About this file

This document is a Mechanical Schedules drawing for the "Expand and Renovate Emergency Department B50" contract opportunity at the Tucson, Arizona VA Medical Center.

The drawing includes schedules for VAV boxes, ductless split systems, humidifiers, and pumps. Key details include VAV box dimensions, airflows, heating capacities, and electrical requirements. The ductless split system schedule provides information on indoor and outdoor unit specifications, capacities, and electrical requirements. The humidifier schedule lists humidifier capacities, manifold dimensions, and electrical requirements. The pump schedule details pump models, flows, heads, motor sizes, and electrical requirements.

The drawing includes numerous notes providing additional requirements and specifications for the mechanical equipment. Overall, this document provides detailed technical information on the mechanical systems required for the contract.

View the file

Other files

File Type Posted
50-EP601.pdf PDF
50-M703.pdf PDF
50-A701.pdf PDF
50-A102.pdf PDF
50-M601.pdf PDF
50-EP101.pdf PDF
50-M704.pdf PDF
50-A504.pdf PDF
50-A104.pdf PDF
50-GC102.pdf PDF
50-CU101.pdf PDF
Addendum 1.pdf PDF
50-M505.pdf PDF
50-A502.pdf PDF
50-MG702.pdf PDF
50-AC101.1.pdf PDF
50-MH101.1.pdf PDF
50-EP102.pdf PDF
11 73 00 Ceiling Mounted Patient Lift_Rev.pdf PDF
08 80 00 Glazing_Rev.pdf PDF
50-A401.pdf PDF
50-AC101.4.pdf PDF
50-A303.pdf PDF
50-GC101.pdf PDF
50-MH104.pdf PDF
50-M702.pdf PDF
50-EP602.pdf PDF
01 00 00 Gen Reqs_Rev.pdf PDF
50-MG100.pdf PDF
Technical Questions Spreadsheet - Tucson - Final.pdf PDF
50-A602.pdf PDF
50-M503.pdf PDF
50-CD101.pdf PDF
50-S450.pdf PDF
50-MG701.pdf PDF
50-S310.pdf PDF
50-M701.pdf PDF
36C77623R0191 0003.pdf PDF
36C77623R0191 0002.pdf PDF
36C77623R0191 0001.pdf PDF
Site Visit Sign in Sheet Pg 1 and 2 - Tucson.pdf PDF
Attachment 8 - Architectural Drawings 2 of 2.pdf PDF
Attachment 14 - Mechanical Drawings.pdf PDF
Attachment 6 - Structural Drawings.pdf PDF
36C77623R0191 - 02-22-24.pdf PDF
Attachment 2 - Specifications - 2 of 3.pdf PDF
Attachment 5 - Civil Drawings.pdf PDF
Attachment 20 - Site Visit Instructions.pdf PDF
Attachment 17 - PTube Drawings.pdf PDF
Attachment 7 - Architectural Drawings 1 of 2.pdf PDF
Show 40 more

Latest 50 of 62 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

VA FORM 08-6231

Office of Facilities Management

U.S. Department of Veterans Affairs

STAMP

Date

Location

Building Number Checked Drawn Drawing Number

Project Number

BID SET

Approved: Director

Approved: Associate Director

Approved: Assistant Director

Approved: Assoc. Director for Patient Care Service/Nurse Executive

Approved: Deputy Assoc. Director of Patient Care Services

Approved: Chief of Staff

Approved: Deputy Chief of Staff

Approved: Chief of Engineering

Approved:

Approved:

ARCHITECT/ENGINEER/CONSULTANTS:

Bancroft Project No.

SAVAHCS, TUCSON, AZ 85723

3300 Dundee Road

Northbrook, IL 60062

T: 847.952.9362

04/30/2024MECHANICAL - SCHEDULES EXPAND AND RENOVATE

EMERGENCY DEPARTMENT B50

50 DGG TE

50-M602

678-331

8-

E X

P A

N D

A N

D R

E N

O V

A T

E E

M E

R G

E N

C Y

D E

P A

R T

M E

N T

B

A

D D

E N

D U

M

SHALL NOT EXCEED 0.3" WG.

