M910 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES AHU-28.pdf

PDF 2 MB Posted

Attached to
Z2DA--Remediate Temperature Controls 539-21-108 Federal contract opportunity
Solicitation number
36C25026B0002
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This document is a technical drawing and sequence of operations for HVAC controls at the Cincinnati VA Medical Center, specifically for Building 1 Pressurization Control Sequences for Air Handling Unit (AHU)-28. The scope of work includes commissioning the air handling unit, recalibrating pressure transducers, performing preventative maintenance on dampers and actuators, cleaning and calibrating air flow monitoring stations, and modifying control sequences.

Key technical requirements include implementing a variable speed drive control system with static pressure sensing, supply air temperature reset following ASHRAE 36.2 standards, and specific night-time setback procedures for exhaust fans and air dampers. The document provides detailed instructions for adjusting system controls, such as resetting supply duct static pressure based on VAV box damper positions, managing humidity-based temperature controls, and establishing protocols for identifying and managing "rogue zones" in the HVAC system. The drawing is dated 1/12/2026 and is part of project number 539-21-108 for the U.S. Department of Veterans Affairs.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--Remediate Temperature Controls 539-21-108, newest first.
File Type Posted
36C25026B0002 0004.pdf PDF
1-M104 - FOURTH FLOOR.pdf PDF
M901 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-4.pdf PDF
M903 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-7.pdf PDF
M908 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-24.pdf PDF
M909 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-26.pdf PDF
PG-M101 - PARKING GARAGE 1ST FLOOR PLAN.pdf PDF
ICRA 539.21.108 Mech Rooms Level II.pdf PDF
Updated Specs Addendum 4.pdf PDF
1-M105 - FIFTH FLOOR.pdf PDF
1-M109 - NINTH FLOOR.pdf PDF
13-M101 - BUILDING 13 FIRST FLOOR.pdf PDF
64-M100 - BUILDING 64 BASEMENT.pdf PDF
M906 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-17.pdf PDF
REVISED STATEMENT OF BID ITEMS.pdf PDF
ICRA 539.21.108 Patient Areas Level III.pdf PDF
Change Summary of Specs and Drawings.pdf PDF
1-M100 - BASEMENT.pdf PDF
64-M102 - BUILDING 64 SECOND FLOOR.pdf PDF
64-M103 - BUILDING 64 THIRD FLOOR.pdf PDF
M004 - TRIDIUM ROUTER SCHEDULE.pdf PDF
M701 - GENERAL CRITERIA HONEYWELL CONTROLS REPLNT.pdf PDF
M902 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-5.pdf PDF
M904 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-8.pdf PDF
M905 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-12.pdf PDF
M907 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-21.pdf PDF
M911 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES AHU-29.pdf PDF
Sign in Sheet Remediate Temp.pdf PDF
1-M103 - THIRD FLOOR.pdf PDF
36C25026B0002 0003.pdf PDF
36C25026B0002 0002.pdf PDF
36C25026B0002 0001.docx DOCX document
Attachment XVI - Directive 1192.01, Flu.pdf PDF
Attachment IX -RTC BID DWGS 7 2025.1023.pdf PDF
Attachment VII - RTC BID DWGS 5 2025.1023.pdf PDF
Attachment VI -RTC BID DWGS 4 2025.1023.pdf PDF
Attachment III -RTC BID DWGS 1 2025.1023.pdf PDF
Attachment I - WD OH20250082.pdf PDF
Attachment XV - 852.219-75 LOS.docx DOCX document
Attachment XIII - RFI Form.pdf PDF
Attachment XVII - ICRA Level 2.pdf PDF
Attachment X - RTC BID DWGS 8 2025.1023.pdf PDF
Attachment V - RTC BID DWGS 3 2025.1023.pdf PDF
Attachment II - CD SPECIFICATION 2025.1023.pdf PDF
36C25026B0002.docx DOCX document
Attachment XIV - EMR Form.pdf PDF
Attachment XII - J A - Redacted.pdf PDF
Attachment XI - RTC BID DWGS 9 2025.1023.pdf PDF
Attachment VIII - RTC BID DWGS 6 2025.1023.pdf PDF
Attachment IV - RTC BID DWGS 2 2025.1023.pdf PDF
Show all 50

Z2DA--Remediate Temperature Controls 539-21-108 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P ro je ct

N o.

