M907 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-21.pdf
PDF 3 MB Posted
- Attached to
- Z2DA--Remediate Temperature Controls 539-21-108 Federal contract opportunity
- Solicitation number
- 36C25026B0002
About this file
This document is an architectural control diagram and sequence of operations for Air Handling Unit AHU-21 at the Cincinnati VA Medical Center, detailing specific control requirements and modifications for building pressurization and temperature management. The scope of work includes commissioning the air handling unit, recalibrating pressure transducers, performing preventative maintenance on dampers and actuators, and implementing revised control sequences with detailed specifications for discharge air temperature reset, night setback operations, and occupancy scheduling.
Key technical requirements include establishing temperature controls with adjustable setpoints between 55-62 degrees Fahrenheit, defining occupied/unoccupied operational modes (Monday-Friday 6:00 AM to 10:00 PM, Saturday 10:00 AM to 3:00 PM), implementing cooling setup and cool-down protocols, and creating morning warm-up sequences. The document also specifies override mechanisms for the auditorium and other spaces, with the unit cycling to occupied mode for 1-2 hours when override buttons are pressed, and includes provisions for managing space temperature, outside air damper positioning, and relief air damper control.
View the file
Other files for this federal contract opportunity
Show all 50
Z2DA--Remediate Temperature Controls 539-21-108 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P ro je ct
N o.
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
E
D
C
B
A
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Manager
Cincinnati V.A Medical Center
U.S. Department of Veterans Affairs
F
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
32 4 5 6 7 8 9 10
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLEREDKEVIN HENDERSONPROJECT NO. STATE COA FIRM NO.
/1
/2
:1
:3
A
M -2
-1
BUILDING 1 PRESSURIZATION
CONTROL SEQUENCES - AHU-21
10/23/25 GSE WJS
REMEDIATE TEMPERATURE
CONTROLS
M907
539-21-108
CINCINNATI, OHIO
2020-05099 01528
SCALE: NONE
AHU-21 CONTROLS - EXISTING CONTROL DIAGRAM
EXISTING SEQUENCES
AHU-21 SEQUENCE OF OPERATIONS
1. GENERAL
A. UNIT IS NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE ECC. H-
O-A SWITCH WILL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS WILL BE
USED ONLY FOR MAINTENANCE.
B. WHEN THE UNIT IS "OFF", FOR ANY REASON, OUTSIDE AIR DAMPERS D-1 & D-5, RELIEF
AIR DAMPERS D-3 & D-4, RETURN AIR SMOKE DAMPER SD-1 AND SUPPLY AIR SMOKE
DAMPERS SD-2, SD-3, SD-4 AND SD-5 WILL BE FULLY CLOSED, RETURN AIR DAMPER D-2
WILL BE FULLY OPEN, AND SUPPLY AND RETURN FANS WILL BE OFF.
C. WHEN THE UNIT IS "ON", ISOLATION SMOKE DAMPERS SD-1, SD-2, SD-3, SD-4 AND SD-5
WILL OPEN, AND ONCE PROVED OPEN, SUPPLY AND RETURN FANS WILL START, AND D-1,
D-2, D-3, D-4 AND D-5 WILL MODULATE IN ACCORDANCE WITH THE FOLLOWING SEQUENCE.
2. TEMPERATURE CONTROL
A. SUPPLY AIR TEMPERATURE, SENSED BY T-7 PRIMARY/T-11 SECONDARY (DEPENDING
ON WHICH SUPPLY FAN IS OPERATING), WILL BE MAINTAINED AT SETPOINT OF 55 DEG. F.
(SEE DISCHARGE AIR RESET SEQUENCE BELOW) VIA DCP BY MODULATING COOLING COIL
VALVE V-1 OR ECONOMIZER DAMPERS D-1, D-2, D-3, D-4 AND D-5 OR PREHEAT COIL VALVE
V-2, IN SEQUENCE. SEPARATE CONTROL LOOPS WILL BE UTILIZED FOR EACH
ECONOMIZER COOLING, MECHANICAL COOLING, AND HEATING FUNCTION.
