7.7 Building System Assessment_Atlanta.xlsx
XLSX spreadsheet 13 KB Posted
- Attached to
- 36-Month Electrical Distribution Testing
- Solicitation number
- 36C24727Q0044
About this file
This is a Building System Assessment document evaluating the electrical distribution infrastructure condition across multiple Veterans Affairs facilities in Atlanta and Fort McPherson. The assessment uses a standardized condition rating scale (A through F, with A representing like-new condition and F representing critical/failing status) to evaluate medium voltage systems, low voltage transformers, emergency systems, and secondary distribution at nine buildings across the main campus and two Fort McPherson locations.
The assessment identifies significant infrastructure challenges requiring attention. At the main campus, Buildings C, D, and M present the most concerning conditions, with Building D rated as poor (D) for emergency systems and low voltage transformers, Building C containing numerous transformers rated C and D with old panels requiring replacement, and Building M featuring 3-phase systems fed by split-phase transformers with a D-rated secondary. Buildings A, B, and T13 maintain better condition ratings (B to B+), as do the Parking Decks and Trinka Davis facility. At Fort McPherson, Buildings 125 through 131 are rated in good condition (B-rated systems). The assessment indicates that multiple buildings contain old transformers and panels past their assigned useful life, with specific notation that Buildings C, D, and M require replacement of aging equipment. This assessment data directly supports the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7's 36-month Electrical Distribution Testing solicitation (36C24727Q0044), which addresses the testing and evaluation requirements identified in this infrastructure condition analysis.
View the file
Other files
Show 40 more
Latest 50 of 53 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| 7.7 BUILDING SYSTEM ASSESSMENT | |||||
| BUILDING | SYSTEM | EQUIPMENT CONDITION | |||
| MEDIUM VOLTAGE - SITE /UNDERGROUND PRIMARY SYSTEM | PRIMARY SERVICE | Utility Owned | |||
| PRIMARY SWITCHES | Utility Owned | ||||
| PRIMARY DISTRIBUTION | Utility Owned | ||||
| FEEDERS | Utility Owned | ||||
| TRANSFORMERS | Utility Owned | ||||
| BUILDING A | |||||
| (Main Campus) | EMERGENCY | B | |||
| LV TRANSFORMERS | C+ | HANDFUL OF OLD XFMRS | |||
| SECONDARY | B | ||||
| BUILDING B | |||||
| (Main Campus) | EMERGENCY | C | |||
| LV TRANSFORMERS | C+ | ||||
| SECONDARY | C | ||||
| BUILDING C | |||||
| (Main Campus) | EMERGENCY | C+ | MOST ARE B WITH A LOT OF C AND D | ||
| LV TRANSFORMERS | C | OLD PANELS NEED TO BE REPLACED | |||
| SECONDARY | C+ | HANDFUL OF OLD XFMRS | |||
| BUILDING D | |||||
| (Main Campus) | EMERGENCY | C | LOTS OF C AND D | ||
| LV TRANSFORMERS | D | OLD XFMRS NEED REPLACE | |||
| SECONDARY | C | ||||
| BUILDING M | |||||
| (Main Campus) | EMERGENCY | D | 3-PHASE FED BY SPLIT PHASE | ||
| LV TRANSFORMERS | N/A | ||||
| SECONDARY | D | ||||
| BUILDING T13 | |||||
| (Main Campus) | EMERGENCY | N/A | |||
| LV TRANSFORMERS | N/A | ||||
| SECONDARY | B | ||||
| PARKING DECKS | |||||
| (Main Campus) | EMERGENCY | B | |||
| LV TRANSFORMERS | B | ||||
| SECONDARY | B | ||||
| TRINKA DAVIS | EMERGENCY | B | WHOLE CAMPUS COMBINED INTO 1 BUILDING | ||
| LV TRANSFORMERS | B | ||||
| SECONDARY | B | ||||
| BUILDING 125 | |||||
| (Ft. McPherson) | EMERGENCY | B | |||
| LV TRANSFORMERS | B | ||||
| SECONDARY | B | ||||
| BUILDING 128 | |||||
| (Ft. McPherson) | EMERGENCY | B | |||
| LV TRANSFORMERS | N/A | ||||
| SECONDARY | B | ||||
| BUILDING 129 | |||||
| (Ft. McPherson) | EMERGENCY | B | |||
| LV TRANSFORMERS | N/A | ||||
| SECONDARY | B | ||||
| BUILDING 130 | |||||
| (Ft. McPherson) | EMERGENCY | B | |||
| LV TRANSFORMERS | N/A | ||||
| SECONDARY | B | ||||
| BUILDING 131 | |||||
| (Ft. McPherson) | EMERGENCY | B | |||
| LV TRANSFORMERS | N/A | ||||
| SECONDARY | B |
| LEGEND: |
| A = Like new condition. Majority of useful life span remains. "Excellent" |
| B = Good condition. Over half of useful life span remains. "Good" or B+ "Very Good" |
| C = Average condition. Less than half of useful life span remains. "Average", "fair", or C+ "Above Average" |
| C-= Workable condition. Past assigned useful life, but still working. "Keep an eye on it" |
| D = Poor condition. Past assigned useful life. Failure is not critical. "Poor" or "Problematic" |
| F = Critical condition. Needs Immediate attention. "Failing" or "Critical" |
7.7-&P
File details come from the government source that posted it. Updated .