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 10

E

D

C

B

A

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Manager

Cincinnati V.A Medical Center

U.S. Department of Veterans Affairs

F

Phase

ARCHITECT/ENGINEER OF RECORDCONSULTANT

32 4 5 6 7 8 9 10

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLEREDKEVIN HENDERSONPROJECT NO. STATE COA FIRM NO.

/1

/2

:1

:3

A

M -2

-1

BUILDING 1 PRESSURIZATION

CONTROL SEQUENCES - AHU-28

10/23/25 GSE WJS

REMEDIATE TEMPERATURE

CONTROLS

M910

539-21-108

CINCINNATI, OHIO

2020-05099 01528

SCALE: NONE

AHU-28 CONTROLS - EXISTING CONTROL DIAGRAM

EXISTING SEQUENCES

AHU-28 SEQUENCE OF OPERATIONS (ITEMS MARKED WITH * FOR IMPLEMENTATION INTO

OTHER AHU SEQUENCES)

1. SAFETY CONTROLS

A. GENERAL WIRING INSTRUCTIONS

1) THE LOW/HIGH PRESSURE CUT-OUTS AND FREEZESTAT SAFETY CIRCUITS WILL BE

HARDWIRED IN SERIES WITH THE SUPPLY AIR FAN MOTOR STARTER CONTROL

CIRCUIT.

2) HARDWIRE INTERLOCK RETURN AIR FAN STARTER CIRCUIT TO SUPPLY AIR FAN

STARTER CIRCUIT VIA NO AUXILIARY CONTACTS ON SUPPLY AIR FAN MOTOR

STARTER.

B. FIRE ALARM RELAY

1) THE BMCS WILL STOP THE SUPPLY/RETURN FAN(S) AND DRIVE ALL CONTROL

DAMPERS TO THEIR FAILED POSITIONS WHENEVER THE EXISTING FIRE ALARM RELAYS

ARE ACTIVATED BY THE FIRE ALARM PANEL.

C. FREEZESTATS

1) ALL UNITS ARE EQUIPPED WITH LOW LIMIT THERMOSTAT(S) WITH MANUAL RESET

DOWNSTREAM OF THE HEATING COIL.

2) WHEN THE LOW LIMIT THERMOSTAT SENSES A TEMPERATURE LESS THAN 38 DEGF

(ADJ.), THE SUPPLY AND RETURN FANS WILL STOP.

D. SAF DISCHARGE PRESSURE SWITCH

1) THE UNIT IS EQUIPPED WITH SAF DISCHARGE PRESSURE SWITCH WITH MANUAL

RESET TO SHUT DOWN SUPPLY AND RETURN FANS IF SUPPLY FAN DISCHARGE STATIC

PRESSURE EXCEEDS SWITCH SETPOINT.

E. RAF DISCHARGE HIGH PRESSURE SWITCH

1) PROVIDE RETURN AIR FAN HIGH DISCHARGE PRESSURE LIMIT SWITCH WITH

MANUAL RESET TO SHUT DOWN SUPPLY AND RETURN FANS IF RETURN FAN

DISCHARGE STATIC PRESSURE EXCEEDS SWITCH SETPOINT.

2. SUPPLY FAN CONTROL

A. SAF VARIABLE AIR VOLUME UNITS

1) IF SAFETY CONTROLS ARE NORMAL, THE VFD(S) FOR THE SUPPLY FAN(S) WILL BE

ENABLED BY THE BMCS AND WILL RUN CONTINUOUSLY.

2) THE VFD(S) WILL VARY THE SPEED OF THE FAN MOTOR(S) AS REQUIRED TO

MAINTAIN THE SUPPLY DUCT STATIC PRESSURE SENSOR SETTING (ADJ.).

