About this file

The provided document is a technical specification for the control system requirements of the supply fans SF-1-1 and SF-1-2 as part of the HVAC system in the Expand and Renovate Emergency Department B50 project at the Tucson VA Medical Center.

The key details include:

  • The supply fans shall be started/stopped manually at the DDC through a bypass starter and operated at constant speed upon failure of the VFD.
  • The system shall provide alarms for VFD faults, fan failure, and fan running in hand mode.
  • The outside air damper shall open/close automatically with the fans, and alarms shall be provided for damper failure.
  • The supply fan VFD speed shall be modulated to maintain a duct static pressure setpoint.
  • The contractor shall be responsible for providing all necessary controls, sensors, and programming for a fully functional system.

This technical specification is part of the bid set documents for the federal contract opportunity 36c77623r0191 - "Y1DA--Expand and Renovate Emergency Department B50 Minor Construction - Tucson VAMC", issued by the Department of Veterans Affairs Technology Acquisition Center Austin.

View the file

Other files

File Type Posted
50-EP601.pdf PDF
50-M703.pdf PDF
50-A701.pdf PDF
50-A102.pdf PDF
50-M601.pdf PDF
50-EP101.pdf PDF
50-M704.pdf PDF
50-A504.pdf PDF
50-A104.pdf PDF
50-GC102.pdf PDF
50-CU101.pdf PDF
Addendum 1.pdf PDF
50-M505.pdf PDF
50-A502.pdf PDF
50-MG702.pdf PDF
50-AC101.1.pdf PDF
50-MH101.1.pdf PDF
50-EP102.pdf PDF
11 73 00 Ceiling Mounted Patient Lift_Rev.pdf PDF
08 80 00 Glazing_Rev.pdf PDF
50-A401.pdf PDF
50-AC101.4.pdf PDF
50-A303.pdf PDF
50-GC101.pdf PDF
50-MH104.pdf PDF
50-M602.pdf PDF
50-EP602.pdf PDF
01 00 00 Gen Reqs_Rev.pdf PDF
50-MG100.pdf PDF
Technical Questions Spreadsheet - Tucson - Final.pdf PDF
50-A602.pdf PDF
50-M503.pdf PDF
50-CD101.pdf PDF
50-S450.pdf PDF
50-MG701.pdf PDF
50-S310.pdf PDF
50-M701.pdf PDF
36C77623R0191 0003.pdf PDF
36C77623R0191 0002.pdf PDF
36C77623R0191 0001.pdf PDF
Site Visit Sign in Sheet Pg 1 and 2 - Tucson.pdf PDF
Attachment 8 - Architectural Drawings 2 of 2.pdf PDF
Attachment 14 - Mechanical Drawings.pdf PDF
Attachment 6 - Structural Drawings.pdf PDF
36C77623R0191 - 02-22-24.pdf PDF
Attachment 2 - Specifications - 2 of 3.pdf PDF
Attachment 5 - Civil Drawings.pdf PDF
Attachment 20 - Site Visit Instructions.pdf PDF
Attachment 17 - PTube Drawings.pdf PDF
Attachment 7 - Architectural Drawings 1 of 2.pdf PDF
Show 40 more

Latest 50 of 62 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SUPPLY TO

VAV UNITS

SPS-1

AI

EMERGENCY CONSTANT SPEED OPERATION

UPON FAILURE OF THE VFD, THE SUPPLY FANS SHALL BE STARTED/STOPPED MANUALLY AT THE

DDC THROUGH THE BY-PASS STARTER. FANS SHALL THEN BE OPERATED AT CONSTANT

SPEED.

AUTOMATIC SHUTDOWN/RESTART

WHEN SMOKE IS DETECTED BY EXISTING DUCT SMOKE DETECTOR, DSD, THE SUPPLY FANS

SHALL SHUT "OFF" AND AN ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM

SYSTEM.

ALARMS

PROVIDE ALARMS FOR SUPPLY FAN VFD FAULT, SUPPLY FAN FAILURE (COMMANDED "ON" BUT

THE STATUS IS "OFF") AND SUPPLY FAN RUNNING IN HAND (COMMANDED "OFF" BUT THE

STATUS IS "ON").

SUPPLY AIR SMOKE DETECTION:

THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A SUPPLY AIR

SMOKE DETECTOR STATUS.

M

VFD-SF-1-1

SF-1-1

BI (FAN STATUS)

AO (VFD SPEED CONTROL)

BI (VFD FAULT)

BO (FAN START/STOP)

M

VFD-SF-1-2

SF-1-2

BI (FAN STATUS)

AO (VFD SPEED CONTROL)

BI (VFD FAULT)

BO (FAN START/STOP)

GENERAL

UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE DDC. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE.

RUN CONDITIONS - CONTINUOUS

THE UNIT SHALL RUN CONTINUOUSLY.

HIGH STATIC SHUTDOWN:

THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A HIGH STATIC SHUTDOWN

SIGNAL.

OUTSIDE AIR DAMPER

THE OUTSIDE AIR DAMPER SHALL OPEN ANYTIME THE UNIT RUNS AND SHALL CLOSE ANYTIME THE UNIT STOPS. THE SUPPLY FAN SHALL START ONLY AFTER THE DAMPER STATUS HAS PROVEN THE DAMPER IS OPEN. THE OUTSIDE AIR DAMPER SHALL CLOSE 5 SEC (ADJ.) AFTER THE SUPPLY FAN

STOPS.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• OUTSIDE AIR DAMPER FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED.

• OUTSIDE AIR DAMPER IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN.

SUPPLY AIR DUCT STATIC PRESSURE CONTROL:

THE CONTROLLER SHALL MEASURE DUCT STATIC PRESSURE AND SHALL MODULATE THE SUPPLY FAN VFD SPEED TO MAINTAIN A DUCT STATIC PRESSURE SETPOINT OF 1.0" W.C. (ADJ.). THE SUPPLY FAN

VFD SPEED SHALL NOT DROP BELOW 30% (ADJ.).

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• HIGH SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS % (ADJ.)

GREATER THAN SETPOINT.

• LOW SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS % (ADJ.)

LESS THAN SETPOINT.

• SUPPLY FAN VFD FAULT.

DUCT STATIC PRESSURE

SENSOR 2/3 ON THE

LONGEST RUN.

NOTE TO TEMPERATURE CONTROL CONTRACTOR:

CONTROL CONTRACTOR SHALL BE RESPONSIBLE FOR

PROVIDING THE CORRECT TYPE, SIZES AND QUANTITIES OF

CONTROL CABLES, CONTROLLERS, SENSORS,

TRANSFORMERS, DEVICES AND PROGRAMMING

NECESSARY FOR A FULLY FUNCTIONAL SYSTEM.

o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

VA FORM 08-6231

Office of Facilities Management

U.S. Department of Veterans Affairs

STAMP

Date

Location

Building Number Checked Drawn Drawing Number

Project Number

BID SET

Approved: Director

Approved: Associate Director

Approved: Assistant Director

Approved: Assoc. Director for Patient Care Service/Nurse Executive

Approved: Deputy Assoc. Director of Patient Care Services

Approved: Chief of Staff

Approved: Deputy Chief of Staff

Approved: Chief of Engineering

Approved:

Approved:

ARCHITECT/ENGINEER/CONSULTANTS:

Bancroft Project No.

