NHSB-BG-1.pdf
PDF 3 MB Posted
- Attached to
- 36-Month Electrical Distribution Testing
- Solicitation number
- 36C24727Q0044
About this file
This is a Preventive Maintenance Report documenting electrical testing and inspection services performed by Georgia Power Company Energy Services at the VA Main Campus in Atlanta, Georgia. The report, dated July 28, 2023, summarizes inspection findings for low voltage circuit breakers in the facility's electrical distribution system.
The report details inspections and testing of five molded case circuit breakers identified as NSHB-BG-1, T-MSBL, H2D1, To NHD-B3-1, and MCC. All equipment was manufactured by Cutler-Hammer with varying specifications: the main breaker (RD65K) has 2000A continuous amperage capacity and 65 kA interrupting rating; the secondary breakers (HKD 65K models) have 800A continuous amperage capacity; and the MCC breaker (L630H) has 630A capacity. Each breaker underwent secondary injection testing for trip functions, including long-time delay, short-time delay, ground fault pickup, and ground fault delay tests. Contact resistance measurements were recorded for all phases (A, B, and C). All equipment received cleaning and inspection services, with physical condition assessments documented as "Acceptable" for case/frame, handle, operation, and trip reset functions. All test results and inspection data passed acceptance criteria, indicating the electrical distribution system is in satisfactory operational condition.
View the file
Other files
Show 40 more
Latest 50 of 53 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .