50-M701.pdf
PDF 342 KB Posted
- Attached to
- Y1DA--Expand and Renovate Emergency Department B50 Minor Construction - Tucson VAMC (VA-24-00001448)
- Solicitation number
- 36c77623r0191
About this file
This document appears to be a Sequence of Operation for an Air Handling Unit (AHU-5) as part of the Expand and Renovate Emergency Department B50 project at the Tucson VA Medical Center.
The document provides detailed specifications for how the AHU-5 unit should operate, including its run conditions, interface with the building automation system, operating modes (normal, emergency/pandemic), damper positions, fan and valve controls, air pressure and temperature monitoring, economizer cycle, energy recovery, humidification, dehumidification, and alarm conditions. Key control points and hardware/software requirements are listed. The unit is designed to provide continuous operation and maintain specific temperature, humidity, and air pressure setpoints to support the expanded emergency department facility.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SEQUENCE OF OPERATION: AHU-5
RUN CONDITIONS - CONTINUOUS
THE UNIT SHALL RUN CONTINUOUSLY.
BUILDING AUTOMATION SYSTEM INTERFACE:
THE BUILDING AUTOMATION SYSTEM (BAS) SHALL SEND THE CONTROLLER NORMAL,
EMERGENCY, ENERGY RECOVERY, COOLING, HUMIDIFICATION AND ECONOMIZER MODES. THE
BAS SHALL ALSO SEND THE DISCHARGE AIR TEMPERATURE SETPOINT AND THE DUCT STATIC
PRESSURE SETPOINT. IF A BAS IS NOT PRESENT, OR COMMUNICATION IS LOST WITH THE BAS
THE CONTROLLER SHALL OPERATE USING DEFAULT MODES AND SETPOINTS.
GENERAL
UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE DDC. H-O-A SWITCH SHALL BE
KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR
MAINTENANCE. WHEN THE UNIT IS "OFF" DAMPERS D-1 AND D-2 SHALL BE FULLY CLOSED.
WHEN THE UNIT IS "ON" EITHER D-1 OR D-2 SHALL OPEN.
NORMAL MODE:
THE SUPPLY FANS SHALL RUN AND THE MOTORIZED DAMPERS (D-1, D-3, D-5, D-7, AND D-9)
SHALL OPEN. MOTORIZED DAMPER (D-2, D-4, AND D-6) SHALL CLOSE. THE CHILLED WATER
VALVE SHALL BE CONTROLLED TO MAINTAIN THE ACTIVE DISCHARGE AIR TEMPERATURE
SETPOINT.
• THE ECONOMIZER IS DE-ACTIVATED.
• EMERGENCY/PANDEMIC IS DE-ACTIVATED.
EMERGENCY/PANDEMIC MODE:
CONTRACTOR TO PROVIDE OVERRIDE TO ALLOW AIR HANDLING UNIT TO ENTER
EMERGENCY/PANDEMIC MODE. DURING EMERGENCY/PANDEMIC MODE THE FOLLOWING SHALL
OCCUR:
• DAMPER D-3, D-5, D-6, AND D-7 SHALL BE IN THE OPEN POSITION.
• DAMPER D-4 AND D-8 SHALL BE IN THE CLOSED POSITION.
• OUTSIDE AIR DAMPER D-1 AND D-2 SHALL BE OPEN POSITION.
THE CHILLED WATER VALVE SHALL BE CONTROLLED TO MAINTAIN DISCHARGE AIR
TEMPERATURE SETPOINT.
HIGH STATIC SHUTDOWN
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN HIGH STATIC
SHUTDOWN SIGNAL.
