Existing-Recommended Breaker Settings - Final.xlsx
XLSX spreadsheet 65 KB Posted
- Attached to
- 36-Month Electrical Distribution Testing
- Solicitation number
- 36C24727Q0044
About this file
This file is a circuit breaker settings reference document for the Atlanta Veterans Affairs Medical Center (VAMC), detailing existing and recommended electrical safety configurations across multiple buildings and facilities.
The document provides comprehensive breaker settings data for six main campus buildings (A through F), two McPherson buildings (125, 128-131), a Trinka Davis facility, and a T13 building. For each breaker location, it specifies manufacturer, model, frame size (in amps), trip settings, and multiple protective parameters including Long-Term Pickup (LTPU), Long-Term Delay (LTD), Short-Term Pickup (STPU), Short-Term Delay (STD), Instantaneous (INST), Ground Fault Pickup (GFPU), and Ground Fault Delay (GFD). The document includes three comparative categories: existing settings, recommended settings, and sections for other recommended changes, replacements, and cable replacements. Primary manufacturers represented include Cutler-Hammer, GE, Square D, Eaton, Challenger, and Siemens across various breaker models. The recommendations indicate adjustments to protective parameters aimed at improving electrical safety and coordination, with specific focus on ground fault protection settings. Cable replacements range from 10 AWG to 500 KCMIL, and breaker replacements typically involve upgrading to higher amperage ratings or different breaker types suited to specific circuit requirements. This reference material appears designed to support the 36-month electrical distribution testing contract (36C24727Q0044) with the VA's Veterans Integrated Service Network 7, providing baseline and target specifications for electrical system upgrades and testing protocols.
View the file
Other files
Show 40 more
Latest 50 of 53 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BREAKER SETTINGS
| MAIN CAMPUS - BUILDING A | |||||||||||||||||||
| EXISTING SETTINGS | RECOMMENDED SETTINGS | ||||||||||||||||||
| BREAKER | MANUFACTURER | MODEL | FRAME SIZE (AMPS) | TRIP (AMPS) | LTPU | LTD | STPU | STD | INST | GFPU | GFD | LTPU | LTD | STPU | STD | INST | GFPU | GFD | |
| GHSB-AG-1 | GHSB-AG-1-(1) | CUTLER-HAMMER | Magnum DS, DT 520 | 3200 | 3200 | 1 | 2 | 2 | 0.2 (I^s T Off) | 4 | - | - | 0.8 | 2 | 2 | 0.2 (I^s T Off) | 2 | - | - |
| GHSB-AG-1-(10) | CUTLER-HAMMER | Magnum DS, DT 520 | 3200 | 3200 | 0.95 | 2 | 2 | 0.1 (I^s T Off) | 4 | - | - | 0.7 | 2 | 2 | 0.1 (I^s T Off) | 4 | - | - | |
| GHSB-AG-1-(2) | CUTLER-HAMMER | Magnum DS, DT 520 | 1600 | 1600 | 1 | 7 | 4 | 0.2 (I^s T Off) | 8 | - | - | 1 | 7 | 4 | 0.2 (I^s T Off) | 8 | - | - | |
| GHSB-AG-1-(3) | CUTLER-HAMMER | Magnum DS, DT 520 | 3200 | 3200 | 1 | 7 | 10 | 0.3 (I^s T Off) | 3200A M1 | - | - | 0.8 | 2 | 2 | 0.1 (I^s T Off) | 4 | - | - | |
| GHSB-AG-1-(4) | CUTLER-HAMMER | Magnum DS, DT 520 | 1600 | 1600 | 1 | 7 | 3 | 0.2 (I^s T Off) | 8 | - | - | 1 | 7 | 3 | 0.2 (I^s T Off) | 8 | - | - | |
| GHSB-AG-1-(5) | CUTLER-HAMMER | Magnum DS, DT 520 | 800 | 400 | 0.5 | 24 | 8 | 0.1 (I^s T Off) | 8 | - | - | 0.5 | 24 | 8 | 0.1 (I^s T Off) | 8 | - | - | |
| GHSB-AG-1-(6) | CUTLER-HAMMER | Magnum DS, DT 520 | 3200 | 3200 | 0.8 | 2 | 2 | 0.2 (I^s T Off) | 3 | - | - | 0.8 | 2 | 2 | 0.2 (I^s T Off) | 3 | - | - | |
| GHSB-AG-1-(7) | CUTLER-HAMMER | Magnum DS, DT 520 | 3200 | 3200 | 1 | 2 | 2 | 0.2 (I^s T Off) | 4 | - | - | 0.8 | 2 | 2 | 0.2 (I^s T Off) | 4 | - | - | |
| GHSB-AG-1-(8) | CUTLER-HAMMER | Magnum DS, DT 520 | 1600 | 1000 | 1 | 2 | 2 | 0.3 (I^s T Off) | 2 | - | - | 1 | 2 | 2 | 0.3 (I^s T Off) | 2 | - | - | |
| GHSB-AG-1-(9) | CUTLER-HAMMER | Magnum DS, DT 520 | 3200 | 2500 | 0.8 | 2 | 2 | 0.3 (I^s T Off) | 4 | - | - | 0.8 | 2 | 2.5 | 0.3 (I^s T Off) | 4 | - | - | |
| GHSB-AG-1-MAIN-(1) | CUTLER-HAMMER | Magnum DS, DT 520 | 3200 | 3200 | 1 | 2 | 2 | 0.5 (I^s T On) | 6 | - | - | 1 | 15 | 4 | 0.5 (I^s T On) | 10 | - | - | |
| GHSB-AG-1-MAIN-(2) | CUTLER-HAMMER | Magnum DS, DT 520 | 3200 | 3200 | 1 | 2 | 2 | 0.5 (I^s T Off) | 6 | - | - | 1 | 15 | 4 | 0.5 (I^s T Off) | 10 | - | - | |
| GHSB-AG-1-MAIN-(3) | CUTLER-HAMMER | Magnum DS, DT 520 | 3200 | 3200 | 1 | 2 | 2 | 0.5 (I^s T Off) | 6 | - | - | 1 | 15 | 4 | 0.5 (I^s T Off) | 10 | - | - | |
| GHSB-AG-2 | GHSB-AG-2-(1) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800 | 800 | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 1 | 10 | 6 | 0.2 (I^s T Off) | 5 | - | - |
