This is a Facility Condition Assessment final submission document in spreadsheet format related to electrical distribution testing services for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7. The spreadsheet appears to contain detailed facility evaluation data, condition assessments, and technical findings regarding the electrical distribution infrastructure at a VA facility. The assessment likely documents the current state of electrical systems, identifies deficiencies or areas requiring maintenance or upgrades, and may include recommendations for remediation or testing protocols that align with the 36-month electrical distribution testing solicitation (36C24727Q0044). This submission represents a comprehensive evaluation of facility electrical systems to support contract requirements and procurement decisions for testing and maintenance services over the specified 36-month period.
View the file
Other files
Show 40 more
Latest 50 of 53 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| 7.6. Facility Condition Assessment Update | ||||||||||
| The items listed below are to be added to the FCA Report by CFM. | ||||||||||
| Atlanta, GA | Atlanta, GA VAMC | |||||||||
| System | Building | Rec No | Condition | Useful Life | Remaining Life | FCA | ||||
| Risk | Correction Cost | Description | ||||||||
| Primary Electrical System | 125 | D | 30 | - | 4 | $13,995 | $8,120.85 | 125-BUS-L1A has burn marks inside the panel. Replace panel and breakers. | ||
| Primary Electrical System | 125 | D | 30 | - | 4 | $2,340 | $1,357.75 | 125-BUS-TGEN-DISC has mixed fuses installed. Replace fuses. | ||
| Primary Electrical System | 125 | D | 30 | - | 4 | $560 | $325.00 | 125-BUS-MCC3 has holes in the panel cover. Install panel blanks. | ||
| Primary Electrical System | 125 | D | 25 | - | 3 | $1,471 | $853.59 | 125-CB-L2B-MAIN is not properly coordinated. Replace breaker. | ||
| Emergency Electrical System | 125 | D | 25 | - | 3 | $6,757 | $3,920.70 | 125-ATS-2 is a 2 pole ATS feeding non-motor loads. Replace with 3 pole ATS to switch neutral. | ||
| Primary Electrical System | 128 | D | 25 | - | 3 | $1,115 | $647.19 | 128-CB-LP2-MAIN is not properly coordinated. Replace breaker. | ||
| Primary Electrical System | 128 | D | 25 | - | 3 | $1,124 | $652.19 | 128-CB-MDP-3 is not properly coordinated. Replace breaker. | ||
| Primary Electrical System | 128 | - | 30 | - | 4 | $7,726 | $4,483.31 | 128-BUS-LP1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. | ||
| Primary Electrical System | 128 | - | 30 | - | 4 | $7,726 | $4,483.31 | 128-BUS-LP2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. | ||
| Emergency Electrical System | 129 | - | 25 | - | 4 | $7,726 | $4,483.31 | 129-BUS-SB1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. | ||
| Primary Electrical System | 131 | - | 25 | - | 4 | $1,186 | $687.94 | 131-CB-MDP-8 cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | 131 | - | 25 | - | 4 | $1,354 | $785.38 | 131-BUS-SB1-1 cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | 131 | - | 25 | - | 4 | $1,354 | $785.38 | 131-BUS-SB1-2 cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | 131 | - | 25 | - | 4 | $1,186 | $687.94 | 131-CB-SB2-2 cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | 131 | - | 25 | - | 4 | $7,726 | $4,483.31 | 131-BUS-SB2A cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. | ||
| Emergency Electrical System | A | D | 25 | - | 4 | $78 | $45.00 | A-BUS-GEN3PNL has a hole in the bottom from removed conduit. Install knockout plug to cover the hole | ||
| Emergency Electrical System | A | D | 25 | - | 4 | $78 | $45.00 | A-BUS-GEN5PNL has a hole in the bottom from removed conduit. Install knockout plug to cover the hole | ||