OUTDOOR AIR DAMPERS
THE MINIMUM OUTDOOR AIR DAMPER D-1 SHALL OPEN WHEN THE UNIT RUNS IN "NORMAL"
MODE. WHEN THE UNIT SWITCHES OVER TO "EMERGENCY" MODE, BOTH OUTDOOR AIR
DAMPERS (D-1 AND D-2) SHALL BE 100% OPEN. BOTH DAMPERS D-1 AND D-2 SHALL CLOSE
ANYTIME THE UNIT STOPS. THE SUPPLY FAN SHALL START ONLY AFTER THE DAMPER STATUS
OF EITHER D-1 OR D-2 HAS PROVEN THE DAMPER IS OPEN. BOTH OUTDOOR AIR DAMPERS
SHALL CLOSE 5 SEC (ADJ.) AFTER THE SUPPLY FAN STOPS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• OUTDOOR AIR DAMPER FAILURE: COMMAND OPEN, BUT THE STATUS IS CLOSED.
• OUTDOOR AIR DAMPER IN HAND: COMMAND CLOSED, BUT THE STATUS IS OPEN.
OUTSIDE AIR DAMPER VENTILATION
THE CONTROLLER SHALL OPEN THE MINIMUM OUTSIDE AIR DAMPER (D-1) WHENEVER THE UNIT
IS ACTIVATED TO RUN. OUTSIDE AIR DAMPER (D-2) WILL REMAIN CLOSED DURING NORMAL
OPERATION, ECONOMIZER, AND ENERGY RECOVERY SYSTEM IS ACTIVATED. THE AIR FLOW
MEASURING DEVICE IS TO MEASURE THE OUTSIDE AIR CFM OF THE AIR HANDLING UNIT.
EXHAUST
AIR
OUTDOOR
AIR
RELIEF
AIR
RETURN
AIR
SUPPLY TO
VAV UNITS
BI - HIGH PRESSURE STATIC
CC
V-1
C H
W R
C H
W S
BI - ALARM
HUMIDIFIER
AFMS-2
AI - MAX. OUTDOOR AIRFLOW
M
(OPEN/CLOSE)
AI - RELIEF DAMPER
(POSITION)
D-9
AIR-TO-AIR
ENERGY
RECOVERY
AO - RELIEF DAMPER
AI
T-2
AI
H-2
AI
T-3
AI
H-3
DP
AI
T-1
AI
H-1
DP
AI - FILTER STATUS (MERV 8)
M D-1
M D-2MM
(OPEN/CLOSE)
BO - MIXED AIR DAMPER
MD-8
D-7 D-5
(OPEN/CLOSE)
BO - EXHAUST AIR DAMPER
(OPEN/CLOSE)
BO - RETURN AIR DAMPER
T-4
AI
DP DP
AI - FILTER STATUS (MERV 11)
AI - FILTER STATUS (MERV 8)
T-5
AI
M M
M M
VFDVFD
VFD VFD
BO (FAN START/STOP)
BI (VFD FAULT)
AO (VFD SPEED CONTROL)
BI (FAN STATUS)
BO (FAN START/STOP)
BI (VFD FAULT)
AO (VFD SPEED CONTROL)
BI (FAN STATUS)
BO (FAN START/STOP)
BI (VFD FAULT)
AO (VFD SPEED CONTROL)
BI (FAN STATUS)
BO (FAN START/STOP)
BI (VFD FAULT)
AO (VFD SPEED CONTROL)
BI (FAN STATUS)
DP
AI - FILTER STATUS (MERV 14)
AI
T-6
AI
H-4
AO - SETPOINT
SPS-1
SF-5-1
BACNET
COMM. (TYP)
MD-6
(OPEN/CLOSE)
BO - RETURN-EXHAUST DAMPER
AO - COOLING VALVE
SUPPLY AIR DUCT STATIC PRESSURE CONTROL
THE CONTROLLER SHALL MEASURE DUCT STATIC PRESSURE AND SHALL MODULATE THE
SUPPLY FAN VFD SPEED TO MAINTAIN A DUCT STATIC PRESSURE SETPOINT OF 1.5 IN H2O
(ADJ.). THE SUPPLY FAN VFD SPEED SHALL NOT DROP BELOW 30% (ADJ.).