| GHSB-AG-2-(1)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800 | 800 | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | |
| GHSB-AG-2-(2) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800 | 800 | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 1 | 7 | 4 | 0.1 (I^s T Off) | 4 | - | - | |
| GHSB-AG-2-(2)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800 | 800 | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | |
| GHSB-AG-2-(3) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800 | 800 | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 1 | 7 | 4 | 0.1 (I^s T Off) | 4 | - | - | |
| GHSB-AG-2-(3)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800 | 800 | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | |
| GHSB-AG-2-(4) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800 | 800 | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 1 | 7 | 4 | 0.1 (I^s T Off) | 4 | - | - | |
| GHSB-AG-2-(4)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800 | 800 | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | |
| GHSB-AG-2-(5) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800 | 250 | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 1 | 7 | 4 | 0.1 (I^s T Off) | 4 | - | - | |
| GHSB-AG-2-(5)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800 | 250 | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | |
| GHSB-AG-2-(6) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800 | 250 | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 1 | 7 | 4 | 0.1 (I^s T Off) | 4 | - | - | |
| GHSB-AG-2-(6)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800 | 250 | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | |
| SWBD-C | SWBD-C-(1) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 3 | 4 | Min (I^s T On) | 15 | - | - | 1 | 3 | 4 | Min (I^s T On) | 15 | - | - |
| SWBD-C-(1)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.5 | Min (I^s T On) | - | - | - | - | - | 0.5 | Min (I^s T On) | |
| SWBD-C-(10) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 4 | 4 | Min (I^s T On) | 15 | - | - | 0.7 | 2 | 4 | Min (I^s T On) | 15 | - | - | |
| SWBD-C-(10)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.2 | Min (I^s T On) | - | - | - | - | - | 0.2 | Min (I^s T On) | |
| SWBD-C-(11) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 4 | 4 | Int (I^s T On) | 10 | - | - | 1 | 4 | 4 | Int (I^s T On) | 10 | - | - | |
| SWBD-C-(11)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.25 | Min (I^s T On) | - | - | - | - | - | 0.25 | Min (I^s T On) | |
| SWBD-C-(12) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 4 | 4 | Min (I^s T On) | 15 | - | - | 1 | 4 | 5 | Min (I^s T On) | 15 | - | - | |
| SWBD-C-(12)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.2 | Min (I^s T On) | - | - | - | - | - | 0.2 | Min (I^s T On) | |
| SWBD-C-(13) | GE | AKR, MVT Plus/PM | 800 | 800 | 0.75 | 4 | 5 | Max (I^s T Off) | 10 | - | - | 0.75 | 4 | 5 | Min (I^s T Off) | 10 | - | - | |
| SWBD-C-(13)-GF | GE | AKR, MVT Plus/PM | 800 | 800 | - | - | - | - | - | 0.3 | Max (I^s T On) | - | - | - | - | - | 0.3 | Min (I^s T On) | |
| SWBD-C-(14) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 4 | 9 | Int (I^s T On) | 15 | - | - | 1 | 4 | 5 | Min (I^s T On) | 15 | - | - | |
| SWBD-C-(14)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.2 | Min (I^s T On) | - | - | - | - | - | 0.2 | Min (I^s T On) | |
| SWBD-C-(15) | GE | AKR, MVT Plus/PM | 800 | 800 | 1 | 4 | 6.5 | Max (I^s T Off) | 7.5 | - | - | 1 | 4 | 4.5 | Min (I^s T Off) | 7.5 | - | - | |
| SWBD-C-(15)-GF | GE | AKR, MVT Plus/PM | 800 | 800 | - | - | - | - | - | 0.3 | Max (I^s T Off) | - | - | - | - | - | 0.3 | Min (I^s T Off) | |
| SWBD-C-(16) | GE | AKR, MVT RMS-9 | 2000 | 2000 | 0.8 | 4 | 4 | Min (I^s T On) | 10 | - | - | 0.8 | 1 | 1.5 | Min (I^s T On) | 1.5 | - | - | |
| SWBD-C-(16)-GF | GE | AKR, MVT RMS-9 | 2000 | 2000 | - | - | - | - | - | 0.35 | Min (I^s T Off) | - | - | - | - | - | 0.25 | Min (I^s T Off) | |
| SWBD-C-(2) | GE | AKR, MVT RMS-9 | 800 | 800 | 0.7 | 3 | 5 | Min (I^s T On) | 15 | - | - | 0.7 | 3 | 5 | Min (I^s T On) | 15 | - | - | |
| SWBD-C-(2)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.2 | Max (I^s T On) | - | - | - | - | - | 0.2 | Min (I^s T On) | |
| SWBD-C-(3) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 2 | 5 | Min (I^s T On) | 15 | - | - | 1 | 2 | 5 | Min (I^s T On) | 15 | - | - | |