| Emergency Electrical System | A | D | 25 | - | 4 | $20,714 | $12,019.47 | A-BUS-NHP-A1-2 has a hole in the cover. Install new panel cover. | ||
| Primary Electrical System | A | D | 30 | - | 4 | $98,690 | $57,264.76 | A-BUS-ED has holes in the cover and has a dead trip unit. Replace trip unit and install panel blanks. | ||
| Emergency Electrical System | A | D | 25 | - | 3 | $6,218 | $3,608.24 | A-CB-CHD-AG-1-(1) is not properly coordinated. Replace breaker. | ||
| Emergency Electrical System | A | D | 25 | - | 3 | $1,941 | $1,126.35 | A-CB-HL-5A-277-2-(1) is not properly coordinated. Replace breaker. | ||
| Emergency Electrical System | A | D | 25 | - | 4 | $16,020 | $9,295.55 | A-CBL-CHD-AG-1-(1) is not properly sized. Install new conductors appropriately sized. | ||
| Emergency Electrical System | A | D | 25 | - | 4 | $2,434 | $1,412.52 | A-CBL-HL-5A-277-2-(1) is not properly sized. Install new conductors appropriately sized. | ||
| Emergency Electrical System | A | D | 25 | - | 4 | $7,726 | $4,483.31 | A-BUS-SLP-AG-1 is past its service life. Replace panel. | ||
| Emergency Electrical System | A | D | 25 | - | 4 | $7,726 | $4,483.31 | A-BUS-LGA SECT 2 is past its service life. Replace panel. | ||
| Emergency Electrical System | A | D | 25 | - | 4 | $13,995 | $8,120.85 | A-BUS-EHD-A4-1 is past its service life. Replace panel. | ||
| Emergency Electrical System | A | D | 25 | - | 4 | $2,340 | $1,357.75 | A-BUS-P11-DISC-1 contains mixed fuses. Replace all fuses with the same type. | ||
| Emergency Electrical System | A | D | 25 | - | 4 | $2,340 | $1,357.75 | A-BUS-P11-DISC-2 contains mixed fuses. Replace all fuses with the same type. | ||
| Emergency Electrical System | A | D | 25 | - | 4 | $2,340 | $1,357.75 | A-BUS-P12-DISC-1 contains mixed fuses. Replace all fuses with the same type. | ||
| Emergency Electrical System | A | D | 25 | - | 4 | $2,340 | $1,357.75 | A-BUS-P12-DISC-2 contains mixed fuses. Replace all fuses with the same type. | ||
| Emergency Electrical System | A | D | 25 | - | 4 | $2,340 | $1,357.75 | A-BUS-P10-DISC-1 contains mixed fuses. Replace all fuses with the same type. | ||
| Emergency Electrical System | A | D | 25 | - | 4 | $2,340 | $1,357.75 | A-BUS-P10-DISC-2 contains mixed fuses. Replace all fuses with the same type. | ||
| Transformer | A | D | 30 | - | 4 | $17,114 | $9,930.36 | A-XF-SX-AG-1 (TLGA) is past its service life. Replace transformer. | ||
| Transformer | A | D | 30 | - | 4 | $8,968 | $5,203.58 | A-XF-SX-AG-2 (T-LG) is past its service life. Replace transformer. | ||
| Transformer | A | D | 30 | - | 4 | $8,968 | $5,203.58 | A-XF-CX-AG-1 (T-EGA) is past its service life. Replace transformer. | ||
| Transformer | A | D | 30 | - | 3 | $333 | $193.04 | A-XF-NX-AG-4 has no grounding electrode. Install conductor in conduit to building steel. | ||
| Transformer | A | D | 30 | - | 4 | $8,968 | $5,203.58 | A-XF-NX-A1-2 is past its service life. Replace transformer. | ||
| Transformer | A | D | 30 | - | 4 | $8,968 | $5,203.58 | A-XF-NX-A1-5 is past its service life. Replace transformer. | ||
| Transformer | A | D | 30 | - | 4 | $8,968 | $5,203.58 | A-XF-EX-A1-1 is past its service life. Replace transformer. | ||
| Transformer | A | D | 30 | - | 4 | $8,968 | $5,203.58 | A-XF-SX-A2-1 is past its service life. Replace transformer. | ||
| Transformer | A | D | 30 | - | 4 | $34,856 | $20,225.37 | A-XF-NX-A3-2 is past its service life. Replace transformer. | ||
| Transformer | A | D | 30 | - | 4 | $8,968 | $5,203.58 | A-XF-SX-A5-1 is past its service life. Replace transformer. | ||
| Emergency Electrical System | A | - | 25 | - | 4 | $13,995 | $8,120.85 | A-BUS-EHDP-AB-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. | ||
| Emergency Electrical System | A | - | 25 | - | 4 | $16,891 | $9,800.86 | A-BUS-NHL-AG-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. | ||