3) FOR DUAL SUPPLY FANS, THE FANS WILL OPERATE IN UNISON AT THE SAME SPEED.

4) PROVIDE SUPPLY FAN(S) WITH CURRENT SWITCH FOR FAN STATUS.

3. SAF STATIC LOAD REDUCTION

A. THE BCMS WILL PROVIDE AUTOMATIC REMOTE STATIC RESET FUNCTIONALITY TO

RESETS THE AIR HANDLER STATIC PRESSURE SETPOINT BASED ON TIME OF DAY,

OUTSIDE AIR TEMPERATURE OR NIGHT SETBACK ROUTINE.

B. THE CONTRACTOR WILL PROVIDE A RESET TABLE GRAPHIC THAT PROVIDES THE

FOLLOWING POINTS FOR EACH AIR HANDLER:

1) AHU REMOTE STATIC PRESSURE

2) REMOTE STATIC SETPOINT

3) TIME OF DAY MULTIPLIER SETPOINT

4) TEMPERATURE MULTIPLIER SETPOINT

5) NIGHT SETBACK MULTIPLIER SETPOINT

6) PERCENT REMOTE STATIC RESET

7) CURRENT REMOTE STATIC RESET VALUE

C. THE BCMS WILL MULTIPLY THE AHU REMOTE STATIC PRESSURE SET POINT BY THE TIME

OF DAY MULTIPLIER SETPOINT, TEMPERATURE MULTIPLIER SETPOINT, AND THE NIGHT

SETBACK MULTIPLIER SETPOINT TO GENERATE A MODIFIED AHU REMOTE STATIC

SETPOINT FOR THE AIR HANDLER.

1) THE CONTRACTOR IS RESPONSIBLE FOR ALL PROGRAMMING NECESSARY TO

IMPLEMENT THE CONTROL LOGIC IN THE BCMS. THE OWNER WILL BE RESPONSIBLE

FOR FINE ADJUSTMENT OF ALL PARAMETER SETTINGS ONCE THE CONTROL LOGIC

HAS BEEN COMMISSIONED AND FOUND SATISFACTORY BY THE BO ENGINEER.

* 4. RETURN FAN CONTROL

A. RAF TRACKING, OBC

1) IF SAFETY CONTROLS ARE NORMAL, THE VFD(S) FOR THE RETURN FAN(S) WILL BE

ENABLED BY THE BMCS AND WILL RUN CONTINUOUSLY.

2) THE VFD(S) WILL VARY THE SPEED OF THE FAN MOTOR(S) AS REQUIRED TO

MAINTAIN A RETURN FAN DISCHARGE STATIC PRESSURE SETPOINT PER THE

SPECIFIED STATIC PRESSURE RESET SCHEDULE. FOR DUAL RETURN FANS, THE FANS

WILL OPERATE IN UNISON AT THE SAME SPEED.

3) THE RETURN AIR PLENUM PRESSURE SETPOINT WILL BE RESET BASE ON RS-4

OUTDOOR AIR ENTHALPY RESET SCHEDULE AS FOLLOWS:

4) AT OR BELOW 17.5 BTU’S PER LB, THE RETURN AIR PLENUM PRESSURE WILL

INITIALLY BE SET AT 0.0 IN WC BY THE BMS CONTRACTOR. FINAL STATIC SETTING WILL

BE DETERMINED BY BO ENGINEER AFTER FIELD ANALYSIS.

5) THE RETURN AIR PLENUM PRESSURE WILL BE LINEARLY RESET UPWARDS AS THE

OUTDOOR AIR ENTHALPY INCREASES FROM 17.5 TO 25.0 BTU’S PER LB. THE INITIAL

BMS CONTRACTOR SETTING OF THIS RESET WILL BE 0.0 IN WC AT 17.5 BTU’S PER LB

AND BE 0.40 IN WC AT 25.0 BTU’S PER LB. FINAL RESET SCHEDULE STATIC SETTING

WILL BE DETERMINED BY BO ENGINEER AFTER FIELD ANALYSIS.

