13-M101 - BUILDING 13 FIRST FLOOR.pdf
PDF 3 MB Posted
- Attached to
- Z2DA--Remediate Temperature Controls 539-21-108 Federal contract opportunity
- Solicitation number
- 36C25026B0002
About this file
This document is an architectural floor plan drawing for Building 13 at the Cincinnati VA Medical Center, dated January 9, 2026. The first floor plan is drawn to a scale of 1/8" = 1'-0" and was prepared by Heapy Engineering and Levin Porter Architects, with Kevin Henderson listed as the Project Manager. The project number is 539-21-108, and the drawing indicates it is part of a construction document set for a fully sprinkled building. The drawing includes three small photographic insets of electrical panels or equipment, and contains a grid-based floor plan layout with multiple room and corridor configurations typical of a medical facility. An addendum was issued on January 12, 2026, suggesting ongoing design refinements.
View the file
Other files for this federal contract opportunity
Show all 50
Z2DA--Remediate Temperature Controls 539-21-108 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
UP
DN
DN
DN
DN
N23
Q
R
S
T
U
V
W
XY
5 6
NAE-11
VALVE OVERRIDE SWITCHES
BUILDING 8 BUILDING 13
NAE-10
5 2 4
2 4
LGR BLDG. 13 1 2 4
MONITOR
PC
PRINTER 6
P ro je ct
N o.
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
E
D
C
B
A
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Manager
Cincinnati V.A Medical Center
U.S. Department of Veterans Affairs
F
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
32 4 5 6 7 8 9 10
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLEREDKEVIN HENDERSONPROJECT NO. STATE COA FIRM NO.
/9
/2
:0
:2
P
M -2
-1
BUILDING 13 FIRST FLOOR
10/23/25 GSE WJS
REMEDIATE TEMPERATURE
CONTROLS
13-M101
539-21-108
CINCINNATI, OHIO
2020-05099 01528
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN N
PLAN NOTES
GENERAL NOTES
A. REFER TO SHEET M001 FOR LEGEND, ABBREVIATIONS AND GENERAL NOTES.
1. PROVIDE NEW JACE BACNET ROUTER NEXT TO EXISTING AUTOMATED LOGIC ROUTER.
FULLY INTEGRATE ALL EXISTING ROUTER POINTS INTO NEW HEAD END THRU JACE.
REFER TO M00 SERIES SHEETS FOR APPROXIMATE QUANTITIES.
2. EXTEND 120V ELECTRIC FROM EXISTING PANEL TO NEW PANEL.
3. PROVIDE CVAMC STANDARD DUAL DATA DROP IN SURFACE MOUNT OUTLET FOR NEW
JACE. PROVIDE NEW PATCH PANEL IN THE CLOSEST EXISTING RACK WITH CAPACITY,
WITHIN DISTANCE LIMITS, TERMINATE NEW DATA CABLING. COORDINATE WITH OIT.
4. REPLACE LOCK IN EXISTING PANEL. ALL PANELS SHALL BE KEYED ALIKE.
5. PROVIDE NEW JACE BACNET ROUTER NEXT TO EXISTING JOHNSON CONTROLS NCE/NIE
DEVICE. ALL CONTROLS ROUTED THRU EXISTING DEVICE SHALL BE REMOVED, RE-
ROUTED AND FULLY INTEGRATED THRU NEW JACE. NCE/NIE DEVICE SHALL REMAIN AS A
FIELD CONTROLLER. FULLY INTEGRATE ALL EXISTING CONTROLLER POINTS INTO NEW
HEAD END THRU JACE. REFER TO M00 SERIES SHEETS FOR APPROXIMATE QUANTITIES.
6. REMOVE EXISTING HONEYWELL CONTROLS SYSTEM AFTER ALL POINTS HAVE BEEN
INTEGRATED INTO NEW TRIDIUM SYSTEM.
7. REPLACE EXISTING JOHNSON CONTROLS NAE WITH NEW JACE. ALL CONTROLS ROUTED
THRU EXISTING DEVICE SHALL BE RE-ROUTED AND FULLY INTEGRATED THRU NEW JACE.
REFER TO M00 SERIES SHEETS FOR APPROXIMATE QUANTITIES.
PHOTO - B13-LGR25 BLDG 13
PHOTO - B13-NAE-10
PHOTO - B13-NAE-11
# DESCRIPTION DATE
1 ADDENDUM 4 01-12-2026
| Sheets |
| 1-M100 - BASEMENT |
| 1-M103 - THIRD FLOOR |
| 1-M104 - FOURTH FLOOR |
| 1-M105 - FIFTH FLOOR |
| 1-M109 - NINTH FLOOR |
| 1-M110 - TENTH FLOOR PENTHOUSE |
| 2-M100 - BUILDING 2 BASEMENT |
| 13-M101 - BUILDING 13 FIRST FLOOR |
| 15-M100 - BUILDING 15 BASEMENT |
| 64-M100 - BUILDING 64 BASEMENT |
| 64-M102 - BUILDING 64 SECOND FLOOR |
| 64-M103 - BUILDING 64 THIRD FLOOR |
| M002 - JOHNSON CONTROLS ROUTER SCHEDULE |
| M004 - TRIDIUM ROUTER SCHEDULE |
| M701 - GENERAL CRITERIA, HONEYWELL CONTROLS REPLACEMENT |
| PG-M101 - PARKING GARAGE FIRST FLOOR PLAN |
File details come from the government source that posted it. Updated .