERWISE NOTED

NURSE CALL STATION.

D I

= NURSE'S CALL DOME LIGHT (SUFFIX INDICATES NO. OF LAMP)

MTD 6" ABOVE DOOR

= CORRIDOOR DOME LIGHT.

= AUXILIARY INTERSECTIONAL DOME LIGHT.

NIGHT LIGHT

PATIENT BED OUTLETB

POWER SUPPLY WITH BATTERY BACKUP

WANDER GUARD

R

C

C

F

K

A

ADDRESSABLE RELAY

ALARM, FIRE, COMMUNICATOR

ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:

FACC = CENTRAL CONSOLE FACP = CONTROL PANEL

MFACP = MASTER CONTROL PANEL FAAP = ANNUNCIATOR PANEL

ALARM, FIRE; LETTERS INDICATE AS FOLLOWS:

BATT = BATTERIES CHR = CHARGER FAR = RECORDER

ALARM, FIRE, VALVE SUPERVISORY SWITCH.

ALARM, FIRE, TERMINAL CABINET.

ALARM, FIRE, POST INDICATOR VALVE.

ALARM, TRANSPONDER OR TRANSMITTER.

ALARM, FIRE, MANUAL PULL STATION

C = WITH CLEAR PLASTIC COVER

ALARM, HORN/LIGHT, ONE ASSEMBLY

C = WITH CHIME

ALARM, HORN/LIGHT, SEPARATE ASSEMBLY

ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE

ALARM, MANUAL CONTROL

ALARM, MINI HORN

ALARM, SPRINKLER SYSTEM WATER FLOW BELL

ALARM, VOICE COMMUNICATION PANEL

ALARM, TAMPER SWITCH

DETECTION, GAS

C = CARBON DIOXIDE TRANSMITTER

DETECTOR, FLOW SWITCH

DETECTOR, HEAT

DETECTOR, SMOKE

DETECTOR, SMOKE, FOR DUCT

ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET

CITY FIRE ALARM MASTER STATION MTD 5'-6" AFF UNLESS NOTED.

FIRE ALARM TRANSMITTER (BASE LOOP) NUMERALS DENOTE CODE.

FIRE ALARM TROUBLE TRANSMITTER (BASE LOOP) NUMERALS

DENOTE CODE.

FIRE SPRINKLE WATER FLOW SWITCH

KITCHEN HOOD FIRE SUPPRESSION SYSTEM

REMOTE ANNUNCIATOR

SPECIAL SYSTEMS

P

AUDIO CONTROLLER

PRESSURE BEACON

PRESSURE DEVICE

SLEEVE WITH BUSHING FIRESTOP AND INNERDUCT FOR

FIBER

SLEEVE OR CONDUIT WITH BUSHING FIRESTOP AND

INNERDUCT FOR FIBER

A

FAC

BATT

FACC

OSY

FATC

PIV

FTR

P

C

M

WB

CP

TS

HD

DH

FAT

2-4-6

2-4-6

FTT

FO

T

S X

S X

R M

R M

NCS

NCT

N

N

M

T

M

M

M

T

M

T

M

T

M

T

M

T

AP

180o

60o

ALARM, CHECK VALVE

ALARM, GONG

ALARM, HORN/LIGHT, ONE ASSEMBLY

SCCP DETECTION, SMOKE CONTROL AND PRESSURE PANEL

EPO

DETECTION SWITCH, ABORT

DETECTION SWITCH, VALVE TAMPER

DETECTOR, FLAME FLICKER

R/T

HD

DETECTOR, HEAT; LETTER INDICATED AS FOLLOWS:

R/T= COMBINATION F= FIXED TEMPERATURE

R/C= RATE COMPENSATION R= RATE OF RISE

H

DETECTOR; LETTER INDICATED AS FOLLOWS:

BLANK= SMOKE DETECTOR

H= HEAT SMOKE

I= IONIZATION SMOKE

P=PHOTOELECTRIC SMOKE

IH= IONIZATION AND HEAT SMOKE

IP= IONIZATION AND PHOTOELECTRIC SMOKE

PH= PHOTOELECTRIC AND HEAT SMOKE

IPH= IONIZATION, PHOTOELECTRIC HEAT

DETECTOR, SWITCH LEVEL

FS FIRE ALARM STATION, MANUAL PULL

FA FIRE ALARM LINE = FA

BI-STATIC BEAM SENSOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T= TECHNOLOGY/TYPE

I-INFRARED M-MICROWAVE

F=FUNCTION

RX=RECEIVE TX-TRANSMIT

M

TF

BIOMETRICS ACCESS CONTROL DEVICE; LETTER IDNICATED AS FOLLOWS:

