50-M503.pdf
PDF 300 KB Posted
- Attached to
- Y1DA--Expand and Renovate Emergency Department B50 Minor Construction - Tucson VAMC (VA-24-00001448)
- Solicitation number
- 36c77623r0191
About this file
This document appears to be a set of mechanical drawings and details for the expansion and renovation of the Emergency Department B50 at the Tucson VA Medical Center. The drawings provide specifications and requirements for various mechanical systems, including HVAC, piping, and exhaust equipment. Key details include:
The drawings show the layout and specifications for chilled water, hot water, and steam piping, including the use of ball and butterfly valves, unions, flexible connections, and instrumentation. There are also details for handling condensate and drain lines, as well as requirements for pipe penetrations through walls. The drawings depict the layout and connections for a steam humidifier system, refrigerant piping for a DX cooling coil, and an up-blast exhaust fan. Typical details are provided for components like air vents, drain valves, and pump connections.
This appears to be part of a larger federal contract opportunity, Solicitation Number 36c77623r0191, for the expansion and renovation of the Emergency Department B50 at the Tucson VA Medical Center. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center Austin.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CHWR
CHWS
PITCH COIL
DRAIN PAN
UNION
FLEX. CONN.
AIR FLOW
FLOW CONTROL BALANCE VALVE
THERMOMETER (TYP.) BALL VALVE (TYP.)
NOTES:
1. ALL VALVES 2" AND SMALLER TO BE BALL VALVES, 2 1/2" AND LARGER TO BE BUTTERFLY VALVES.
2. INSTALL PIPE UNIONS ON 2" AND SMALLER PIPE, FLANGED PIPE 2 1/2" AND LARGER.
3. ALL COILS TO BE FACTORY TAPPED FOR MANUAL AIR VENT AT HIGH POINT AND DRAIN AT LOW POINT OF COIL.
4. ALL COILS TO BE PIPED FOR COUNTER FLOW OF AIR AND WATER.
5. PIPING TO COIL SHALL BE ARRANGED SO AS NOT TO BLOCK OFF ANY ACCESS REQUIREMENTS OR SERVICE
AREAS OF AIR HANDLING UNIT.
6. SEE FLOOR PLANS FOR PIPE SIZES.
7. PROVIDE FLEXIBLE PIPING CONNECTIONS AS SHOWN WHERE AIR HANDLING UNIT IS NOT INTERNALLY
ISOLATED OR WHERE SPECIFICALLY CALLED FOR ON DRAWINGS.
8. PIPING CONTRACTOR SHALL FURNISH/INSTALL TEMPERATURE WELLS AS SHOWN FOR FUTURE USE EVEN IF
SENSORS ARE NOT PROVIDED UNDER THIS PROJECT.
2-WAY VALVE BY T.C. CONTR.,
INSTALLED BY PIPING CONTR.
TEMPERATURE WELL BY PIPING
CONTR., SENSOR BY T.C.
CONTRACTOR (TYP.)
INCREASER OR
DECREASER AS
REQUIRED (TYP.)
PRESSURE/TEMPERATURE PLUG
WITH CAP FOR MANUAL
READINGS (TYP.)
1/2" COIL DRAIN VALVE W/ HOSE
THREAD OUTLET (TYP.)
DRAIN LINE TRAP.
STRAINER
PACK VOID BETWEEN PIPE OR INSULATION AND WALL
WITH FIBERGLASS BATT, THEN SEAL WITH A SILICONE
COMPOUND OR OTHER APPROVED SEALANTS. IF
WALL IS FIRE RATED, FILL VOID BETWEEN PIPE OR
INSULATION AND WALL WITH FIRE BARRIER CAULK.
CONTINUOUS SEALANT AROUND
OPENING BOTH SIDE OF WALL.
PIPE INSULATION.
SEE DRAWINGS FOR PIPE
SIZE AND MATERIAL.
NOTES:
1. I.D. OF WALL OPENING TO BE A MIN. OF 1/2" LARGER THAN O.D. OF PIPE OR INSULATION PASSING
THROUGH WALL.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF THEIR WALL OPENINGS WITH
OTHER TRADES AND/OR CONTRACTORS.
3. PIPE PENETRATIONS OF SMOKE OR FIRE WALLS SHALL BE IN COMPLIANCE WITH NFPA-90A.
PROVIDE A MINIMUM OF 1/2"
CLEARANCE BETWEEN WALL
AND PIPE OR INSULATION.
FACE OF WALL.
USE "S" SEPARATOR WHEN THE STEAM DISTRIBUTOR IS LOWER
THAN THE HUMIDIFIER STEAM OUTLET
SEE PLUMBING
DWG FOR R.O.
