7.6 Facility Condition Assessment - Final Submission.xlsx

XLSX spreadsheet 31 KB Posted

Attached to
36-Month Electrical Distribution Testing
Solicitation number
36C24727Q0044
Issued by

About this file

This is a Facility Condition Assessment final submission document in spreadsheet format related to electrical distribution testing services for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7. The spreadsheet appears to contain detailed facility evaluation data, condition assessments, and technical findings regarding the electrical distribution infrastructure at a VA facility. The assessment likely documents the current state of electrical systems, identifies deficiencies or areas requiring maintenance or upgrades, and may include recommendations for remediation or testing protocols that align with the 36-month electrical distribution testing solicitation (36C24727Q0044). This submission represents a comprehensive evaluation of facility electrical systems to support contract requirements and procurement decisions for testing and maintenance services over the specified 36-month period.

View the file

Other files

File Type Posted
Final - AF Label List.xlsx XLSX spreadsheet
final remote - gen device eval.pdf PDF
Attachment B - Fort McPherson Equipment Schedule - REV19.1.xlsx XLSX spreadsheet
Drawing List.pdf PDF
GHTA-AG-1.pdf PDF
final main site - util input report.pdf PDF
NHSB-BG-1.pdf PDF
20200603 - Final Combined pdfs.pdf PDF
final main site - util device eval.pdf PDF
final main site - util bus eval.pdf PDF
Existing-Recommended Breaker Settings - Final.xlsx XLSX spreadsheet
GHSB-C3-1.pdf PDF
final remote - gen results report.pdf PDF
NHSB-CB-1.pdf PDF
final main site - gen bus eval.pdf PDF
Equipment Condition Assessment Sheets.xlsx XLSX spreadsheet
GHTA-CB-1.pdf PDF
final remote - gen input report.pdf PDF
final remote - util results report.pdf PDF
Questions and Answers.docx DOCX document
Attachment C - Trinka-Davis Equipment Schedule - REV19.1.xlsx XLSX spreadsheet
Switchboard C.pdf PDF
Attachment D - Equipment and Test Matrix - REV19.1.docx DOCX document
Electrical Distribution Testing SOW final.docx DOCX document
final remote - util bus eval.pdf PDF
NHSB-C3-2.pdf PDF
final main site - gen device eval.pdf PDF
GHSB-AG-1.pdf PDF
Electrical Directive 1028 D 2020-02-24.pdf PDF
GHTA-CB-2.pdf PDF
final remote - util device eval.pdf PDF
ArcFlash - Atlanta Main Site Final.xls XLS spreadsheet
Attachment A - Main Campus Equipment Schedule - REV19.1.xlsx XLSX spreadsheet
ArcFlash - Atlanta Remote Sites Final.xls XLS spreadsheet
final remote - gen bus eval.pdf PDF
NSHB-CB-2.pdf PDF
NHSB-C3-1 Fast Transfer.pdf PDF
36C24727Q0044 0002.pdf PDF
7.7 Building System Assessment_Atlanta.xlsx XLSX spreadsheet
NHSB-C3-1.pdf PDF
Wage Determination 2015-4471.docx DOCX document
final main site - gen input report.pdf PDF
Switchgear ED.pdf PDF
final main site - gen results report.pdf PDF
final remote - util input report.pdf PDF
Atlanta VA Main Campus 2022 IR Report.pdf PDF
final main site - util results report.pdf PDF
36C24727Q0044 0001.pdf PDF
36C24727Q0044_1 36-Month Electrical Distribution Testing.docx DOCX document
Attachment D - Equipment and Test Matrix - REV19.docx DOCX document
Show 40 more