M=MOUNT

C-CEILING

T= TECHNOLOGY/TYPE

F-FINGER PRINT H-HAND GEOMETRY I-EYE IRIS

R-EYE RETINA V-VOICE

M

T

CARD READER WITH TIME AND ATTENDANCE; LETTER INDICAED AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

M

CENTRAL PROCESSING UNIT

CONTROL PANEL; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BURGLAR D-DOOR F-FIRE P-PERIMETER

M

T

EXIT DEVICE; LETTER INDICATED AS FOLLOWS:

T=TECHNOLOGY/TYPE

D-DELAYED EGRESS E-ELECTRIFIED M-MECHANICAL X-HIGH SECURITY

T

FIBER OPTIC MODULE; LETTER INDICATED AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

R-RECIEVER T-TRANSCEIVER TX-TRANSMITTER

M

T

FIELD PANEL; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

M

T

GLASS BREAKAGE SENSOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

A-AUDIO S-SHOCK

M

T

MONITOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DATA G-GRAPHIC M-MULTISCREEN V-VIDEO

M

T

RECORDER; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

A-AUDIO D-DIGITAL V-VIDEO

M

T

SECURITY ACCESS, BUZZER. MTD 1'-6" {457mm} AFF UNLESS OTHERWISE NOTED

SECURITY ACCESS, "X" INDICATES THE TYPE, PROVIDE SCHEDULE OR LEGENDX

SECURITY ACCESS, HORN OR SIREN

SECURITY ACCESS, OUTDOOR MICROWAVE TRANSMISSION UNIT

SECURITY ACCESS, PANIC ALARM

O

X

SECURITY ACCESS, VIDEO CAMERA WITH LENS

M = MOTION DETECTOR

PZ = MOTION DETECTOR WITH PAN AND ZOOM

PTZ = MOTION DETECTOR WITH PAN, TILT, AND ZOOM

M PTZ

SECURITY ACCESS, VOLUMETRIC SENSOR

SECURITY SCREEN WITH ALARM; LETTER INDICATES AS FOLLOWS:

T=TECHNOLOGY/TYPE

B-BIND S-SHADE

T

SECURITY WINDOW SCREEN; LETTER INDICATED AS FOLLOWS:

T=TECHNOLOGY/TYPE

B-BLIND

T

VIDEO CONTROL KEYBOARD

VIDEO MOTION DETECTOR

SECURITY ACCESS, SENSOR, BURIED VEHICULAR

SECURITY ACCESS, SWITCH, BALANCED MAGNETIC CONTROL

CODE ONE CONTROL AND ALARM STATION. MTD 5'-0" [1524mm] AFF UNLESS

OTHERWISE NOTED.

NIP

CODE ONE TERMINAL CABINET.NIT

CODE ONE ANNUNCIATOR PANEL.NIA

CODE ONE BEDSIDE STATION.NI

CODE ONE DUTY STATION, MTD 5'-0" [1524mm] AFF UNLESS OTHERWISE NOTED.NID

X

V I

H

CONDUIT OR EQUIPMENT TO BE REMOVED

CONDUIT ROUTED UNDERGROUND OR

UNDERFLOOR

CONDUIT CONCEILED IN WALL, CEILING,

OR UNDER FLOOR WHERE POSSIBLE,

OTHERWISE EXPOSED

EXISTING CONDUIT EXPOSED, EXISTING

TO REMAIN UNLESS OTHERWISE NOTED

EXISTING CONDUIT ROUTED UNDERGROUND,

EXISTING TO REMAIN UNLESS OTHERWISE

NOTED

EXTRA-HARD USAGE FLEXIBLE CORD

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

657-21-701JB

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES ETG001

LRL/WNM JGE/JBB

CONSTRUCTION

DOCUMENTS

03/31/2022

TELECOMMUNICATIONS LEGEND, GENERAL

NOTES, AND ABBREVIATIONS

Revisions: Date: 301 OF 435

DN

UP

DN

2 2

2 2

2 2

4160 VO

LTS

DUST CO

LLECTO

R

LIQ UEFIED PETRO LEUM G AS

FLAM M ABLE G AS 2

TRASH COM

PACTO

R

P

SILVERBUILDING 1 23

VA PO

LICE

E

LECTRIC ACCESS

TRANSFO

RM

ER

TRANSFO

RM

ER

TRANSFO

RM

ER

HVAC UNIT

E

LECTRIC PANEL

HVAC UNIT

S&C PAD M

O

UNTED G

EAR

CATALO

G

# 55152-C3DGIG

2P1V M

O

DEL# PM

H-9

EE13299 SG

-52

13278

BUILDING

A

A

A.1

A.1 A.3A.2 B C.1

D.2

D.2C

D.1

D.1D

E.1

E

F

F

G

G

H

H

J.1

J

H.2 J.2

K

L M

M

N

N

O

O

P

P Q

R.3

R.1

R.1 R.2 S U

V.3

V.3T V.2V V.1

A.4 B.1 B.2 C.2 R.4 T.1 T.2 U.1

G.1 H.1 K.2

N.1

N.1

R

01ET400a

01ET400a

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1 WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