| SWBD-C-(3)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.3 | Min (I^s T On) | - | - | - | - | - | 0.3 | Min (I^s T On) | |
| SWBD-C-(4) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 4 | 9 | Min (I^s T On) | 15 | - | - | 1 | 4 | 7 | Min (I^s T On) | 15 | - | - | |
| SWBD-C-(4)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.5 | Min (I^s T On) | - | - | - | - | - | 0.5 | Min (I^s T On) | |
| SWBD-C-(5) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 4 | 9 | Min (I^s T On) | 15 | - | - | 1 | 4 | 5 | Min (I^s T On) | 15 | - | - | |
| SWBD-C-(5)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.5 | Min (I^s T On) | - | - | - | - | - | 0.5 | Min (I^s T On) | |
| SWBD-C-(6) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 4 | 7 | Min (I^s T On) | 15 | - | - | 1 | 3 | 3 | Min (I^s T On) | 3 | - | - | |
| SWBD-C-(6)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.5 | Min (I^s T On) | - | - | - | - | - | 0.5 | Min (I^s T On) | |
| SWBD-C-(7) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 4 | 9 | Min (I^s T On) | 15 | - | - | 1 | 4 | 5 | Min (I^s T On) | 15 | - | - | |
| SWBD-C-(7)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.2 | Min (I^s T On) | - | - | - | - | - | 0.2 | Min (I^s T On) | |
| SWBD-C-(8) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 4 | 9 | Min (I^s T On) | 15 | - | - | 1 | 4 | 7 | Min (I^s T On) | 15 | - | - | |
| SWBD-C-(8)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.25 | Min (I^s T On) | - | - | - | - | - | 0.25 | Min (I^s T On) | |
| SWBD-C-(9) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 4 | 7 | Max (I^s T On) | 15 | - | - | 1 | 3 | 3 | Min (I^s T On) | 3 | - | - | |
| SWBD-C-(9)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.25 | Min (I^s T On) | - | - | - | - | - | 0.25 | Min (I^s T On) | |
| SWBD-C-MAIN | GE | AKR, MVT RMS-9 | 4000 | 4000 | 1 | 4 | 4 | Int (I^s T On) | - | - | - | 0.6 | 1 | 1.5 | Min (I^s T On) | - | - | - | |
| SWBD-C-MAIN-GF | GE | AKR, MVT RMS-9 | 4000 | 4000 | - | - | - | - | - | 0.2 | Int (I^s T On) | - | - | - | - | - | 0.2 | Int (I^s T On) | |
| ED | ED-(1) | GE | AKR, MVT RMS-9 | 800 | 400 | 0.7 | 4 | 9 | Max (I^s T Off) | 15 | - | - | 0.7 | 4 | 9 | Max (I^s T Off) | 15 | - | - |
| ED-(1)-GF | GE | AKR, MVT RMS-9 | 800 | 400 | - | - | - | - | - | 0.4 | Min (I^s T Off) | - | - | - | - | - | 0.4 | Min (I^s T Off) | |
| ED-(2) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 4 | 5 | Int (I^s T On) | 10 | - | - | 1 | 4 | 5 | Int (I^s T On) | 10 | - | - | |
| ED-(2)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.25 | Max (I^s T On) | - | - | - | - | - | 0.25 | Min (I^s T On) | |
| ED-(3) | GE | AKR, MVT RMS-9 | 800 | 400 | 1 | 4 | 9 | Int (I^s T On) | 13 | - | - | 1 | 4 | 9 | Int (I^s T On) | 13 | - | - | |
| ED-(3)-GF | GE | AKR, MVT RMS-9 | 800 | 400 | - | - | - | - | - | 0.4 | Min (I^s T On) | - | - | - | - | - | 0.4 | Min (I^s T On) | |
| ED-(4) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 4 | 5 | Int (I^s T On) | 10 | - | - | 1 | 4 | 5 | Int (I^s T On) | 10 | - | - | |
| ED-(4)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.3 | Max (I^s T On) | - | - | - | - | - | 0.3 | Min (I^s T On) | |
| ED-(5) | GE | AKR, MVT Plus/PM | 800 | 800 | 1.1 | 4 | 8 | Max (I^s T Off) | 12.5 | - | - | 1.1 | 4 | 8 | Max (I^s T Off) | 12.5 | - | - | |
| ED-(6) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 4 | 5 | Int (I^s T On) | 10 | - | - | 1 | 4 | 5 | Int (I^s T On) | 10 | - | - | |
| ED-(6)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.25 | Min (I^s T On) | - | - | - | - | - | 0.25 | Min (I^s T On) | |
| ED-(7) | GE | AKR, MVT RMS-9 | 800 | 800 | 1 | 4 | 5 | Int (I^s T On) | 10 | - | - | 1 | 4 | 5 | Int (I^s T On) | 10 | - | - | |
| ED-(7)-GF | GE | AKR, MVT RMS-9 | 800 | 800 | - | - | - | - | - | 0.25 | Int (I^s T On) | - | - | - | - | - | 0.25 | Min (I^s T On) | |
| ED-MAIN | GE | AKR, MVT Plus/PM (RMS-9C) | 4000 | 4000 | 1 | 4 | 3 | Max (I^s T On) | - | - | - | 1 | 4 | 3 | Max (I^s T On) | - | - | - | |
| ED-MAIN-GF | GE | AKR, MVT Plus/PM (RMS-9C) | 4000 | 4000 | - | - | - | - | - | 0.25 | Int (I^s T On) | - | - | - | - | - | 0.25 | Max (I^s T On) | |
| GHSB-CB-1 | GHSB-CB-1-(1) | CUTLER-HAMMER | Magnum SB, DT 1150/1150i | 3000 | 3000 | 0.95 | 2 | 8 | 0.3 (I^s T Off) | 2 | - | - | 0.75 | 2 | 2 | 0.15 (I^s T Off) | 2 | - | - |