B. REHEAT COILS 1-RH21A AND 1-RH21B - VALVES V-5 AND V-6 WILL MODULATE TO
MAINTAIN DISCHARGE AIR TEMPERATURE SET POINTS BASED ON A RESET SCHEDULE OF
95 DEG. DISCHARGE AIR TEMPERATURE SENSED BY T-1 AND T-8 AT 0 DEG. OUTSIDE AIR
TEMPERATURE AND 80 DEG DISCHARGE AIR TEMPERATURE AT 60 DEG OUTSIDE AIR
TEMPERATURE.
3. ENTHALPY ECONOMIZER CONTROL
A. OUTSIDE AIR TEMPERATURE AND HUMIDITY, AND RETURN AIR TEMPERATURE AND
HUMIDITY WILL BE MEASURED, AND THE ENTHALPY OF EACH DETERMINED. IF THE
ENTHALPY OF THE OUTSIDE AIR IS LESS THAN THE ENTHALPY OF THE RETURN AIR, THE
ECONOMIZER WILL BE ENABLED. WHEN THE OUTSIDE AIR ENTHALPY IS HIGHER THAN THE
RETURN AIR ENTHALPY AND MECHANICAL COOLING IS AVAILABLE, THE ECONOMIZER WILL
BE DISABLED.
4. ECONOMIZER CYCLE
A. DURING THE "ECONOMIZER" CYCLE, THE AMOUNT OF OUTSIDE AIR AND RELIEF AIR
WILL BE INCREASED AS REQUIRED TO MAINTAIN THE UNIT DISCHARGE AIR TEMPERATURE
SETPOINT, AS SENSED BY T-7 OR T-11. PROVIDE A MIXED AIR SENSOR AND LOW LIMIT
CONTROL (T-5) SET AT 50 DEGREES F. TO PREVENT OVER-OPENING OF THE ECONOMIZER
OUTSIDE AIR DAMPERS. ALL CONTROL SETPOINTS WILL BE FULLY ADJUSTABLE TO MEET
JOB CONDITIONS.
5. MINIMUM OUTSIDE AIR
A. MINIMUM OUTSIDE AIR WILL BE PROVIDED PER 5.2 AND 5.3 BELOW BY OPENING AND
MODULATING MINIMUM OUTSIDE AIR DAMPERS D-1 TO MAINTAIN THE MINIMUM OUTSIDE
AIR SET POINT (SEE AHU SCHEDULE) AS MEASURED BY OUTSIDE AIR FLOW SIGNAL VPS-4.
THE RETURN AIR DAMPERS D-2 WILL OPEN FULL AND RELIEF AIR DAMPERS D-3 AND D-4
WILL REMAIN CLOSED. THIS CONDITION WILL BE MAINTAINED EXCEPT DURING THE
"ECONOMIZER" CYCLE.
B. WHEN 1-SF21A OPERATES, MINIMUM OUTSIDE AIR SET POINT 1 WILL BE MAINTAINED.
C. WHEN 1-SF21B OPERATES, DAMPERS WILL MODULATE AS DETERMINED BY A SPACE
MOUNTED CO2 SENSOR. THE CONTROL WILL BE LINEAR WITH AIR FLOW AT SET POINT 1
AT 800 PPM AND AT SET POINT 2 AT 1000 PPM.
6. AIR FLOW CONTROL
A. 1 1-SF21A - THE SUPPLY AIR FLOW WILL BE CONTROLLED BY THE DCP MODULATING
THE SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER (VSMC) TO MAINTIAN 1.0" OF
DUCT STATIC PRESSURE (FIELD ADJUSTABLE), SENSED BY SPS-1, SPS-2, SPS-6 AND SPS-7
LOCATED 2/3 DISTANCE DOWN THE SUPPLY DUCTS.
B. 1-SF21B - THE SUPPLY AIR FLOW WILL BE CONTROLLED BY THE DCP MODULATING THE
SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER (VSMC) TO MAINTAIN SPACE
TEMPERATURE IN THE AUDITORIUM AS SENSED BY T-10. IF THE SPACE FALLS OR RISES
MORE THAN 2 DEGREES F. FROM THE SETPOINT, THE FAN SPEED WILL BE INCREASED
SLOWLY UNTIL THE SPACE IS WITHIN 1.5 DEGREES F. OF SETPOINT. WHEN THE OUTSIDE
AIR TEMPERATURE IS BELOW 60 DEGREES F., THE FAN WILL REMAIN AT 50 PERCENT AIR
FLOW.