SYSTEM
NOTES:
1. USE ONLY STAINLESS STEEL PIPING OR MANUFACTURER RECOMMENDED MATERIAL.
2. SLOPE STEAM PIPING PER MANUFACTURER'S RECOMMENDATION.
3. PROVIDE FIRST VERTICAL 12" OF STEAM LINE OFF THE TOP OF THE HUMIDIFIER WITH NO BENDS OR TURN.
4. INSULATE PIPE PER SPECIFICATION.
STRAINER
UNION
MAIN DRAIN (SIZE PER
MANUFACTURER'S
RECOMMENDATIONS)
PAN DRAIN (SIZE PER
MANUFACTURER'S
RECOMMENDATIONS)
CONNECT TO OPEN DRAIN
CONNECT TO OPEN DRAIN
(HUM-5)
HUMIDIFIER FOR
AHU-5
LONG RADIUS
STAINLESS STEEL PIPE .
RIGID STAINLESS
STEEL PIPING WITH
INSULATION
12"
15°
15°
AHU-5
4" MIN.
FLEX HOSE
WITH CLAMP
STEAM DISTRIBUTION
MANIFOLD
12" MIN.
SIZE PER
MANUFACTURER'S
RECOMMENDATIONS
PIPING CURB
SEE ' ROOF SLEEVE'
DETAIL #10 ON SHEET 50-M501
SENSING BULB
RUNNING TRAP W/CLEANOUTS
EQUALIZING LINE
OIL TRAP
CONTROL WIRING IN CONDUIT
LIQUID LINE
SUCTION LINE
OIL TRAP
STRAINER
INSULATED
DRIP PAN
SIGHT GLASS/MOISTURE
INDICATOR
SOLENOID VALVE
THERMAL EXPANSION VALVE
PITCH IN DIRECTION
OF FLOW
FILTER/DRYER
EQUIPMENT RAILS
ROOF
NOTES:
1. REFRIGERANT PIPING AS SHOWN IS TO ILLUSTRATE GENERAL REQUIREMENTS. PIPING SHALL BE SIZED, PITCHED, AND ARRANGED PER CONDENSING UNIT MANUFACTURER'S RECOMMENDATIONS AND
REQUIREMENTS.
POWER WIRING IN CONDUIT
CHARGING VALVE
AIR COOLED
CONDENSING
UNIT
"DX"
COOLING COIL
MASON SUPER-W PAD
(OR VA APPROVED EQUAL)
TERMINATE 3/4" CONDENSATE DRAIN
OUT EXTERIOR WALL WITH DOWN
TURNED TYPE "K" COPPER ELBOW
PIPE HANGERS - PROVIDE DOUBLE DEFLECTION
NEOPRENE (TYPE HN) FOR FIRST TWO ON EACH
SIDE OF PUMP (SEE NOTE NO. 1)
PRESSURE GAGE
1/2"
STRAINERFLEXIBLE
CONNECTION
BALL OR BUTTERFLY
TYP.
NOTES:
1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.
BALANCING
DEVICE
CONCENTRIC REDUCER
LINE SIZE AIR CHAMBER 6"
HIGH AT EACH AIR VENT
DIRECTION
OF FLOW
DROP IN DIRECTION OF FLOW OF
WATER SUPPLY OR RETURN PIPING
1/8" COPPER TUBE, EXTEND
TO A POINT OF ACCESS
DOLE CO. No. 14 AIR VENT
MAXIMUM 6" ABOVE CEILING.
6" MAX.
CEILING ACCESS PANEL
INACCESSIBLE CEILING.
TYPICAL MANUAL AIR VENTTYPICAL CHILLED AND HOT WATER PIPING
DRAIN VALVE CONNECTIONS
ELEVATION
THREADED PIPING
ELEVATION
WELDED PIPING
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
3/4" BALL VALVE
ADAPTER TO 3/4" HOSE THREAD-
PROVIDE HOSE CAP NUT
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR PLANS
LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
AIR VENT
1/2" BALL VALVE
1/4" COPPER TUBING
1/2" x 4" NIPPLE
CIRCULATING WATER PIPING
ELEVATION
NOTES:
1. VENT ALL HIGH POINTS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.
MV
OR
AV
D
PROVIDE UNION UNLESS SAFETY VALVE
HAS FLANGED OUTLET
SAFETY VALVE
OPEN DRAIN (NOTE 3)
CONNECTION TO PRESSURE
VESSEL OR PIPE
VENT PIPE THROUGH ROOF
SUPPORT AS INDICATED ON
DWGS. (NOTES 1, 2)
PIPE THREADED INTO ELBOW (SAME
SIZE AS ELBOW)
DRIP PAN ELBOW
(SECTIONAL VIEW)
3/4" DRAIN TO FLOOR DRAIN OR
OPEN SIGHT DRAIN (NOTE 4)
ELEVATION
FLEXIBLE
CONNECTOR
3"
NOTES:
1. UNLESS OTHERWISE SHOWN ON THE DRAWINGS, SIZE THE VENT PIPE SO THAT STEAM IS NOT
BLOWN OUT AT THE VENT PIPE ENTRANCE. UTILIZE THE CALCULATION METHOD CONTAINED IN
ANSI B31.1. POWER PIPING CODE, APPENDIX II.
