50-M704.pdf
PDF 275 KB Posted
- Attached to
- Y1DA--Expand and Renovate Emergency Department B50 Minor Construction - Tucson VAMC (VA-24-00001448)
- Solicitation number
- 36c77623r0191
About this file
This document is a control diagram and points list for a ductless split system (DSS-1) and heating hot water pumps related to a federal contract opportunity.
The key details include:
- The ductless split system shall have a wall-mounted programmable controller to maintain a room temperature setpoint of 72°F. An independent sensor will monitor room temperature and send an alarm to the BMS if it rises above 85°F.
- The control sequence for the variable air terminal boxes is described, including how they will maintain cooling and heating setpoints by modulating airflow and enabling heating valves.
- The control sequence for the heating hot water pumps is provided, including lead/standby operation, differential pressure control, and associated alarms.
- The contract opportunity is for the expansion and renovation of the Emergency Department B50 at the Tucson VAMC, with a solicitation number of 36c77623r0191 and an opportunity type of Solicitation.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
M
1. DUCTLESS SPLIT SYSTEMS (DSS-1)
A. DUCTLESS SPLIT SYSTEMS SHALL HAVE SYSTEM MANUFACTURER'S STANDARD WALL-MOUNTED PROGRAMMABLE CONTROLLER. SYSTEM
SHALL OPERATE UNDER ITS BUILT-IN, FACTORY INSTALLED CONTROL SYSTEM TO MAINTAIN ROOM TEMPERATURE SET POINT (72°F). AN INDEPENDENT, WALL-MOUNTED TEMPERATURE SENSOR SHALL MONITOR ROOM TEMPERATURE AND SEND AN ALARM TO THE BMS PANEL IF ROOM TEMPERATURE RISES ABOVE 85°F (ADJUSTABLE). HIGH TEMPERATURE ALARM SHALL REQUIRE MANUAL RESET. THE BMS SHALL
MONITOR COMPRESSOR STATUS.
BI-COMPRESSOR STATUS
CT
BI-FAN STATUS
EP
AI-SPACE TEMPERATURE
EP
AIR-COOLED CONDENSER
DUCTLESS SPLIT SYSTEM EVAPORATOR FAN
CT
AI -ZONE TEMP
AI -ZONE SETPOINT ADJUST
SEQUENCE OF OPERATION
VARIABLE TERMINAL AIR BOX
1. GENERAL
A. THE VARIABLE TERMINAL AIR BOX SHALL ACCORDING TO USER DEFINABLE TIME SCHEDULE IN THE
FOLLOWING MODES:
2. TEMPERATURE CONTROL
A. THE UNIT SHALL MAINTAIN
a. A 75°F (ADJ) COOLING SETPOINT
b. A 72°F (ADJ) HEATING SETPOINT
B. THE UNIT SHALL MAINTAIN ZONE SETPOINTS BY CONTROLLING THE AIRFLOW THROUGH ONE OF THE
FOLLOWING.
C. NORMAL AND EMERGENCY MODE:
a. WHEN THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT, THE ZONE DAMPER
SHALL MODULATE BETWEEN THE MINIMUM OCCUPIED AIRFLOW (ADJ) AND THE MAXIMUM COOLING
AIRFLOW (ADJ) UNTIL THE ZONE IS SATISFIED.
b. WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING SETPOINT AND THE HEATING SETPOINT, THE ZONE DAMPER SHALL MAINTAIN THE MINIMUM ZONE AIRFLOW (ADJ).
c. WHEN THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT, THE CONTROLLER SHALL
ENABLE HEATING VALVE AND THE ZONE DAMPER SHALL MODULATE BETWEEN THE MINIMUM AND
MAXIMUM HEATING CFM TO MAINTAIN THE ZONE TEMPERATURE AT THE HEATING SETPOINT.
NOTE:
1. PROVIDE CONTROL TRANSFORMER
SERVINGLOCAL GROUPS OF AIR TERMINAL
UNITS (5 VAV BOXES MAX PER TRANSFORMER.)