DUPLICATION

GE09A

OFFICE

GE10A

STORAGE

GE10

OI&T

GE11

MAIL RM.

GE09

CORRIDOR

H001

STORAGE

GE07

STORAGE

GE12

OI&T

GE13

TOILET

GE05

STORAGE

GE04

STORAGE

GE03

VEST.

GE02

STORAGE

GE01

STAIRWELL #1

S001

LINEN CHUTE

GE15

CORRIDOR

H002

STORAGE

GE16

CORRIDOR

H003

STORAGE

GE18

STORAGE

GE18A

STORAGE

GE18B

ELEVATOR #2

E2

HAC

GE35

HAC

GE34

RECEIVING

GE17

STORAGE

GE19

CORRIDOR

H004

OFFICE

GE21

OFFICE

GE20

PREP. RM.

GE32

TOILET

GE22

TOILET

GE23

CORRIDOR

GE31

CORRIDOR

H005

DECONTAMINATION AREA

GE29

MECH. RM.

GE26

HAC

GC09

COOLER

GC10A

MECH. RM.

GC10B

TOILET, MEN

GC08

HAC

GC07A

CORRIDOR

H008

FILE RM.

GC03

STORAGE

GC02

UTILITY RM.

GC01

TRANSFORMER RM.

GC16A

MECH. RM.

GC13

OI&T

GC12

FACILITIES ENGINEERING

GC17C

CORRIDOR

H007

STORAGE

GC17BELECTRIC CARTS

GC17E

SERVICE RM.

GC22

STORAGE

GC21

STORAGE

GC20

STORAGE

GC19

HAC

GC17G

PATRIOT CAFE

GC17

PUMP RM.

GC18

IV RM.

GW05A

UNLOADING AREA

GW04A

PHARMACY

GW04

OFFICE

GW06

PHARMACY

GW07

DISPENSING

GW08

MECH. RM.

GW03

WAITING RM.

GW02

CORRIDOR

H010

PRESCRIPTION INTAKE

GW09

WAITING RM.

GW09A

CHECK-IN

GW10B

HAC

GW10A

STAIRWELL #3

S003

STORAGE

GW19

OFFICE

GW10

MECH. RM.

GW11

LOCKER RM., FEMALE

GW17

OFFICE

GW12

OFFICE

GW12A

OFFICE

GW12B

OFFICE

GW12C

FLUID STORAGE

GW16

TELEMED

GW15

STORAGE

GW13

TOILET

GE14

PHARMACY SUPPLIES

GW05

ELEVATOR #1

E02

CORRIDOR

H011

STORAGE

GW19A

CORRIDOR

H009

PHARMACY VAULT

GW14

TOILET, FEMALE

GW18

MECH.

GC17A

STORAGE

GC17D

ELEC. CLOSET

GC15

ELEC. SUPPLY

GC15A

OI&T

GC12A

OI&T

GC11B

OI&T

GC11A

CORRIDOR

H006

UTILITY RM.

GE06

HAC

GE24

STEAM RM.

GE28

STORAGE

GE32A

CANTEEN

GC17F

D.W.

E3

CHASE

CH-C-1

CHASE

CH-W-1

UNDER CONSTRUCTION

GW17A

STAIRWELL #4

S004

WAP 1

WAP 1

WAP 1

2 2

WAP 1

WAP 1

2 2

10.1

8.1

TYP

STORAGE

GE19

01ET400b

01ET400b

Hand Hole

SIDE-B FIBER-

OPTIC BACKBONE:

REFERENCE

COMMUNICATION

SHEETS FOR

ADDITIONAL

INFORMATION

REGARDING

HANDHOLE,

CONDUIT, FIBER-

OPTIC CABLING,

AND RACEWAY

INFORMATION

B-SIDE:

TO TR 1E15

FROM GC12 TDU

TYP

B-SIDE:

TO TR 2C10A,

E303, AND 3C13

FROM GC12 TDU

B-SIDE:

TO TR C102D

FROM GC12 TDU

EXISTING SIDE-A FIBER-OPTIC BACKBONE

BUILDING ENTRY POINT (APPROXIMATE

LOCATION). ROUTE FIBER-OPTIC CABLES TO TRs

AS INDICATED ON COMMUNICATIONS DRAWINGS;

REFERENCE COMMUNICATIONS DRAWINGS FOR

ALL FIBER-OPTIC CABLING, RACEWAY TYPES,

SPECIFICATIONS, AND RATINGS. REFERENCE KEY

NOTES ON THIS SHEET REGARDING CABLE TRAY

AND VERTICAL/HORIZONTAL ROUTING FOR

ADDITIONAL FIBER BACKBONE CABLING

REQUIREMENTS.

DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE

SERVED FROM TELECOMMUNICATION ROOM GC12.

ALL BACKBONE CABLING ROUTES ARE

DIAGRAMMATICAL; CONTRACTOR SHALL ENSURE A-

SIDE AND B-SIDE ROUTING IS AS DIVERSE AS

PRACTICAL. REFERENCE COMMUNICATIONS

DRAWINGS FOR ALL REQUIRED FIBER-OPTIC

CABLING.

TYP

BLDG 01

AREA OF WORK

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED SHALL

BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF REQUIRED.

COORDINATE WITH ARCHITECTURAL DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE UPGRADED WITH CAT6A PORTS AND CABLE QUANTITIES

INDICATED, UNLESS NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED BY EXISTING CABLING AS CONDUIT FILL ALLOWS.

PROVIDE ADDITIONAL RACEWAYS TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY

INDICATED.

7. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT6A CABLING FROM EACH WAO (WORK AREA OUTLET) TO ITS

RESPECTIVE TR.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT CONDUIT RUNS, OR CONDUIT CONTAINING BENDS

TOTALING MORE THAN 180 DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR PARTITION TYPES

AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD; DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING TRANSPORTATION, FOR ALL WORK TO DESIRED VA

STORAGE LOCATION. COORDINATE WITH VA AS REQUIRED.

12. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

13. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE DIAGRAMMATICAL.

COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS, ARCHITECTURAL FEATURES,

MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER OBSTRUCTIONS PRIOR TO

INSTALLATION.

- 1/16" = 1'-0"

1 BLDG 01 - FLOOR 0 - TELECOMMUNICATIONS PLAN

PROJECT

NORTH

0' 8' 16' 32'

KEY PLAN

PROJECT

NORTH

KEY NOTES

GENERAL NOTES

PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE EXISTING TELECOMMUNICATIONS OUTLET;

EXISTING OUTLET CONDUIT SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE SHEET DETAIL '1' ON SHEET ET503 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.

EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH CAT6A CABLING.

REMOVE AND REPLACE EXISTING CABLE TRAY IN THE AREAS SHOWN AS REQUIRED; IF CABLE TRAY IS NON-EXISTENT, PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL ‘6’ ON SHEET ET503 AND TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET ET701. WHERE WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO CONDUIT SLEEVES [(2) 4”, MINIMUM] WITH APPROPRIATE FIRE-PROOFING AND CAULKING TO PASS THROUGH WALL WHERE EXISTING CABLE TRAY AND/OR SLEEVES ARE DISCOVERED, EVALUATE CONDITION AND RACEWAY CAPACITY; IF CABLE TRAY AND/OR SLEEVES APPEAR TO BE REUSABLE, NOTIFY

COR FOR POSSIBLE REUSE.

FIBER-OPTIC CABLE VERTICAL ROUTING; COORDINATE EXACT LOCATIONS PRIOR TO INSTALLATION. UTILIZE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AND ALL REQUIRED APPURTENANCES AS REQUIRED. REFERENCE DETAIL 2 ON SHEET ET503 FOR ADDITIONAL

INFORMATION.

FIBER-OPTIC CABLE HORIZONTAL ROUTING SHALL BE CONCEALED ABOVE DROP CEILING WHEREVER POSSIBLE. UTILIZE CABLE TRAY AS APPLICABLE. PROVIDE CONDUIT SLEEVE WITH FIREPROOFING AS REQUIRED WHERE WALL PENETRATIONS ARE REQUIRED.

REFERENCE DETAIL 2 ON SHEET ET503 FOR ADDITIONAL INFORMATION.

UTILIZE EXISTING PACS SECURITY HEAD END LOCATION FOR NEW OR RELOCATED PACS SECURITY TR EQUIPMENT. UPGRADE OR MODIFY EXISTING HEAD END LOCATION AS REQUIRED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL TR PACS SECURITY SYSTEM.

PROVIDE EQUIPMENT, RACEWAYS, AND CABLING AS REQUIRED. COORDINATE WITH VA PRIOR TO CONSTRUCTION. CONTRACTOR SHALL

VERIFY EXACT HEAD END LOCATION AS REQUIRED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

657-21-701JB

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES 01ET100

BLDG 01 - FLOOR 0 -

TELECOMMUNICATIONS PLAN 01

LRL/WNM JGE/JBB

CONSTRUCTION

DOCUMENTS

03/31/2022

Revisions: Date:

2 2

2 2

2 2

4160 VO

LTS

DUST CO

LLECTO

R

LIQ UEFIED PETRO LEUM G AS

FLAM M ABLE G AS 2

TRASH COM

PACTO

R

P

SILVERBUILDING 1 23

VA PO

LICE

E

LECTRIC ACCESS

TRANSFO

RM

ER

TRANSFO

RM

ER

TRANSFO

RM

ER

HVAC UNIT

E

LECTRIC PANEL

HVAC UNIT

S&C PAD M

O

UNTED G

EAR

CATALO

G

# 55152-C3DGIG

2P1V M

O

DEL# PM

H-9

EE13299 SG

-52

13278

BUILDING

CONNECTING CORRIDORS

TO BUILDING 23

CONNECTING CORRIDORS

TO BUILDING 24

UP

UP

UP

UP

EXTERIOR

SURFACE

BASEMENT

LEVEL

TRENCH

STAIRS TO

BASEMENT

LEVEL

ROOF

BELOW

A

A

A.1

A.1 A.3A.2 B C.1

D.2

D.2C

D.1

D.1D

E.1

E

F

F

G

G

H

H

J.1

J

H.2 J.2

K

L M

M

N

N

O

O

P

P Q

R.3

R.1

R.1 R.2

S U

V.3

V.3T V.2V V.1

A.4 B.1 B.2 C.2 R.4 T.1 T.2 U.1

4.7

8.1

10.1

G.1

G.1 K.2

N.1

N.1

R

01ET401a

01ET401b

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 4

WAP 1

WAP 4

01ET401a

01ET401a

OFFICE

C105

EXISTING DISPATCH

1E11A

GROUP ROOM

1W08B

GROUP ROOM

1W08A

OFFICE

1W09

VEST.

1W08

TOILET

1W07A

WAITING ROOM

1W07OFFICE

1W10

OFFICE

1W11A

CORRIDOR

H119

OFFICE

1W06

TOILET

1W05

VEST.

1W06A

OFFICE

1W11B

CONSULT

1W12

OFFICE

1W04

CORRIDOR

1W13

CONSULT

1W03

MECH. RM.

1W02

CONSULT

1W14

OFFICE

1W15

ELEV 1

E1

MECH

1W01

CORRIDOR

H116

OFFICE

1W16

STAIR 3

S103

TOILET

1W31

CONSULT

1W17

STORAGE

1W18

WAITING

1W30AOFFICE

1W18A

OFFICE

1W20

OFFICE

1W21

OFFICE

1W22A

OFFICE

1W30

OFFICE

1W29

TOILET

1W28

WAITING RM.

1W27

OFFICE

1W22

HALLWAY

1W24

TOILET

1W25

STORAGE

1W23

SHARED OFFICE

C106A OFFICE

C106

OFFICE

C108

LACTATION

C108A

CORRIDOR

H111

OT GROUP ROOM

C104

CONTROL

C102E

FES UTILITY

C101

STAIR 2

S102

VEST.

H109

CLEAN UTILITY

C102J

CORRIDOR

H113

OFFICE

C110

COPY RM.

C109

OFFICE

C111

OFFICE

C112

OFFICE

C113

OFFICE

C114

OFFICE

C115OFFICE

C116

OFFICE

C117

OFFICE

C115A

OFFICE

C115B

AGENT CASHIER

C119

OFFICE

C122A

OFFICE

C122

VACANT

C120

HAC

C121

VACANT

C123C

OFFICE

C123B

OFFICE

C123A

LOBBY

C124

HALLWAY

C123

CORRIDOR

H106

TOILET, MALE

C127

TOILET, FEMALE

C126

OFFICE

C125

CLOSET

C126A

MEDICAL PROVIDERS

PREP

STAIRWELL NO. 1

S101

CLEAN LINEN RM.

1E136

COPY/STORAGE

1W13A

STORAGE

C129

WAITING RM.

C131

ALCOVE

H113A

CORRIDOR

H118

CORRIDOR

H117

CORRIDOR

1W28A

ALCOVE

H117A

CORRIDOR

H114

RECEPTION

C118

CORRIDOR

H110

CORRIDOR

H108

CORRIDOR

H107

WAITING RM.