2. VENT PIPE SHALL TERMINATE 6' MIN. ABOVE FINISHED ROOF.
3. DISCHARGE OF DRAIN MUST BE DIRECTED AWAY FROM PLATFORMS OR OTHER AREAS WHICH
PERSONNEL MAY OCCUPY.
4. DO NOT CONNECT ANY OTHER DRAIN TO THE DRIP PAN ELBOW DRAIN PIPE.
24" MAX.
1" M
IN
NOTES:
1. CONSTRUCT PLATFORM TO ACCOMMODATE ROOF SLOPE AND PROVIDE LEVEL SURFACE FOR EQUIPMENT MOUNTING.
2. SECURE PLATFORM TO ROOF STRUCTURE AND SECURE EQUIPMENT TO PLATFORM.
3. 10 FEET MINIMUM HEIGHT IS SHOWN. INCREASE THE HEIGHT AS REQUIRED TO COMPLY WITH THE RECOMMENDATIONS
OF THE DISPERSION ANALYSIS.
2" SPRING VIBRATION
ISOLATORS WITH SEISMIC
RESTRAINTS. SECURE TO
PLATFORM, TYP.
SUPPORT DUCT WITH 1-1/2"x1-1/2"x22
GA SHEET METAL ANGLES SET ON
4x4 SHEET METAL BASE WITH ALL
EDGES HEMMED IN MASTIC
WELDED STAINLESS STEEL
EXHAUST STACK
DRAIN
MIN. 2 X 10's
@16" O.C.3/4" EXTERIOR
GRADE PLYWOOD
22 GA. GALV. S.M. PLATFORM COVER,
SOLDER ALL SEAMS, HEM ALL EDGES
RAIN SHIELD / SUNSHIELD
OVER FLEXIBLE CONNECTION
UP-BLAST
EXHAUST FAN
FULL WEATHER
COVER
ROOF
3" CANT STRIP,
CONTINUOUS
M
IN
. 4 0"
M
IN
. 1 0'-
0"
MIN. 3 x DIAMETER OF STRAIGHT RUN
FLEX CONNECTION
SIZE TO MAINTAIN 3,500
FPM OUTLET VELOCITY
1" GALVANIZED STEEL STRAP
SECURED TO EXHAUST STACK
GUY WIRE (4 REQUIRED)
AS
R
EQ
UI
RE
D
BIRD SCREEN
15°
SECURE GUY WIRE
TO ROOF (TYP.)
NOT TO SCALE
CHILLED WATER COIL 2-WAY VALVE PIPING
NOT TO SCALE
PIPE PENETRATION OF INTERIOR WALL
o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
VA FORM 08-6231
Office of Facilities Management
U.S. Department of Veterans Affairs
STAMP
Date
Location
Building Number Checked Drawn Drawing Number
Project Number
BID SET
Approved: Director
Approved: Associate Director
Approved: Assistant Director
Approved: Assoc. Director for Patient Care Service/Nurse Executive
Approved: Deputy Assoc. Director of Patient Care Services
Approved: Chief of Staff
Approved: Deputy Chief of Staff
Approved: Chief of Engineering
Approved:
Approved:
ARCHITECT/ENGINEER/CONSULTANTS:
Bancroft Project No.
SAVAHCS, TUCSON, AZ 85723
3300 Dundee Road
Northbrook, IL 60062
T: 847.952.9362
04/30/2024MECHANICAL - DETAILS EXPAND AND RENOVATE
EMERGENCY DEPARTMENT B50
50 DGG TE
50-M503
678-331
8-
E X
P A
N D
A N
D R
E N
O V
A T
E E
M E
R G
E N
C Y
D E
P A
R T
M E
N T
B
A
D D
E N
D U
M
NOT TO SCALE
ELECTRICAL TO STEAM HUMIDIFIER PIPING CONNECTIONS
NOT TO SCALE
DFSS REFRIGERANT PIPING
NOT TO SCALE
IN-LINE PUMPS - CONNECTIONS DETAIL
NOT TO SCALE
MANUAL AIR VENT
NOT TO SCALE
DRAIN VALVE AND AIR VENT CONNECTIONS (HYDRONIC SYSTEMS)
NOT TO SCALE
STEAM SAFETY VALVE
NOT TO SCALE
UP-BLAST EXHAUST FAN (EF-2A AND EF-2B)
Revisions: Date:
BID SET 05/01/2023
ADDENDUM 1 04/30/2024
| Sheets |
| 50-M503 - MECHANICAL - DETAILS |
| 50-M701 - MECHANICAL - CONTROLS |
| 50-M702 - MECHANICAL - CONTROLS |
File details come from the government source that posted it. Updated .