The provided document is a technical specification for the control system requirements of the supply fans SF-1-1 and SF-1-2 as part of the HVAC system in the Expand and Renovate Emergency Department B50 project at the Tucson VA Medical Center.
The key details include:
- The supply fans shall be started/stopped manually at the DDC through a bypass starter and operated at constant speed upon failure of the VFD.
- The system shall provide alarms for VFD faults, fan failure, and fan running in hand mode.
- The outside air damper shall open/close automatically with the fans, and alarms shall be provided for damper failure.
- The supply fan VFD speed shall be modulated to maintain a duct static pressure setpoint.
- The contractor shall be responsible for providing all necessary controls, sensors, and programming for a fully functional system.
This technical specification is part of the bid set documents for the federal contract opportunity 36c77623r0191 - "Y1DA--Expand and Renovate Emergency Department B50 Minor Construction - Tucson VAMC", issued by the Department of Veterans Affairs Technology Acquisition Center Austin.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUPPLY TO
VAV UNITS
SPS-1
AI
EMERGENCY CONSTANT SPEED OPERATION
UPON FAILURE OF THE VFD, THE SUPPLY FANS SHALL BE STARTED/STOPPED MANUALLY AT THE
DDC THROUGH THE BY-PASS STARTER. FANS SHALL THEN BE OPERATED AT CONSTANT
SPEED.
AUTOMATIC SHUTDOWN/RESTART
WHEN SMOKE IS DETECTED BY EXISTING DUCT SMOKE DETECTOR, DSD, THE SUPPLY FANS
SHALL SHUT "OFF" AND AN ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM
SYSTEM.
ALARMS
PROVIDE ALARMS FOR SUPPLY FAN VFD FAULT, SUPPLY FAN FAILURE (COMMANDED "ON" BUT
THE STATUS IS "OFF") AND SUPPLY FAN RUNNING IN HAND (COMMANDED "OFF" BUT THE
STATUS IS "ON").
SUPPLY AIR SMOKE DETECTION:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A SUPPLY AIR
SMOKE DETECTOR STATUS.
M
VFD-SF-1-1
SF-1-1
BI (FAN STATUS)
AO (VFD SPEED CONTROL)
BI (VFD FAULT)
BO (FAN START/STOP)
M
VFD-SF-1-2
SF-1-2
BI (FAN STATUS)
AO (VFD SPEED CONTROL)
BI (VFD FAULT)
BO (FAN START/STOP)
GENERAL
UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE DDC. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE.
RUN CONDITIONS - CONTINUOUS
THE UNIT SHALL RUN CONTINUOUSLY.
HIGH STATIC SHUTDOWN:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A HIGH STATIC SHUTDOWN
SIGNAL.
OUTSIDE AIR DAMPER
THE OUTSIDE AIR DAMPER SHALL OPEN ANYTIME THE UNIT RUNS AND SHALL CLOSE ANYTIME THE UNIT STOPS. THE SUPPLY FAN SHALL START ONLY AFTER THE DAMPER STATUS HAS PROVEN THE DAMPER IS OPEN. THE OUTSIDE AIR DAMPER SHALL CLOSE 5 SEC (ADJ.) AFTER THE SUPPLY FAN
STOPS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• OUTSIDE AIR DAMPER FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED.
• OUTSIDE AIR DAMPER IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN.
SUPPLY AIR DUCT STATIC PRESSURE CONTROL:
THE CONTROLLER SHALL MEASURE DUCT STATIC PRESSURE AND SHALL MODULATE THE SUPPLY FAN VFD SPEED TO MAINTAIN A DUCT STATIC PRESSURE SETPOINT OF 1.0" W.C. (ADJ.). THE SUPPLY FAN
VFD SPEED SHALL NOT DROP BELOW 30% (ADJ.).
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS % (ADJ.)
GREATER THAN SETPOINT.
• LOW SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS % (ADJ.)
LESS THAN SETPOINT.
• SUPPLY FAN VFD FAULT.