5. HOT WATER COIL WATER PRESSURE DROP SHALL NOT EXCEED 5' AND AIR PRESSURE DROP

STATIC PRESSURE SHALL NOT BE LESS THAN 0.25" AT AIR FLOW RATE SCHEDULED. ELECTRICAL DRAWINGS FOR QUANTITY AND LOCATION.

4. REGARDLESS OF HOT WATER COIL AIR PRESSURE DROP, AVAILABLE DISCHARGE 9. PROVIDE NECESSARY 120V / 24V POWER SUPPLY FOR CONTROLLER POWER. COORDINATE WITH

ON ARI-880-98. AND EXISTING FIELD CONDITIONS.

DISCHARGE PRESSURE. NOISE CRITERIA (NC) SOUND INFORMATION IS BASED 8. COORDINATE LEFT HANDED/RIGHT HANDED COIL CONNECTIONS WITH DESIGN DRAWINGS

3. SOUND LEVELS (NC) AST FULL AIR FLOW WITH 0.75" INLET STATIC PRESSURE AND 0.5" 7. PROVIDE WITH ACCESS DOORS FOR REHEAT COIL AND FACTORY MOUNTED DISCONNECT.

DISCONNECT TOGGLE SWITCH FOR EACH VAV BOX. MANUFACTURER HAS COORDINATED WITH T.C. CONTRACTOR.

2. PROVIDE FACTORY MOUNTED TRANSFORMER WITH PROPERLY SIZED FUSE AND 120V FURNISHED BY THE T.C. CONTRACTOR. BOXES SHALL NOT BE RELEASED FOR PRODUCTION UNTIL BOX

1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUAL. 6. VAV MANUFACTURER TO MOUNT IN FACTORY THE DDC CARD/CONTROLLER AND DAMPER ACTUATOR

NOTES:

VAV-5-1065 1065, C4 TITUS DESV 545 545 8 12x10 10.0 15.5 12.0 545.0 11.8 55 75 180 0.6 1 20 20 NO 1,2,3,4,5,6,7,8,9

VAV-5-1064 1064, C4 TITUS DESV 590 835 10 14x12.5 12.5 15.5 14.0 835.0 18.0 55 75 180 1.2 1 23 19 NO 1,2,3,4,5,6,7,8,9

VAV-5-1061 1061, 1062 TITUS DESV 115 255 6 12X10 10.0 15.5 12.0 255.0 5.8 55 76 180 0.3 1 17 15 NO 1,2,3,4,5,6,7,8,9

VAV-5-1060 1060 TITUS DESV 385 385 6 12x8 8.0 15.5 12.0 385.0 8.2 55 75 180 0.5 1 23 20 NO 1,2,3,4,5,6,7,8,9

VAV-5-1059 1058, 1059 TITUS DESV 250 250 6 12x8 8.0 15.5 12.0 250.0 5.8 55 76 180 0.3 1 17 15 NO 1,2,3,4,5,6,7,8,9

VAV-5-1056 1055, 1056, 1057, C9 TITUS DESV 630 630 8 12x10 10.0 15.5 12.0 630.0 13.6 55 75 180 0.9 1 23 21 NO 1,2,3,4,5,6,7,8,9

VAV-5-1053 1052, 1053, C7 TITUS DESV 530 530 8 12x10 10.0 15.5 12.0 530.0 11.4 55 75 180 0.6 1 20 19 NO 1,2,3,4,5,6,7,8,9

