Change Summary of Specs and Drawings.pdf

PDF 46 KB Posted

Attached to
Z2DA--Remediate Temperature Controls 539-21-108 Federal contract opportunity
Solicitation number
36C25026B0002
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This document is an Addendum (No. 4) for a VA Cincinnati Project (No. 539-21-108) to Remediate Temperature Controls, issued by Heapy (Project No. 2020-05099) on 01/12/2026. The addendum includes multiple specification and drawing modifications, primarily focused on HVAC and temperature control system updates.

Key changes include revisions to technical specifications across multiple sections, updates to infection control requirements, clarification on commissioning agent responsibilities (to be hired by the prime contractor), and numerous drawing modifications affecting Network Area Engine (NAE) devices. Specific drawing changes involve reusing or replacing various NAE components, adding a Tridium Building Control Router, modifying network VLAN assignments, revising scope of work notes, and eliminating certain equipment replacement requirements like air compressors and convector pneumatic controls. The addendum comprehensively addresses technical details for temperature control remediation at the VA Cincinnati facility.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--Remediate Temperature Controls 539-21-108, newest first.
File Type Posted
Sign in Sheet Remediate Temp.pdf PDF
1-M103 - THIRD FLOOR.pdf PDF
1-M110 - TENTH FLOOR PENTHOUSE.pdf PDF
2-M100 - BUILDING 2 BASEMENT.pdf PDF
15-M100 - BUILDING 15 BASEMENT.pdf PDF
M002 - JOHNSON CONTROLS ROUTER SCHEDULE.pdf PDF
M910 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES AHU-28.pdf PDF
36C25026B0002 0004.pdf PDF
1-M104 - FOURTH FLOOR.pdf PDF
M901 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-4.pdf PDF
M903 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-7.pdf PDF
M908 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-24.pdf PDF
M909 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-26.pdf PDF
PG-M101 - PARKING GARAGE 1ST FLOOR PLAN.pdf PDF
ICRA 539.21.108 Mech Rooms Level II.pdf PDF
Updated Specs Addendum 4.pdf PDF
1-M105 - FIFTH FLOOR.pdf PDF
1-M109 - NINTH FLOOR.pdf PDF
13-M101 - BUILDING 13 FIRST FLOOR.pdf PDF
64-M100 - BUILDING 64 BASEMENT.pdf PDF
M906 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-17.pdf PDF
REVISED STATEMENT OF BID ITEMS.pdf PDF
ICRA 539.21.108 Patient Areas Level III.pdf PDF
1-M100 - BASEMENT.pdf PDF
64-M102 - BUILDING 64 SECOND FLOOR.pdf PDF
64-M103 - BUILDING 64 THIRD FLOOR.pdf PDF
M004 - TRIDIUM ROUTER SCHEDULE.pdf PDF
M701 - GENERAL CRITERIA HONEYWELL CONTROLS REPLNT.pdf PDF
M902 - BUILDING 1 PRESSURIZATION CONTROL SEQUENCES - AHU-5.pdf PDF
36C25026B0002 0003.pdf PDF
36C25026B0002 0002.pdf PDF
36C25026B0002 0001.docx DOCX document
Attachment XIV - EMR Form.pdf PDF
Attachment XII - J A - Redacted.pdf PDF
Attachment XI - RTC BID DWGS 9 2025.1023.pdf PDF
Attachment VIII - RTC BID DWGS 6 2025.1023.pdf PDF
Attachment IV - RTC BID DWGS 2 2025.1023.pdf PDF
Attachment XVI - Directive 1192.01, Flu.pdf PDF
Attachment IX -RTC BID DWGS 7 2025.1023.pdf PDF
Attachment VII - RTC BID DWGS 5 2025.1023.pdf PDF
Attachment VI -RTC BID DWGS 4 2025.1023.pdf PDF
Attachment III -RTC BID DWGS 1 2025.1023.pdf PDF
Attachment I - WD OH20250082.pdf PDF
Attachment XV - 852.219-75 LOS.docx DOCX document
Attachment XIII - RFI Form.pdf PDF
Attachment XVII - ICRA Level 2.pdf PDF
Attachment X - RTC BID DWGS 8 2025.1023.pdf PDF
Attachment V - RTC BID DWGS 3 2025.1023.pdf PDF
Attachment II - CD SPECIFICATION 2025.1023.pdf PDF
36C25026B0002.docx DOCX document
Show all 50

Z2DA--Remediate Temperature Controls 539-21-108 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Cleveland • Columbus • Dayton • Findlay • Indianapolis • Raleigh