DUCT STATIC PRESSURE
SENSOR 2/3 ON THE
LONGEST RUN.
NOTE TO TEMPERATURE CONTROL CONTRACTOR:
CONTROL CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING THE CORRECT TYPE, SIZES AND QUANTITIES OF
CONTROL CABLES, CONTROLLERS, SENSORS,
TRANSFORMERS, DEVICES AND PROGRAMMING
NECESSARY FOR A FULLY FUNCTIONAL SYSTEM.
o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
VA FORM 08-6231
Office of Facilities Management
U.S. Department of Veterans Affairs
STAMP
Date
Location
Building Number Checked Drawn Drawing Number
Project Number
BID SET
Approved: Director
Approved: Associate Director
Approved: Assistant Director
Approved: Assoc. Director for Patient Care Service/Nurse Executive
Approved: Deputy Assoc. Director of Patient Care Services
Approved: Chief of Staff
Approved: Deputy Chief of Staff
Approved: Chief of Engineering
Approved:
Approved:
ARCHITECT/ENGINEER/CONSULTANTS:
Bancroft Project No.
SAVAHCS, TUCSON, AZ 85723
3300 Dundee Road
Northbrook, IL 60062
T: 847.952.9362
04/30/2024MECHANICAL - CONTROLS EXPAND AND RENOVATE
EMERGENCY DEPARTMENT B50
50 DGG TE
50-M702
678-331
8-
E X
P A
N D
A N
D R
E N
O V
A T
E E
M E
R G
E N
C Y
D E
P A
R T
M E
N T
B
A
D D
E N
D U
M
NOT TO SCALE
SUPPLY FAN (SF-1A AND SF-1B) CONTROLS DIAGRAM
SUPPLY FAN SF-1-2 RUNTIME EXCEEDED X
SUPPLY FAN SF-1-1 RUNTIME EXCEEDED X
SUPPLY FAN SF-1-2 IN HAND X
SUPPLY FAN SF-1-1 IN HAND X
SUPPLY FAN SF-1-2 FAILURE X
SUPPLY FAN SF-1-1 FAILURE X
SCHEDULE X
STATIC PRESSURE SETPOINT X X X
SUPPLY FAN SF-1-2 START/STOP X X X
SUPPLY FAN SF-1-1 START/STOP X X X
SUPPLY FAN SF-1-2 VFD FAULT X X
SUPPLY FAN SF-1-1 VFD FAULT X X
SUPPLY FAN SF-1-2 STATUS X X X
SUPPLY FAN SF-1-1 STATUS X X X
SUPPLY FAN SF-1-2 DAMPER ACTUATOR X X X
SUPPLY FAN SF-1-1 DAMPER ACTUATOR X X X
SUPPLY FAN SF-1-2 VFD SPEED CONTROL X X X
SUPPLY FAN SF-1-1 VFD SPEED CONTROL X X X
STATIC PRESSURE SENSOR, SPS-1 X X X
POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON GRAPHIC
HARDWARE POINTS SOFTWARE POINTS
SUPPLY FAN (SF-1-1, AND SF-1-2) POINTS LIST
EXHAUST FAN EF-5-6 VFD FAULT X X
EXHAUST FAN EF-5-5 VFD FAULT X X
EXHAUST FAN EF-5-4 VFD FAULT X X
EXHAUST FAN EF-5-3 VFD FAULT X X
EXHAUST FAN EF-5-2 VFD FAULT X X
EXHAUST FAN EF-5-1 VFD FAULT X X
SUPPLY FAN SF-5-6 VFD FAULT X X
SUPPLY FAN SF-5-5 VFD FAULT X X
SUPPLY FAN SF-5-4 VFD FAULT X X