| Emergency Electrical System | A | - | 25 | - | 4 | $13,995 | $8,120.85 | A-BUS-SHL-AG-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. | ||
| Emergency Electrical System | A | - | 25 | - | 4 | $1,471 | $853.59 | A-CB-CHD-AG-1-(3) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | A | - | 25 | - | 4 | $1,342 | $778.94 | A-CB-EHDP-AB-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | A | - | 25 | - | 4 | $1,471 | $853.59 | A-CB-NHL-A4-3-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | A | - | 25 | - | 4 | $1,342 | $778.94 | A-CB-NHLP-AB-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | A | - | 25 | - | 4 | $1,342 | $778.94 | A-CB-SHL-AG-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | A | - | 25 | - | 4 | $1,342 | $778.94 | A-CB-SHL-AG-1-MAIN cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | A | D | 25 | - | 3 | $66,255 | $38,444.66 | A-BUS-GHTA-AG-1 is 3-pole with no bypass isolation. Replace with a 4 pole ATS with a maintenance bypass. | ||
| Emergency Electrical System | B | D | 25 | - | 3 | $1,409 | $817.84 | B-CB-NHL-B2-1-MAIN is not properly coordinated. Replace breaker. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-CLP-BG-1 (LCGB1/2) is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-CLP-BG-1-2 (LCGB1/2) is past its service life. Replace panel. | ||
| Primary Electrical System | B | D | 30 | - | 4 | $13,995 | $8,120.85 | B-BUS-NHL-BG-2 (1PJ1) is past its service life. Replace panel. | ||
| Primary Electrical System | B | D | 30 | - | 4 | $13,995 | $8,120.85 | B-BUS-NLR-BG-1 (PPJ1) is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-SLP-BG-1 (LEGB) is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $13,995 | $8,120.85 | B-BUS-EHL-BG-1 is past its service life. Replace panel. | ||
| Primary Electrical System | B | D | 30 | - | 4 | $13,995 | $8,120.85 | B-BUS-NHL-B1-1 is past its service life. Replace panel. | ||
| Primary Electrical System | B | D | 30 | - | 4 | $7,726 | $4,483.31 | B-BUS-NLP-B1-3 is past its service life. Replace panel. | ||
| Primary Electrical System | B | D | 30 | - | 4 | $7,726 | $4,483.31 | B-BUS-NLP-B1-6 (PPG4) is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-CLP-B2-3 (E2D2) has holes in the cover. Install panel blanks. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $13,995 | $8,120.85 | B-BUS-NHL-B2-5 is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-CLP-BG-2 is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-NLP-B1-1 is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-NLP-B1-1-2 is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-NLP-B1-4 is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-NLP-B1-4-2 is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-NLP-B1-5 is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-NLP-B2-5 has holes in the cover. Install panel blanks. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $13,995 | $8,120.85 | B-BUS-NHL-BG-1 is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-NLP-BG-1-2 is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-NLP-BG-1-2-1 is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-NLP-B1-6 (PPG4) is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-NLP-B1-4-2 (PPG1/2) is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-NLP-B1-4-3 (PPG2/2) is past its service life. Replace panel. | ||
| Emergency Electrical System | B | D | 25 | - | 4 | $7,726 | $4,483.31 | B-BUS-NLP-B1-5 (PPG3) is past its service life. Replace panel. | ||
| Transformer | B | D | 30 | - | 4 | $9,879 | $5,732.26 | B-XF-CX-B2-4 (T-E2D2) is past its service life. Replace transformer. | ||
| Transformer | B | D | 30 | - | 3 | $644 | $373.54 | B-XF-NX-P2-2 (a.k.a B-XF-T-LN2B2) has no neutral ground bond. Install a N-G bond in the transformer. | ||