Latest 50 of 53 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

7.6. Facility Condition Assessment Update
The items listed below are to be added to the FCA Report by CFM.
Atlanta, GAAtlanta, GA VAMC
SystemBuildingRec NoConditionUseful LifeRemaining LifeFCA
RiskCorrection CostDescription
Primary Electrical System125D30-4$13,995$8,120.85125-BUS-L1A has burn marks inside the panel. Replace panel and breakers.
Primary Electrical System125D30-4$2,340$1,357.75125-BUS-TGEN-DISC has mixed fuses installed. Replace fuses.
Primary Electrical System125D30-4$560$325.00125-BUS-MCC3 has holes in the panel cover. Install panel blanks.
Primary Electrical System125D25-3$1,471$853.59125-CB-L2B-MAIN is not properly coordinated. Replace breaker.
Emergency Electrical System125D25-3$6,757$3,920.70125-ATS-2 is a 2 pole ATS feeding non-motor loads. Replace with 3 pole ATS to switch neutral.
Primary Electrical System128D25-3$1,115$647.19128-CB-LP2-MAIN is not properly coordinated. Replace breaker.
Primary Electrical System128D25-3$1,124$652.19128-CB-MDP-3 is not properly coordinated. Replace breaker.
Primary Electrical System128-30-4$7,726$4,483.31128-BUS-LP1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Primary Electrical System128-30-4$7,726$4,483.31128-BUS-LP2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical System129-25-4$7,726$4,483.31129-BUS-SB1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Primary Electrical System131-25-4$1,186$687.94131-CB-MDP-8 cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical System131-25-4$1,354$785.38131-BUS-SB1-1 cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical System131-25-4$1,354$785.38131-BUS-SB1-2 cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical System131-25-4$1,186$687.94131-CB-SB2-2 cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical System131-25-4$7,726$4,483.31131-BUS-SB2A cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemAD25-4$78$45.00A-BUS-GEN3PNL has a hole in the bottom from removed conduit. Install knockout plug to cover the hole
Emergency Electrical SystemAD25-4$78$45.00A-BUS-GEN5PNL has a hole in the bottom from removed conduit. Install knockout plug to cover the hole
Emergency Electrical SystemAD25-4$20,714$12,019.47A-BUS-NHP-A1-2 has a hole in the cover. Install new panel cover.
Primary Electrical SystemAD30-4$98,690$57,264.76A-BUS-ED has holes in the cover and has a dead trip unit. Replace trip unit and install panel blanks.
Emergency Electrical SystemAD25-3$6,218$3,608.24A-CB-CHD-AG-1-(1) is not properly coordinated. Replace breaker.
Emergency Electrical SystemAD25-3$1,941$1,126.35A-CB-HL-5A-277-2-(1) is not properly coordinated. Replace breaker.
Emergency Electrical SystemAD25-4$16,020$9,295.55A-CBL-CHD-AG-1-(1) is not properly sized. Install new conductors appropriately sized.
Emergency Electrical SystemAD25-4$2,434$1,412.52A-CBL-HL-5A-277-2-(1) is not properly sized. Install new conductors appropriately sized.
Emergency Electrical SystemAD25-4$7,726$4,483.31A-BUS-SLP-AG-1 is past its service life. Replace panel.
Emergency Electrical SystemAD25-4$7,726$4,483.31A-BUS-LGA SECT 2 is past its service life. Replace panel.
Emergency Electrical SystemAD25-4$13,995$8,120.85A-BUS-EHD-A4-1 is past its service life. Replace panel.
Emergency Electrical SystemAD25-4$2,340$1,357.75A-BUS-P11-DISC-1 contains mixed fuses. Replace all fuses with the same type.
Emergency Electrical SystemAD25-4$2,340$1,357.75A-BUS-P11-DISC-2 contains mixed fuses. Replace all fuses with the same type.
Emergency Electrical SystemAD25-4$2,340$1,357.75A-BUS-P12-DISC-1 contains mixed fuses. Replace all fuses with the same type.
Emergency Electrical SystemAD25-4$2,340$1,357.75A-BUS-P12-DISC-2 contains mixed fuses. Replace all fuses with the same type.
Emergency Electrical SystemAD25-4$2,340$1,357.75A-BUS-P10-DISC-1 contains mixed fuses. Replace all fuses with the same type.
Emergency Electrical SystemAD25-4$2,340$1,357.75A-BUS-P10-DISC-2 contains mixed fuses. Replace all fuses with the same type.
TransformerAD30-4$17,114$9,930.36A-XF-SX-AG-1 (TLGA) is past its service life. Replace transformer.
TransformerAD30-4$8,968$5,203.58A-XF-SX-AG-2 (T-LG) is past its service life. Replace transformer.
TransformerAD30-4$8,968$5,203.58A-XF-CX-AG-1 (T-EGA) is past its service life. Replace transformer.
TransformerAD30-3$333$193.04A-XF-NX-AG-4 has no grounding electrode. Install conductor in conduit to building steel.
TransformerAD30-4$8,968$5,203.58A-XF-NX-A1-2 is past its service life. Replace transformer.
TransformerAD30-4$8,968$5,203.58A-XF-NX-A1-5 is past its service life. Replace transformer.
TransformerAD30-4$8,968$5,203.58A-XF-EX-A1-1 is past its service life. Replace transformer.
TransformerAD30-4$8,968$5,203.58A-XF-SX-A2-1 is past its service life. Replace transformer.
TransformerAD30-4$34,856$20,225.37A-XF-NX-A3-2 is past its service life. Replace transformer.
TransformerAD30-4$8,968$5,203.58A-XF-SX-A5-1 is past its service life. Replace transformer.
Emergency Electrical SystemA-25-4$13,995$8,120.85A-BUS-EHDP-AB-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemA-25-4$16,891$9,800.86A-BUS-NHL-AG-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemA-25-4$13,995$8,120.85A-BUS-SHL-AG-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemA-25-4$1,471$853.59A-CB-CHD-AG-1-(3) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemA-25-4$1,342$778.94A-CB-EHDP-AB-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemA-25-4$1,471$853.59A-CB-NHL-A4-3-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemA-25-4$1,342$778.94A-CB-NHLP-AB-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemA-25-4$1,342$778.94A-CB-SHL-AG-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemA-25-4$1,342$778.94A-CB-SHL-AG-1-MAIN cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemAD25-3$66,255$38,444.66A-BUS-GHTA-AG-1 is 3-pole with no bypass isolation. Replace with a 4 pole ATS with a maintenance bypass.