C128

CORRIDOR

H115

TOILET

C103

CLOSET

1W06B

CHASE

CH-C-1

ELEVATOR NO. 2

E2

CHASE

CH-1W-4

CHASE

CH-1W-3

CHASE

CH-1W-2

CHASE

CH-C-2

CHASE

CH-C-3

CHASE

CH-1W-1

D.W.

E3

UTILITY

E4

WAITING RM.

H115A

MAIL RM.

C115C

AGENT CASHIER

C119B

TOILET

C127

STAIR 4

S104

CHASE

CH-E-2

CHASE

CH-E-1

CHASE

CH-C-5

CHASE

CH-1W-6

CHASE

CH-C-4COMMUNITY BREAK ROOM

1W32

TR

C102D

MVP

C102A

TRAINING

MENS RESTROOM/LOCKER ROOM

STORAGE

106A

CORRIDOR

KITCHENETTE

HOLDING

ARMS

WOMENS RESTROOM/LOCKER

ROOM

STORAGE

1E13

INTERVIEW

STORAGE

1E02

STORAGE

1E01

STORAGE

1E14

DATA OUTLETS AND

DEVICES IN THIS AREA

SHALL BE SERVED

FROM

TELECOMMUNICATION

ROOM C102D

DATA OUTLETS AND

DEVICES IN THIS AREA

SHALL BE SERVED

FROM

TELECOMMUNICATION

ROOM 1E15

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

01ET401a

01ET401b

01ET401a

01ET401b

TR

1E15

MEDICATION/LOGISTICS

EXAM

EXAM

EXAM

SOILED UTILITY

EXAM

EXAM

DOCTOR OFFICE

IMAGING

RESTROOM

EXAM

EXAM

EXAM

LPN/VITALS

WAITING

RECEPTION

SERVER RM

1E07

B-SIDE:

TO TR 2C10A, E303,

AND 3C13 FROM

GC12 TDU, FROM

FLR 00 TO 01

B-SIDE:

TO TR 2C10A, E303,

AND 3C13 FROM

GC12 TDU, FROM

FLR 01 TO 02

TYP

B-SIDE:

TO TR 1E15 FROM

GC12 TDU

B-SIDE:

TO TR C102D

FROM GC12 TDU

ALL BACKBONE CABLING ROUTES ARE

DIAGRAMMATICAL; CONTRACTOR SHALL ENSURE A-SIDE

AND B-SIDE ROUTING IS AS DIVERSE AS PRACTICAL.

REFERENCE COMMUNICATIONS DRAWINGS FOR ALL

REQUIRED FIBER-OPTIC CABLING.

TYP

5 6

BLDG 01

AREA OF WORK

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED. COORDINATE WITH ARCHITECTURAL DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE UPGRADED WITH CAT6A PORTS AND CABLE

QUANTITIES INDICATED, UNLESS NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS TO EXTEND TO ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A

FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT 6A CABLING FROM EACH WAO (WORK

AREA OUTLET) TO ITS RESPECTIVE TR.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT CONDUIT RUNS, OR CONDUIT

CONTAINING BENDS TOTALING MORE THAN 180 DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL

DRAWINGS FOR PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD; DOCUMENT VARIANCES ON AS-

BUILT DRAWINGS.

10. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING TRANSPORTATION, FOR ALL WORK

TO DESIRED VA STORAGE LOCATION. COORDINATE WITH VA AS REQUIRED.

11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY

DIVIDERS AS REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

13. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE DIAGRAMMATICAL.

COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS, ARCHITECTURAL FEATURES,

MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER OBSTRUCTIONS PRIOR TO

INSTALLATION.

- 1/16" = 1'-0"

1 BLDG 01 - FLOOR 1 - TELECOMMUNICATIONS PLAN

PROJECT

NORTH

0' 8' 16' 32'

KEY PLAN

KEY NOTES

GENERAL NOTES

PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE EXISTING

TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE SHEET DETAIL '1' ON SHEET ET503 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL

INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.

EXISTING WIRELESS ACCESS POINT TO BE RE-FED WITH CAT6A CABLING.

REMOVE AND REPLACE EXISTING CABLE TRAY IN THE AREAS SHOWN AS REQUIRED; IF CABLE TRAY IS NON- EXISTENT, PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL ‘6’ ON SHEET ET503 AND TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET ET701. WHERE WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO CONDUIT SLEEVES [(2) 4”, MINIMUM] WITH APPROPRIATE FIRE-PROOFING AND CAULKING TO PASS THROUGH WALL WHERE EXISTING CABLE TRAY AND/OR SLEEVES ARE DISCOVERED, EVALUATE CONDITION AND RACEWAY CAPACITY; IF CABLE TRAY AND/OR SLEEVES APPEAR TO BE REUSABLE, NOTIFY COR FOR POSSIBLE

REUSE

FIBER-OPTIC CABLE VERTICAL ROUTING; COORDINATE EXACT LOCATIONS PRIOR TO INSTALLATION. UTILIZE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AND ALL REQUIRED APPURTENANCES AS REQUIRED. REFERENCE DETAIL 2

ON SHEET ET503 FOR ADDITIONAL INFORMATION.

UTILIZE EXISTING PACS SECURITY HEAD END LOCATION FOR NEW OR RELOCATED PACS SECURITY TR EQUIPMENT.

UPGRADE OR MODIFY EXISTING HEAD END LOCATION AS REQUIRED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL TR PACS SECURITY SYSTEM. PROVIDE EQUIPMENT, RACEWAYS, AND CABLING AS REQUIRED.

COORDINATE WITH VA PRIOR TO CONSTRUCTION. CONTRACTOR SHALL VERIFY EXACT HEAD END LOCATION AS

REQUIRED.

SECURITY SYSTEMS CAMPUS WIDE HEADEND EQUIPMENT LOCATED IN 1E11. COORDINATE EXACT LOCATION WITH VA. PROVIDE NEW FIBER-OPTIC CONNECTION AS REQUIRED TO ASSIMILATE WITH THE NEW FIBER-OPTIC BACKBONE UPGRADE; REPLACE EXISTING HARDWARE AS REQUIRED. REFERENCE SHEET 01ET401b FOR ADDITIONAL

INFORMATION.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

ST. LOUIS VA MEDICAL CENTER - JEFFERSON BARRACKS, MO

657-21-701JB

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES 01ET101

BLDG 01 - FLOOR 1 -

TELECOMMUNICATIONS PLAN 01

LRL/WNM JGE/JBB

CONSTRUCTION

DOCUMENTS

03/31/2022

Revisions: Date:

PROJECT

NORTH

2 2

2 2

2 2

2 22

4160 VO

LTS

DUST CO

LLECTO

R

LIQ UEFIED PETRO LEUM G AS

FLAM M ABLE G AS 2

TRASH COM

PACTO

R

P

SILVERBUILDING 1 23

VA PO

LICE

E

LECTRIC ACCESS

TRANSFO

RM

ER

TRANSFO

RM

ER

TRANSFO

RM

ER

HVAC UNIT

E

LECTRIC PANEL

HVAC UNIT

S&C PAD M

O

UNTED G

EAR

CATALO

G

# 55152-C3DGIG

2P1V M

O

DEL# PM

H-9

EE13299 SG

-52

13278

BUILDING

ROOF BELOW

ROOF BELOW

DNUP

DN

UP

SHRED

REF

1 2

REF

MICRO

A

A

A.1

A.1 A.3A.2 B C.1

D.2

D.2C

D.1

D.1D

E.1

E F G H

J.1

J

H.2 J.2

K

L

M N O P Q

R.2

R

R

R.1

R.1

S U

V.3

V.3T

V.2

V.2V V.1

A.4 B.1 B.2 C.2 R.3 T.1 T.2 U.1

10.1

8.1

01ET402

01ET402

WAP 1

WAP 1 WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 4

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 4

WAP 1 WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1

WAP 1 WAP 1

WAP 1

WAP 1

WAP 1

WAP 4

WAP 1

WAP 1 WAP 1

OFFICE

2W29B

WAP 1 WAP 1

WAP 1

WAP 1

WAP 4

TYP

LAB.

2C07

LAB.

2C08UNDER CONSTRUCTION

2C09

CORRIDOR

H204

OFFICE

2C04

VETERAN HEALTH EDUCATION

2C03

LOW VISION THERAPY

2C02

OFFICE

2C01A

LOW VISION CLINIC

2C01

RECEPTION

2C01B

WAITING RM.

2E27

TOILET

2E28

OXYGEN STORAGE

2E30

EXAM

2E29

TOILET, STAFF

2E31

OFFICE

2C05

HAC

2C06

CORRIDOR

H210 STORAGE

2E16A

EXAM

2E21

EXAM

2E20

TOILET

2E22A

CORRIDOR

H203

OFFICE

2E22

STAIR 1

S201

EXAM

2E26

TOILET

2E25B

EXAM

2E25A

OFFICE

2E23

TOILET

2E24

EXAM

2E25

HIMS WORK ROOM

2C19

CORRIDOR

H206

EXAM

2W22C

TOILET

2W23

OFFICE

2W26

OFFICE

2W24

MECH

2W25

CORRIDOR

H207

OFFICE

2W27

OFFICE

2W28

OFFICE

2W28A

OFFICE

2W29

OFFICE

2W28C

TELEHEALTH

2W28B

CLEAN SUPPLY

2W29A

STORAGE

SW29C

TOILET, STAFF

2W29F

VEST.