SAVAHCS, TUCSON, AZ 85723

3300 Dundee Road

Northbrook, IL 60062

T: 847.952.9362

04/30/2024MECHANICAL - CONTROLS EXPAND AND RENOVATE

EMERGENCY DEPARTMENT B50

50 DGG TE

50-M702

678-331

8-

E X

P A

N D

A N

D R

E N

O V

A T

E E

M E

R G

E N

C Y

D E

P A

R T

M E

N T

B

A

D D

E N

D U

M

NOT TO SCALE

SUPPLY FAN (SF-1A AND SF-1B) CONTROLS DIAGRAM

SUPPLY FAN SF-1-2 RUNTIME EXCEEDED X

SUPPLY FAN SF-1-1 RUNTIME EXCEEDED X

SUPPLY FAN SF-1-2 IN HAND X

SUPPLY FAN SF-1-1 IN HAND X

SUPPLY FAN SF-1-2 FAILURE X

SUPPLY FAN SF-1-1 FAILURE X

SCHEDULE X

STATIC PRESSURE SETPOINT X X X

SUPPLY FAN SF-1-2 START/STOP X X X

SUPPLY FAN SF-1-1 START/STOP X X X

SUPPLY FAN SF-1-2 VFD FAULT X X

SUPPLY FAN SF-1-1 VFD FAULT X X

SUPPLY FAN SF-1-2 STATUS X X X

SUPPLY FAN SF-1-1 STATUS X X X

SUPPLY FAN SF-1-2 DAMPER ACTUATOR X X X

SUPPLY FAN SF-1-1 DAMPER ACTUATOR X X X

SUPPLY FAN SF-1-2 VFD SPEED CONTROL X X X

SUPPLY FAN SF-1-1 VFD SPEED CONTROL X X X

STATIC PRESSURE SENSOR, SPS-1 X X X

POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON GRAPHIC

HARDWARE POINTS SOFTWARE POINTS

SUPPLY FAN (SF-1-1, AND SF-1-2) POINTS LIST

EXHAUST FAN EF-5-6 VFD FAULT X X

EXHAUST FAN EF-5-5 VFD FAULT X X

EXHAUST FAN EF-5-4 VFD FAULT X X

EXHAUST FAN EF-5-3 VFD FAULT X X

EXHAUST FAN EF-5-2 VFD FAULT X X

EXHAUST FAN EF-5-1 VFD FAULT X X

SUPPLY FAN SF-5-6 VFD FAULT X X

SUPPLY FAN SF-5-5 VFD FAULT X X

SUPPLY FAN SF-5-4 VFD FAULT X X

SUPPLY FAN SF-5-3 VFD FAULT X X

SUPPLY FAN SF-5-2 VFD FAULT X X

SUPPLY FAN SF-5-1 VFD FAULT X X

EXHAUST FAN EF-5-6 STATUS X X X

EXHAUST FAN EF-5-5 STATUS X X X

EXHAUST FAN EF-5-4 STATUS X X X

EXHAUST FAN EF-5-3 STATUS X X X

EXHAUST FAN EF-5-2 STATUS X X X

EXHAUST FAN EF-5-1 STATUS X X X

SUPPLY FAN SF-5-6 STATUS X X X

SUPPLY FAN SF-5-5 STATUS X X X

SUPPLY FAN SF-5-4 STATUS X X X

SUPPLY FAN SF-5-3 STATUS X X X

SUPPLY FAN SF-5-2 STATUS X X X

SUPPLY FAN SF-5-1 STATUS X X X

HUMIDIFIER HUM-5 SETPOINT X X X

COOLING VALVE, V-1 X X X

RELIEF DAMPER, D-9 X X X

MIXED AIR DAMPER, D-8 X X X

RETURN-EXHAUST DAMPER, D-6 X X X

HX BYPASS DAMPER, D-4 X X X

MAX. OUTDOOR AIR DAMPER, D-2 X X X

MIN. OUTDOOR AIR DAMPER, D-1 X X X

EXHAUST FAN EF-5-6 DAMPER ACTUATOR X X X

EXHAUST FAN EF-5-5 DAMPER ACTUATOR X X X

EXHAUST FAN EF-5-4 DAMPER ACTUATOR X X X

EXHAUST FAN EF-5-3 DAMPER ACTUATOR X X X

EXHAUST FAN EF-5-2 DAMPER ACTUATOR X X X

EXHAUST FAN EF-5-1 DAMPER ACTUATOR X X X

SUPPLY FAN SF-5-6 DAMPER ACTUATOR X X X

SUPPLY FAN SF-5-5 DAMPER ACTUATOR X X X

SUPPLY FAN SF-5-4 DAMPER ACTUATOR X X X

SUPPLY FAN SF-5-3 DAMPER ACTUATOR X X X

SUPPLY FAN SF-5-2 DAMPER ACTUATOR X X X

SUPPLY FAN SF-5-1 DAMPER ACTUATOR X X X

EXHAUST FAN EF-5-6 VFD SPEED CONTROL X X X

EXHAUST FAN EF-5-5 VFD SPEED CONTROL X X X

EXHAUST FAN EF-5-4 VFD SPEED CONTROL X X X

EXHAUST FAN EF-5-3 VFD SPEED CONTROL X X X

EXHAUST FAN EF-5-2 VFD SPEED CONTROL X X X

EXHAUST FAN EF-5-1 VFD SPEED CONTROL X X X

SUPPLY FAN SF-5-6 VFD SPEED CONTROL X X X

SUPPLY FAN SF-5-5 VFD SPEED CONTROL X X X

SUPPLY FAN SF-5-4 VFD SPEED CONTROL X X X