6) THE RETURN AIR PLENUM PRESSURE WILL BE +/- 2.5 IN WC WHEN IN THE

ECONOMIZER IS IN THE OUTSIDE AIR LOCK-OUT MODE AND THE AIR HANDLERS

EXHAUST AIR DAMPERS WILL BE 100% CLOSED. FINAL STATIC PRESSURE RESET

SETTINGS WILL BE DETERMINE BY BO ENGINEER AFTER FIELD ANALYSIS.

B. ALL RETURN AIR FANS:

1) THE BMCS WILL MONITOR RETURN FAN(S) STATUS WITH CURRENT SWITCH(S) AND

ISSUE ALARMS TO THE OPERATOR ON FAN FAILURE.

* 5. OUTSIDE AIR AND RETURN AIR DAMPER CONTROL

A. ECONOMIZER, OBC (RA AND SINGLE OSA DAMPER)

1) PROVIDE VARYING SUPPLY AIR TEMPERATURE PID CONTROL LOOP SPEEDS FOR

SUMMER AND WINTER COOLING PERIODS. THE SUPPLY AIR CONTROL LOOP WILL

REACT VERY SLOWLY IN THE COLDEST MONTHS, AND THEN GRADUALLY INCREASE IN

SPEED AS THE OUTDOOR AIR TEMPERATURES INCREASE. THE CONTROL LOOPS MUST

BE FAST ENOUGH TO MAINTAIN SUPPLY TEMPERATURE SETPOINT AT ALL TIMES BUT

SLOW ENOUGH TO PREVENT RESENT FREEZESTAT TRIPS IN THE WINTER.

2) WHEN THE ECONOMIZER CONTROL IS INACTIVE, MODULATE THE OUTSIDE AIR

DAMPER AS REQUIRED TO MAINTAIN THE SCHEDULED MINIMUM OUTSIDE AIR

QUANTITY AS MEASURED BY THE OUTSIDE AIRFLOW STATION.

3) DURING NORMAL OCCUPIED MODES OF OPERATION, THE RETURN AIR DAMPER

CONTROL SIGNAL WILL BE RESET WHEN REQUIRED TO ASSIST IN MAINTAINING

MINIMUM OUTSIDE AIRFLOW. THE BMCS WILL COMPARE THE NORMAL RETURN AIR

DAMPER POSITION COMMAND SIGNAL TO THE MINIMUM OUTSIDE AIR RESET

SCHEDULE RS-1 (SEE RESET SCHEDULE TABLE) AND MAINTAIN THE RETURN AIR

DAMPER IN THE MOST CLOSED POSITION REQUEST BY THE BMCS.

4) WHEN THE ECONOMIZER CONTROL IS ACTIVE, THE OSA DAMPER AND RETURN AIR

DAMPER WILL BE SEQUENCE TO CONTROL THE AIR HANDLERS SUPPLY AIR

TEMPERATURE WHILE MAINTAINING MINIMUM OSA FLOW REQUIREMENTS AT ALL TIME

AS FOLLOWS:

A) THE OUTSIDE AIR DAMPER WILL REFERENCE A MAXIMUM SIGNAL SELECTOR

OUTPUT TO DETERMINE ITS DAMPER POSITION. THIS MAXIMUM SIGNAL SELECTOR

WILL COMPARE THE MINIMUM OSA REQUIREMENTS CONTROL LOOP SIGNAL

STRENGTH TO THE COOLING CONTROL LOOP SIGNAL STRENGTH AND SELECT THE

MAXIMUM CONTROL SIGNAL TO CONTROL THE OSA DAMPER POSITION.

B) IF THE COOLING DEMAND IS GREATER THAN THE MINIMUM OSA REQUIREMENT

DEMAND, THE BMCS WILL IGNORE THE MINIMUM OSA CONTROL SIGNAL AND

MODULATE THE OSA DAMPER AS THE FIRST STAGE OF COOLING.