| Emergency Electrical System | B | - | 25 | - | 4 | $16,891 | $9,800.86 | B-BUS-CHD-BG-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. | ||
| Emergency Electrical System | B | - | 25 | - | 4 | $13,995 | $8,120.85 | B-BUS-NHL-BG-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. | ||
| Emergency Electrical System | B | - | 25 | - | 4 | $1,343 | $779.23 | B-CB-CHD-BG-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | B | - | 25 | - | 4 | $1,343 | $779.23 | B-CB-CHD-BG-1-(2) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | B | - | 25 | - | 4 | $1,296 | $751.77 | B-CB-CHD-BG-1-(3) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | B | - | 25 | - | 4 | $1,343 | $779.23 | B-CB-CHD-BG-1-(5) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | B | - | 25 | - | 4 | $1,296 | $751.77 | B-CB-CHD-BG-1-(6) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | B | - | 25 | - | 4 | $1,343 | $779.23 | B-CB-CHD-BG-1-(7) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Emergency Electrical System | B | - | 25 | - | 4 | $1,343 | $779.23 | B-CB-NHL-BG-2-MAIN cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. | ||
| Primary Electrical System | C | D | 30 | - | 4 | $11,000,000 | Main Bus Duct distribution to Building C is in poor condition. Estimated cost is based on replacement and was provided by the site | |||
| Primary Electrical System | C | D | 30 | - | 4 | $7,726 | $4,483.31 | C-BUS-ELP-C3-4 (3MLX) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-EHL-C3-1 (3HX) is past its service life. Replace panel and breakers. | ||
| Primary Electrical System | C | D | 30 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-CB-1 (BLD) is past its service life. Replace panel and breakers. | ||
| Primary Electrical System | C | D | 30 | - | 4 | $213 | $123.60 | C-BUS-NX-C13-2 DISCONNECT PRIMARY has broken conduit feeding it. Replace conduit to prevent water from entering enclosure. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-ELP-C12-1 (12LXA) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C11-3 (11HA) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C11-7 (11LXA) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C11-8 is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C11-4 (11HB) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C11-4 (11LB) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C6-4 (6HB) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-ELP-C6-2 (6LXB) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C6-4 (6LB) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C6-3 (6HA) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-ELP-C6-1 (6LXA) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C5-6-2 (5LB) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C5-4 (5HB) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C5-5 (5LA) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $14,828 | $8,603.78 | C-BUS-NLP-C5-3 is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C5-3 (5HA) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C5-7 is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C4-4 (4LB) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C4-3 (4HA) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C4-3 (4LA) is past its service life. Replace panel and breakers. | ||
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-ELP-CB-4 (BX) is past its service life. Replace panel and breakers. | ||
| Primary Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C3-1 |
(3LB) is past its service life. Replace panel and breakers.
Emergency Electrical System C D 25 - 4 $7,726 $4,483.31 C-BUS-ELP-C3-3 (3LXB) is past its service life. Replace panel and breakers.
Emergency Electrical System C D 25 - 4 $7,726 $4,483.31 C-BUS-ELP-C3-1 (3LXA) is past its service life. Replace panel and breakers.