VAV-5-1050 1050, 1051 TITUS DESV 250 250 6 12x8 8.0 15.5 12.0 250.0 5.4 55 76 180 0.3 1 17 15 NO 1,2,3,4,5,6,7,8,9

VAV-5-1048 1048, 1049 TITUS DESV 290 290 6 12x8 8.0 15.5 12.0 290.0 6.3 55 75 180 0.3 1 18 17 NO 1,2,3,4,5,6,7,8,9

VAV-5-1046 1046, 1046A TITUS DESV 585 585 8 12x10 10.0 15.5 12.0 585.0 12.6 55 75 180 0.7 1 22 20 NO 1,2,3,4,5,6,7,8,9

VAV-5-1045 1045 TITUS DESV 80 215 6 12x8 8.0 15.5 12.0 215.0 4.6 55 79 180 0.3 1 14 13 NO 1,2,3,4,5,6,7,8,9

VAV-5-1044 1044 TITUS DESV 480 2,050 14 20x17.5 17.5 15.5 20.0 480.0 8.9 55 90 180 0.9 1 24 18 NO 1,2,3,4,5,6,7,8,9

VAV-5-1042 1042 TITUS DESV 250 250 6 12x8 8.0 15.5 12.0 250.0 5.8 55 76 180 0.3 1 17 15 NO 1,2,3,4,5,6,7,8,9

VAV-5-1041 1041 TITUS DESV 280 280 6 12x8 8.0 15.5 12.0 280.0 6.0 55 75 180 0.3 1 18 17 NO 1,2,3,4,5,6,7,8,9

VAV-5-1038 1038, 1039, 1040, 1V2 TITUS DESV 210 845 10 14x12.5 12.5 15.5 14.0 845.0 23.4 55 81 180 0.9 2 22 18 NO 1,2,3,4,5,6,7,8,9

VAV-5-1036 1036 TITUS DESV 240 240 6 12x8 8.0 15.5 12.0 240.0 5.7 55 77 180 0.3 1 16 15 NO 1,2,3,4,5,6,7,8,9

VAV-5-1035 1035 TITUS DESV 305 305 6 12x8 8.0 15.5 12.0 305.0 8.9 55 82 180 0.8 1 20 17 NO 1,2,3,4,5,6,7,8,9

VAV-5-1034 1034 TITUS DESV 150 150 4 12x8 8.0 15.5 12.0 150.0 3.2 55 86 180 0.3 1 22 22 NO 1,2,3,4,5,6,7,8,9

VAV-5-1033 1033, C1 TITUS DESV 275 515 8 12x10 10.0 15.5 12.0 515.0 13.9 55 80 180 1.2 1 20 19 NO 1,2,3,4,5,6,7,8,9

VAV-5-1032 1032 TITUS DESV 240 240 6 12x8 8.0 15.5 12.0 240.0 5.7 55 77 180 0.3 1 16 15 NO 1,2,3,4,5,6,7,8,9

VAV-5-1031 1030, 1031, C2 TITUS DESV 550 550 8 12x10 10.0 15.5 12.0 550.0 12.4 55 76 180 0.7 1 22 20 NO 1,2,3,4,5,6,7,8,9

VAV-5-1029 1028, 1029, C2 TITUS DESV 550 550 8 12x10 10.0 15.5 12.0 550.0 12.4 55 76 180 0.7 1 22 20 NO 1,2,3,4,5,6,7,8,9

VAV-5-1027 1027, C11 TITUS DESV 265 330 6 12x8 8.0 15.5 12.0 330 8.2 55 78 180 0.5 1 21 17 NO 1,2,3,4,5,6,7,8,9

VAV-5-1026 1026(A-G), 1026 TITUS DESV 1,145 1,315 12 16x15 15.0 15.5 16.0 1315 32.6 55 83 180 0.9 2 23 20 NO 1,2,3,4,5,6,7,8,9

VAV-5-1023 1023, 1024, 1025 TITUS DESV 310 420 8 12x10 10.0 15.5 12.0 420.0 11.6 55 80 180 0.8 1 18 18 NO 1,2,3,4,5,6,7,8,9

VAV-5-1021 1020, 1021, 1022 TITUS DESV 300 410 8 12x10 10.0 15.5 12.0 410.0 12.6 55 83 180 1.1 1 18 18 NO 1,2,3,4,5,6,7,8,9