Emergency Electrical SystemBD25-3$1,409$817.84B-CB-NHL-B2-1-MAIN is not properly coordinated. Replace breaker.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-CLP-BG-1 (LCGB1/2) is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-CLP-BG-1-2 (LCGB1/2) is past its service life. Replace panel.
Primary Electrical SystemBD30-4$13,995$8,120.85B-BUS-NHL-BG-2 (1PJ1) is past its service life. Replace panel.
Primary Electrical SystemBD30-4$13,995$8,120.85B-BUS-NLR-BG-1 (PPJ1) is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-SLP-BG-1 (LEGB) is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$13,995$8,120.85B-BUS-EHL-BG-1 is past its service life. Replace panel.
Primary Electrical SystemBD30-4$13,995$8,120.85B-BUS-NHL-B1-1 is past its service life. Replace panel.
Primary Electrical SystemBD30-4$7,726$4,483.31B-BUS-NLP-B1-3 is past its service life. Replace panel.
Primary Electrical SystemBD30-4$7,726$4,483.31B-BUS-NLP-B1-6 (PPG4) is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-CLP-B2-3 (E2D2) has holes in the cover. Install panel blanks.
Emergency Electrical SystemBD25-4$13,995$8,120.85B-BUS-NHL-B2-5 is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-CLP-BG-2 is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-NLP-B1-1 is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-NLP-B1-1-2 is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-NLP-B1-4 is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-NLP-B1-4-2 is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-NLP-B1-5 is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-NLP-B2-5 has holes in the cover. Install panel blanks.
Emergency Electrical SystemBD25-4$13,995$8,120.85B-BUS-NHL-BG-1 is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-NLP-BG-1-2 is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-NLP-BG-1-2-1 is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-NLP-B1-6 (PPG4) is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-NLP-B1-4-2 (PPG1/2) is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-NLP-B1-4-3 (PPG2/2) is past its service life. Replace panel.
Emergency Electrical SystemBD25-4$7,726$4,483.31B-BUS-NLP-B1-5 (PPG3) is past its service life. Replace panel.
TransformerBD30-4$9,879$5,732.26B-XF-CX-B2-4 (T-E2D2) is past its service life. Replace transformer.
TransformerBD30-3$644$373.54B-XF-NX-P2-2 (a.k.a B-XF-T-LN2B2) has no neutral ground bond. Install a N-G bond in the transformer.
Emergency Electrical SystemB-25-4$16,891$9,800.86B-BUS-CHD-BG-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemB-25-4$13,995$8,120.85B-BUS-NHL-BG-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemB-25-4$1,343$779.23B-CB-CHD-BG-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemB-25-4$1,343$779.23B-CB-CHD-BG-1-(2) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemB-25-4$1,296$751.77B-CB-CHD-BG-1-(3) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemB-25-4$1,343$779.23B-CB-CHD-BG-1-(5) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemB-25-4$1,296$751.77B-CB-CHD-BG-1-(6) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemB-25-4$1,343$779.23B-CB-CHD-BG-1-(7) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemB-25-4$1,343$779.23B-CB-NHL-BG-2-MAIN cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Primary Electrical SystemCD30-4$11,000,000Main Bus Duct distribution to Building C is in poor condition. Estimated cost is based on replacement and was provided by the site
Primary Electrical SystemCD30-4$7,726$4,483.31C-BUS-ELP-C3-4 (3MLX) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$13,995$8,120.85C-BUS-EHL-C3-1 (3HX) is past its service life. Replace panel and breakers.
Primary Electrical SystemCD30-4$7,726$4,483.31C-BUS-NLP-CB-1 (BLD) is past its service life. Replace panel and breakers.
Primary Electrical SystemCD30-4$213$123.60C-BUS-NX-C13-2 DISCONNECT PRIMARY has broken conduit feeding it. Replace conduit to prevent water from entering enclosure.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-ELP-C12-1 (12LXA) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$13,995$8,120.85C-BUS-NHL-C11-3 (11HA) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-NLP-C11-7 (11LXA) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-NLP-C11-8 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$13,995$8,120.85C-BUS-NHL-C11-4 (11HB) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-NLP-C11-4 (11LB) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$13,995$8,120.85C-BUS-NHL-C6-4 (6HB) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-ELP-C6-2 (6LXB) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-NLP-C6-4 (6LB) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$13,995$8,120.85C-BUS-NHL-C6-3 (6HA) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-ELP-C6-1 (6LXA) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-NLP-C5-6-2 (5LB) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$13,995$8,120.85C-BUS-NHL-C5-4 (5HB) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-NLP-C5-5 (5LA) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$14,828$8,603.78C-BUS-NLP-C5-3 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$13,995$8,120.85C-BUS-NHL-C5-3 (5HA) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-NLP-C5-7 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-NLP-C4-4 (4LB) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$13,995$8,120.85C-BUS-NHL-C4-3 (4HA) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-NLP-C4-3 (4LA) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-ELP-CB-4 (BX) is past its service life. Replace panel and breakers.
Primary Electrical SystemCD25-4$7,726$4,483.31C-BUS-NLP-C3-1