1400 W Dorothy Lane

Dayton, OH 45409

(937) 224-0861 www.heapy.com

An ISO 9001-2015 Certified Company FS 98575 © Heapy All Rights Reserved

2020-05099_Addendum #4.doc 1/12/2026 11:27 AM

VA CINCINNATI PROJECT NO. 539-21-108

REMEDIATE TEMPERATURE CONTROLS

ADDENDUM NO. #4

HEAPY PROJECT NO. 2020-05099

01/12/2026

GENERAL

ITEM NO. 1 Specifications

A. New PDF of Technical Specifications is included with

B. Revisions to document are bolded

C. Revised project # header to 539-21-108 for all specifications

ITEM NO. 2 Section 013526

A. Revised section 1.12 infection control

1) Added ICRA level and category for project

ITEM NO. 3 Add New Section 014500

ITEM NO. 4 Section 019100

A. Section 1.1 A-clarification that the Commissioning agent shall be paid by the prime contractor

B. Section 1.8 Members appointed by Contractor – add #3 commissioning agent.

Revised 1.8 C members appointed by VA

1) Section 1.10 added item A.

a. Commissioning agent shall be hired by the prime contractor.

HVAC

SPECIFICATIONS

ITEM NO. 5 Section 23 08 00

A. Delete paragraph 1.1(C).

1) Commissioning agent shall be hired by the prime contractor.

ITEM NO. 6 All Division 23 Specifications re-issued with the correct project number in the header.

Cincinnati • Cleveland • Columbus • Dayton • Indianapolis • Pittsburgh • Raleigh • Tampa

An ISO 9001-2015 Certified Company FS 98575

DRAWINGS

ITEM NO. 1 Drawing No. M002 (Revised sheet attached):

A. Revised NAE-31.

ITEM NO. 2 Drawing No. M004 (Revised sheet attached):

A. Added a Tridium Building Control Router.

ITEM NO. 3 Drawing No. M701 (Revised sheet attached):

A. Revised sheet title.

B. Modified notes on Miscellaneous Honeywell Points List Schedule.

C. Added “MISCELLANEOUS CONTROLS REQUIREMENTS”

1) Meter Dashboard.

2) Move JCI Metasys and ALC Supervisory Controllers along with BACnet over IP components such as meters and routers from VLAN 76 to VLAN 39.

ITEM NO. 4 Drawing No. M901, 902, 903, 904, 905, 906, 907, 908, 909, 910, & 911.

A. Revise SCOPE OF WORK note to only report worn damper seals and malfunctioning actuators, not replace.

ITEM NO. 5 Drawing No. 1-M100 (Revised sheet attached):

A. NAE-03 to be re-used instead of replaced.

B. NAE-04 to be re-used instead of replaced.

C. NAE-23 to be replaced instead of re-used.

D. NAE-29 to be replaced instead of re-used.

ITEM NO. 6 Drawing No. 1-M103 (Revised sheet attached):

A. NAE-05 to be re-used instead of replaced.

B. NAE-13 to be replaced instead of re-used.

C. NAE-26 to be re-used instead of replaced.

ITEM NO. 7 Drawing No. 1-M104 (Revised sheet attached):

A. NAE-14 to be replaced instead of re-used.

ITEM NO. 8 Drawing No. 1-M105 (Revised sheet attached):

A. Eliminated convector pneumatic controls replacements.

Cincinnati • Cleveland • Columbus • Dayton • Indianapolis • Pittsburgh • Raleigh • Tampa

An ISO 9001-2015 Certified Company FS 98575

B. NAE-06 to be re-used instead of replaced.

ITEM NO. 9 Drawing No. 1-M109 (Revised sheet attached):

A. NAE-07 to be re-used instead of replaced.

ITEM NO. 10 Drawing No. 1-M110 (Revised sheet attached):

A. Eliminated requirement to remove air compressor.

ITEM NO. 11 Drawing No. 2-M100 (Revised sheet attached):

A. NAE-15 to be re-used instead of replaced.

B. NAE-33 to be re-used instead of replaced.

ITEM NO. 12 Drawing No. 13-M101 (Revised sheet attached):

A. NAE-11 to be replaced instead of re-used.

ITEM NO. 13 Drawing No. 15-M100 (Revised sheet attached):

A. NAE-08 to be re-used instead of replaced.

B. NAE-27 to be re-used instead of replaced.

ITEM NO. 14 Drawing No. 64-M100 (Revised sheet attached):

A. NAE-09 to be re-used instead of replaced.

ITEM NO. 15 Drawing No. 64-M102 (Revised sheet attached):

A. NAE-16 to be re-used instead of replaced.

B. NAE-17 to be re-used instead of replaced.

C. NAE-18 to be re-used instead of replaced.

ITEM NO. 16 Drawing No. 64-M103 (Revised sheet attached):

A. Renamed NAE-32 to NAE-31.

ITEM NO. 17 Drawing No. PG-M101 (Revised sheet attached):

A. NAE-25 to be replaced instead of re-used.

File details come from the government source that posted it. Updated .