VAV-5-1018 1017, 1018, 1019, C12 TITUS DESV 565 740 8 12x10 10.0 15.5 12.0 740 22.1 55 83 180 0.9 2 23 20 NO 1,2,3,4,5,6,7,8,9

VAV-5-1015 1015, 1016 TITUS DESV 250 390 6 12x8 8.0 15.5 12.0 390 11.2 55 85 180 0.6 2 22 18 NO 1,2,3,4,5,6,7,8,9

VAV-5-1014 1013, 1014, C12 TITUS DESV 455 595 8 12x10 10.0 15.5 12.0 595 16.4 55 80 180 0.6 2 20 19 NO 1,2,3,4,5,6,7,8,9

VAV-5-1009 1007, 1009, C13 TITUS DESV 365 445 8 12x10 10.0 15.5 12.0 445 11.6 55 79 180 0.7 1 19 18 NO 1,2,3,4,5,6,7,8,9

VAV-5-1008 1008 TITUS DESV 130 130 4 12x8 8.0 15.5 12.0 130 3.3 55 89 180 0.3 1 18 20 NO 1,2,3,4,5,6,7,8,9

VAV-5-1006 1006, 1004 TITUS DESV 190 190 6 12x8 8.0 15.5 12.0 190 4.9 55 81 180 0.3 1 13 11 NO 1,2,3,4,5,6,7,8,9

VAV-5-1002 1002, 1010 TITUS DESV 115 535 8 12x10 10.0 15.5 12.0 535 14.1 55 79 180 1.2 1 20 19 NO 1,2,3,4,5,6,7,8,9

VAV-5-1001C 1001 TITUS DESV 1,050 1,050 10 14x12.5 12.5 15.5 14.0 1050 29.4 55 81 180 1.2 2 23 20 NO 1,2,3,4,5,6,7,8,9

VAV-5-1001B 1001, 1001A, 1003 TITUS DESV 1,265 1,265 12 16x15 15.0 15.5 16.0 1265 36.2 55 81 180 1.2 2 20 19 NO 1,2,3,4,5,6,7,8,9

VAV-5-1001A 1001, 1001B, 1003 TITUS DESV 1,615 1,615 12 16x15 15.0 15.5 16.0 1615 43.9 55 80 180 1.5 2 24 22 NO 1,2,3,4,5,6,7,8,9

MIN. MAX.

INLET

SIZE

OUTLET

SIZE

H L W

HEATING

CFM

CAPACITY

(MBH)

EAT

(°F)

LAT

(°F)

EWT

(°F)

GPM ROWS RADIATED DISCHARGE

EQUIPMENT TAG AREAS SERVED MANUFACTURER MODEL

AIRFLOW (CFM) APPROX. DIMENSIONS (IN.) HOT WATER COIL NOISE LEVEL(NC)

INTEGRAL

SOUND

ATTENUATOR

NOTES

VAV BOX WITH HOT WATER REHEAT SCHEDULE

4. PROVIDE THE FOLLOWING FACTORY INSTALLED ACCESSORIES FOR THE OUTDOOR UNIT: NEMA 3R DISCONNECT.

3. WALL MOUNTED TEMPERATURE SENSOR.

2. INDOOR UNIT SHALL BE INTERLOCKED TO OUTDOOR UNIT FOR POWER AND CONTROL WIRING.

1. ACCEPTABLE MANUFACTURERS: VA APPROVED EQUALS.

NOTES:

DFSS-AHU-5 AHU-5 VESTIBULE CARRIER 40MAHBQ24XA3 HIGH WALL 15 45 11 719 80° 67° 24,000 - 19,800 1 0.6 - 208 CLEANABLE ACCU-AHU-5 38MARBQ24AA3 ROOF 134.5 2 R-410A 86.4 21.5 25 35 1 208 1,2,3,4

DFSS-1025 1025 - OIT COMM CLOSET CARRIER 40MAHBQ24XA3 HIGH WALL 15 45 11 719 80° 67° 24,000 - 19,800 1 0.6 - 208 CLEANABLE ACCU-1025 38MARBQ24AA3 ROOF 134.5 2 R-410A 86.4 21.5 25 35 1 208 1,2,3,4

H W D

TOTAL

CFM

EAT. D.B.