C) IF THE MINIMUM OSA REQUIREMENT DEMAND IS GREATER THAN THE COOLING

DEMAND, THE BMCS WILL IGNORE THE COOLING DEMAND CONTROL SIGNAL AND

MODULATE THE OSA DAMPER TO MAINTAIN MINIMUM OSA FLOW.

5) THE ECONOMIZER CONTROL WILL BE ACTIVATED WHEN THE OUTSIDE AIR

ENTHALPY IS LESS THAN 25 BTU'S.

6) WHEN THE SUPPLY AND RETURN FANS ARE OFF, THE NORMALLY CLOSED OUTSIDE

AIR DAMPER WILL BE CLOSED, AND THE NORMALLY OPEN RETURN AIR DAMPER WILL

BE OPEN.

7) THE BMCS WILL USE RAMPING LOGIC TO SLOWLY ENTER OR EXIT THE ECONOMIZER

CYCLE.

8) THE ECONOMIZER CONTROL DAMPERS SHALL BE RAMPED OPEN OR CLOSED NOT

MORE THAN 1% PER 9 SECONDS WHEN ENTERING OR EXITING THE ECONOMIZER

CYCLE (0-100 % = 15-MINUTES RAMP TIME).

9) DURING START-UP PERIODS, THE BMCS SHALL USE THE FOLLOWING RAMPING-UP

LOGIC TO SLOWLY DECREASES THE AIR HANDLERS SUPPLY AIR TEMPERATURE TO

SETPOINT:

A) ABOVE 40 DEGF, THE OSA DAMPER(S) SHALL BE SEQUENCED OPEN USING A

MINIMUM OF 15-MINUTES RAMP PERIOD TO GO FROM 0 TO 100% OPEN.

B) BELOW 40 DEGF, THE OSA DAMPER(S) SHALL BE SEQUENCED OPEN USING A

MINIMUM OF 30-MINUTES RAMP PERIOD TO GO FROM 0 TO 100% OPEN. GREATER

RAMP PERIODS MAY BE REQUIRED TO PREVENT NUISANCE FREEZESTAT SHUT-

DOWNS.

C) THE MINIMUM OSA FLOW SHALL BE SET TO ZERO (0) CFM UNTIL THE UNIT HAS

REACHED SA TEMPERATURE SETPOINT.

D) BELOW 25 DEGF, THE OSA DAMPER(S) SHALL BE SEQUENCED OPEN USING A

MINIMUM OF 45-MINUTES RAMP PERIOD TO GO FROM 0 TO 100% OPEN.

E) GREATER RAMP PERIODS MAY BE REQUIRED TO PREVENT NUISANCE

FREEZESTAT SHUT-DOWNS. ALWAYS USE THE SLOWEST RAMP TIMES POSSIBLE

DURING COLD WEATHER OPERATIONS. IN MOST CASES, EVEN A 1-HOUR RAMP

TIME WILL ALLOW THE AIR HANDLER TO COME TO SETPOINT WITHIN 15-MINUTES

BECAUSE THE DAMPER WILL NEVER DRIVE TO 100% DURING START-UP.

* 6. RELIEF AIR DAMPER CONTROL

A. RELIEF AIR DAMPER CONTROL

1) THE RELIEF AIR DAMPER WILL BE MODULATED AS REQUIRED TO MAINTAIN A

BUILDING STATIC PRESSURE OF 0.05 IN WG (ADJ.) RELATIVE TO THE OUTSIDE AIR

PRESSURE.

2) WHEN THE AIR HANDLER IS OFF, THE RELIEF AIR DAMPER WILL BE CLOSED.

7. PREHEAT CONTROL

A. HOT WATER PREHEAT COIL:

1) IF THE MIXED AIR TEMPERATURE IS BELOW 50 DEGF (ADJ.) OR IF THE OUTDOOR AIR

TEMPERATURE IS BELOW 40 DEGF (ADJ.), THE PREHEAT COIL CONTROL SHALL BE

ENABLED AND MODULATE TO MAINTAIN SUPPLY AIR TEMPERATURE SETPOINT OF 55

DEGF (ADJ.).