AO - REHEAT VALVE
AI - DISCHARGE AIR TEMPERATURE
DISCHARGE AIR
AO - ZONE DAMPER
AI - AIRFLOW
SUPPLY AIR
T M
H W
S H
W R
T
T
T
HEAT EXCHANGER
VFD
DPS
SEQUENCE OF OPERATION
HEATING HOT WATER PUMPS
1. GENERAL
A. TWO 100% CAPACITY HEATING WATER PUMPS ARE PROVIDED IN THE SYSTEM (ONE
PUMP IS REDUNDANT).
2. HOT WATER PUMP LEAD/STANDBY OPERATON:
A. THE TWO HOT WATER PUMPS SHALL OPERATE IN LEAD/STANDBY FASHION.
a. THE LEAD PUMP SHALL RUN FIRST.
b. ON FAILURE OF THE LEAD PUMP, THE STANDBY PUMP SHALL RUN AND THE LEAD
PUMP SHALL TURN OFF.
B. THE DESIGNATED LEAD PUMP SHALL ROTATE UPON ONE OF THE FOLLOWING
CONDITIONS (USER SELECTABLE):
a. MANUALLY THROUGH A SOFTWARE SWITCH
b. IF PUMP RUNTIME (ADJ.) IS EXCEEDED
c. DAILY
d. WEEKLY
e. MONTHLY
C. ALARMS SHALL BE PROVIDED AS FOLLOWS:
HOT WATER PUMP 1
a. FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
b. RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
c. RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT.
HOT WATER PUMP 2
a. FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
b. RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
c. RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT.
A0 DIFFERENTIAL PRESSURE SETPOINT
AI DIFFERENTIAL PRESSURE SETPOINT
HWS HWS HWS
HWR HWR HWR
HWR
LPS
HWS
VFD
BI HOT WATER PUMP LEAD/LAG
BI PUMP STATUS
BO PUMP START/STOP
AO PUMP VFD SPEED
BI PUMP VFD FAULT
3. HOT WATER DIFFERENTIAL PRESSURE CONTROL:
A. THE CONTROLLER SHALL MEASURE HOT WATER DIFFERENTIAL PRESSURE AND
MODULATE THE HOT WATER PUMP VFD TO MAINTAIN ITS HOT WATER DIFFERENTIAL
PRESSURE SETPOINT. ALL SETPOINTS SHALL BE FIELD ADJUSTED DURING THE
COMMISSIONING PERIOD TO MEET THE REQUIREMENTS OF ACTUAL FIELD CONDITIONS.
B. THE CONTROLLER SHALL MODULATE HOT WATER PUMP SPEEDS TO MAINTAIN A HOT
WATER DIFFERENTIAL PRESSURE (ADJ.). THE VFDS MINIMUM SPEED SHALL NOT DROP
BELOW 20% (ADJ.).
C. ALARMS SHALL BE PROVIDED AS FOLLOWS:
a. HIGH HOT WATER DIFFERENTIAL PRESSURE: IF 25% (ADJ.) GREATER THAN
SETPOINT.
b. LOW HOT WATER DIFFERENTIAL PRESSURE: IF 25% (ADJ.) LESS THAN SETPOINT.
BI HOT WATER PUMP LEAD/LAG
BI PUMP STATUS
BO PUMP START/STOP
AO PUMP VFD SPEED
BI PUMP VFD FAULT
DUCT STATIC PRESSURE
SENSOR 2/3 ON THE
LONGEST RUN.
NOTE TO TEMPERATURE CONTROL CONTRACTOR:
CONTROL CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING THE CORRECT TYPE, SIZES AND QUANTITIES OF
CONTROL CABLES, CONTROLLERS, SENSORS,
TRANSFORMERS, DEVICES AND PROGRAMMING
NECESSARY FOR A FULLY FUNCTIONAL SYSTEM.
o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
VA FORM 08-6231
Office of Facilities Management
U.S. Department of Veterans Affairs
STAMP
Date
Location
Building Number Checked Drawn Drawing Number
Project Number
BID SET
Approved: Director
Approved: Associate Director
Approved: Assistant Director
Approved: Assoc. Director for Patient Care Service/Nurse Executive
Approved: Deputy Assoc. Director of Patient Care Services
Approved: Chief of Staff
Approved: Deputy Chief of Staff
Approved: Chief of Engineering
Approved:
Approved:
ARCHITECT/ENGINEER/CONSULTANTS:
Bancroft Project No.