(°F)

EAT. W.B.

(°F)

COOLING

(BTUH)

HEATING

(KW)

HEATING

(BTUH)

PHASE MCA MOCP VOLTS

SIZE

(TONS)

REF.

TYPE

EAT (°F) SEER MCA MOCP PHASE VOLTS

MODEL TYPE

DIMENSIONS (IN.) AIRFLOW CAPACITY ELECTRICAL DATA

FILTERS

EQUIPMENT

TAG

MODEL LOCATION WEIGHT

COMPRESSOR ELECTRICAL DATA

EQUIPMENT

TAG

LOCATION

BASIS OF

DESIGN

INDOOR UNIT OUTDOOR UNIT

NOTES

DUCT FREE SPLIT SYSTEM SCHEDULE

8. HUMIDIFER MUST BE FULLY INSULATED WITH A STAINLESS STEEL BOTTOM DRAIN PAN, ANTI-FREEZE CAPABILITY AND OVERHEAT PROTECTION.

7. HUMIDIFERS INCLUDE INTERNAL DRAIN WATER TEMPERING TO 140°F.

6. PROVIDE WITH MANUFACTURER'S SUPPORT STAND AND STAINLESS STEEL HUMIDIFIER CABINET.

AIR FLOW PROVING SAFETIES. CONTROL SIGNAL TO HUMIDIFIER FROM BMS.

5. PROVIDE FULLY MODULATING CONTROL VALVE AND BMS COMMUNICATION VIA BACNet PROTOCOL. MANUFACTURER TO PROVIDE DUCT MOUNTED HIGH-LIMIT AND

SHIP THE MANIFOLD TO THE JOBSITE FOR INSTALLATION BY THE CONTRACTOR.

4. PROVIDE HEADER, DOUBLE WALLED, STAINLESS STEEL DISPERSION MANIFOLD TUBES WITH ARMACELL FOAM ENCAPSULATED INSULATION, MOUNTING FRAME, AND INLET KIT.

3. ELECTRIC HUMIDIFIERS INCLUDE FULL MODULATING OF CAPACITY VIA SOLID STATE RELAYS.

2. PROVIDE ON/OFF DIGITAL DUCT HUMIDISTAT, AIR PROVING SWITCH, AND REMOTE WALL HUMIDITY SENSOR c/w DIGITAL DISPLAY.

1. PROVIDE NECESSARY STAND TO AHU MANIFOLD TO ACHIEVE DRAIN HEIGHT. FOLLOW ALL MANUFACTURER'S RECOMMENDATION.

NOTES:

HUM-5 AHU-5 20,000 100% 15 120 x48 18 270 90 480 3 48 x 33 x 24-3/8 444 NEPTRONIC SKE4-N90M-480-3W 1 THRU 8

RATED POWER

(kW)

VOLT PHASE MANUFACTURER MODEL

EQUIPMENT

TAG

SERVICE

AIRFLOW

(CFM)

OA

ABSORPTION

DISTANCE MAX.

(IN)

MANIFOLD

DIMENSIONS

(W x H)

NO. OF

DISPERSION

TUBES

CAPACITY

(lbs/hr)

ELECTRICAL

DIMENSIONS

( H x W x D)

UNIT

WEIGHT

(lbs)

BASIS OF DESIGN

REMARKS

HUMIDIFIER SCHEDULE

2. PROVIDE SHAFT GROUNDING RING, PREMIUM EFFICIENCY MOTOR, AND VFD RATED MOTOR, SEE VFD SCHEDULE.

1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUAL

NOTES:

P 50-2 MECH RM - 342

HEATING

HOT WATER

BELL & GOSSET E-80 2.5x2.5x9.5C

IN-LINE

CENTRIFUGAL

WATER 160.0 60.0 5.8 8.375 1750 63.4% 3.98 7.5 3 480 1, 2

P 50-1 MECH RM - 342

HEATING

HOT WATER

BELL & GOSSET E-80 2.5x2.5x9.5C

IN-LINE

CENTRIFUGAL

WATER 160.0 60.0 5.8 8.375 1750 63.4% 3.98 7.5 3 480 1, 2

MANUFACTURER MODEL BHP HP PHASE VOLT

EQUIPMENT

TAG

LOCATION SERVICE

BASIS OF DESIGN

TYPE FLUID TYPE GPM

HEAD

(FT.)