Emergency Electrical System C D 25 - 4 $7,726 $4,483.31 C-BUS-ELP-C3-2 (3LXA-2) is past its service life. Replace panel and breakers.
| Emergency Electrical System | C | D | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-EHL-C13-2 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-ELP-C13-4 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $16,891 | $9,800.86 | C-BUS-EHL-C13-5 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $14,828 | $8,603.78 | C-BUS-NLP-C11-5 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C11-3 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-ELP-C12-2 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C12-2 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C12-2 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-CHL-C6-2 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-CHL-C6-1 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C6-3 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C5-6 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $14,828 | $8,603.78 | C-BUS-NLP-C5-4 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C4-4 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-EHL-C13-4 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-ELP-C13-2 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 3 | $164 | $95.00 | C-BUS-CLP-C2-3 has missing panel blanks. Install new panel planks. |
| Primary Electrical System | C | D | 30 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C2-1 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 3 | $164 | $95.00 | C-BUS-ELP-CG-12 has missing panel blanks. Install new panel blanks. |
| Transformer | C | D | 30 | - | 4 | $23,644 | $13,719.55 | C-XF-EX-C3-4 (T-3MLX) is past its service life. Replace transformer. |
| Transformer | C | D | 30 | - | 4 | $16,203 | $9,401.68 | C-XF-EX-C3-1 (T-3LXA) is past its service life. Replace transformer. |
| Transformer | C | D | 30 | - | 4 | $30,443 | $17,664.65 | C-XF-NX-C11-2 (T-11PLB) is past its service life. Replace transformer. |
| Transformer | C | D | 30 | - | 4 | $30,443 | $17,664.65 | C-XF-NX-C5-4 (T-5PLB) is past its service life. Replace transformer. |
| Transformer | C | D | 30 | - | 4 | $30,443 | $17,664.65 | C-XF-NX-C5-3 (T-5PLA) is past its service life. Replace transformer. |
| Transformer | C | D | 30 | - | 4 | $13,670 | $7,931.86 | C-XF-NX-C3-1 (T-3LB) is past its service life. Replace transformer. |
| Transformer | C | D | 30 | - | 4 | $927 | $537.80 | C-XF-NX-C1-3 (T-LN14) has no GEC or N-G bond installed. Install new conductors for GEC and N-G bond. |
| Transformer | C | D | 30 | - | 4 | $9,879 | $5,732.26 | C-XF-SX-CG-2 is past its service life. Replace transformer. |
| Transformer | C | D | 30 | - | 4 | $9,879 | $5,732.26 | C-XF-EX-C13-4 |
(T-EMMR) is past its service life. Replace transformer.
Transformer C D 30 - 4 $30,443 $17,664.65 C-XF-NX-C11-1 (T-11PLA) is past its service life. Replace transformer.
| Transformer | C | D | 30 | - | 4 | $9,879 | $5,732.26 | C-XF-EX-C13-2 is past its service life. Replace transformer. |
| Emergency Electrical System | C | D | 25 | - | 4 | $16,891 | $9,800.86 | C-BUS-NLP-C11-6 (11PLB) is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 4 | $16,891 | $9,800.86 | C-BUS-EHL-C13-1 (MCC-2) is past its service life. Replace panel and breakers. |
| Emergency Electrical System | C | D | 25 | - | 3 | $1,342 | $778.94 | C-CB-EHL-CB-1-(4) is not properly coordinated. Replace existing breaker. |
| Emergency Electrical System | C | D | 25 | - | 3 | $1,401 | $812.84 | C-CB-NHD-C13-1-(1) is not properly coordinated. Replace existing breaker. |
| Emergency Electrical System | C | D | 25 | - | 3 | $1,471 | $853.59 | C-CB-NLP-C7-3-MAIN is not properly coordinated. Replace existing breaker. |
| Emergency Electrical System | C | D | 25 | - | 4 | $18,646 | $10,819.60 | C-CBL-EHD-CG-2-(2) is not properly sized. Install new conductors appropriately sized. |