| GHSB-CB-1-(2) | CUTLER-HAMMER | Magnum SB, DT 1150/1150i | 800 | 250 | 1 | 24 | 6 | 0.1 (I^s T Off) | M1(14x) | - | - | 1 | 24 | 6 | 0.1 (I^s T Off) | M1(14x) | - | - | |
| GHSB-CB-1-(3) | CUTLER-HAMMER | Magnum SB, DT 1150/1150i | 800 | 800 | 0.4 | 2 | 2 | 0.3 (I^s T Off) | 2 | - | - | 0.45 | 2 | 2 | 0.3 (I^s T Off) | 2 | - | - | |
| GHSB-CB-1-(4) | CUTLER-HAMMER | Magnum SB, DT 1150/1150i | 4000 | 4000 | 0.7 | 2 | 2.5 | 0.1 (I^s T Off) | 3 | - | - | 0.6 | 3 | 2 | 0.1 (I^s T Off) | 3 | - | - | |
| GHSB-CB-1-(5) | CUTLER-HAMMER | Magnum SB, DT 1150/1150i | 800 | 800 | 0.4 | 2 | 2 | 0.2 (I^s T Off) | 2 | - | - | 0.4 | 2 | 2 | 0.2 (I^s T Off) | 2 | - | - | |
| GHSB-CB-1-(6) | CUTLER-HAMMER | Magnum SB, DT 1150/1150i | 800 | 800 | 1 | 10 | 4 | 0.3 (I^s T Off) | M1(14x) | - | - | 1 | 10 | 4 | 0.15 (I^s T Off) | M1(14x) | - | - | |
| GHSB-CB-1-(7) | CUTLER-HAMMER | Magnum SB, DT 1150/1150i | 800 | 400 | 1 | 4 | 4 | 0.1 (I^s T Off) | 10 | - | - | 1 | 4 | 4 | 0.1 (I^s T Off) | 10 | - | - | |
| GHSB-CB-1-(8) | CUTLER-HAMMER | Magnum SB, DT 1150/1150i | 2000 | 2000 | 1 | 24 | 6 | 0.5 (I^s T Off) | 3 | - | - | 1 | 5 | 6 | 0.5 (I^s T Off) | 2 | - | - | |
| GHSB-CB-1-MAIN-(1) | CUTLER-HAMMER | Magnum SB, DT 1150/1150i | 3000 | 3000 | 0.9 | 4 | 2 | 0.2 (I^s T Off) | 3 | - | - | 0.9 | 4 | 2 | 0.2 (I^s T Off) | 3 | - | - | |
| GHSB-CB-1-MAIN-(2) | CUTLER-HAMMER | Magnum SB, DT 1150/1150i | 3000 | 3000 | 0.9 | 4 | 2 | 0.2 (I^s T Off) | 3 | - | - | 0.9 | 4 | 2 | 0.2 (I^s T Off) | 3 | - | - |
| MAIN CAMPUS - BUILDING B | |||||||||||||||||||
| EXISTING SETTINGS | RECOMMENDED SETTINGS | ||||||||||||||||||
| BREAKER | MANUFACTURER | MODEL | FRAME SIZE (AMPS) | TRIP (AMPS) | LTPU | LTD | STPU | STD | INST | GFPU | GFD | LTPU | LTD | STPU | STD | INST | GFPU | GFD | |
| NHSB-BG-1 | NHSB-BG-1-(1) | CUTLER-HAMMER | MDL, RMS 310 (06/07) | 800.0 | 800.0 | 800A | Fixed | 6 | 200 ms (I^s T Off) | Fixed | - | - | 800A | Fixed | 6 | 200 ms (I^s T Off) | Fixed | - | - |
| NHSB-BG-1-(10) | CUTLER-HAMMER | HKD, RMS 310 | 400.0 | 400.0 | 400A | Fixed | 8 | 100 ms (I^s T Off) | Fixed | - | - | 400A | Fixed | 8 | 100 ms (I^s T Off) | Fixed | - | - | |
| NHSB-BG-1-(11) | CUTLER-HAMMER | HKD, RMS 310 | 400.0 | 400.0 | 400A | Fixed | 8 | 100 ms (I^s T Off) | Fixed | - | - | 400A | Fixed | 8 | 100 ms (I^s T Off) | Fixed | - | - | |
| NHSB-BG-1-(12) | CUTLER-HAMMER | HKD, RMS 310 | 400.0 | 400.0 | 300A | Fixed | 8 | 300 ms (I^s T Off) | Fixed | - | - | 300A | Fixed | 8 | 300 ms (I^s T Off) | Fixed | - | - | |
| NHSB-BG-1-(13) | CUTLER-HAMMER | HKD, RMS 310 | 400.0 | 400.0 | 300A | Fixed | 8 | 300 ms (I^s T Off) | Fixed | - | - | 300A | Fixed | 8 | 300 ms (I^s T Off) | Fixed | - | - | |
| NHSB-BG-1-(14) | CUTLER-HAMMER | HKD, RMS 310 | 400.0 | 400.0 | 300A | Fixed | 8 | 100 ms (I^s T Off) | Fixed | - | - | 300A | Fixed | 8 | 100 ms (I^s T Off) | Fixed | - | - | |
| NHSB-BG-1-(15) | EATON | NG-Frame, 310+ | 1200.0 | 1200.0 | H | 2 | 2 | Inst | 12 | - | - | H | 2 | 2 | Inst | 12 | - | - | |
| NHSB-BG-1-(16) | CUTLER-HAMMER | LG, Series G | 630.0 | 600.0 | H | 2 | 2 | 120ms | 12 x In | - | - | H | 2 | 2 | 120ms | 12 x In | - | - | |
| NHSB-BG-1-(2) | CUTLER-HAMMER | HFD | 125.0 | 125.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHSB-BG-1-(3) | CUTLER-HAMMER | HFD | 150.0 | 150.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHSB-BG-1-(4) | CUTLER-HAMMER | HFD | 125.0 | 125.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHSB-BG-1-(5) | CUTLER-HAMMER | HFD | 125.0 | 125.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHSB-BG-1-(6) | CUTLER-HAMMER | HFD | 125.0 | 125.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHSB-BG-1-(7) | CUTLER-HAMMER | HFD | 150.0 | 150.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHSB-BG-1-(8) | CUTLER-HAMMER | HFD | 150.0 | 150.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHSB-BG-1-(9) | CUTLER-HAMMER | HFD | 150.0 | 150.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHSB-BG-1-GF-(1) | CUTLER-HAMMER | MDL, DT RMS 310 (06/07) | 800.0 | 800.0 | - | - | - | - | - | 3 x Ig | 300 ms (I^s T Off) | - | - | - | - | - | 3 x Ig | 150 ms (I^s T Off) | |
| NHSB-BG-1-GF-(10) | CUTLER-HAMMER | HKD, RMS 310 | 400.0 | 400.0 | - | - | - | - | - | 2 x Ig | 150 ms (I^s T Off) | - | - | - | - | - | 2 x Ig | 150 ms (I^s T Off) | |
| NHSB-BG-1-GF-(11) | CUTLER-HAMMER | HKD, RMS 310 | 400.0 | 400.0 | - | - | - | - | - | 5 x Ig | 150 ms (I^s T Off) | - | - | - | - | - | 5 x Ig | 150 ms (I^s T Off) | |
| NHSB-BG-1-GF-(12) | CUTLER-HAMMER | HKD, RMS 310 | 400.0 | 400.0 | - | - | - | - | - | 1 x Ig | 500 ms (I^s T Off) | - | - | - | - | - | 1 x Ig | 150 ms (I^s T Off) | |
| NHSB-BG-1-GF-(13) | CUTLER-HAMMER | HKD, RMS 310 | 400.0 | 400.0 | - | - | - | - | - | 1 x Ig | 500 ms (I^s T Off) | - | - | - | - | - | 1 x Ig | 150 ms (I^s T Off) | |
| NHSB-BG-1-GF-(14) | CUTLER-HAMMER | HKD, RMS 310 | 400.0 | 400.0 | - | - | - | - | - | 2 x Ig | 150 ms (I^s T Off) | - | - | - | - | - | 2 x Ig | 150 ms (I^s T Off) | |
| NHSB-BG-1-GF-(16) | CUTLER-HAMMER | LG, Series G | 600.0 | 600.0 | - | - | - | - | - | .2X | 120ms (K,N,Q) | - | - | - | - | - | .2X | 120ms (K,N,Q) | |
| NHSB-BG-1-MAIN | CUTLER-HAMMER | RD, RMS 310 | 2000.0 | 2000.0 | Fixed | Fixed | 8 | Fixed (I^s T On) | Fixed | - | - | Fixed | Fixed | 8 | Fixed (I^s T On) | Fixed | - | - | |
| NHSB-BG-1-MAIN-GF | CUTLER-HAMMER | RD, RMS 310 | 2000.0 | 2000.0 | - | - | - | - | - | F - K | 500 ms (I^s T Off) | - | - | - | - | - | C | 300 ms (I^s T Off) |
| MAIN CAMPUS - BUILDING C | |||||||||||||||||||
| EXISTING SETTINGS | RECOMMENDED SETTINGS | ||||||||||||||||||
| BREAKER | MANUFACTURER | MODEL | FRAME SIZE (AMPS) | TRIP (AMPS) | LTPU | LTD | STPU | STD | INST | GFPU | GFD | LTPU | LTD | STPU | STD | INST | GFPU | GFD | |
| GHSB-C3-1 | GHSB-C3-1-(1) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800.0 | 600.0 | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 1 | 24 | 8 | 0.4 (I^s T Off) | 6.5 | - | - |
| GHSB-C3-1-(1)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800.0 | 600.0 | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | |
| GHSB-C3-1-(2) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800.0 | 800.0 | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 1 | 24 | 10 | 0.4 (I^s T Off) | 7 | - | - | |
| GHSB-C3-1-(2)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | |
| GHSB-C3-1-(3) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800.0 | 800.0 | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | |
| GHSB-C3-1-(3)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | |
| GHSB-C3-1-(4) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800.0 | 800.0 | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 1 | 24 | 10 | 0.4 (I^s T Off) | 6.5 | - | - | |
| GHSB-C3-1-(4)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | |
| GHSB-C3-1-(5) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800.0 | 800.0 | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 1 | 14 | 10 | 0.4 (I^s T Off) | 6 | - | - | |
| GHSB-C3-1-(5)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | |
| GHSB-C3-1-(6) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800.0 | 800.0 | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 1 | 14 | 10 | 0.4 (I^s T Off) | 6 | - | - | |
| GHSB-C3-1-(6)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | |
| GHSB-C3-1-(7) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800.0 | 800.0 | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 1 | 20 | 6 | 0.15 (I^s T Off) | 6 | - | - | |
| GHSB-C3-1-(7)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | |
| GHSB-C3-1-MAIN | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 4000.0 | 4000.0 | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 0.4 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | |
| GHSB-C3-1-MAIN-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 4000.0 | 4000.0 | - | - | - | - | - | 0.25 | 0.1 (I^s T Off) | - | - | - | - | - | 0.25 | 0.3 (I^s T Off) | |
| GHTA-CB-1 | GHTA-CB-1-MAIN-(1) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 2000.0 | 1600.0 | 1 | 2 | 12 | 0.5 (I^s T Off) | 12 | - | - | 0.85 | 2 | 4 | 0.15 (I^s T Off) | 12 | - | - |
| GHTA-CB-1-MAIN-(1)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 2000.0 | 1600.0 | - | - | - | - | - | 0.4 | 0.3 (I^s T Off) | - | - | - | - | - | 0.4 | 0.3 (I^s T Off) | |
| GHTA-CB-2 | GHTA-CB-2-MAIN(1)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 2000.0 | 1600.0 | - | - | - | - | - | 0.4 | 0.3 (I^s T Off) | - | - | - | - | - | 0.5 | 0.4 (I^s T Off) |
| GHTA-CB-2-MAIN(2)-GF | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 2000.0 | 1600.0 | - | - | - | - | - | 0.3 | 0.3 (I^s T On) | - | - | - | - | - | 0.5 | 0.4 (I^s T On) | |
| GHTA-CB-2-MAIN-(1) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 2000.0 | 1600.0 | 1 | 6 | 12 | 0.5 (I^s T Off) | 12 | - | - | 1 | 24 | 12 | 0.5 (I^s T Off) | 12 | - | - | |
