50-A502.pdf
PDF 581 KB Posted
- Attached to
- Y1DA--Expand and Renovate Emergency Department B50 Minor Construction - Tucson VAMC (VA-24-00001448)
- Solicitation number
- 36c77623r0191
About this file
This document appears to be a set of architectural plans and details related to a federal contract opportunity to expand and renovate the Emergency Department B50 at the Tucson VA Medical Center.
The key details include the solicitation number 36c77623r0191, the contract name "Y1DA--Expand and Renovate Emergency Department B50 Minor Construction - Tucson VAMC (VA-24-00001448)", and the requirement to install EIFS systems, sprayed fireproofing, and various wall partition types per the plans. The plans provide detailed dimensions and specifications for column types, wall assemblies, and other construction elements across multiple floors. This document appears to be part of the solicitation package providing technical specifications for the required construction work.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3.8
J
/4
1/
4"
1' - 6 1/2"
EIFS SYSTEM, INSTALLED
PER MANUFACTURER
RECOMENDATIONS
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
J
6 3/4" 1' - 11 1/2"
EIFS SYSTEM, INSTALLED
PER MANUFACTURER
RECOMENDATIONS
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
4.6
J
/4
1/
4"
EQ EQ
1' - 11 1/2"
EIFS SYSTEM, INSTALLED
PER MANUFACTURER
RECOMENDATIONS
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
J
/4
1/
4"
11 3/4" 1' - 2 3/4"
EIFS SYSTEM, INSTALLED
PER MANUFACTURER
RECOMENDATIONS
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
110°
1/2" FIBERGLASS BD;
REFER BALLISTIC
PARTITION TYPE
J
8.3
1'
- 0
9"
10" 10"
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
STOREFRONT SYSTEM
1' - 8"
SPANDREL PANEL
JOINT SEALANT
ALIGN GYP BD WITH MULLION
3.8
I
EQ
EQ
EIFS SYSTEM, INSTALLED
PER MANUFACTURER
RECOMENDATIONS
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
1' - 6 1/2"
1'
- 1
1/
2"
4.6
I
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
EQ
EQ
1'
- 1
1/
2"
1' - 1" 1' - 0 1/2"
5.5
I
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
(1) LAYER OF 5/8" TYPE X GYPSUM
BOARD ON BOTH SIDES OF MTL. STUDS
HANDRAIL; REFER FLOOR PLAN
1HR. RATED PARTITION;
REFER PARTITION TYPES
/4
1'
- 2
/4
10 1/2" 1' - 0 1/4"
REFER TO FLOOR PLAN
FOR PARTITION TYPES 6.3
I
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
EQ
EQ
1'
- 1
1/
2"
5 1/4" 1' - 1 1/2"
I
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
EQ EQ
1' - 11 1/2"
/4
/4
1'
- 1
1/
2"
3.8
H
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
6 3/4" 11 3/4"
9" 1'
- 1
1/ 2"
1/
4"
1/ 4"
1' - 6 1/2"
5.5
H
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
10 1/2" 1' - 0 1/4"
/4
/4
3.8
G
EIFS SYSTEM, INSTALLED
PER MANUFACTURER
RECOMENDATIONS
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
6 3/4" 11 3/4"
6 3/4" 11 3/4"
/4
/4
4.6
G
/4
/4
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
8 1/4" 11 3/4"
1'
- 1
1/
2"
5.5
G
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
11 1/2" 1' - 0 1/4"
1'
- 0
1'
- 0
/4
6.3
G
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
(1) LAYER OF 5/8" TYPE X GYPSUM
BOARD ON BOTH SIDES OF MTL. STUDS
1HR. RATED PARTITION; REFER PARTITION TYPES
50-A501
50-A501
11 1/2" 11 3/4"
2'
- 1
/4
G
1' - 11 3/4"
1'
- 8
/4
50-A501
J
8.5
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
REFER SF4 / A604
SPANDREL PANEL
10" 10"
1' - 8"
1'
- 0
ALIGN GYP BD WITH MULLION
JOINT SEALANT
(1) LAYER OF 5/8" TYPE X GYPSUM
BOARD ON BOTH SIDES OF MTL. STUDS
1HR. RATED PARTITION;
REFER PARTITION TYPES
EIFS SYSTEM, INSTALLED
PER MANUFACTURER
RECOMENDATIONS
HSS COLUMN PER STRUCTURAL
A1
AA
REFER TO FLOOR PLAN FOR
PARTITION TYPES
SPANDREL PANEL
3/
4"
1' - 0 1/2"
7 1/4"
REFER SF4 / A604
8 1/4"
STOREFRONT SYSTEM
SPRAYED FIREPROOFING
COLUMN PER STRUCTURAL
BB
EIFS SYSTEM, INSTALLED PER
MANUFACTURER RECOMENDATIONS
SPRAYED FIREPROOFING
COLUMN PER STRUCTURAL
4"
COLUMN PER STRUCTURAL
A1
BB
COLUMN PER STRUCTURAL
SPRAYED FIREPROOFING
REFER TO FLOOR PLAN FOR
PARTITION TYPES
EQ
EQ
1' - 11 1/2"
6 3 /4"
5" STOREFRONT SYSTEM
JOINT SEALANT
o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Drawing Title Project Title
VA FORM 08-6231
Office of Facilities Management
U.S. Department of Veterans Affairs
STAMP
Date
Location
Building Number Checked Drawn Drawing Number
Project Number
BID SET
Approved: Director
Approved: Associate Director
Approved: Assistant Director
Approved: Assoc. Director for Patient Care Service/Nurse Executive
Approved: Deputy Assoc. Director of Patient Care Services
Approved: Chief of Staff
Approved: Deputy Chief of Staff
Approved: Chief of Engineering
Approved:
Approved:
ARCHITECT/ENGINEER/CONSULTANTS:
Bancroft Project No.