THE STATIC PRESSURE SETPOINT SHALL BE RESET BASED UPON THE POSITION OF THE ZONE
DAMPERS, WITH A GOAL OF REDUCING THE STATIC PRESSURE UNTIL AT LEAST ONE ZONE
DAMPER IS NEARLY WIDE OPEN. THE CONTROLLER SHALL UTILIZE THE OUTPUT SIGNAL FROM
ALL SUPPLY DAMPER POSITIONS TO RESET THE SUPPLY DUCT STATIC PRESSURE SETPOINT
AS REQUIRED TO MAINTAIN AT LEAST ONE SUPPLY DAMPER 95% (ADJ.) OPEN.
THE INITIAL DUCT STATIC PRESSURE SETPOINT SHALL BE 1.5 IN H2O (ADJ.). IF NO ZONE
DAMPER IS NEARLY WIDE OPEN, THE SETPOINT SHALL INCREMENTALLY RESET DOWN TO A
MINIMUM OF 1.0 IN H2O (ADJ.) .AS ONE OR MORE DAMPERS NEARS THE WIDE OPEN POSITION, THE SETPOINT SHALL INCREMENTALLY RESET UP TO A MAXIMUM OF 1.5 IN H2O (ADJ.).
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH SUPPLY STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS
GREATER THAN SETPOINT.
• LOW SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS
LESS THAN SETPOINT.
• SUPPLY FAN VFD FAULT
IF THE SUPPLY FAN FAILS TO PROVE STATUS FOR 30 SECONDS (ADJ.), THE FAN SHALL BE
COMMANDED OFF, THE OUTSIDE AIR DAMPERS SHALL CLOSE, AND AN ALARM SHALL
ANNUNCIATE AT THE BAS. A MANUAL RESET SHALL BE REQUIRED TO RESTART THE FAN. A
HARDWIRED, HIGH STATIC PRESSURE CUT-OFF SWITCH SHALL BE ELECTRICALLY
INTERLOCKED WITH THE VARIABLE SPEED DRIVE. IF THE HIGH STATIC PRESSURE CUT-OFF
SWITCH IS TRIPPED THE FAN SHALL BE COMMANDED OFF, THE OUTSIDE AIR DAMPER SHALL
CLOSE, COOLING SHALL BE DISABLED, AND AN ALARM SHALL ANNUNCIATE AT THE BAS. A
MANUAL RESET OF THE HIGH STATIC PRESSURE CUT-OFF SWITCH SHALL BE REQUIRED TO
RESTART THE FAN.
SUPPLY AIR TEMPERATURE
THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE.
SUPPLY AIR SMOKE DETECTION
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A SUPPLY AIR
SMOKE DETECTOR STATUS.
ALARMS SHALL BE PROVIDED AS FOLLOWS
• HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS GREATER THAN
120°F (ADJ.).
• LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS LESS THAN 45°F
(ADJ.).
RETURN AIR DUCT STATIC PRESSURE CONTROL
THE RETURN FAN SHALL RUN WHENEVER THE SUPPLY FAN RUNS. THE CONTROLLER SHALL
MEASURE RETURN PLENUM STATIC PRESSURE AND MODULATE THE RETURN FAN VFD SPEED
TO MAINTAIN A RETURN PLENUM STATIC PRESSURE SETPOINT DETERMINED BY THE CONTROL
CONTRACTOR AND TEST AND BALANCER. THE RETURN FAN VFD SPEED SHALL NOT DROP
BELOW 20% (ADJ.).
ALARMS SHALL BE PROVDED AS FOLLOWS:
• RETURN FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF
• RETURN FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON
• RETURN RAN RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE
LIMIT (ADJ)
• RETURN FAN VFD FAULT
• HIGH RETURN PLENUM STATIC PRESSURE: IF THE RETURN AIR PLENUM STATIC
PRESSURE IS 25% (ADJ.) GREATER THAN SETPOINT.
• LOW RETURN PLENUM STATIC PRESSURE: IF THE RETURN AIR PLENUM STATIC
PRESSURE IS 25% (ADJ.) LESS THAN SETPOINT.
AIR FLOW MEASURING STATION:
THE CONTROLLER SHALL MONITOR ALL THE AIR FLOW MEASURING STATION TO CONTROL AND
MODULATED THE SUPPLY AND RETURN FAN VFD TO MAINTAIN THE REQUIRED AIRFLOWS.
COOLING COIL VALVE
THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND MODULATE THE
COOLING COIL VALVE TO MAINTAIN ITS COOLING SETPOINT.
THE COOLING SHALL BE ENABLED WHEN ALL THE FOLLOWING AT MET:
• OUTDOOR AIR TEMPERATURE IS GREATER THAN 60°F (ADJ.).
• THE SUPPLY AIR TEMPERATURE IS ABOVE COOLING SETPOINT.
• THE FAN STATUS IS ON.
FREEZE PROTECTION
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECIEVING A FREEZESTAT
STATUS.
A HARDWIRED, LOW LIMIT TEMPERATURE SWITCH SHALL BE ELECTRICALLY INTERLOCKED
WITH THE VARIABLE SPEED DRIVE. IF THE LOW LIMIT TEMPERATURE SWITCH IS TRIPPED
(35.0°F ADJ.), THE SUPPLY FAN SHALL BE DISABLED, THE OUTSIDE AIR DAMPER SHALL
CLOSE, CHILLED WATER VALVES SHALL OPEN TO 100% AND AN ALARM SHALL BE
ANNUNCIATED AT THE BAS. A MANUAL RESET OF THE LOW LIMIT TEMPERATURE SWITCH
SHALL BE REQUIRED TO RESTART THE FAN.
FILTER STATUS
THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FILTER(S)
WHEN THE FAN IS RUNNING.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• PRE-FILTER CHANGE REQUIRED: PREFILTER DIFFERENTIAL PRESSURE EXCEEDS
A USER DEFINABLE LIMIT (ADJ.).
• FINAL FILTER CHANGE REQUIRED: FINAL FILTER DIFFERENTIAL PRESSURE
EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
ECONOMIZER CYCLE
PROVIDE THE UNIT WITH AN ECONOMIZER CYCLE: OPERATION SHALL BE SUCH THAT WHEN:
• THE OUTDOOR AIR TEMPERATURE IS LESS THAN THE RETURN AIR
TEMPERATURE, THE ECONOMIZER IS ENABLED (DISABLE ECONOMIZER WHEN
OUTSIDE AIR TEMPERATURE IS GREATER THAN RETURN AIR TEMPERATURES BY
1°F (ADJ) AND OA-T< 60°F (ADJ.) AND THE SUPPLY FAN STATUS IS ON.
• DAMPER D-4 AND D-6 SHALL BE ACTIVATED (NORMALLY OPEN)
• DAMPER D-3 AND D-8 SHALL BE DEACTIVATED (NORMALLY CLOSED)
ENERGY RECOVERY OPERATION
ENERGY RECOVERY CONTROL: BAS SHALL ENABLE THE ENERGY RECOVERY SYSTEM WHEN
EVER AHU IS ACTIVATED. THE ENERGY RECOVERY SYSTEM DURING NORMAL OPERATIONS
SHALL HAVE THE FOLLOWING DAMPERS ACTIVATED (NORMALLY OPEN) D-3, D-5, AND D-8.
DAMPER D-4 AND D-6 SHALL BE DE-ACTIVATED (NORMALLY CLOSED) WHEN ENERGY
RECOVERY IS ACTIVATED.