| GHTA-CB-2-MAIN-(2) | CUTLER-HAMMER | Magnum DS, DT 1150/1150i | 2000.0 | 1600.0 | 1 | 2 | M1(12x) | 0.5 (I^s T Off) | 12 | - | - | 1 | 24 | M1(12x) | 0.5 (I^s T Off) | 12 | - | - | |
| NHD-C3-1 | NHD-C3-1-(1) | SQUARE D | LX & LXI, Micrologic (1993) | 400.0 | 400.0 | 1 | 2 | 2 | 0.1 | 2.5 | - | - | 1 | 14 | 4 | 0.5 | 6 | - | - |
| NHD-C3-1-(2) | SQUARE D | LX & LXI, Micrologic (1993) | 400.0 | 400.0 | 1 | 2 | 2 | 0.1 | 2.5 | - | - | 1 | 2 | 2 | 0.1 | 2.5 | - | - | |
| NHD-C3-1-(3) | SQUARE D | LX & LXI, Micrologic (1993) | 400.0 | 400.0 | 1 | 2 | 2 | 0.1 | 2.5 | - | - | 1 | 2 | 2 | 0.1 | 2.5 | - | - | |
| NHD-C3-1-(4) | SQUARE D | LX & LXI, Micrologic (1993) | 400.0 | 400.0 | 1 | 2 | 2 | 0.1 | 2.5 | - | - | 1 | 2 | 2 | 0.1 | 2.5 | - | - | |
| NHD-C3-1-(5) | SQUARE D | LX & LXI, Micrologic (1993) | 400.0 | 400.0 | 1 | 2 | 2 | 0.1 | 2.5 | - | - | 1 | 2 | 2 | 0.1 | 2.5 | - | - | |
| NHD-C3-1-(6) | SQUARE D | LX & LXI, Micrologic (1993) | 400.0 | 400.0 | 1 | 2 | 2 | 0.1 | 2.5 | - | - | 1 | 2 | 2 | 0.1 | 2.5 | - | - | |
| NHD-C3-1-(7) | SQUARE D | LX & LXI, Micrologic (1993) | 400.0 | 400.0 | 1 | 2 | 2 | 0.1 | 2.5 | - | - | 1 | 14 | 5 | 0.5 | 6 | - | - | |
| NHD-C3-1-(8) | SQUARE D | LX / LXI, Micrologic | 400.0 | 400.0 | 1 | 2 | 2 | .1 (I^s T Off) | 2.5 | - | - | 1 | 2 | 2 | .1 (I^s T Off) | 2.5 | - | - | |
| NHD-C3-2 | NHD-C3-2-(1) | SQUARE D | LX / LXI, Micrologic | 400.0 | 400.0 | 1 | 2 | 2 | .1 (I^s T Off) | 2.5 | - | - | 1 | 2 | 2 | .1 (I^s T Off) | 2.5 | - | - |
| NHD-C3-2-(2) | SQUARE D | LX / LXI, Micrologic | 400.0 | 400.0 | 1 | 2 | 2 | .1 (I^s T Off) | 2.5 | - | - | 1 | 2 | 2 | .1 (I^s T Off) | 2.5 | - | - | |
| NHD-C3-2-(3) | SQUARE D | LX / LXI, Micrologic | 400.0 | 400.0 | 1 | 2 | 2 | .1 (I^s T Off) | 2.5 | - | - | 1 | 2 | 2 | .1 (I^s T Off) | 2.5 | - | - | |
| NHD-C3-2-(4) | SQUARE D | LX / LXI, Micrologic | 400.0 | 400.0 | 1 | 2 | 2 | .1 (I^s T Off) | 2.5 | - | - | 1 | 8 | 7 | .5 (I^s T Off) | 8 | - | - | |
| NHD-C3-2-(5) | SQUARE D | LX / LXI, Micrologic | 400.0 | 400.0 | 1 | 2 | 2 | .1 (I^s T Off) | 2.5 | - | - | 1 | 14 | 4 | .1 (I^s T Off) | 5 | - | - | |
| NHD-C3-2-(6) | SQUARE D | LX / LXI, Micrologic | 400.0 | 400.0 | 1 | 2 | 2 | .5 (I^s T On) | 2.5 | - | - | 1 | 14 | 8.5 | .5 (I^s T On) | 10 | - | - | |
| NHSB-C3-1 | NHSB-C3-1-(1) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | 0.7 | 9 | 6 | 0.2 (I^s T Off) | 10 | - | - | 0.7 | 9 | 6 | 0.2 (I^s T Off) | 10 | - | - |
| NHSB-C3-1-(1)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | - | - | - | - | - | 0.9 | 0.5 (I^s T Off) | - | - | - | - | - | 0.9 | 0.3 (I^s T Off) | |
| NHSB-C3-1-(2) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 2000.0 | 2000.0 | 0.6 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 0.6 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | |
| NHSB-C3-1-(2)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 2000.0 | 2000.0 | - | - | - | - | - | 0.75 | 0.5 (I^s T Off) | - | - | - | - | - | 0.35 | 0.3 (I^s T Off) | |
| NHSB-C3-1-(3) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | 1 | 16 | 4 | 0.2 (I^s T Off) | 12 | - | - | 1 | 16 | 4 | 0.2 (I^s T Off) | 12 | - | - | |
| NHSB-C3-1-(3)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-1-(4) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | 1 | 8 | 4 | 0.1 (I^s T Off) | 8 | - | - | 1 | 8 | 4 | 0.1 (I^s T Off) | 8 | - | - | |
| NHSB-C3-1-(4)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 0.75 | 0.3 (I^s T Off) | |
| NHSB-C3-1-(5) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | 1 | 8 | 4 | 0.2 (I^s T Off) | 10 | - | - | 1 | 8 | 4 | 0.2 (I^s T Off) | 10 | - | - | |
| NHSB-C3-1-(5)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-1-(6) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 1600.0 | 1200.0 | 1 | 4 | 6 | 0.1 (I^s T Off) | 12 | - | - | 1 | 4 | 6 | 0.1 (I^s T Off) | 12 | - | - | |
| NHSB-C3-1-(6)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 1600.0 | 1200.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 0.75 | 0.3 (I^s T Off) | |
| NHSB-C3-1-(7) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | 1 | 8 | 4 | 0.1 (I^s T Off) | 12 | - | - | 1 | 8 | 4 | 0.1 (I^s T Off) | 12 | - | - | |
| NHSB-C3-1-(7)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-1-(8) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 400.0 | 1 | 20 | 8 | 0.1 (I^s T Off) | 12 | - | - | 1 | 24 | 8 | 0.1 (I^s T Off) | 12 | - | - | |
| NHSB-C3-1-(8)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-1-MAIN-(B) | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 3200.0 | 1 | 2 | 1.5 | 0.25 (I^s T Off) | 5 | - | - | 0.65 | 2 | 2 | 0.15 (I^s T Off) | 5 | - | - | |