SUPPLY FAN SF-5-3 VFD SPEED CONTROL X X X

SUPPLY FAN SF-5-2 VFD SPEED CONTROL X X X

SUPPLY FAN SF-5-1 VFD SPEED CONTROL X X X

POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON GRAPHIC

HARDWARE POINTS SOFTWARE POINTS

AIR HANDLING UNIT (AHU-5) POINTS LIST

EXHAUST FAN EF-5-6 FAILURE X

EXHAUST FAN EF-5-5 FAILURE X

EXHAUST FAN EF-5-4 FAILURE X

EXHAUST FAN EF-5-3 FAILURE X

EXHAUST FAN EF-5-2 FAILURE X

EXHAUST FAN EF-5-1 FAILURE X

SUPPLY FAN SF-5-6 FAILURE X

SUPPLY FAN SF-5-5 FAILURE X

SUPPLY FAN SF-5-4 FAILURE X

SUPPLY FAN SF-5-3 FAILURE X

SUPPLY FAN SF-5-2 FAILURE X

SUPPLY FAN SF-5-1 FAILURE X

LOW RETURN AIR HUMIDITY X

LOW RETURN AIR TEMPERATURE X

LOW MIXED AIR TEMPERATURE X

LOW SUPPLY AIR TEMPERATURE X

LOW SUPPLY AIR STATIC PRESSURE X

HIGH RETURN AIR HUMIDITY X

HIGH RETURN AIR TEMPERATURE X

HIGH MIXED AIR TEMPERATURE X

HIGH SUPPLY AIR TEMPERATURE X

HIGH SUPPLY AIR STATIC PRESSURE X

SCHEDULE X

EXHAUST FAN EF-5-2 VFD HOA STATUS X X X

EXHAUST FAN EF-5-1 VFD HOA STATUS X X X

SUPPLY FAN SF-5-4 VFD HOA STATUS X X X

SUPPLY FAN SF-5-3 VFD HOA STATUS X X X

SUPPLY FAN SF-5-2 VFD HOA STATUS X X X

SUPPLY FAN SF-5-1 VFD HOA STATUS X X X

DEHUMIDIFICATION SETPOINT X X X

BUILDING STATIC PRESSURE SET POINT X X X

FILTER DIFF. PRESSURE ALARM SET POINT X X X

RELIEF AIR FLOW SET POINT, D-9 X X X

EXHAUST AIR FLOW SET POINT, D-5 X X X

RETURN AIR FLOW SET POINT, D-7 X X X

MAX. OUTDOOR AIR FLOW SET POINT, D-2 X X X

MIN. OUTDOOR AIR FLOW SET POINT, D-1 X X X

SUPPLY AIR TEMPERATURE SET POINT X X X

EXHAUST FAN EF-5-6 START/STOP X X X X X

EXHAUST FAN EF-5-5 START/STOP X X X X X

EXHAUST FAN EF-5-4 START/STOP X X X X X

EXHAUST FAN EF-5-3 START/STOP X X X X X

EXHAUST FAN EF-5-2 START/STOP X X X X X

EXHAUST FAN EF-5-1 START/STOP X X X X X

SUPPLY FAN SF-5-6 START/STOP X X X X X

SUPPLY FAN SF-5-5 START/STOP X X X X X

SUPPLY FAN SF-5-4 START/STOP X X X X X

SUPPLY FAN SF-5-3 START/STOP X X X X X

SUPPLY FAN SF-5-2 START/STOP X X X X X

SUPPLY FAN SF-5-1 START/STOP X X X X X

MIXED AIR DAMPER POSITION, D-8 X X X

RETURN DAMPER POSITION, D-7 X X X

RETURN AIR DAMPER POSITION, D-6 X X X

EXHAUST AIR DAMPER POSITION, D-5 X X X

HX DAMPER POSITION, D-3 X X X

HUMIDIFIER HUM-5 ALARM X X

FREEZE PROTECTION X X

SUPPLY DUCT SMOKE DETECTOR, DSD-1 X X X X

DUCT HIGH PRESSURE SAFETY, SPS-2 X X X X

POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON GRAPHIC

HARDWARE POINTS SOFTWARE POINTS

AIR HANDLING UNIT (AHU-5) POINTS LIST

EXHAUST FAN EF-5-6 IN HAND X

EXHAUST FAN EF-5-5 IN HAND X

EXHAUST FAN EF-5-4 IN HAND X

EXHAUST FAN EF-5-3 IN HAND X

EXHAUST FAN EF-5-2 IN HAND X

EXHAUST FAN EF-5-1 IN HAND X

SUPPLY FAN SF-5-6 IN HAND X

SUPPLY FAN SF-5-5 IN HAND X

SUPPLY FAN SF-5-4 IN HAND X

SUPPLY FAN SF-5-3 IN HAND X

SUPPLY FAN SF-5-2 IN HAND X

SUPPLY FAN SF-5-1 IN HAND X

POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON GRAPHIC

HARDWARE POINTS SOFTWARE POINTS

AIR HANDLING UNIT (AHU-5) POINTS LIST

Revisions: Date:

BID SET 05/01/2023

ADDENDUM 1 04/30/2024

Sheets
50-M702 - MECHANICAL - CONTROLS