| Emergency Electrical System | C | D | 25 | - | 4 | $1,462 | $848.60 | C-CBL-EHL-CB-1-(4) is not properly sized. Install new conductors appropriately sized. |
| Emergency Electrical System | C | - | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C4-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $16,891 | $9,800.86 | C-BUS-NHL-C4-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $16,891 | $9,800.86 | C-BUS-NHL-C5-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $16,891 | $9,800.86 | C-BUS-NHL-C6-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $16,891 | $9,800.86 | C-BUS-NHL-C8-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-CHL-C6-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-EHL-C3-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-EHL-CG-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-CHL-C6-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-EHL-C3-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C4-3 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C4-4 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C5-3 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C5-4 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-C6-3 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $16,891 | $9,800.86 | C-BUS-NHL-CB-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $13,995 | $8,120.85 | C-BUS-NHL-CG-4 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C11-7 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $7,726 | $4,483.31 | C-BUS-NLP-C11-8 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $16,891 | $9,800.86 | C-BUS-CHL-C5-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $16,891 | $9,800.86 | C-BUS-CHL-C5-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $7,390 | $4,287.96 | C-CB-CHD-C3-1-(2) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,343 | $779.23 | C-CB-EHL-C3-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,343 | $779.23 | C-CB-EHL-C3-1-(2) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,471 | $853.59 | C-CB-EHL-CG-2-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $7,535 | $4,372.33 | C-CB-NHD-C1-1-(2) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $7,535 | $4,372.33 | C-CB-NHD-C1-1-(3) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $16,334 | $9,477.67 | C-CB-NHD-C1-1-MAIN cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $7,535 | $4,372.33 | C-CB-NHD-C1-2-(3) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,471 | $853.59 | C-CB-NHD-C1-2-(5) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,471 | $853.59 | C-CB-NHD-C1-2-(6) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $7,390 | $4,287.96 | C-CB-NHD-C1-2-(7) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $16,334 | $9,477.67 | C-CB-NHD-C1-2-MAIN cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,471 | $853.59 | C-CB-NHL-C2-3-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,343 | $779.23 | C-CB-NHL-C4-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,343 | $779.23 | C-CB-NHL-C4-2-(2) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,343 | $779.23 | C-CB-NHL-C5-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,471 | $853.59 | C-CB-NHL-C5-2-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,343 | $779.23 | C-CB-NHL-C6-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,471 | $853.59 | C-CB-NHL-C6-2-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,343 | $779.23 | C-CB-NHL-CB-2-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,471 | $853.59 | C-CB-NHL-CG-2-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,296 | $751.77 | C-CB-NHL-CG-4-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $1,186 | $687.94 | C-CB-NLD-CG-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | C | - | 25 | - | 4 | $991 | $575.00 | C-CB-NHD-C13-1-MAIN has a ground fault trip unit, but is on the secondary side of an ATS. Replace trip unit. |