FZ
BI - TEMPERATURE TSL
(OPEN/CLOSE)
AO - MAX. OUTDOOR AIR DAMPER
(POSITION)
AI - MAX. OUTDOOR AIR DAMPER
(OPEN/CLOSE)
AO - MIN. OUTDOOR AIR DAMPER
HUMIDIFIER CONTROL:
THE CONTROLLER SHALL MEASURE THE RETURN AIR HUMIDITY AND MODULATE THE
HUMIDIFIER TO MAINTAIN A SETPOINT OF 35% RH (ADJ.). THE HUMIDIFIER SHALL BE ENABLED
WHENEVER THE SUPPLY FAN STATUS IS ON.
THE HUMIDIFIER SHALL TURN OFF WHENEVER:
• SUPPLY AIR HUMIDITY RISES FROM 90% RH TO 95% RH (ADJ.)
• LOSS OF SUPPLY FAN STATUS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH SUPPLY AIR HUMIDITY: IF THE SUPPLY AIR HUMIDITY IS GREATER THAN 90%
RH (ADJ.)
• LOW SUPPLY AIR HUMIDITY: IF THE SUPPLY AIR HUMIDITY IS LESS THAN 25% RH
(ADJ.).
HUMIDIFICATION SHALL BE ENABLED WHEN DEHUMIDIFICATION IS DISABLED, START UP DELAY HAS TERMINATED AND HUMIDITY IS BELOW SETPOINT. THE HIGH LIMIT HUMIDISTAT SHALL BE
LOCATED DOWNSTREAM FROM THE HUMIDIFIER SHALL OVERRIDE THE HUMIDIFIER CONTROL
TO PREVENT LOCAL SATURATION AT THE POINT OF STEAM INSTRUCTION. HUMIDIFICATION
SHALL BE DISABLED WHEN THE HUMIDITY RISES ABOVE THE SETPOINT PLUS THE DEADBAND.
DEHUMIDIFICATION:
THE CONTROLLER SHALL MEASURE THE RETURN AIR HUMIDITY WHENEVER THE SPACE
HUMIDITY EXCEEDS THE SETPOINT OF 65%RH (ADJ) . THE CONTROLLER WILL OVERRIDE THE
COOLING SEQUENCE TO MAINTAIN RETURN AIR HUMIDITY AT OR BELOW 60%RH (ADJ). THE
COOLING COIL TO PROVIDE MAXIMUM COOLING DOWN TO A MINIMUM COIL LEAVING
TEMPERATURE OF 52°F(ADJ).
CONSTANT SPEED OPERATION
UPON FAILURE OF THE VFD, THE SUPPLY AND EXHAUST FANS SHALL BE STARTED/STOPPED
MANUALLY AT THE DDC THROUGH THE BY-PASS STARTER. FANS SHALL THEN BE OPERATED
AT CONSTANT SPEED.
ALL VAV BOXES WILL BE INDEXED TO MAXIMUM FLOW TO ACCOMMODATE THE MAXIMUM
SUPPLY FAN FLOW.
AUTOMATIC SHUTDOWN / RESTART
WHEN SMOKE IS DETECTED BY DUCT SMOKE DETECTOR, DSD, THE SUPPLY FANS SHALL SHUT
"OFF" AND AN ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE-ALARM SYSTEM. ALL
SMOKE DAMPERS IN THE SUPPLY AND RETURN DUCTS SHALL CLOSE. (HARDWIRE INTERLOCK
FROM FIRE RELAY AND THE VFD SAFETY CIRCUIT.)
SUPPLY FANS SHALL RESTART AND SMOKE DAMPERS SHALL OPEN WHEN FIRE ALARM CIRCUIT
IS RESET.
ALARMS
PROVIDE ALARMS FOR THE FOLLOWING:
• SUPPLY / EXHAUST FAN(S) VFD FAULT
• SUPPLY / EXHAUST FAN(S) FAILURE (COMMANDED "ON" BUT THE STATUS IS
"OFF")
• SUPPLY / EXHAUST FAN(S) RUNNING IN HAND (COMMANDED "OFF" BUT THE
STATUS IS "ON"
• HIGHER PRE-FILTER / FINAL FILTER DIFFERENTIAL STATIC PRESSURES.
ON A RISE IN SUPPLY AIR TEMPERATURE ABOVE (53°F PLUS 1.5°F DEADBAND, ADJ.), THE
CHILLED WATER VALVE SHALL MODULATE TO MAINTAIN SETPOINT. ON A FALL IN SUPPLY AIR
TEMPERATURE BELOW 53°F (MINUS 1.5°F DEADBAND, ADJ.), THE CHILLED WATER VALVE SHALL
CLOSE. ON A RISE IN SUPPLY AIR TEMPERATURE ABOVE SETPOINT FOR GREATER THAN 5
MINUTES, AN ALARM SHALL BE SIGNALED TO THE DDC SYSTEM.
MD-4
(OPEN/CLOSE)
AO - HX BYPASS DAMPER
SUPPLY FAN
(QTY. 6)
M
M
VFD
VFD
BO (FAN START/STOP)
BI (VFD FAULT)
AO (VFD SPEED CONTROL)
BI (FAN STATUS)
BO (FAN START/STOP)
BI (VFD FAULT)
AO (VFD SPEED CONTROL)
BI (FAN STATUS)
SF-5-2
SF-5-3
SF-5-4
SF-5-5
SF-5-6
M M
M M
VFDVFD
BO (FAN START/STOP)
BI (VFD FAULT)
AO (VFD SPEED CONTROL)
BI (FAN STATUS)
BO (FAN START/STOP)
BI (VFD FAULT)
AO (VFD SPEED CONTROL)
BI (FAN STATUS)
EF-5-1
EXHAUST FAN
(QTY. 6)
M
M
VFD
BO (FAN START/STOP)
BI (VFD FAULT)
AO (VFD SPEED CONTROL)
BI (FAN STATUS)
EF-5-2
EF-5-3
VFD
EF-5-6
AI - FILTER STATUS (MERV 8)
BO (FAN START/STOP)
BI (VFD FAULT)
AO (VFD SPEED CONTROL)
BI (FAN STATUS)
VFD
EF-5-4
BO (FAN START/STOP)
BI (VFD FAULT)
AO (VFD SPEED CONTROL)
BI (FAN STATUS)
VFD
EF-5-5
BO (FAN START/STOP)
BI (VFD FAULT)
AO (VFD SPEED CONTROL)
BI (FAN STATUS)
M
D-3 (OPEN/CLOSE)
BO - HX DAMPER
T-7
H-5
AI
AI
AFMS-4
AI -RETURN AIRFLOW
AFMS-3
AI - EXHAUST AIRFLOW
AFMS-1
AI - MIN. OUTDOOR AIRFLOW
AI
SPS-3
HUM-5
SPS-2
DSD-1
AFMS-5
BI TO FIRE ALARM
AI SUPPLY AIRFLOW
AI
CONTROLS SYMBOLS
AI ANALOG INPUT
AO ANALOG OUTPUT
BI BINARY INPUT
BO BINARY OUTPUT
AV ANALOG VALUE
BV BINARY VALUE
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
CONTROL SYMBOL LIST
ADJ ADJUSTABLE
AFMS AIRFLOW MEASURING STATION
DP DIFFERENTIAL PRESSURE
DSD DUCT SMOKE DETECTOR
H HUMIDITY SENSOR
HOA HAND-OFF-AUTO
BAS BUILDING AUTOMATION SYSTEM
N.O. NORMALLY OPEN
N.C. NORMALLY CLOSED
SPS STATIC PRESSURE SENSOR
T TEMPERATURE SENSOR
VFD VARIABLE FREQUENCY DRIVE
EP POWER WIRING
CT CONTROLLER
SYMBOL DESCRIPTION
COOLING COIL
M
M
MOTORIZED DAMPER (SPRING RETURN)
MOTOR (FAN)
TRANSMITTER
TRANSMITTER, AVERAGING ELEMENT
PUMP
CONTROL VALVE
FZ FREEZESTAT
TSL TEMPERATURE SWITCH, LOW (FREEZESTAT)
NOTE TO TEMPERATURE CONTROL CONTRACTOR:
CONTROL CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING THE CORRECT TYPE, SIZES AND QUANTITIES OF
CONTROL CABLES, CONTROLLERS, SENSORS,
TRANSFORMERS, DEVICES AND PROGRAMMING
NECESSARY FOR A FULLY FUNCTIONAL SYSTEM.