C. THE DCP, USING TOTAL SUPPLY AIR, OUTSIDE AIR AND RETURN AIR FLOW SIGNALS
(VPS-1, VPS-2, VPS-3, VPS-4 AND VPS-5), WILL RESET THE RETURN AIR FAN VARIABLE
SPEED MOTOR CONTROLLER (VSMC) TO MAINTAIN A CONSTANT AIR FLOW DIFFERENCE
BETWEEN THE SUPPLY AIR AND THE RETURN AIR EQUAL TO MINIMUM OUTSIDE AIR (SEE 5
ABOVE).
D. VARIABLE SPEED MOTOR CONTROLLERS WILL RESPOND TO START/STOP COMMANDS
AND ALL SAFETIES (FREEZE, SMOKE, ETC.) WHETHER IN THE AUTOMATIC OR BYPASS
MODES.
E. THE DCP, USING HIGH PRESSURE SENSORS SPS-3 AND SPS-5 LOCATED AT THE SUPPLY
FAN DISCHARGES, WILL PREVENT THE SUPPLY FANS FROM DEVELOPING OVER 3 INCHES
AND 4 INCHES RESPECTIVELY, OF POSITIVE STATIC PRESSURE (FIELD ADJUSTABLE). IF
STATIC PRESSURE AT SPS-3 OR SPS-5 EXCEEDS THEIR ASSOCIATED PRESSURE,
THE SUPPLY AND RETURN FANS WILL STOP. 6.6 THE DCP, USING HIGH PRESSURE SENSOR
SPS-4 LOCATED AT THE RETURN FAN INLET, WILL PREVENT THE RETURN FAN FROM
DEVELOPING OVER 3 INCHES OF NEGATIVE STATIC PRESSURE (FIELD ADJUSTABLE). IF
STATIC PRESSURE AT SPS-4 EXCEEDS 3 INCHES OF NEGATIVE PRESSURE, THE SUPPLY
AND RETURN FANS WILL STOP.
7. HUMIDITY CONTROL
A. WHEN THE DCP IS NOT CALLING FOR HUMIDITY, SENSED BY RETURN AIR HUMIDITY
SENSOR H-1, 2-WAY "ON-OFF" CONTROL VALVE V-3 WILL REMAIN CLOSED. WHEN THE DCP
IS CALLING FOR HUMIDITY, V-3 WILL REMAIN OPEN.
B. RETURN AIR HUMIDITY, SENSED BY H-1, WILL BE MAINTAINED AT SETPOINT (30% RH,
ADJUSTABLE) VIA DCP BY MODULATING HUMIDIFIER CONTROL VALVE V-4 TO MAINTAIN
THE DESIRED HUMIDITY. THE DCP WILL OVERRIDE THIS CONTROL TO MAINTAIN A
MAXIMUM HUMIDITY LEVEL OF 80% AS SENSED BY H-2 AND H-3. DCP WILL CLOSE VALVE
V-3 WHENEVER THE SUPPLY FAN IS OFF. VALVE V-4 WILL BE INTERLOCKED WITH A FLOAT
SWITCH TO KEEP THE HUMIDIFIER OFF IF THE HEADER IS FLOODED.
C. UPON A CALL FOR HUMIDITY, THE ON-OFF SOLENOID VALVE V-7 WILL OPEN TO
PRESSURIZE THE CONDENSATE RETURN FROM THE HUMIDIFICATION HEADER.
D. ON-OFF CONTROL VALVE V-3 WILL REMAIN CLOSED WHENEVER THE OUTSIDE AIR
TEMPERATURE IS ABOVE 55 DEG. F.
8. FREEZE PROTECTION
A. IF THE AIR TEMPERATURE AS SENSED BY T-3 FALLS BELOW 40 DEGF, AN ALARM SIGNAL
WILL INDICATE AT THE DCP AND ECC. IF THIS TEMPERATURE FALLS BELOW 35 DEG.F, THE
SUPPLY AND RETURN FANS WILL SHUT DOWN AND A CRITICAL ALARM WILL INDICATE AT
THE DCP AND ECC.