SAVAHCS, TUCSON, AZ 85723
3300 Dundee Road
Northbrook, IL 60062
T: 847.952.9362
04/30/2024ARCHITECTURAL - PLAN DETAILS EXPAND AND RENOVATE
EMERGENCY DEPARTMENT B50
50 CZ DTB
50-A502
678-331
19-103
8-
E X
P A
N D
A N
D R
E N
O V
A T
E E
M E
R G
E N
C Y
D E
P A
R T
M E
N T
B
A
D D
E N
D U
M
1" = 1'-0"
FIRST FLOOR COLUMN J-3.8
1" = 1'-0"
FIRST FLOOR COLUMN NEAR J-4
1" = 1'-0"
FIRST FLOOR COLUMN J-4.6, NEAR J-5.5, NEAR J-6
1" = 1'-0"
FIRST FLOOR COLUMN J-7
1" = 1'-0"
FIRST FLOOR COLUMN J-8.3, 8.5
1" = 1'-0"
FIRST FLOOR COLUMN I-3.8
1" = 1'-0"
FIRST FLOOR COLUMN I-4.6, H-4.6
1" = 1'-0"
FIRST FLOOR COLUMN I-5.5
1" = 1'-0"
FIRST FLOOR COLUMN I-6.3, H-6.3
1" = 1'-0"
FIRST FLOOR COLUMN I-7
1" = 1'-0"
FIRST FLOOR COLUMN H-3.8
1" = 1'-0"
FIRST FLOOR COLUMN H-5.5
1" = 1'-0"
FIRST FLOOR COLUMN G-3.8
1" = 1'-0"
FIRST FLOOR COLUMN G-4.6
1" = 1'-0"
FIRST FLOOR COLUMN G-5.5
1" = 1'-0"
FIRST FLOOR COLUMN G-6.3
1" = 1'-0"
FIRST FLOOR COLUMN G-7
0 1/2' 1' 2' 0 1/2' 1' 2' 0 1/2' 1' 2' 0 1/2' 1' 2' 0 1/2' 1' 2'
0 1/2' 1' 2' 0 1/2' 1' 2' 0 1/2' 1' 2' 0 1/2' 1' 2' 0 1/2' 1' 2'
0 1/2' 1' 2' 0 1/2' 1' 2' 0 1/2' 1' 2' 0 1/2' 1' 2' 0 1/2' 1' 2'
0 1/2' 1' 2' 0 1/2' 1' 2'
1" = 1'-0"
FIRST FLOOR COLUMN J-8.5
0 1/2' 1' 2'
1" = 1'-0"
1HR RATED WALL
0 1/2' 1' 2'
1" = 1'-0"
FIRST FLOOR COLUMN A1-AA
1" = 1'-0"
COLUMN AT VESTIBULE
1" = 1'-0"
FIRST FLOOR COLUMN A1-BB
0 1/2' 1' 2' 0 1/2' 1' 2' 0 1/2' 1' 2'
Revisions: Date:
BID SET 05/01/2023
ADDENDUM 1 04/30/2024
| Sheets |
| 50-A502 - ARCHITECTURAL - PLAN DETAILS |
File details come from the government source that posted it. Updated .