(3LB) is past its service life. Replace panel and breakers.

Emergency Electrical System C D 25 - 4 $7,726 $4,483.31 C-BUS-ELP-C3-3 (3LXB) is past its service life. Replace panel and breakers.

Emergency Electrical System C D 25 - 4 $7,726 $4,483.31 C-BUS-ELP-C3-1 (3LXA) is past its service life. Replace panel and breakers.

Emergency Electrical System C D 25 - 4 $7,726 $4,483.31 C-BUS-ELP-C3-2 (3LXA-2) is past its service life. Replace panel and breakers.

Emergency Electrical SystemCD25-4$13,995$8,120.85C-BUS-EHL-C13-2 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-ELP-C13-4 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$16,891$9,800.86C-BUS-EHL-C13-5 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$14,828$8,603.78C-BUS-NLP-C11-5 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-NLP-C11-3 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-ELP-C12-2 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-NLP-C12-2 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$13,995$8,120.85C-BUS-NHL-C12-2 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$13,995$8,120.85C-BUS-CHL-C6-2 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$13,995$8,120.85C-BUS-CHL-C6-1 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-NLP-C6-3 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-NLP-C5-6 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$14,828$8,603.78C-BUS-NLP-C5-4 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$13,995$8,120.85C-BUS-NHL-C4-4 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$13,995$8,120.85C-BUS-EHL-C13-4 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$7,726$4,483.31C-BUS-ELP-C13-2 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-3$164$95.00C-BUS-CLP-C2-3 has missing panel blanks. Install new panel planks.
Primary Electrical SystemCD30-4$13,995$8,120.85C-BUS-NHL-C2-1 is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-3$164$95.00C-BUS-ELP-CG-12 has missing panel blanks. Install new panel blanks.
TransformerCD30-4$23,644$13,719.55C-XF-EX-C3-4 (T-3MLX) is past its service life. Replace transformer.
TransformerCD30-4$16,203$9,401.68C-XF-EX-C3-1 (T-3LXA) is past its service life. Replace transformer.
TransformerCD30-4$30,443$17,664.65C-XF-NX-C11-2 (T-11PLB) is past its service life. Replace transformer.
TransformerCD30-4$30,443$17,664.65C-XF-NX-C5-4 (T-5PLB) is past its service life. Replace transformer.
TransformerCD30-4$30,443$17,664.65C-XF-NX-C5-3 (T-5PLA) is past its service life. Replace transformer.
TransformerCD30-4$13,670$7,931.86C-XF-NX-C3-1 (T-3LB) is past its service life. Replace transformer.
TransformerCD30-4$927$537.80C-XF-NX-C1-3 (T-LN14) has no GEC or N-G bond installed. Install new conductors for GEC and N-G bond.
TransformerCD30-4$9,879$5,732.26C-XF-SX-CG-2 is past its service life. Replace transformer.
TransformerCD30-4$9,879$5,732.26C-XF-EX-C13-4