9. AUTOMATIC SHUTDOWN / RESTART
A. WHEN SMOKE IS DETECTED BY ANY OF THE DUCT SMOKE DETECTORS (DSD-1 THRU
DSD-5), THE SUPPLY AND RETURN AIR FANS WILL SHUT "OFF", ISOLATION SMOKE
DAMPERS SD-1, SD-2, SD-3, SD-4 AND SD-5 WILL CLOSE, AN ALARM SIGNAL WILL BE
TRANSMITTED TO THE FIRE ALARM SYSTEM, AND AN ALARM SIGNAL WILL INDICATE AT THE
DCP AND ECC. EXHAUST FANS SERVING AREA OF THE SUPPLY FAN WILL CONTINUE TO
RUN, SMOKE DAMPERS WILL OPEN AND SUPPLY AND RETURN FANS WILL RESTART WHEN
THE FIRE ALARM CIRCUIT IS RESET.
10. EMERGENCY CONSTANT SPEED OPERATION
A. UPON FAILURE OF THE INDIVIDUAL FAN VSMC, THE ASSOCIATED SUPPLY AND RETURN
FANS WILL BE STARTED/STOPPED MANUALLY AT THE DCP OR THE ECC THROUGH THE BY-
PASS STARTER. FANS WILL THEN BE OPERATED AT CONSTANT SPEED.
11. SUPPLY FAN ISOLATION
A. WHENEVER SUPPLY FAN SF-21A OR SF-21B IS NOT RUNNING, FOR ANY REASON,
CORRESPONDING ISOLATION SMOKE DAMPERS ID-1 OR ID-2 WILL BE CLOSED.
12. DEMAND CONTROL VENTILATION
A. MODULATE OUTSIDE AIR, RETURN AIR AND AND RELIEF AIR DAMPERS IN RESPONSE TO
DEMAND CONTROL VENTILATION CONTROL SEQUENCES PROVIDED IN VA PROJECT
NUMBER 539-13-105.
13. RELIEF AIR DAMPER CONTROL
A. THE RELIEF AIR DAMPER SHALL BE MODULATED AS REQUIRED TO MAINTAIN A
BUILDING STATIC PRESSURE OF 0.05 IN WG (ADJ.) RELATIVE TO THE OUTSIDE AIR
PRESSURE.
B. WHEN THE AIR HANDLER IS OFF, THE RELIEF AIR DAMPER SHALL BE CLOSED.
SCOPE OF WORK
A. COMMISSION AHU TO VERIFY IT IS OPERATING PER THE WRITTEN SEQUENCE OF
OPERATIONS.
B. RECALIBRATE ALL PRESSURE TRANSDUCERS.
C. PROVIDE PREVENTATIVE MAINTENANCE ON ALL DAMPERS AND ACTUATORS. CLEAN,
LUBRICATE AND ENSURE SMOOTH OPERATION OF DAMPERS AND ACTUATUORS. VERIFY
DAMPER IS CLOSING AND SEALING SHUT. REPORT ANY WORN DAMPER SEALS AND/OR
MALFUNCTIONING ACTUATORS TO THE VA.
D. CLEAN AND CALIBRATE ALL AIR FLOW MONITORING STATIONS.
E. REVISE CONTROL SEQUENCES TO INCLUDE THE FOLLOWING:
a. DISCHARGE AIR RESET
• THE AIR HANDLING UNIT CONTROLS WILL PROVIDE DISCHARGE AIR TEMPERATURE
CONTROL BASED ON ZONE DEMAND DEVIATION FROM SETPOINT. ALL ZONES WITH
DDC CONTROLS WILL BE SAMPLED AND THE ZONE FURTHEST FROM SETPOINT
WILL GOVERN. AS THE DEVIATION FROM SETPOINT DECREASES, THE DISCHARGE
AIR WILL BE RESET. 55 DEG. F AND 62 DEG. F WILL BE THE LOW AND HIGH RESET
LIMITS, RESPECTIVELY. ALL CONTROL SETPOINTS (INCLUDING HIGH AND LOW SET
POINTS FOR DISCHARGE AIR TEMPERATURE) WILL BE FULLY ADJUSTABLE TO MEET
JOB CONDITIONS.
b. NIGHT SET BACK
• THE AIR HANDLING UNIT (ASSOCIATED SUPPLY AND RETURN FANS) WILL BE ABLE
TO BE SCHEDULED FOR OCCUPIED/UNOCCUPIED 7-DAY AND HOLIDAY OPERATION.