2W29E

TELEHEALTH

2W29D

OFFICE

2W33

EXAM

2W32

OFFICE

2W30

HAC

2W36

TOILET

2W34

SHARED OFFICE

2W35

STAIR 3

S203

STORAGE

2C22

TOILET

2C24

STORAGE

2C21

LAB.

2C20

OFFICE

2C29

STAIR 2

S202LAB.

2C23

TOILET, FEMALE

2C27

HAC

2C28

EXAM

2C25

EXAM

2C11

OPTICAL SHOP

2C12

NURSE STATION

2C13

EXAM

2C14

ELEC RM.

2C18

KITCHENETTE

2C17

SHARED OFFICE

2C15

TOILET, MALE

2C16

CORRIDOR

H205

CLOSET

2C20A

TOILET

2W03

MED. PREP.

2W04

STORAGE

2W05

BREAK RM.

2W06

TOILET

2W08

EXAM

2W07

TOILET

2W11

EXAM

2W10

EXAM

2W09

EXAM

2W12

RECEPTION

2W01

CORRIDOR

H208

CORRIDOR

H209

OFFICE

2W21

PATIENT NOUR.

2W22

OFFICE

2W22A

CLEAN LINEN / STORAGE

2W22B

CORRIDOR

2W19

TOILET, STAFF

2W20

SHARED OFFICE

2W18

TOILET

2W17

TOILET

2W14

EXAM

2W15

EXAM

2W16

EXAM

2W13

FAX RM.

2W02

ELEV 1

E1

CHASE

CH-C-6

CHASE

CH-C-3

CHASE

CH-C-1

ELEC. CLOSET

2C03A

CHASE

CH-E-3

CHASE

CH-W-2

CHASE

CH-W-4

CHASE

CH-W-3

CHASE

CH-W-5

ELEVATOR NO. 2

E2

CHASE

CH-C-4

D.W.

E3

CHASE

CH-W-8

CHASE

CH-E-8

STAIR 4

S204

2 2

WAP 1

2 2

WAP 1

WAP 1

WAP 1

2 2 2

WAP 1

01ET402

TR

2C10A

LAB.

2C10

RECEPTION

2E18

VITAL SIGN RM

2E19

KITCHENETTE

2E17

EXAM

2E16

LACTATION RM

2E15

STORAGE

2E03

HAC

2E01

STORAGE

2E02

TREAT RM

2E13

OFFICE

2E12

ELEC RM

2E04

TOILET

2E05A

OFFICE

2E05

TELERETINAL IMAGING

2E11

TOILET

2E10

OFFICE

2E09

FAX RM

2E05B

OFFICE

2E06

OFFICE

2E08

TOILET

2E06A

TOILET

2E07B

OFFICE

2E07

TOILET

2E07C

OFFICE

2E07A

CORRIDOR

H201

B-SIDE:

TO TR 2C10A, E303,

AND 3C13 FROM

GC12 TDU, FROM

FLR 01 TO 02

TYP

DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE

SERVED FROM TELECOMMUNICATION ROOM 2C10A.

ALL BACKBONE CABLING ROUTES ARE

DIAGRAMMATICAL; CONTRACTOR SHALL ENSURE A-

SIDE AND B-SIDE ROUTING IS AS DIVERSE AS

PRACTICAL. REFERENCE COMMUNICATIONS

DRAWINGS FOR ALL REQUIRED FIBER-OPTIC CABLING.

BLDG 01

AREA OF WORK

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL FIELD VERIFY

ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS REQUIRED. ALL RACEWAYS

AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED SHALL BE DEMOLISHED

BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY DAMAGED

MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE REPAIRED OR REPLACED AT

THE EXPENSE OF THE CONTRACTOR TO THE ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE RATING OR NEW

FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE UPGRADED WITH CAT6A

PORTS AND CABLE QUANTITIES INDICATED, UNLESS NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS TO EXTEND TO ASSOCIATED

TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT

QUANTITY INDICATED.

7. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT6A CABLING FROM

EACH WAO (WORK AREA OUTLET) TO ITS RESPECTIVE TR.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180 DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND…