50-A303.pdf
PDF 489 KB Posted
- Attached to
- Y1DA--Expand and Renovate Emergency Department B50 Minor Construction - Tucson VAMC (VA-24-00001448)
- Solicitation number
- 36c77623r0191
About this file
This document appears to be an architectural drawing set for the Expand and Renovate Emergency Department B50 Minor Construction project at the Tucson VAMC. The drawings provide wall section details for the exterior wall assemblies, including EIFS, modified bituminous roofing, and other construction materials and specifications.
The related federal contract opportunity is Solicitation Number 36c77623r0191, titled "Y1DA--Expand and Renovate Emergency Department B50 Minor Construction - Tucson VAMC (VA-24-00001448)". This is a solicitation issued by the Department of Veterans Affairs Technology Acquisition Center Austin for the expansion and renovation of the emergency department at the Tucson VAMC facility in Arizona 85723. The drawings provided appear to be part of the bid set for this construction project.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Floor 1 59'-8 3/8"
Floor 2 73'-8 3/8"
0"
A1
50-A701
50-A701
50-A701
VESTIBULE
1V1
11'-2 1/2" T/SLAB
50-A701
50-A603
50-A701
50-A703
MB-2 ROOF ASSEMBLY
MB-1 ROOF ASSEMBLY
SCHEDULED CEILING
STRUCTURAL STEEL. REFER TO
STRUCTURAL DRAWINGS.
STONE VENEER WALL ASSEMBLY
BOLLARD. REFER TO CIVIL DRAWINGS
FOR MORE INFORMATION.
CONCRETE SLAB -
REFER TO STRUCTURAL
DRAWINGS - PROVIDE
VAPOR BARRIER PER
SPECIFICATION SECTION
03 30 00.
50-A701
Floor 1 59'-8 3/8"
Floor 2 73'-8 3/8"
7 8
0"
EXISTING WINDOW TO REMAIN
EXISTING SLAB/BEAM TO REMAIN
50-A701
50-A603
AMBULANCE
VESTIBULE
1V2
11'-2 1/2" T/SLAB
50-A703
EIFS-3 CANOPY WALL ASSEMBLY
MB-1 ROOF ASSEMBLY
SCHEDULED CEILING
CONCRETE SLAB - REFER TO
STRUCTURAL DRAWINGS -
PROVIDE VAPOR BARRIER
PER SPECIFICATION SECTION
03 30 00.
o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
VA FORM 08-6231
Office of Facilities Management
U.S. Department of Veterans Affairs
STAMP
Date
Location
Building Number Checked Drawn Drawing Number
Project Number
BID SET
Approved: Director
Approved: Associate Director
Approved: Assistant Director
Approved: Assoc. Director for Patient Care Service/Nurse Executive
Approved: Deputy Assoc. Director of Patient Care Services
Approved: Chief of Staff
Approved: Deputy Chief of Staff
Approved: Chief of Engineering
Approved:
Approved:
ARCHITECT/ENGINEER/CONSULTANTS:
Bancroft Project No.
SAVAHCS, TUCSON, AZ 85723
3300 Dundee Road
Northbrook, IL 60062
T: 847.952.9362
04/30/2024ARCHITECTURAL - WALL
SECTIONS
EXPAND AND RENOVATE
EMERGENCY DEPARTMENT B50
50 CZ DTB
50-A303
678-331
19-103
8-
E X
P A
N D
A N
D R
E N
O V
A T
E E
M E
R G
E N
C Y
D E
P A
R T
M E
N T
B
A
D D
E N
D U
M
0 2' 3'1'0 2' 3'1'3/4" = 1'-0"
WALL SECTION
3/4" = 1'-0"
WALL SECTION
EXTERIOR ASSEMBLIES
EIFS-1 (EXTERIOR WALL ASSEMBLY)
• EIFS (BASIS OF DESIGN: DRYVIT OUTSULATION PLUS MD SYSTEM)
• 1 1/2” EXPANDED POLYSTYRENE INSULATION BOARD (R5)
• ADHESIVE
• AIR/WATER RESISTIVE BARRIER
• 1 1/4" PLYWOOD
• HSS5X3 AT 24" ON CENTER + 6" METAL STUDS AT 16" ON CENTER
• 5/8” GYPSUM WALL BOARD
• 3 1/2" BATT INSULATION (R13) BETWEEN METAL STUDS
EIFS-2 (PARAPET WALL ASSEMBLY)
• EIFS (BASIS OF DESIGN: DRYVIT OUTSULATION PLUS MD SYSTEM)
• 1 1/2” EXPANDED POLYSTYRENE INSULATION BOARD (R5)
• ADHESIVE
• AIR/WATER RESISTIVE BARRIER
• 1 1/4" PLYWOOD
• 6" METAL STUDS AT 24" ON CENTER WITH KICKER
• 1/2" COVER BOARD
EIFS-3 (CANOPY WALL ASSEMBLY)
• EIFS (BASIS OF DESIGN: DRYVIT OUTSULATION PLUS MD SYSTEM)
• 1” EXPANDED POLYSTYRENE INSULATION BOARD
• ADHESIVE
• 3/4" PLYWOOD
• 3 5/8" METAL STUDS AT 16" ON CENTER
• 1/2" COVER BOARD
MB-1 (ROOF ASSEMBLY)
• SBS MODIFIED BITUMINOUS MEMBRANE ROOFING
• 1/2" COVER BOARD
• TAPERED INSULATION
• 5" POLISOCYANURATE RIGID INSULATION (R-25)
• CONCRETE SLAB ON METAL DECK
MB-2 (ROOF ASSEMBLY)
• SBS MODIFIED BITUMINOUS MEMBRANE ROOFING
• 1/2" COVER BOARD
• TAPERED INSULATION
• METAL DECK
GENERAL NOTES
1. REFER TO SPECIFICATION SECTION 08 56 53 FOR BLAST DESIGN REQUIREMENTS OF
EXTERIOR FACADE SYSTEMS.
Revisions: Date:
BID SET 05/01/2023
ADDENDUM 1 04/30/2024
| Sheets |
| 50-A303 - ARCHITECTURAL - WALL SECTIONS |
File details come from the government source that posted it. Updated .