(T-EMMR) is past its service life. Replace transformer.

Transformer C D 30 - 4 $30,443 $17,664.65 C-XF-NX-C11-1 (T-11PLA) is past its service life. Replace transformer.

TransformerCD30-4$9,879$5,732.26C-XF-EX-C13-2 is past its service life. Replace transformer.
Emergency Electrical SystemCD25-4$16,891$9,800.86C-BUS-NLP-C11-6 (11PLB) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-4$16,891$9,800.86C-BUS-EHL-C13-1 (MCC-2) is past its service life. Replace panel and breakers.
Emergency Electrical SystemCD25-3$1,342$778.94C-CB-EHL-CB-1-(4) is not properly coordinated. Replace existing breaker.
Emergency Electrical SystemCD25-3$1,401$812.84C-CB-NHD-C13-1-(1) is not properly coordinated. Replace existing breaker.
Emergency Electrical SystemCD25-3$1,471$853.59C-CB-NLP-C7-3-MAIN is not properly coordinated. Replace existing breaker.
Emergency Electrical SystemCD25-4$18,646$10,819.60C-CBL-EHD-CG-2-(2) is not properly sized. Install new conductors appropriately sized.
Emergency Electrical SystemCD25-4$1,462$848.60C-CBL-EHL-CB-1-(4) is not properly sized. Install new conductors appropriately sized.
Emergency Electrical SystemC-25-4$13,995$8,120.85C-BUS-NHL-C4-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$16,891$9,800.86C-BUS-NHL-C4-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$16,891$9,800.86C-BUS-NHL-C5-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$16,891$9,800.86C-BUS-NHL-C6-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$16,891$9,800.86C-BUS-NHL-C8-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$13,995$8,120.85C-BUS-CHL-C6-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$13,995$8,120.85C-BUS-EHL-C3-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$13,995$8,120.85C-BUS-EHL-CG-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$13,995$8,120.85C-BUS-CHL-C6-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$13,995$8,120.85C-BUS-EHL-C3-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$13,995$8,120.85C-BUS-NHL-C4-3 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$13,995$8,120.85C-BUS-NHL-C4-4 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$13,995$8,120.85C-BUS-NHL-C5-3 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$13,995$8,120.85C-BUS-NHL-C5-4 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$13,995$8,120.85C-BUS-NHL-C6-3 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$16,891$9,800.86C-BUS-NHL-CB-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$13,995$8,120.85C-BUS-NHL-CG-4 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$7,726$4,483.31C-BUS-NLP-C11-7 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$7,726$4,483.31C-BUS-NLP-C11-8 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$16,891$9,800.86C-BUS-CHL-C5-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$16,891$9,800.86C-BUS-CHL-C5-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemC-25-4$7,390$4,287.96C-CB-CHD-C3-1-(2) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,343$779.23C-CB-EHL-C3-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,343$779.23C-CB-EHL-C3-1-(2) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,471$853.59C-CB-EHL-CG-2-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$7,535$4,372.33C-CB-NHD-C1-1-(2) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$7,535$4,372.33C-CB-NHD-C1-1-(3) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$16,334$9,477.67C-CB-NHD-C1-1-MAIN cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$7,535$4,372.33C-CB-NHD-C1-2-(3) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,471$853.59C-CB-NHD-C1-2-(5) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,471$853.59C-CB-NHD-C1-2-(6) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$7,390$4,287.96C-CB-NHD-C1-2-(7) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$16,334$9,477.67C-CB-NHD-C1-2-MAIN cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,471$853.59C-CB-NHL-C2-3-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,343$779.23C-CB-NHL-C4-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,343$779.23C-CB-NHL-C4-2-(2) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,343$779.23C-CB-NHL-C5-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,471$853.59C-CB-NHL-C5-2-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,343$779.23C-CB-NHL-C6-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,471$853.59C-CB-NHL-C6-2-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,343$779.23C-CB-NHL-CB-2-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,471$853.59C-CB-NHL-CG-2-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,296$751.77C-CB-NHL-CG-4-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$1,186$687.94C-CB-NLD-CG-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemC-25-4$991$575.00C-CB-NHD-C13-1-MAIN has a ground fault trip unit, but is on the secondary side of an ATS. Replace trip unit.
Emergency Electrical SystemC-25-4$12,600$7,311.08C-CB-NHD- C3-3-MAIN has a ground fault trip unit, but is on the secondary side of an ATS. Replace circuit breaker.
Emergency Electrical SystemCD25-3$58,921$34,189.06C-BUS-GHTA-CB-1 is 3-pole with no bypass isolation. Replace with a 4 pole ATS with a maintenance bypass.
Emergency Electrical SystemCD25-3$58,921$34,189.06C-BUS-GHTA-CB-2 is 3-pole with no bypass isolation. Replace with a 4 pole ATS with a maintenance bypass.
Emergency Electrical SystemDD25-4$13,995$8,120.85D-BUS-NHL-DB-1 (NHBA) is past its service life. Replace panel and breakers.
Emergency Electrical SystemDD25-4$13,995$8,120.85D-BUS-NHL-D2-1 (NH2A) is past its service life. Replace panel and breakers.
Emergency Electrical SystemDD25-4$7,726$4,483.31D-BUS-ELP-D2-2 (EL2B) is past its service life. Replace panel and breakers.
Emergency Electrical SystemDD25-4$13,995$8,120.85D-BUS-SHL-D2-1 (MH2A) is past its service life. Replace panel and breakers.
Emergency Electrical SystemDD25-4$7,726$4,483.31D-BUS-ELP-D2-1 (EL2A) is past its service life. Replace panel and breakers.
Emergency Electrical SystemDD25-4$7,726$4,483.31D-BUS-NLP-D2-1 (NL2A) is past its service life. Replace panel and breakers.
Emergency Electrical SystemDD25-4$13,995$8,120.85D-BUS-NHL-D3-1 (NH3A) is past its service life. Replace panel and breakers.
Emergency Electrical SystemDD25-4$7,726$4,483.31D-BUS-ELP-D3-2 (ELSB) is past its service life. Replace panel and breakers.
Emergency Electrical SystemDD25-4$13,995$8,120.85D-BUS-SHL-D3-1 (MH3A) is past its service life. Replace panel and breakers.
Emergency Electrical SystemDD25-4$7,726$4,483.31D-BUS-ELP-D3-1 (EL3A) is past its service life. Replace panel and breakers.
Emergency Electrical SystemDD25-4$7,726$4,483.31D-BUS-NLP-D3-1 (NL3A) is past its service life. Replace panel and breakers.
Emergency Electrical SystemDD25-4$7,726$4,483.31D-BUS-NLP-D1-3 is past its service life. Replace panel and breakers.
Emergency Electrical SystemDD25-4$7,726$4,483.31D-BUS-NLP-D2-2 is past its service life. Replace panel and breakers.
Emergency Electrical SystemDD25-4$7,726$4,483.31D-BUS-NLP-D3-2 is past its service life. Replace panel and breakers.
TransformerDD30-4$9,879$5,732.26D-XF-NX-DB-1 (T-NLBA) is past its service life. Replace transformer.
TransformerDD30-4$9,879$5,732.26D-XF-SX-DB-1 (T-MLBA) is past its service life. Replace transformer.
TransformerDD30-4$13,670$7,931.86D-XF-EX-DB-1

(T-ELBA) is past its service life. Replace transformer.

TransformerDD30-3$563$326.44D-XF-T-B1O has no GEC. Install new conductor for GEC.
TransformerDD30-4$16,203$9,401.68D-XF-NX-D1-1

(T-NL1A) is past its service life. Replace transformer.

Transformer D D 30 - 4 $16,203 $9,401.68 D-XF-NX-D1-4 (T-NLB1) is past its service life. Replace transformer.