SUPPLY FAN SF-5-3 VFD FAULT X X
SUPPLY FAN SF-5-2 VFD FAULT X X
SUPPLY FAN SF-5-1 VFD FAULT X X
EXHAUST FAN EF-5-6 STATUS X X X
EXHAUST FAN EF-5-5 STATUS X X X
EXHAUST FAN EF-5-4 STATUS X X X
EXHAUST FAN EF-5-3 STATUS X X X
EXHAUST FAN EF-5-2 STATUS X X X
EXHAUST FAN EF-5-1 STATUS X X X
SUPPLY FAN SF-5-6 STATUS X X X
SUPPLY FAN SF-5-5 STATUS X X X
SUPPLY FAN SF-5-4 STATUS X X X
SUPPLY FAN SF-5-3 STATUS X X X
SUPPLY FAN SF-5-2 STATUS X X X
SUPPLY FAN SF-5-1 STATUS X X X
HUMIDIFIER HUM-5 SETPOINT X X X
COOLING VALVE, V-1 X X X
RELIEF DAMPER, D-9 X X X
MIXED AIR DAMPER, D-8 X X X
RETURN-EXHAUST DAMPER, D-6 X X X
HX BYPASS DAMPER, D-4 X X X
MAX. OUTDOOR AIR DAMPER, D-2 X X X
MIN. OUTDOOR AIR DAMPER, D-1 X X X
EXHAUST FAN EF-5-6 DAMPER ACTUATOR X X X
EXHAUST FAN EF-5-5 DAMPER ACTUATOR X X X
EXHAUST FAN EF-5-4 DAMPER ACTUATOR X X X
EXHAUST FAN EF-5-3 DAMPER ACTUATOR X X X
EXHAUST FAN EF-5-2 DAMPER ACTUATOR X X X
EXHAUST FAN EF-5-1 DAMPER ACTUATOR X X X
SUPPLY FAN SF-5-6 DAMPER ACTUATOR X X X
SUPPLY FAN SF-5-5 DAMPER ACTUATOR X X X
SUPPLY FAN SF-5-4 DAMPER ACTUATOR X X X
SUPPLY FAN SF-5-3 DAMPER ACTUATOR X X X
SUPPLY FAN SF-5-2 DAMPER ACTUATOR X X X
SUPPLY FAN SF-5-1 DAMPER ACTUATOR X X X
EXHAUST FAN EF-5-6 VFD SPEED CONTROL X X X
EXHAUST FAN EF-5-5 VFD SPEED CONTROL X X X
EXHAUST FAN EF-5-4 VFD SPEED CONTROL X X X
EXHAUST FAN EF-5-3 VFD SPEED CONTROL X X X
EXHAUST FAN EF-5-2 VFD SPEED CONTROL X X X
EXHAUST FAN EF-5-1 VFD SPEED CONTROL X X X
SUPPLY FAN SF-5-6 VFD SPEED CONTROL X X X
SUPPLY FAN SF-5-5 VFD SPEED CONTROL X X X
SUPPLY FAN SF-5-4 VFD SPEED CONTROL X X X
SUPPLY FAN SF-5-3 VFD SPEED CONTROL X X X
SUPPLY FAN SF-5-2 VFD SPEED CONTROL X X X
SUPPLY FAN SF-5-1 VFD SPEED CONTROL X X X
POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON GRAPHIC
HARDWARE POINTS SOFTWARE POINTS
AIR HANDLING UNIT (AHU-5) POINTS LIST
EXHAUST FAN EF-5-6 FAILURE X
EXHAUST FAN EF-5-5 FAILURE X
EXHAUST FAN EF-5-4 FAILURE X
EXHAUST FAN EF-5-3 FAILURE X
EXHAUST FAN EF-5-2 FAILURE X
EXHAUST FAN EF-5-1 FAILURE X
SUPPLY FAN SF-5-6 FAILURE X
SUPPLY FAN SF-5-5 FAILURE X
SUPPLY FAN SF-5-4 FAILURE X
SUPPLY FAN SF-5-3 FAILURE X
SUPPLY FAN SF-5-2 FAILURE X
SUPPLY FAN SF-5-1 FAILURE X
LOW RETURN AIR HUMIDITY X
LOW RETURN AIR TEMPERATURE X
LOW MIXED AIR TEMPERATURE X
LOW SUPPLY AIR TEMPERATURE X