| Emergency Electrical System | C | - | 25 | - | 4 | $12,600 | $7,311.08 | C-CB-NHD- C3-3-MAIN has a ground fault trip unit, but is on the secondary side of an ATS. Replace circuit breaker. |
| Emergency Electrical System | C | D | 25 | - | 3 | $58,921 | $34,189.06 | C-BUS-GHTA-CB-1 is 3-pole with no bypass isolation. Replace with a 4 pole ATS with a maintenance bypass. |
| Emergency Electrical System | C | D | 25 | - | 3 | $58,921 | $34,189.06 | C-BUS-GHTA-CB-2 is 3-pole with no bypass isolation. Replace with a 4 pole ATS with a maintenance bypass. |
| Emergency Electrical System | D | D | 25 | - | 4 | $13,995 | $8,120.85 | D-BUS-NHL-DB-1 (NHBA) is past its service life. Replace panel and breakers. |
| Emergency Electrical System | D | D | 25 | - | 4 | $13,995 | $8,120.85 | D-BUS-NHL-D2-1 (NH2A) is past its service life. Replace panel and breakers. |
| Emergency Electrical System | D | D | 25 | - | 4 | $7,726 | $4,483.31 | D-BUS-ELP-D2-2 (EL2B) is past its service life. Replace panel and breakers. |
| Emergency Electrical System | D | D | 25 | - | 4 | $13,995 | $8,120.85 | D-BUS-SHL-D2-1 (MH2A) is past its service life. Replace panel and breakers. |
| Emergency Electrical System | D | D | 25 | - | 4 | $7,726 | $4,483.31 | D-BUS-ELP-D2-1 (EL2A) is past its service life. Replace panel and breakers. |
| Emergency Electrical System | D | D | 25 | - | 4 | $7,726 | $4,483.31 | D-BUS-NLP-D2-1 (NL2A) is past its service life. Replace panel and breakers. |
| Emergency Electrical System | D | D | 25 | - | 4 | $13,995 | $8,120.85 | D-BUS-NHL-D3-1 (NH3A) is past its service life. Replace panel and breakers. |
| Emergency Electrical System | D | D | 25 | - | 4 | $7,726 | $4,483.31 | D-BUS-ELP-D3-2 (ELSB) is past its service life. Replace panel and breakers. |
| Emergency Electrical System | D | D | 25 | - | 4 | $13,995 | $8,120.85 | D-BUS-SHL-D3-1 (MH3A) is past its service life. Replace panel and breakers. |
| Emergency Electrical System | D | D | 25 | - | 4 | $7,726 | $4,483.31 | D-BUS-ELP-D3-1 (EL3A) is past its service life. Replace panel and breakers. |
| Emergency Electrical System | D | D | 25 | - | 4 | $7,726 | $4,483.31 | D-BUS-NLP-D3-1 (NL3A) is past its service life. Replace panel and breakers. |
| Emergency Electrical System | D | D | 25 | - | 4 | $7,726 | $4,483.31 | D-BUS-NLP-D1-3 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | D | D | 25 | - | 4 | $7,726 | $4,483.31 | D-BUS-NLP-D2-2 is past its service life. Replace panel and breakers. |
| Emergency Electrical System | D | D | 25 | - | 4 | $7,726 | $4,483.31 | D-BUS-NLP-D3-2 is past its service life. Replace panel and breakers. |
| Transformer | D | D | 30 | - | 4 | $9,879 | $5,732.26 | D-XF-NX-DB-1 (T-NLBA) is past its service life. Replace transformer. |
| Transformer | D | D | 30 | - | 4 | $9,879 | $5,732.26 | D-XF-SX-DB-1 (T-MLBA) is past its service life. Replace transformer. |
| Transformer | D | D | 30 | - | 4 | $13,670 | $7,931.86 | D-XF-EX-DB-1 |
(T-ELBA) is past its service life. Replace transformer.
| Transformer | D | D | 30 | - | 3 | $563 | $326.44 | D-XF-T-B1O has no GEC. Install new conductor for GEC. |
| Transformer | D | D | 30 | - | 4 | $16,203 | $9,401.68 | D-XF-NX-D1-1 |
(T-NL1A) is past its service life. Replace transformer.
Transformer D D 30 - 4 $16,203 $9,401.68 D-XF-NX-D1-4 (T-NLB1) is past its service life. Replace transformer.
Transformer D D 30 - 4 $13,670 $7,931.86 D-XF-NX-D1-3 (T-NL1B) is past its service life. Replace transformer.
Transformer D D 30 - 4 $16,203 $9,401.68 D-XF-NX-D2-2 (T-NL2B) is past its service life. Replace transformer.
Transformer D D 30 - 4 $16,203 $9,401.68 D-XF-EX-D2-2 (T-EL2B) is past its service life. Replace transformer.
Transformer D D 30 - 4 $16,203 $9,401.68 D-XF-EX-D2-1 (T-EL2A) is past its service life. Replace transformer.
Transformer D D 30 - 4 $16,203 $9,401.68 D-XF-NX-D2-1 (T-NL2A) is past its service life. Replace transformer.
Transformer D D 30 - 4 $16,203 $9,401.68 D-XF-NX-D3-2 (T-NL3B) is past its service life. Replace transformer.
