This document is a mechanical schedule for an Expand and Renovate Emergency Department project at the Tucson VAMC. The key details include:
The project requires a new air handling unit (AHU-5) with supply and exhaust fans, air valves, diffusers, grilles, and registers. The AHU will have a total CFM of 55,500, with 7,000 CFM of minimum outside air. It will include features such as a plate energy recovery system, MERV 8/11/14 filters, and direct drive fans with VFDs. Exhaust fans EF-2A and EF-2B will serve the isolation rooms. The document also includes schedules for the variable frequency drives and air distribution devices.
The related federal contract opportunity is Solicitation Number 36c77623r0191 for the Expand and Renovate Emergency Department B50 project at the Tucson VAMC. It is a minor construction solicitation issued by the Department of Veterans Affairs Technology Acquisition Center Austin.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
VA FORM 08-6231
Office of Facilities Management
U.S. Department of Veterans Affairs
STAMP
Date
Location
Building Number Checked Drawn Drawing Number
Project Number
BID SET
Approved: Director
Approved: Associate Director
Approved: Assistant Director
Approved: Assoc. Director for Patient Care Service/Nurse Executive
Approved: Deputy Assoc. Director of Patient Care Services
Approved: Chief of Staff
Approved: Deputy Chief of Staff
Approved: Chief of Engineering
Approved:
Approved:
ARCHITECT/ENGINEER/CONSULTANTS:
Bancroft Project No.
SAVAHCS, TUCSON, AZ 85723
3300 Dundee Road
Northbrook, IL 60062
T: 847.952.9362
04/30/2024MECHANICAL - SCHEDULES EXPAND AND RENOVATE
EMERGENCY DEPARTMENT B50
50 DGG TE
50-M601
678-331
8-
E X
P A
N D
A N
D R
E N
O V
A T
E E
M E
R G
E N
C Y
D E
P A
R T
M E
N T
B
A
D D
E N
D U
M
MERV 8 &
MERV 11
12 (24x24) 12 (24x24)
85.5 / 60.30 55.0 / 54.0 46 56 0.77 474 668.1 668.1 4 / 12 WATER 6.8 133.0
AIR-TO-AIR
PLATE
MERV 8 106 / 66 75 / 60 86.5 / 60.3 94.5 / 65.6 23.2 62.8 50.2 31.6 / 25 70 / 55 55.3 / 42.6 44.4 / 39.4 40.0 66.6 57.3 MERV 14 12 (24x24) - - 250 3 480 1 THRU 27
TYPE QTY.
LATENT
SENSIBLE
TOTAL
LATENT
SENSIBLE
TOTAL
TYPE QTY.
FLA
(AMPS)
MCA
(AMPS)
MOCP
(AMPS)
PHASE VOLTS
OA
DB/WB
(°F)
RA
DB/WB
(°F)
SA
DB/WB
(°F)
EA
DB/WB
(°F)
EFFECTIVENESS
OA
DB/WB
(°F)
RA
DB/WB
(°F)
SA
DB/WB
(°F)
EA
DB/WB
(°F)
EFFECTIVENESS
PRE
FILTERS
EAT
DB/WB
(°F)
LAT
DB/WB
(°F)
EWT
(°F)
LWT
(°F)
AIR
P.D.
(IN)
AIR
VELOCITY
(FPM)
TOTAL
MBH
SENS.
BH
ROWS /
FPI
FLUID
TYPE
FLUID
P.D.
(FT)
GPM TYPE PREFILTER
SUMMER CONDITIONS WINTER CONDITIONS
CHW COOLING COIL ENERGY RECOVERY (WHEN RUNNING 100% OA)
FINAL
FILTER
ELECTRICAL
NOTES
AIR HANDLING UNIT SCHEDULE (CONTINUED)
3. INTERNAL SPRING VIBRATION ISOLATORS FOR EACH FAN.
2. FIELD VERIFY AHU DIMENSIONS. 5. PROVIDE BACK DRAFT DAMPER AND SHAFT GROUNDING RINGS.
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUALS. 4. ALL CONTROLS, ACTUATORS, & END DEVICES TO BE FIELD PROVIDED & INSTALLED BY BAS CONTRACTOR.
