This architectural drawing is a detailed tenth floor penthouse plan for the Cincinnati VA Medical Center, prepared by Heapy Engineering and Levin Porter Architects. The document is dated January 9, 2026, with project number 539-21-108 and 2020-05099, and includes an addendum (Addendum 4) issued on January 12, 2026. The drawing shows a floor plan at 1/16" = 1'-0" scale, featuring multiple mechanical spaces including air handling units (AHU-2, AHU-3), fan rooms, and various labeled room spaces. The plan is fully sprinklered and includes grid-based architectural layout with multiple grid lines and room designations. Key consultants and project managers are noted, including Kevin Henderson as the Project Manager, and the drawing is part of construction documents for the U.S. Department of Veterans Affairs.
View the file
Other files for this federal contract opportunity
Show all 50
Z2DA--Remediate Temperature Controls 539-21-108 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D
AHU-3 AHU-2
Room
A10002
Stair 1
S*10*1
Fan Room
A10001
NAE-20
NAE-21
ABCDEFGHILMOPQRSTU
4a
8a
16a
16.5
17a
17b
19a
J
Lb.2
Lb.1
Kb
Jb
Ib.1
Ib.2
Hb Fb
Nb
PbQbRbSbTb
Mb Lb
16b
10a
Ga
Ib.14
Ib.22
Ib.23
Ib.24
Ib.27
7a
6a
Ib.28
Ib.29
3a
N
Fa
K
OaPa
Eb
1 4
210TH FLR MER
P ro je ct
N o.
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
E
D
C
B
A
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Manager
Cincinnati V.A Medical Center
U.S. Department of Veterans Affairs
F
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
32 4 5 6 7 8 9 10
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLEREDKEVIN HENDERSONPROJECT NO. STATE COA FIRM NO.
/9
/2
:0
:2
P
M -2
-1
TENTH FLOOR PENTHOUSE
10/23/25 GSE WJS
REMEDIATE TEMPERATURE
CONTROLS
1-M110
539-21-108
CINCINNATI, OHIO
2020-05099 01528
SCALE: 1/16" = 1'-0"
TENTH FLOOR PLAN N
PLAN NOTES
GENERAL NOTES
A. REFER TO SHEET M001 FOR LEGEND, ABBREVIATIONS AND GENERAL NOTES.
1. PROVIDE NEW JACE BACNET ROUTER NEXT TO EXISTING JOHNSON CONTROLS NCE/NIE
DEVICE. ALL CONTROLS ROUTED THRU EXISTING DEVICE SHALL BE REMOVED, RE-
ROUTED AND FULLY INTEGRATED THRU NEW JACE. NCE/NIE DEVICE SHALL REMAIN AS A
FIELD CONTROLLER. FULLY INTEGRATE ALL EXISTING CONTROLLER POINTS INTO NEW
HEAD END THRU JACE. REFER TO M00 SERIES SHEETS FOR APPROXIMATE QUANTITIES.
2. EXTEND 120V ELECTRIC FROM EXISTING PANEL TO NEW PANEL.
3. PROVIDE CVAMC STANDARD DUAL DATA DROP IN SURFACE MOUNT OUTLET FOR NEW
JACE. PROVIDE NEW PATCH PANEL IN THE CLOSEST EXISTING RACK WITH CAPACITY,
WITHIN DISTANCE LIMITS, TERMINATE NEW DATA CABLING. COORDINATE WITH OIT.
4. REPLACE LOCK IN EXISTING PANEL. ALL PANELS SHALL BE KEYED ALIKE.
5. EXISTING PNEUMATIC CONTROLS COMPRESSOR AND ASSOCIATED PNEUMATIC
CONTROLS COMPONENTS ON THIS FLOOR SHALL REMAIN.
6. REMOVE EXISTING HONEYWELL CONTROLS PANEL AND ALL ASSOCIATED COMPONENTS
AFTER ALL POINTS HAVE BEEN INTEGRATED INTO NEW TRIDIUM SYSTEM. THIS SCOPE
SHALL NOT BE EXECUTED UNTIL VERIFICATION THAT NO SYSTEMS ARE RELIANT UPON
THESE COMPONENTS. COORDINATE CLOSELY WITH COR. REMOVE ELECTRIC BACK TO
SOURCE.
# DESCRIPTION DATE
1 ADDENDUM 4 01-12-2026
| Sheets |
| 1-M100 - BASEMENT |
| 1-M103 - THIRD FLOOR |
| 1-M104 - FOURTH FLOOR |
| 1-M105 - FIFTH FLOOR |
| 1-M109 - NINTH FLOOR |
| 1-M110 - TENTH FLOOR PENTHOUSE |
| 2-M100 - BUILDING 2 BASEMENT |
| 13-M101 - BUILDING 13 FIRST FLOOR |
| 15-M100 - BUILDING 15 BASEMENT |
| 64-M100 - BUILDING 64 BASEMENT |
| 64-M102 - BUILDING 64 SECOND FLOOR |
| 64-M103 - BUILDING 64 THIRD FLOOR |
| M002 - JOHNSON CONTROLS ROUTER SCHEDULE |
| M004 - TRIDIUM ROUTER SCHEDULE |
| M701 - GENERAL CRITERIA, HONEYWELL CONTROLS REPLACEMENT |
| PG-M101 - PARKING GARAGE FIRST FLOOR PLAN |
File details come from the government source that posted it. Updated .