SAVAHCS, TUCSON, AZ 85723
3300 Dundee Road
Northbrook, IL 60062
T: 847.952.9362
04/30/2024MECHANICAL - CONTROLS EXPAND AND RENOVATE
EMERGENCY DEPARTMENT B50
50 DGG TE
50-M704
678-331
8-
E X
P A
N D
A N
D R
E N
O V
A T
E E
M E
R G
E N
C Y
D E
P A
R T
M E
N T
B
A
D D
E N
D U
M
NOT TO SCALE
DUCTLESS SPLIT SYSTEM (DSS-1) CONTROL DIAGRAM
NOT TO SCALE
VARIABLE TERMINAL AIR BOX
LOW ZONE TEMPERATURE X
LOW DISCHARGE AIR TEMPERATURE X
HIGH ZONE TEMPERATURE X
HIGH DISCHARGE AIR TEMPERATURE X
HEATING/COOLING MODE X X
DISCHARGE AIR TEMPERATURE HEATING LIMIT X
COOLING/HEATING SETPOINT X X X
AIRFLOW SETPOINT X X X
ZONE DAMPER X X X
HOT WATER HEATING VALVE X X X
ZONE TEMPERATURE X X X
AIRFLOW X X X
ZONE SETPOINT ADJUST X X
DISCHARGE AIR TEMPERATURE X X X
POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON GRAPHIC
HARDWARE POINTS SOFTWARE POINTS
VARIABLE TERMINAL AIR BOX POINTS LIST
COMPRESSOR STATUS X X X X
SPACE TEMPERATURE X X X X
FAN STATUS X X
POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON GRAPHIC
HARDWARE POINTS SOFTWARE POINTS
DUCTLESS SPLIT (DSS-1) SYSTEM POINTS LIST
HOT WATER PUMP 2 RUNTIME EXCEEDED X
HOT WATER PUMP 2 RUNNING IN HAND X
HOT WATER PUMP 2 FAILURE X
HOT WATER PUMP 2 START/STOP X X
HOT WATER PUMP 2 STATUS X X X
HOT WATER PUMP 2 VFD FAULT X X X
HOT WATER PUMP 2 VFD SPEED X X X
HOT WATER PUMP 1 RUNTIME EXCEEDED X
HOT WATER PUMP 1 RUNNING IN HAND X
HOT WATER PUMP 1 FAILURE X
HOT WATER PUMP 1 START/STOP X X
HOT WATER PUMP 1 STATUS X X X
HOT WATER PUMP 1 VFD FAULT X X X
HOT WATER PUMP 1 VFD SPEED X X X
LOW HOT WATER DIFF. PRESSURE SETPOINT X
HIGH HOT WATER DIFF. PRESSURE SETPOINT X
HOT WATER DIFF. PRESSURE SETPOINT X X
HOT WATER DIFF. PRESSURE X X X
POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON GRAPHIC
HARDWARE POINTS SOFTWARE POINTS
HEATING HOT WATER PUMPS POINTS LIST
NOT TO SCALE
HEATING HOT WATER PUMPS CONTROL DIAGRAM
Revisions: Date:
BID SET 05/01/2023
ADDENDUM 1 04/30/2024
| Sheets |
| 50-M701 - MECHANICAL - CONTROLS |
| 50-M702 - MECHANICAL - CONTROLS |
| 50-M703 - MECHANICAL - CONTROLS |
| 50-M704 - MECHANICAL - CONTROLS |
File details come from the government source that posted it. Updated .