NOTES:
SF-1-1
SF-1-2
MECH RM -
AHU-1
SUPPLY
FAN
TWIN CITY FAN MPLQS 30.3 30.3 33.1 454 2 1 x 2 6,000 3,000 5.7 2.5
DIRECT
DRIVE
2,978 3.97 7.5 3600 3 460 6.46 1,2,3,4,5
MANUFACTURER MODEL H W L BHP / FAN
HP /
FAN
RPM PH VOLT KW
# OF
FANS
# FANS
HIGH
x
# FANS
WIDE
EQUIPMENT TAG LOCATION UNIT FUNCTION
BASIS OF DESIGN
APPROX. OVERALL
DIMENSIONS (IN.)
WEIGHT
PER FAN
(LBS)
FAN ARRANGEMENT
TOTAL
CFM
CFM PER
FAN
TSP
(IN. WG)
ESP
(IN. WG)
TYPE
FAN
RPM
MOTOR
NOTES
FAN SCHEDULE
7. VFD SHALL INCLUDE REAL TIME CLOCK WITH BATTERY BACKUP (INCLUDE 10 YEAR BATTERY). 13. BYPASS SHALL BE FULLY FUNCTIONAL IN THE EVENT OF A VFD FAILURE. BYPASS SHALL NOT RELY ON THE VFD.
6. VFD SHALL BE BTL LISTED FOR BACNET MS/TP, AND ALSO INCLUDE MODBUS AND N2. 12. INCLUDE FAST ACTING DRIVE ISOLATION FUSES.
5. PROVIDE INTERNAL EMI/RFI FILTER PER IEC 61800-3. VFD INPUT AMPS SHALL NOT EXCEED VFD OUTPUT AMPS. 11. BYPASS OPERATION TO AUTO-RESET AFTER A BROWN OUT CONDITION.
4. VFD SHALL INCLUDE ALPHA-NUMERIC KEYPAD INTERFACE, WITH DISPLAY IN PLAIN ENGLISH. FIREMAN'S OVERRIDE FUNCTIONALITY.
3. PROVIDE UL1449 SURGE SUPPRESSION DEVICE. 10. VFD AND BYPASS SHALL BOTH INCLUDE BACnet MS/TP, DAMPER CONTROL AND
SIZED TO 5% EQUIVALENT IMPEDANCE. ALLOWING +30% TO -30% INPUTE VOLTAGE TOLERANCE.
2. AT MINIMUM, VFD SHALL INCLUDE 5% IMPEDANCE VIA 5% AC LINE REACTOR OR DUAL DC CHOKES 9. BYPASS CONTACTORS SHALL BE POWERED BY SWITCH MODE POWER SUPPLY,
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUAL. 8. PHASE LOSS PROTECTION & BROKEN BELT (LOSS OF LOAD) INDICATION WHILE IN BYPASS.
NOTES:
VFD-P-50-2 MECH RM - 342 P 50-2 ABB ACH580-VCR-012A-4 NEMA 1 UNISTRUT 40.2 x 5.4 x 10.6 CIRCUIT BREAKER FVNR (BYPASS SYTLE) 12 7 1/2 1800 60 3 480 1 THRU 13
VFD-P-50-1 MECH RM - 342 P 50-1 ABB ACH580-VCR-012A-4 NEMA 1 UNISTRUT 40.2 x 5.4 x 10.6 CIRCUIT BREAKER FVNR (BYPASS SYTLE) 12 7 1/2 1800 60 3 480 1 THRU 13
VFD-SF-1-2 MECH RM - 147 AHU-1 (SF-1-2) ABB ACH580-PDR-012A-4 NEMA 1 UNISTRUT 24.6 x 6.4 x 12.5 DISCONNECT NONE 12 7 1/2 3600 60 3 480 1 THRU 7
VFD-SF-1-1 MECH RM - 147 AHU-1 (SF-1-1) ABB ACH580-PDR-012A-4 NEMA 1 UNISTRUT 24.6 x 6.4 x 12.5 DISCONNECT NONE 12 7 1/2 3600 60 3 480 1 THRU 7
VFD-EF-2B ELEC RM - 342A EF-2B ABB ACH580-VCR-04A8-4 NEMA 1 UNISTRUT 33.4 x 17.7 x 14.0 CIRCUIT BREAKER FVNR (BYPASS SYTLE) 4.8 3 3500 60 3 480 1 THRU 13
VFD-EF-2A ELEC RM - 342A EF-2A ABB ACH580-VCR-04A8-4 NEMA 1 UNISTRUT 33.4 x 17.7 x 14.0 CIRCUIT BREAKER FVNR (BYPASS SYTLE) 4.8 3 3500 60 3 480 1 THRU 13
MANUFACTURER MODEL H W D HP (MAX.) RPM FREQ (Hz) PHASE VOLT
EQUIPMENT TAG LOCATION EQUIPMENT SERVED
BASIS OF DESIGN
ENCLOSURE MOUNTING
SIZE (IN.)