DURING THE OCCUPIED MODE, THE TEMPERATURE CONTROLS WILL FUNCTION AS
SPECIFIED,DURING UNOCCUPIED MODE THE AIR HANDLING UNIT CONTROLS WILL
FUNCTION AS SPECIFIED EXCEPT THE OUTSIDE AIR DAMPERS WILL REMAIN
CLOSED. THE CONTROLS WILL CYCLE THE UNIT TO MAINTAIN A REDUCED SPACE
TEMPERATURE OF 60 DEGREES F.
• INITIAL SCHEDULE - UNIT WILL OPERATE MONDAY THRU FRIDAY 6:00 AM TO 10:00
PM, SATURDAY 10:00 AM TO 3:00 PM. UNIT WILL BE OFF AFTER SCHEDULED HOURS,
SUNDAY AND ALL LEGAL HOLIDAYS. COORDINATE EXACT SCHEDULE WITH COR.
• COOLING SETUP CONTROL AND COOL DOWN - DURING THE UNOCCUPIED TIME, IF
THE SPACE TEMPERATURE RISES ABOVE 82 DEGREES F. THE UNIT WILL CYCLE ON
TO COOL THE SPACE DOWN TO 79 DEGREES F. AND THEN TURN OFF. OUTSIDE AIR
WILL BE USED FOR COOLING FIRST UNLESS THE ECONOMIZER IS LOCKED OUT. AN
OPTIMAL START PROGRAM WILL START THE UNIT IN ADVANCE OF OCCUPIED TIME
TO ENSURE PROPER SPACE TEMPERATURES AT OCCUPANCY TIME. DURING SET
UP OR COOL DOWN OPERATION IF THE ECONOMIZER IS INACTIVE, THE OUTSIDE
AIR DAMPERS WILL REMAIN CLOSED.
• MORNING WARM-UP AND INITIAL START - AIR HANDLING SYSTEM WILL ENTER A
MORNING WARM-UP MODE IN ADVANCE OF THE OCCUPIED TIME VIA AN OPTIMAL
START SEQUENCE, THE OUTSIDE AIR DAMPERS WILL REMAIN COMPLETELY
CLOSED AND THE RETURN DAMPERS WILL REMAIN FULLY OPEN. THIS MODE WILL
CONTINUE UNTIL THE RETURN TEMPERATURE RISES ABOVE 68 DEGREES F., AT
WHICH TIME THE ECONOMIZER DAMPERS WILL BE POSITIONED TO MINIMUM.
ECONOMIZER DAMPER CONTROL WILL BE DELAYED TWO MINUTES DURING
START-UP TO PREVENT CABINET HEAT FROM FALSE LOADING THE SYSTEM.
• DURING UNOCCUPIED MODE, WHEN AN OVERRIDE BUTTON AT T-10 IS PRESSED IN
THE AUDITORIUM, THE UNIT WILL CYCLE TO OCCUPIED MODE FOR 2 HOURS. WHEN
ANY OTHER OVERRIDE BUTTON IS PRESSED, THE UNIT WILL CYCLE TO OCCUPIED
MODE FOR 1 HOUR.
F. MODIFY RELIEF AIR DAMPER CONTROL FOR MAX SPACE PRESSURE PER SHEET M900.
GENERAL NOTES
1. DIAGRAM AND SEQUENCE OF OPERATION IS INFORMATION FROM ORIGINAL SHOP
DRAWINGS AND IS FOR REFERENCE ONLY.
# DESCRIPTION DATE
1 ADDENDUM 4 01-12-2026
| Sheets |
| M901 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-4 |
| M902 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-5 |
| M903 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-7 |
| M904 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-8 |
| M905 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-12 |
| M906 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-17 |
| M907 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-21 |
| M908 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-24 |
| M909 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-26 |
| M910 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-28 |
| M911 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-29 |
File details come from the government source that posted it. Updated .