LOW SUPPLY AIR STATIC PRESSURE X
HIGH RETURN AIR HUMIDITY X
HIGH RETURN AIR TEMPERATURE X
HIGH MIXED AIR TEMPERATURE X
HIGH SUPPLY AIR TEMPERATURE X
HIGH SUPPLY AIR STATIC PRESSURE X
SCHEDULE X
EXHAUST FAN EF-5-2 VFD HOA STATUS X X X
EXHAUST FAN EF-5-1 VFD HOA STATUS X X X
SUPPLY FAN SF-5-4 VFD HOA STATUS X X X
SUPPLY FAN SF-5-3 VFD HOA STATUS X X X
SUPPLY FAN SF-5-2 VFD HOA STATUS X X X
SUPPLY FAN SF-5-1 VFD HOA STATUS X X X
DEHUMIDIFICATION SETPOINT X X X
BUILDING STATIC PRESSURE SET POINT X X X
FILTER DIFF. PRESSURE ALARM SET POINT X X X
RELIEF AIR FLOW SET POINT, D-9 X X X
EXHAUST AIR FLOW SET POINT, D-5 X X X
RETURN AIR FLOW SET POINT, D-7 X X X
MAX. OUTDOOR AIR FLOW SET POINT, D-2 X X X
MIN. OUTDOOR AIR FLOW SET POINT, D-1 X X X
SUPPLY AIR TEMPERATURE SET POINT X X X
EXHAUST FAN EF-5-6 START/STOP X X X X X
EXHAUST FAN EF-5-5 START/STOP X X X X X
EXHAUST FAN EF-5-4 START/STOP X X X X X
EXHAUST FAN EF-5-3 START/STOP X X X X X
EXHAUST FAN EF-5-2 START/STOP X X X X X
EXHAUST FAN EF-5-1 START/STOP X X X X X
SUPPLY FAN SF-5-6 START/STOP X X X X X
SUPPLY FAN SF-5-5 START/STOP X X X X X
SUPPLY FAN SF-5-4 START/STOP X X X X X
SUPPLY FAN SF-5-3 START/STOP X X X X X
SUPPLY FAN SF-5-2 START/STOP X X X X X
SUPPLY FAN SF-5-1 START/STOP X X X X X
MIXED AIR DAMPER POSITION, D-8 X X X
RETURN DAMPER POSITION, D-7 X X X
RETURN AIR DAMPER POSITION, D-6 X X X
EXHAUST AIR DAMPER POSITION, D-5 X X X
HX DAMPER POSITION, D-3 X X X
HUMIDIFIER HUM-5 ALARM X X
FREEZE PROTECTION X X
SUPPLY DUCT SMOKE DETECTOR, DSD-1 X X X X
DUCT HIGH PRESSURE SAFETY, SPS-2 X X X X
POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON GRAPHIC
HARDWARE POINTS SOFTWARE POINTS
AIR HANDLING UNIT (AHU-5) POINTS LIST
EXHAUST FAN EF-5-6 IN HAND X
EXHAUST FAN EF-5-5 IN HAND X
EXHAUST FAN EF-5-4 IN HAND X
EXHAUST FAN EF-5-3 IN HAND X
EXHAUST FAN EF-5-2 IN HAND X
EXHAUST FAN EF-5-1 IN HAND X
SUPPLY FAN SF-5-6 IN HAND X
SUPPLY FAN SF-5-5 IN HAND X
SUPPLY FAN SF-5-4 IN HAND X
SUPPLY FAN SF-5-3 IN HAND X
SUPPLY FAN SF-5-2 IN HAND X
SUPPLY FAN SF-5-1 IN HAND X
POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON GRAPHIC
HARDWARE POINTS SOFTWARE POINTS
AIR HANDLING UNIT (AHU-5) POINTS LIST
Revisions: Date:
BID SET 05/01/2023
ADDENDUM 1 04/30/2024
| Sheets |
| 50-M702 - MECHANICAL - CONTROLS |