Transformer D D 30 - 4 $16,203 $9,401.68 D-XF-EX-D3-1 (T-NL3A) is past its service life. Replace transformer.
| Emergency Electrical System | D | D | 25 | - | 4 | $16,096 | $9,339.80 | D-BUS-NHD-DB-2 (1) is missing pieces of the panel. Replace panelboard. |
| Emergency Electrical System | D | - | 25 | - | 4 | $29,432 | $17,078.07 | D-BUS-NHD-DB-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | D | - | 25 | - | 4 | $21,870 | $12,690.06 | D-BUS-NHD-DB-2-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | D | - | 25 | - | 4 | $13,995 | $8,120.85 | D-BUS-NHL-D1-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation. |
| Emergency Electrical System | D | - | 25 | - | 4 | $1,354 | $785.38 | D-CB-NHD-DB-2-(2) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | D | - | 25 | - | 4 | $1,471 | $853.59 | D-CB-NHD-DB-2-2-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | D | - | 25 | - | 4 | $1,471 | $853.59 | D-CB-NHL-D1-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation. |
| Emergency Electrical System | M | D | 25 | - | 4 | $14,828 | $8,603.78 | M-BUS-F has a split phase feed serving a 3 phase panel with one phase jumpered onto the third phase. Replace panel with a 120/240V split phase panel. |
| Emergency Electrical System | M | D | 25 | - | 4 | $14,828 | $8,603.78 | M-BUS-D has a split phase feed serving a 3 phase panel with phase 1 jumpered onto phase 2. Replace panel with a 120/240V split phase panel. |
| Emergency Electrical System | M | D | 25 | - | 4 | $14,828 | $8,603.78 | M-BUS-B has a split phase feed serving a 3 phase panel with phase 1 jumpered onto phase 2. Replace panel with a 120/240V split phase panel. |
| Emergency Electrical System | Parking Decks | D | 25 | - | 3 | $164 | $95.00 | PD-BUS-NLP-SG-1 has a missing panel blank. Install panel blank. |
| Emergency Electrical System | Parking Decks | D | 25 | - | 3 | $164 | $95.00 | F-BUS-T3 has a missing panel blank. Install panel blank. |
| Emergency Electrical System | Parking Decks | D | 25 | - | 4 | $991 | $575.00 | PD-BUS-NHL-SG-1 is missing a panel cover. Install a panel cover. |
| Transformer | Parking Decks | D | 30 | - | 3 | $333 | $193.04 | E-XF-EX-L1-1 has no grounding electrode. Install new grounding electrode. |
| Emergency Electrical System | Parking Decks | D | 25 | - | 4 | $22,332 | $12,958.44 | F-BUS-NHDP-LG-1 is past its service life. Replace panel. |
| Emergency Electrical System | TD | D | 25 | - | 3 | $16,366 | $9,496.20 | TD-ATS1 is a 3 pole ATS but should be a 4 pole ATS with maintenance bypass. Replace ATS to meet requirement. |
| Emergency Electrical System | TD | D | 25 | - | 3 | $16,366 | $9,496.20 | TD-ATS2 is a 3 pole ATS but should be a 4 pole ATS with maintenance bypass. Replace ATS to meet requirement. |
| Emergency Electrical System | TD | D | 25 | - | 3 | $16,366 | $9,496.20 | TD-ATS3 is a 3 pole ATS but should be a 4 pole ATS with maintenance bypass. Replace ATS to meet requirement. |
| Emergency Electrical System | TD | D | 25 | - | 3 | $16,366 | $9,496.20 | TD-ATS4 is a 3 pole ATS but should be a 4 pole ATS with maintenance bypass. Replace ATS to meet requirement. |
| Primary Electrical System | TD | D | 25 | - | 3 | $1,354 | $785.38 | TD-CB-EGHA-2 is not properly coordinated. Replace breaker. |
| Primary Electrical System | TD | D | 25 | - | 3 | $1,342 | $778.94 | TD-CB-EGLA-MAIN is not properly coordinated. Replace breaker. |