| NHSB-C3-1-MAIN-(B)-GF | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 3200.0 | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | |
| NHSB-C3-1-MAIN-(N) | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 4000.0 | 1 | 2 | 1.5 | 0.25 (I^s T Off) | 5 | - | - | 1 | 2 | 1.5 | 0.25 (I^s T Off) | 5 | - | - | |
| NHSB-C3-1-MAIN-(N)-GF | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 4000.0 | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | |
| NHSB-C3-1-TIE | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 4000.0 | 1 | 2 | 1.5 | 0.25 (I^s T Off) | 5 | - | - | 1 | 2 | 1.5 | 0.25 (I^s T Off) | 5 | - | - | |
| NHSB-C3-1-TIE-GF | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 4000.0 | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | |
| NHSB-C3-2 | NHSB-C3-2-(1) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | 1 | 4 | 4 | 0.1 (I^s T Off) | 10 | - | - | 1 | 4 | 4 | 0.1 (I^s T Off) | 10 | - | - |
| NHSB-C3-2-(1)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-2-(10) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | 1 | 8 | 4 | 0.1 (I^s T Off) | 10 | - | - | 1 | 8 | 4 | 0.1 (I^s T Off) | 10 | - | - | |
| NHSB-C3-2-(10)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-2-(2) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | 1 | 24 | 5 | 0.2 (I^s T Off) | 12 | - | - | 1 | 8 | 2.5 | 0.1 (I^s T Off) | 12 | - | - | |
| NHSB-C3-2-(2)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-2-(3) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | 1 | 24 | 5 | 0.2 (I^s T Off) | 12 | - | - | 1 | 24 | 2 | 0.1 (I^s T Off) | 12 | - | - | |
| NHSB-C3-2-(3)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-2-(4) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | 1 | 20 | 4 | 0.1 (I^s T Off) | 10 | - | - | 1 | 20 | 3 | 0.1 (I^s T Off) | 10 | - | - | |
| NHSB-C3-2-(4)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-2-(5) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | 1 | 8 | 4 | 0.2 (I^s T Off) | 10 | - | - | 1 | 8 | 4 | 0.2 (I^s T Off) | 10 | - | - | |
| NHSB-C3-2-(5)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-2-(6) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 1600.0 | 1200.0 | 1 | 4 | 6 | 0.1 (I^s T Off) | 12 | - | - | 1 | 4 | 6 | 0.1 (I^s T Off) | 12 | - | - | |
| NHSB-C3-2-(6)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 1600.0 | 1200.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 0.75 | 0.3 (I^s T Off) | |
| NHSB-C3-2-(7) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 400.0 | 1 | 20.5 | 5 | 0.1 (I^s T Off) | 12 | - | - | 1 | 20.5 | 5 | 0.1 (I^s T Off) | 12 | - | - | |
| NHSB-C3-2-(7)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 400.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-2-(8) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | 1 | 8 | 4 | 0.2 (I^s T Off) | 10 | - | - | 1 | 8 | 4 | 0.2 (I^s T Off) | 10 | - | - | |
| NHSB-C3-2-(8)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-2-(9) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | 1 | 8 | 4 | 0.1 (I^s T Off) | 10 | - | - | 1 | 8 | 4 | 0.1 (I^s T Off) | 10 | - | - | |
| NHSB-C3-2-(9)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-2-MAIN-(E) | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 3200.0 | 1 | 2 | 1.5 | 0.25 (I^s T Off) | 5 | - | - | 0.65 | 2 | 1.5 | 0.15 (I^s T Off) | 5 | - | - | |
| NHSB-C3-2-MAIN-(E)-GF | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 3200.0 | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | |
| NHSB-C3-2-MAIN-(N) | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 4000.0 | 1 | 2 | 1.5 | 0.25 (I^s T Off) | 5 | - | - | 1 | 2 | 4 | 0.25 (I^s T Off) | 5 | - | - | |
| NHSB-C3-2-MAIN-(N)-GF | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 4000.0 | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | |
| NHSB-C3-2-TIE | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 4000.0 | 1 | 2 | 6 | 0.1 (I^s T Off) | 8 | - | - | 0.8 | 2 | 4 | 0.1 (I^s T Off) | 4 | - | - | |
| NHSB-C3-2-TIE-GF | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 4000.0 | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | - | - | - | - | - | 0.25 | 0.3 (I^s T Off) | |
| NHSB-C3-3 | NHSB-C3-3-(1) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 250.0 | 1 | 4 | 4 | 0.1 (I^s T Off) | 10 | - | - | 1 | 4 | 4 | 0.1 (I^s T Off) | 10 | - | - |