NPSHr

IMP.

DIA.

(IN.)

RPM

MINIMUM

EFFICIENCY

MOTOR

NOTES

PUMP SCHEDULE

11. SEE SPECIFICATIONS AND DETAILS FOR ADDITIONAL REQUIREMENTS.

10. HOUSING AND FILTERS MUST BE MANUFACTURED UNDER STRICT GUIDELINES THAT CONFORM TO ASME NQA-1.

9. EACH TIER MUST BE SEPARATELY DUCTED AND HAVE INLET AND OUTLET BUBBLE-TIGHT DAMPERS THAT ARE EQUAL TO FLANDERS DBTM-FB-2H1W-304-20.

8. EACH UNIT MUST HAVE A REDUNDANT TIER THAT CAN BE ISOLATED FOR DECONTAMINATION AND/OR FILTER CHANGE PROCESSES.

7. PROVIDE 3" DECON PORTS W/ CAPS.

6. PROVIDE UPSTREAM AEROSOL SAMPLE PORT FACTORY INSTALLED ON HOUSING, UPSTREAM INJECTION PORT AND DOWNSTREAM SAMPLE PORT SHIPPED LOOSE FOR FIELD INSTALLATION PER MANUFACTURERS RECOMMENDATIONS.

5. PROVIDE LIFTING LUGS & STAINLESS STEEL MOUNTING BASE.

4. PROVIDE STATIC PRESSURE TAPS AND PROVIDE WEATHER COVER.

3. PROVIDE SEPARATE ACCESS DOORS FOR PREFILTERS AND HEPA FILTERS.

2. PROVIDE STATIC PRESSURE TAPS AND WEATHER PROOF MAGNEHELIC GAGES TO READ ACROSS PREFILTER AND HEPA FILTER BANKS INDIVIDUALLY.

1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUAL.

NOTES:

HEPA HOUSING BF1-2H1W-4GGF-304-D3

HEPA FILTER 99.99% 24 24 11.5 2 2 1 MEGAcel I 0.30 2.00

TEST HOUSING N/A N/A

F-2A/2B

ISOLATION EXAM

ROOMS

THIRD FLOOR

ROOF

FLANDERS 1,000

PREFILTER >85% / MERV-9 24 24 4 2 2 1 MEGApleat M9 0.08 1.00

3 1,2,3,4,5,6,7,8,9,10,11

HEIGHT

(IN)

WIDTH

(IN)

DEPTH

(IN)

TOTAL

NUMBER OF

UNITS

NUMBER

UNITS

HIGH

NUMBER

UNITS

WIDE

CLEAN DIRTY

TAG SERVICE LOCATION MANUFACTURER

CFM MAX

CAPACITY

TYPE

% Efficiency ASHRAE

STANDARDS 52.1 / 52.2

FILTER MODULE

NOMINAL SIZE

FILTER MODULE

ARRANGEMENT

PREFILTER, HEPA FILTER AND

BAG-IN BAG-OUT HOUSING

MODEL NUMBERS

MAXIMUM PRESSURE

DROP (IN WG)

TOTAL HOUSING

FINAL PRESSURE

DROP

(IN WG)

REMARKS

HEPA FILTER HOUSING SCHEDULE

Revisions: Date:

BID SET 05/01/2023

ADDENDUM 1 04/30/2024

Sheets
50-M503 - MECHANICAL - DETAILS
50-M505 - MECHANICAL - DETAILS
50-M601 - MECHANICAL - SCHEDULES
50-M602 - MECHANICAL - SCHEDULES