8. CHILLED WATER COOLING COIL CONTROL

A. CHILLED WATER COOLING COIL CONTROL

1) WHEN OUTSIDE AIR TEMPERATURE IS ABOVE 55 DEGF (ADJ.) AND CHILLED WATER

IS AVAILABLE, THE CHILLED WATER COOLING COIL CONTROL SHALL BE ENABLED AND

MODULATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE AT 55 DEGF (ADJ.).

2) ON ECONOMIZER EQUIPPED UNITS, THE CHILLED WATER CONTROL VALVE SHALL BE

SEQUENCED WITH THE OSA CONTROL DAMPER(S) AS THE FINAL STAGE OF COOLING.

THE CHILLED WATER CONTROL VALVE SHALL NOT BEGIN TO MODULATE OPEN UNTIL

ALL ECONOMIZER DAMPERS HAVE BEEN SEQUENCED OPEN TO THE FULL 100% OPEN

POSITION BY THE COOLING PID CONTROL LOOP.

3) THE CHILLED WATER CONTROL VALVE SHALL NOT MODULATE OPEN UNTIL ALL

PREHEAT DEVICES HAVE BEEN DISABLED FOR A CONTINUOUS 30 MINUTES.

9. DIRECT INJECTION STEAM HUMIDIFIER CONTROL

A. DIRECT INJECTION STEAM HUMIDIFIER CONTROL:

1) WHEN OUTDOOR AIR TEMPERATURE IS BELOW 50 DEGF (ADJ.), THE HUMIDIFIER

CONTROL SHALL BE ENABLED AND THE NORMALLY-CLOSED TWO POSITION JACKET

STEAM CONTROL VALVE SHALL BE OPEN.

2) IF ALL SPACES SERVED BY THE HUMIDIFIER ARE UNOCCUPIED, THE HUMIDIFIER

SHALL BE OFF.

3) WHEN THE SUPPLY FAN AND RETURN FANS ARE PROVED TO BE ON, THE

HUMIDIFIER CONTROL VALVE (FURNISHED WITH HUMIDIFIER) SHALL MODULATE AS

REQUIRED TO MAINTAIN A RETURN PLENUM RELATIVE HUMIDITY OF 30% (ADJ.).

4) THE HUMIDIFIER CONTROL VALVE SHALL NOT BE ALLOWED TO OPEN UNLESS

TEMPERATURE SWITCH (FURNISHED WITH HUMIDIFIER) IS SATISFIED.

5) THE TEMPERATURE SWITCH SHALL BE INTERFACED DIRECTLY TO THE HUMIDIFIER

CONTROL VALVE INDEPENDENT OF THE BMCS.

6) IF SUPPLY DUCT RELATIVE HUMIDITY EXCEEDS 85% (ADJ.) AS SENSED BY HUMIDITY

SENSOR LOCATED IN THE AIR HANDLING UNIT SUPPLY PLENUM DOWNSTREAM OF

FINAL FILTERS, THE HUMIDIFIER CONTROL VALVE SHALL BE SUPPRESSED.

7) UNITS SHALL HAVE RETURN RELATIVE HUMIDITY SENSOR REGARDLESS OF

WHETHER OR NOT IT HAS A HUMIDIFIER.

10. MISCELLANEOUS

A. POWER MONITORING

1) THE BMCS SHALL MONITOR THE KWH POWER CONSUMPTION OF ALL AIR HANDLER

SUPPLY, RETURN AND EXHAUST AIR FANS OF THE FOLLOWING AIR HANDLER

FANS:

A) SUPPLY AIR FANS:

B) RETURN AIR FANS:

C) EXHAUST AIR FANS:

2) CHILLED WATER SUB-METERING: (TBD)

3) HOT WATER SUB-METERING: (TBD)

B. FILTRATION MONITORING:

1) MONITOR PRE-FILTER STATUS (DI):

A) THE BMCS SHALL MONITOR THE PRE-FILTER STATUS (DI) AND ISSUE AN ALARM

TO THE OPERATOR WHEN ACTIVATED.