DISCONNECT BYPASS
MAX. DRIVE
OUTPUT
CURRENT
MOTOR
NOTES
VARIABLE FREQUENCY DRIVES
DISCHARGE VELOCITY. STACK TO BE A MINIMUM 10 FEET ABOVE THE ROOF.
5. CUSTOMIZE WELDED STAINLESS STEEL EXHAUST STACK WITH 3,500 FPM
4. FAN MOTORS AND VFD'S WILL BE INDIVIDUALLY FED APPROPRIATE ZONE CATEGORY C, SHAFT GROUND RINGS AND FLUME STACK.
3. FAN SHALL COME IN STANDARD ENAMEL GREY COLOR. 8. PROVIDE FLANGED INLET AND OUTLET, VIBRATION ISOLATORS FOR SEISMIC BRACING
2. PROVIDE NEMA 3R MAIN DISCONNECT SWITCH. 7. MOTORIZED DAMPER POWER SHALL BE FROM FAN CIRCUIT VIA INTEGRAL TRANSFORMER.
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUALS. 6. PROVIDE VFD RATED MOTOR, SEE VFD SCHEDULE.
NOTES:
EF-2B GREENHECK USF-12
THIRD FLOOR
ROOF
FIRST FLOOR
ISOLATION
ROOMS
UNIVERSAL
SINGLE
WIDTH
DIRECT 292 900 7 38.0 3,552 1.43 3 3500 3 460 BAS 1 THRU 9
EF-2A GREENHECK USF-12
THIRD FLOOR
ROOF
FIRST FLOOR
ISOLATION
ROOMS
UNIVERSAL
SINGLE
WIDTH
DIRECT 292 900 7 38.0 3,552 1.43 3 3500 3 460 BAS 1 THRU 9
MANUFACTURER MODEL HP RPM PHASE VOLT
EQUIPMENT TAG
BASIS OF DESIGN
LOCATION AREA SERVED TYPE DRIVE
WEIGHT
(LBS)
CFM
SP
(IN.)
MAXIMUM
SONES
FAN RPM BHP
MOTOR
CONTROL
TYPE
NOTES
EXHAUST FAN SCHEDULE
EXCEED 0.25" WC. FLOW MEASUREMENT.
INLET TO OUTLET OF VALVE ASSEMBLY SHALL NOT 6. ALL VALVES TO BE CLOSED LOOP CONTROL WITH DEAD ENDED
3. MAXIMUM REQUIRED STATIC PRESSURE DIFFERENTIAL ACROSS. 5. ALL VALVES TO BE FAIL SAFE.
2. MINIMUM NOISE LEVEL SHALL NOT EXCEED 35 NC. AND MAX. CFM SETTINGS. (READILY FIELD ADJUSTABLE)
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUAL. 4. ALL VALVES TO BE PRESSURE INDEPENDENT WITH FACTORY SET MIN.
NOTES:
EAV-1036 CORRIDOR C3 1036, 1036A PHOENIX EXV EXHAUST OPEN
EF-2A
EF-2B
415 8" 7.875 7.875 23.5 1,2,3,4,5,6
EAV-1032 CORRIDOR C3 1032, 1032A PHOENIX EXV EXHAUST OPEN
EF-2A
EF-2B
415 8" 7.875 7.875 23.5 1,2,3,4,5,6
MANUFACTURER MODEL
MAX.
CFM
VALVE
SIZE
INLET SIZE
(IN.)
OUTLET SIZE
(IN.)
LENGTH
(IN.)
EQUIPMENT
TAG
LOCATION AREA SERVED
BASIS OF DESIGN
FUNCTION
FAIL
POSITION
SYSTEM
SERVED
NOTES
AIR VALVE SCHEDULE
16. OPEN AREA ABOVE CC, SF, CART FILTER, HUMI AND DISCHARGE SECTION TO BE CABINET STORAGE AREA. SEE AHU DETAILS ON SHEET 50-M505 FOR REQUIRED SECTIONS AND COMPONENTS.
