15-M100 - BUILDING 15 BASEMENT.pdf
PDF 2 MB Posted
- Attached to
- Z2DA--Remediate Temperature Controls 539-21-108 Federal contract opportunity
- Solicitation number
- 36C25026B0002
About this file
This document is an architectural floor plan drawing for Building 15 Basement at the Cincinnati VA Medical Center. The blueprint is dated 01-12-2026 and is part of project number 2020-05099, with a project manager named Kevin Henderson from Heavey Architects. The drawing shows a detailed basement floor plan at a scale of 1/8" = 1'-0", with gridlines, room layouts, and a mechanical room (B-01) labeled. An electrical panel photo is included in the top right corner, and the document indicates the building will be fully sprinkled. The project number is 539-21-108, and the drawing was last modified on 1/9/2026 at 3:06:29 PM.
View the file
Other files for this federal contract opportunity
Show all 50
Z2DA--Remediate Temperature Controls 539-21-108 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D
D.1
B
A.1 A
D
123456789
C
MECH. ROOM
B-01
TO
B1
TO
B14 NAE-08 AND NAE-27
1 2 4
P ro je ct
N o.
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
E
D
C
B
A
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Manager
Cincinnati V.A Medical Center
U.S. Department of Veterans Affairs
F
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
32 4 5 6 7 8 9 10
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLEREDKEVIN HENDERSONPROJECT NO. STATE COA FIRM NO.
/9
/2
:0
:2
P
M -2
-1
BUILDING 15 BASEMENT
10/23/25 GSE WJS
REMEDIATE TEMPERATURE
CONTROLS
15-M100
539-21-108
CINCINNATI, OHIO
2020-05099 01528
SCALE: 1/8" = 1'-0"
BASEMENT FLOOR PLAN N
PLAN NOTES
GENERAL NOTES
A. REFER TO SHEET M001 FOR LEGEND, ABBREVIATIONS AND GENERAL NOTES.
1. PROVIDE NEW JACE BACNET ROUTERS NEXT TO EXISTING JOHNSON CONTROLS NCE/NIE
DEVICES. ALL CONTROLS ROUTED THRU EXISTING DEVICE SHALL BE REMOVED, RE-
ROUTED AND FULLY INTEGRATED THRU NEW JACES. NCE/NIE DEVICES SHALL REMAIN AS
FIELD CONTROLLERS. FULLY INTEGRATE ALL EXISTING CONTROLLER POINTS INTO NEW
HEAD END THRU JACES. REFER TO M00 SERIES SHEETS FOR APPROXIMATE QUANTITIES.
2. EXTEND 120V ELECTRIC FROM EXISTING PANEL TO NEW PANEL.
3. PROVIDE CVAMC STANDARD DUAL DATA DROP IN SURFACE MOUNT OUTLET FOR NEW
JACE'S. PROVIDE NEW PATCH PANEL IN THE CLOSEST EXISTING RACK WITH CAPACITY,
WITHIN DISTANCE LIMITS, TERMINATE NEW DATA CABLING. COORDINATE WITH OIT.
4. REPLACE LOCK IN EXISTING PANEL. ALL PANELS SHALL BE KEYED ALIKE.
PHOTO - B15-B-01 NAE-8 AND NAE-27
# DESCRIPTION DATE
1 ADDENDUM 4 01-12-2026
| Sheets |
| 1-M100 - BASEMENT |
| 1-M103 - THIRD FLOOR |
| 1-M104 - FOURTH FLOOR |
| 1-M105 - FIFTH FLOOR |
| 1-M109 - NINTH FLOOR |
| 1-M110 - TENTH FLOOR PENTHOUSE |
| 2-M100 - BUILDING 2 BASEMENT |
| 13-M101 - BUILDING 13 FIRST FLOOR |
| 15-M100 - BUILDING 15 BASEMENT |
| 64-M100 - BUILDING 64 BASEMENT |
| 64-M102 - BUILDING 64 SECOND FLOOR |
| 64-M103 - BUILDING 64 THIRD FLOOR |
| M002 - JOHNSON CONTROLS ROUTER SCHEDULE |
| M004 - TRIDIUM ROUTER SCHEDULE |
| M701 - GENERAL CRITERIA, HONEYWELL CONTROLS REPLACEMENT |
| PG-M101 - PARKING GARAGE FIRST FLOOR PLAN |
File details come from the government source that posted it. Updated .