2) MONITOR FINAL FILTER STATUS (DI):

A) THE BMCS SHALL MONITOR THE FINAL-FILTER STATUS (DI) AND ISSUE AN ALARM

TO THE OPERATOR WHEN ACTIVATED.

* RESET SCHEDULES

AHU RETURN DAMPER RESET FOR MINIMUM OSA

MINIMUM OSA DAMPER POSITION RETURN AIR DAMPER POSITION

0 TO 95% 100% OPEN

100% OPEN 80% OPEN

RETURN PLENUM PRESSURE SETPOINT RESET

OSA ENTHALPY RETURN AIR PRESSURE SETPOINT

17.5 BTU'S PER Lb 0.0 In WC

25 BTU'S PER Lb 0.1 In WC

BO ENGINEER TO ADJUST AND SET FINAL PLENUM PRESSURE SETPOINTS IN FIELD. BMS

CONTRACTOR SHALL HARD CODE THESE SETTINGS IN AHU PROGRAM ONCE FINAL

PARAMETERS ARE ESTABLISHED BY BO ENGINEER.

TIME OF DAY REMOTE STATIC RESET

PHOTO CELL BREAK (DUSK) SP MULTIPLIER INWC

DAY TIME AHU REMOTE SP

SETPOINT 1.0

DUSK AHU REMOTE SP

SETPOINT (AFTER SPECIFIED DELAY) 1 (ADJ.)

BO ENGINEER TO ADJUST AND SET FINAL PLENUM PRESSURE SETPOINTS IN FIELD. BMS

CONTRACTOR SHALL HARD CODE THESE SETTINGS IN AHU PROGRAM ONCE FINAL

PARAMETERS ARE ESTABLISHED BY BO ENGINEER.

SCOPE OF WORK

A. COMMISSION AHU TO VERIFY IT IS OPERATING PER THE WRITTEN SEQUENCE OF

OPERATIONS.

B. RECALIBRATE ALL PRESSURE TRANSDUCERS.

C. PROVIDE PREVENTATIVE MAINTENANCE ON ALL DAMPERS AND ACTUATORS. CLEAN,

LUBRICATE AND ENSURE SMOOTH OPERATION OF DAMPERS AND ACTUATUORS. VERIFY

DAMPER IS CLOSING AND SEALING SHUT. REPORT ANY WORN DAMPER SEALS AND/OR

MALFUNCTIONING ACTUATORS TO THE VA.

D. CLEAN AND CALIBRATE ALL AIR FLOW MONITORING STATIONS.

E. MODIFY SEQUENCES TO TURN OFF ALL EXHAUST FANS AT NIGHT.

1. COORDINATE TIMES WITH COR.

F. DIAGRAM BELOW DOES NOT PROPERLY REPRESENT THE FOLLOWING:

1. EXISTING HOT WATER RUN-AROUND PUMP TO REMAIN.

2. EXISTING CHILLED WATER RUN-AROUND PUMP TO REMAIN.

G. REVISE SUPPLY FAN CONTROL AS FOLLOWS:

1. SUPPLY FAN SYSTEM SPEED CONTROL

A. THE VARIABLE SPEED DRIVES SHALL BE MODULATED BY A STATIC PRESSURE

SENSOR LOCATED TWO-THIRDS DOWN THE MAIN SUPPLY DUCT, AND A

PROPORTIONAL PLUS INTEGRAL CONTROL SHALL PROVIDE A SIGNAL TO

MODULATE THE VFD SPEED OF THE SUPPLY FAN SYSTEM TO MAINTAIN THE STATIC

PRESSURE SETPOINT (INITIALLY SET TO 0.75” W.C.).