o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
VA FORM 08-6231
Office of Facilities Management
U.S. Department of Veterans Affairs
STAMP
Date
Location
Building Number Checked Drawn Drawing Number
Project Number
BID SET
Approved: Director
Approved: Associate Director
Approved: Assistant Director
Approved: Assoc. Director for Patient Care Service/Nurse Executive
Approved: Deputy Assoc. Director of Patient Care Services
Approved: Chief of Staff
Approved: Deputy Chief of Staff
Approved: Chief of Engineering
Approved:
Approved:
ARCHITECT/ENGINEER/CONSULTANTS:
Bancroft Project No.
SAVAHCS, TUCSON, AZ 85723
3300 Dundee Road
Northbrook, IL 60062
T: 847.952.9362
04/30/2024MECHANICAL - CONTROLS EXPAND AND RENOVATE
EMERGENCY DEPARTMENT B50
50 DGG TE
50-M701
678-331
8-
E X
P A
N D
A N
D R
E N
O V
A T
E E
M E
R G
E N
C Y
D E
P A
R T
M E
N T
B
A
D D
E N
D U
M
RETURN AIR TEMPERATURE, T-7 X X X X
SUPPLY AIR TEMPERATURE, T-6 X X X X
CHILLED AIR TEMPERATURE, T-5 X X X X
MIXED AIR TEMPERATURE, T-4 X X X X
EXHAUST AIR TEMPERATURE, T-3 X X X X
ENERGY RECOVERY AIR TEMPERATURE, T-2 X X X X
OUTDOOR AIR TEMPERATURE, T-1 X X X X
EXHAUST AIR STATIC PRESSURE, SPS-3 X X X X
SUPPLY AIR STATIC PRESSURE, SPS-1 X X X X
RELIEF DAMPER, D-9 X X X
MAX. OUTDOOR AIR DAMPER, D-2 X X X
FINAL FILTER DIFF. PRESSURE (MERV 14) X X X
MIXED AIR FILTER DIFF. PRESSURE (MERV 11) X X X
MIXED AIR FILTER DIFF. PRESSURE (MERV 8) X X X
EA FILTER DIFF. PRESSURE (MERV 8) X X X
OA FILTER DIFF. PRESSURE (MERV 8) X X X
RELIEF DAMPER POSITION, D-9 X X X
MAX. OUTDOOR AIR DAMPER POSITION, D-2 X X X
RETURN AIR HUMIDITY, H-5 X X X
SUPPLY AIR HUMIDITY, H-4 X X X
EXHAUST AIR HUMIDITY, H-3 X X X
ENERGY RECOVERY HUMIDITY, H-2 X X X
OUTDOOR AIR HUMIDITY, H-1 X X X
SUPPLY AIRFLOW MEASURING STATION, AFMS-5 X X X
RETURN AIRFLOW MEASURING STATION, AFMS-4 X X X
EXHAUST AIRFLOW MEASURING STATION, AFMS-3 X X X
MAX. OA AIRFLOW MEASURING STATION, AFMS-2 X X X
MIN. OA AIRFLOW MEASURING STATION, AFMS-1 X X X
POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON GRAPHIC
HARDWARE POINTS SOFTWARE POINTS
AIR HANDLING UNIT (AHU-5) POINTS LIST
CONTINUED ON SHEET M702