Transformer D D 30 - 4 $13,670 $7,931.86 D-XF-NX-D1-3 (T-NL1B) is past its service life. Replace transformer.

Transformer D D 30 - 4 $16,203 $9,401.68 D-XF-NX-D2-2 (T-NL2B) is past its service life. Replace transformer.

Transformer D D 30 - 4 $16,203 $9,401.68 D-XF-EX-D2-2 (T-EL2B) is past its service life. Replace transformer.

Transformer D D 30 - 4 $16,203 $9,401.68 D-XF-EX-D2-1 (T-EL2A) is past its service life. Replace transformer.

Transformer D D 30 - 4 $16,203 $9,401.68 D-XF-NX-D2-1 (T-NL2A) is past its service life. Replace transformer.

Transformer D D 30 - 4 $16,203 $9,401.68 D-XF-NX-D3-2 (T-NL3B) is past its service life. Replace transformer.

Transformer D D 30 - 4 $16,203 $9,401.68 D-XF-EX-D3-1 (T-NL3A) is past its service life. Replace transformer.

Emergency Electrical SystemDD25-4$16,096$9,339.80D-BUS-NHD-DB-2 (1) is missing pieces of the panel. Replace panelboard.
Emergency Electrical SystemD-25-4$29,432$17,078.07D-BUS-NHD-DB-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemD-25-4$21,870$12,690.06D-BUS-NHD-DB-2-2 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemD-25-4$13,995$8,120.85D-BUS-NHL-D1-1 cannot withstand the interrupt current. Replace device/panel to pass equipment evaluation.
Emergency Electrical SystemD-25-4$1,354$785.38D-CB-NHD-DB-2-(2) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemD-25-4$1,471$853.59D-CB-NHD-DB-2-2-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemD-25-4$1,471$853.59D-CB-NHL-D1-1-(1) cannot withstand the interrupt current. Replace breaker to pass equipment evaluation.
Emergency Electrical SystemMD25-4$14,828$8,603.78M-BUS-F has a split phase feed serving a 3 phase panel with one phase jumpered onto the third phase. Replace panel with a 120/240V split phase panel.
Emergency Electrical SystemMD25-4$14,828$8,603.78M-BUS-D has a split phase feed serving a 3 phase panel with phase 1 jumpered onto phase 2. Replace panel with a 120/240V split phase panel.
Emergency Electrical SystemMD25-4$14,828$8,603.78M-BUS-B has a split phase feed serving a 3 phase panel with phase 1 jumpered onto phase 2. Replace panel with a 120/240V split phase panel.
Emergency Electrical SystemParking DecksD25-3$164$95.00PD-BUS-NLP-SG-1 has a missing panel blank. Install panel blank.
Emergency Electrical SystemParking DecksD25-3$164$95.00F-BUS-T3 has a missing panel blank. Install panel blank.
Emergency Electrical SystemParking DecksD25-4$991$575.00PD-BUS-NHL-SG-1 is missing a panel cover. Install a panel cover.
TransformerParking DecksD30-3$333$193.04E-XF-EX-L1-1 has no grounding electrode. Install new grounding electrode.
Emergency Electrical SystemParking DecksD25-4$22,332$12,958.44F-BUS-NHDP-LG-1 is past its service life. Replace panel.
Emergency Electrical SystemTDD25-3$16,366$9,496.20TD-ATS1 is a 3 pole ATS but should be a 4 pole ATS with maintenance bypass. Replace ATS to meet requirement.
Emergency Electrical SystemTDD25-3$16,366$9,496.20TD-ATS2 is a 3 pole ATS but should be a 4 pole ATS with maintenance bypass. Replace ATS to meet requirement.
Emergency Electrical SystemTDD25-3$16,366$9,496.20TD-ATS3 is a 3 pole ATS but should be a 4 pole ATS with maintenance bypass. Replace ATS to meet requirement.
Emergency Electrical SystemTDD25-3$16,366$9,496.20TD-ATS4 is a 3 pole ATS but should be a 4 pole ATS with maintenance bypass. Replace ATS to meet requirement.
Primary Electrical SystemTDD25-3$1,354$785.38TD-CB-EGHA-2 is not properly coordinated. Replace breaker.
Primary Electrical SystemTDD25-3$1,342$778.94TD-CB-EGLA-MAIN is not properly coordinated. Replace breaker.