B. SUPPLY AIR STATIC PRESSURE SETPOINT RESET

i. THE SUPPLY AIR STATIC PRESSURE SETPOINT SHALL BE RESET BY POLLING

ALL VAV BOX DAMPER POSITIONS. IF ALL VAV BOX DAMPERS ARE BELOW 80

PERCENT OF FULL OPEN, RESET THE SUPPLY DUCT STATIC PRESSURE

SETPOINT DOWNWARD 0.05” W.C. EVERY 10 MINUTES UNTIL AT LEAST ONE VAV

BOX DAMPER IS 80 PERCENT OF FULL OPEN. IF ANY BOX DAMPER IS MORE

THAN 90 PERCENT OF FULL OPEN, REVERSE THE SEQUENCE (RESET THE

STATIC SETPOINT UPWARD 0.05” W.C. EVERY 5 MINUTES UNTIL ALL VAV BOX

DAMPERS ARE LESS THAN 90 PERCENT OF FULL OPEN. LOW LIMIT OF THE

SETPOINT SHALL BE 0.25” W.C. AND HIGH LIMIT SETPOINT SHALL BE 1.25” W.C.

AUTOMATICALLY DETECT THOSE ZONES THAT MAY BE EXCESSIVELY DRIVING

THE RESET LOGIC AND GENERATE AN ALARM TO THE SYSTEM OPERATOR.

READILY ALLOW OPERATOR REMOVAL OF ZONE(S) FROM THE RESET

ALGORITHM.

H. REVISE/ADD SUPPLY AIR TEMPERATURE RESET AS FOLLOWS:

1. THE RESET SHALL FOLLOW ASHRAE 36.

2. PROVIDE A REQUEST TABLE GRAPHIC.

A. THE COR WILL PROVIDE AN IMPORTANCE MULTIPLIER FOR EACH ZONE.

B. THE IMPORTANCE MULTIPLIER SHALL BE SHOWN ON THE REQUEST TABLE.

C. A PERCENTAGE OF TIME A ZONE HAS BEEN IN REQUEST FOR THE PAST MONTH

SHALL BE PROVIDED.

D. THIS WILL ASSIST IN IDENTIFYING ROGUE ZONES.

3. ROGUE ZONE ALARMS SHALL BE SENT TO THE ENERGY MANAGER.

A. THE COR WILL PROVIDE THE IGNORE REQUEST SETPOINT (ADJ).

B. THE PROGRAM SHALL ALLOW THE TRIM AND RESPONSE PROGRAM TO DISREGARD

ROGUE ZONES UNTIL THEY ARE FIXED.

4. TEMPERATURE RESET

A. WHEN THE HUMIDITY LEVEL IN THE RETURN, EXHAUST, OR ROOM EXCEEDS 61%,

THE TRIM AND RESPOND COMMAND WILL BE BASED ON THE HUMIDITY LEVEL AND

NOT ON THE ROOM TEMPERATURE IN EACH ZONE. ONCE THE HUMIDITY LEVEL

DROP BELOW 57%, THE TRIM AND RESPOND WILL BE BASED ON ROOM

TEMPERATURE IN EACH ZONE.

I. MODIFY RELIEF AIR DAMPER CONTROL FOR MAX SPACE PRESSURE PER SHEET M900.

J. TURN OFF EXHAUST FANS (EXCEPT EF-32) DURING NIGHT TIME SETBACK. COORDINATE

TIMES WITH COR.

K. ADD MOTORIZED DAMPER IN EF-32 DUCTWORK TO ISOLATE WAITING ROOM (CLOSE AIR

VALVE C2061) AND ALLOW RESTROOMS TO CONTINUE TO BE EXHAUSTED DURING NIGHT

TIME SETBACK.

L. ADJUST EF-32 AIR FLOW FOR NIGHT TIME SETBACK.

M. CLOSE AIR VALVES C2025 AND C2009 DURING NIGHT TIME SETBACK

GENERAL NOTES

1. DIAGRAM AND SEQUENCE OF OPERATION IS INFORMATION FROM ORIGINAL SHOP

DRAWINGS AND IS FOR REFERENCE ONLY.

# DESCRIPTION DATE

1 ADDENDUM 4 01-12-2026

Sheets
M901 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-4
M902 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-5
M903 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-7
M904 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-8
M905 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-12
M906 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-17
M907 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-21
M908 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-24
M909 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-26
M910 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-28
M911 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-29

File details come from the government source that posted it. Updated .