15. PROVIDE PROTECTIVE SAFETY GRATES ON ALL BOTTOM OPENINGS. BLANK SECTION (HUMIDIFIER), DISCHARGE PLENUM.
14. INNERGYTECH (OR VA APPROVED EQUAL) AIR-TO-AIR FIXED CORE ENERGY RECOVERY WITH BYPASS. MERV 8 & 11 FITLERS (QTY: 12 (24x24)), COOLING COIL, SUPPLY FANS (6), HIGH EFFICIENCY MERV 14 FILTERS (QTY: 12 (24x24)),
13. FACTORY PRESSURE TEST COILS TO 450PSIG. MERV 8 FITLER (QTY: 12 (24x24)), EXHAUST PLENUM WITH DAMPERS, RETURN PLENUM WITH DAMPERS, MIXED AIR PLENUM,
12. SIGHT GLASS 8X8” WINDOWS ON FAN SECTIONS. BOTTOM TIER: MIN AND MAX OUTSIDE AIR DAMPERS, MERV 8 FILTERS (QTY: 12 (24x24), PLATE TO PLATE HEAT EXCHANGER W/ BYPASS DAMPER,
11. FAN AIRFLOW MEASURING PER FAN (6) SUPPLY FANS, (6) EXHAUST FANS. FANS CERTIFIED PER AMCA 210 AND AMCA 300. TOP TIER: EXHAUST DAMPER, RETURN FAN (6), PLATE TO PLATE HEAT EXCHANGER WITH BYPASS DAMPER
10. DIRECT DRIVE PLENUM FANS, MOTOR SHAFT GROUND RING, VFD PER MOTOR, INDIVIDUAL OVERLOAD PER MOTOR. 27. UNIT SHALL HAVE THE FOLLOWING CONFIGURATION: (SEE DETAILS ON DRAWINGS FOR ADDITIONAL INFORMATION)
9. 50,000 HR MOVABLE (MAGNETICALLY ATTACHED) MARINE LED LIGHTS FACTORY WIRED TO EXTERNAL SWITCH WITH GFCI OUTLET. 26. VENTILATED AND CONDITIONED VESTIBULE TO HOUSE FIELD INSTALLED MECHANICAL EQUIPMENT.
8. REFER TO STRUCTURAL DRAWINGS FOR CONCRETE ROOF CURB DETAILS AND LOCATION. 25. PROVIDE RA DAMPERS PER QTY, SIZE AND LOCATION DETAILED.
7. MAGNEHELIC GAGES ACROSS EACH FILTER. 24. PROVIDE MIN OA DAMPER AND MAX OA DAMPER WITH AIRFLOW MEASURING STATIONS.
WITH ONE FACTORY MOUNTED MAIN DISCONNECT. 23. UNIT TO BE SHIPPED IN SECTIONS FOR ASSEMBLY IN FIELD.
6. FACTORY MOUNTED ENCLOSURE CONTAINING A VFD FOR EACH FAN. UNIT SHALL HAVE A SINGLE POINT CONNECTION 22. COORDINATE LEFT HANDED/RIGHT HANDED COIL CONNECTIONS WITH DESIGN DRAWINGS AND EXISTING FIELD CONDITIONS.
5. LOCATE SERVICE VESTIBULE DOUBLE DOORS IN FRONT OF CHILLED WATER COILS FOR EASE OF REMOVAL. 21. ALUMINUM FLOOR, CONTINUOUSLY WELDED WATERTIGHT, 3/16” TREADPLATE, FLOOR DRAINS, THERMAL BREAK BASE, STRUCTURAL STEEL BASE.
4. PRE-INSULATED STAINLESS STEEL DRAIN PAN. 20. PROVIDE FULLY WELDED ASTM STRUCTURAL STEEL BASE FRAME.
3. HINGED ACCESS DOORS AND MARINE LIGHTS AT EACH SECTION. 19. PROVIDE T&B TEST PORTS ON DOORS AND SIDES OF UNIT – FACTORY INSTALLED TO PRESERVE LEAK-TIGHT INTEGRITY OF UNIT CASING.
2. INTERNAL SPRING VIBRATION ISOLATORS FOR SEISMIC BRACING APPROPRIATE FOR SEISMIC ZONE CATEGORY C FOR EACH FAN. THERMAL BREAK CASING. THERMAL BREAKS DOORS.
MUST MEET BUY AMERICAN ACT (BAA). 18. MINIMUM R-VALUE OF R-18 AND MINIMUM 3-INCH FOAM-INJECTED CASING. COMPLETE NO THROUGH-METAL,
1. OTHER ACCEPTABLE MANUFACTURER'S: AIRFLOW EQUIPMENT, ANNEX AIR OR VA APPROVED EQUAL. 17. 2” MERV 8 + 4” MERV 11 PLEATED MEDIA PRE-FILTERS BEFORE COOLING COIL. 12” MERV 14 CARTRIDGE FINAL FILTER.
NOTES:
AHU-5
NEW ADDITION
ROOF (OUTDOOR)
EMERGENCY
DEPARTMENT
TRANE
TCPA
(CUSTOM)
VAV 120 234 535 55,500 7,000 20,170 23,000 10.9 3.5
DIRECT
DRIVE
6 4,698 57.6 3,600 10.0 20,000 6.2 1.5
DIRECT
DRIVE
6 4,020 35.0 3,600 7.5
MANUFACTURER MODEL H W L
DIMENSIONS (IN.)
WEIGHT
(LBS.)
TOTAL
BHP
RPM
HP /
FAN
TOTAL
BHP
RPM
HP /
FAN
EQUIPMENT
TAG
LOCATION AREA SERVED
BASIS OF DESIGN
TYPE OF
SYSTEM
PHYSICAL CHARACTERISTICS
CFM MAX CFM
TSP
(IN. WG)
ESP
(IN.)
TYPE QTY.
FAN
RPM
MOTOR
CFM
TSP
(IN. WG)
ESP
(IN.)
TYPE QTY.
FAN
RPM
MOTOR
GENERAL
MIN.
O.A.
SUPPLY FAN EXHAUST FAN
AIR HANDLING UNIT SCHEDULE
7. REAR OPERATED OPPOSED BLADE BALANCING DAMPER WHERE INDICATED ON DRAWINGS.
6. PROVIDE WITH ANGLE FRAME FOR FIELD WELDING.
5. PROVIDE DAMPER AT NECK.
4. 1/2"x1/2"x1/2" GRID WITH 45 DEGREE BLADES.
3. FINISH AS SELECTED BY ARCHITECT.
2. COORDINATE FRAME TYPE WITH CEILING/WALL TYPE, REFER TO ARCHITECTURAL DRAWINGS.
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUALS.
NOTES:
H
SUPPLY /
RETURN
TITUS SD-SG
MAXIMUM SECURITY SUICIDE
DETERRENT
VARIES STEEL 30 1,2,3,6,7
G EXHAUST TITUS 350F 35 DEG. DEFLECTION REGISTER VARIES ALUMINUM 30 1,2,3
F EXHAUST TITUS 350RL-SS 35 DEG. DEFLECTION REGISTER VARIES
STAINLESS
STEEL
30 1,2,3
E
RETURN /
EXHAUST
TITUS 45F EGG CRATE VARIES ALUMINUM 30 1,2,3,4
D SUPPLY TITUS TRITEC-SS RADIAL AIR DIFFUSION 24"x24"
STAINLESS
STEEL
30 1,2,3
C SUPPLY TITUS 301RL-HD LOUVERED SUPPLY GRILLE VARIES STEEL 30 1,2,3,5
B SUPPLY TITUS OMNI-AA SQUARE PANEL FACE 24"x24" ALUMINUM 30 1,2,3
A SUPPLY TITUS OMNI SQUARE PANEL FACE 24"x24" STEEL 30 1,2,3
MANUFACTURER MODEL
EQUIPMENT
TAG
USE
BASIS OF DESIGN
TYPE
NOMINAL
FACE SIZE
MATERIAL
MAX.
N.C.
NOTES
DIFFUSER, GRILLE, AND REGISTER SCHEDULE
Revisions: Date:
BID SET 05/01/2023
ADDENDUM 1 04/30/2024
1 1 1 1
1 1 1 1 1
| Sheets |
| 50-M601 - MECHANICAL - SCHEDULES |
File details come from the government source that posted it. Updated .