| NHSB-C3-3-(1)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 250.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-3-(2) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 400.0 | 1 | 4 | 4 | 0.1 (I^s T Off) | 10 | - | - | 1 | 4 | 4 | 0.1 (I^s T Off) | 10 | - | - | |
| NHSB-C3-3-(2)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 400.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-3-(3) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | 1 | 24 | 6 | 0.1 (I^s T Off) | 12 | - | - | 1 | 24 | 6 | 0.1 (I^s T Off) | 12 | - | - | |
| NHSB-C3-3-(3)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-3-(4) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | 1 | 24 | 6 | 0.1 (I^s T Off) | 12 | - | - | 1 | 24 | 6 | 0.1 (I^s T Off) | 12 | - | - | |
| NHSB-C3-3-(4)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-3-(5) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | 1 | 24 | 6 | 0.1 (I^s T Off) | 12 | - | - | 1 | 24 | 6 | 0.1 (I^s T Off) | 12 | - | - | |
| NHSB-C3-3-(5)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-3-(6) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | 1 | 24 | 6 | 0.1 (I^s T Off) | 12 | - | - | 1 | 24 | 6 | 0.1 (I^s T Off) | 12 | - | - | |
| NHSB-C3-3-(6)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-3-(7) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | 1 | 24 | 6 | 0.1 (I^s T Off) | 2 | - | - | 1 | 24 | 6 | 0.1 (I^s T Off) | 2 | - | - | |
| NHSB-C3-3-(7)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-3-(8) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | 1 | 24 | 6 | 0.1 (I^s T Off) | 12 | - | - | 1 | 24 | 6 | 0.1 (I^s T Off) | 12 | - | - | |
| NHSB-C3-3-(8)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-3-(9) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | 1 | 24 | 6 | 0.1 (I^s T Off) | 12 | - | - | 1 | 24 | 6 | 0.1 (I^s T Off) | 12 | - | - | |
| NHSB-C3-3-(9)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.3 (I^s T Off) | |
| NHSB-C3-3-MAIN-(E) | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 4000.0 | 0.9 | 2 | 3 | 0.25 (I^s T Off) | 9 | - | - | 0.9 | 2 | 3 | 0.25 (I^s T Off) | 9 | - | - | |
| NHSB-C3-3-MAIN-(E)-GF | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 4000.0 | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | |
| NHSB-C3-3-MAIN-(N) | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 4000.0 | 1 | 10 | 6 | 0.1 (I^s T Off) | 8 | - | - | 1 | 10 | 6 | 0.1 (I^s T Off) | 8 | - | - | |
| NHSB-C3-3-MAIN-(N)-GF | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 4000.0 | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | |
| NHSB-C3-3-TIE | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 4000.0 | 0.8 | 2 | 6 | 0.1 (I^s T Off) | 8 | - | - | 0.8 | 2 | 6 | 0.1 (I^s T Off) | 8 | - | - | |
| NHSB-C3-3-TIE-GF | CUTLER-HAMMER | Magnum DS-X, DT 1150/1150i | 4000.0 | 4000.0 | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) | - | - | - | - | - | 0.3 | 0.5 (I^s T Off) |
| MAIN CAMPUS - BUILDING D | |||||||||||||||||||
| EXISTING SETTINGS | RECOMMENDED SETTINGS | ||||||||||||||||||
| BREAKER | MANUFACTURER | MODEL | FRAME SIZE (AMPS) | TRIP (AMPS) | LTPU | LTD | STPU | STD | INST | GFPU | GFD | LTPU | LTD | STPU | STD | INST | GFPU | GFD | |
| NHD-DB-1 | NHD-DB-1-(1) | CUTLER-HAMMER | HFD | 100.0 | 100.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
| NHD-DB-1-(10) | CUTLER-HAMMER | HFD | 70.0 | 70.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHD-DB-1-(11) | CUTLER-HAMMER | HFD | 70.0 | 70.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHD-DB-1-(12) | CUTLER-HAMMER | HFD | 70.0 | 70.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHD-DB-1-(2) | CUTLER-HAMMER | HFD | 150.0 | 150.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHD-DB-1-(3) | CUTLER-HAMMER | HFD | 90.0 | 90.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHD-DB-1-(4) | CUTLER-HAMMER | HFD | 90.0 | 90.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHD-DB-1-(5) | CUTLER-HAMMER | HFD | 70.0 | 70.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHD-DB-1-(6) | CUTLER-HAMMER | HFD | 70.0 | 70.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHD-DB-1-(7) | CUTLER-HAMMER | HFD | 70.0 | 70.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHD-DB-1-(8) | CUTLER-HAMMER | HFD | 200.0 | 200.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHD-DB-1-(9) | CUTLER-HAMMER | HFD | 90.0 | 90.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHD-DB-1-MAIN | CUTLER-HAMMER | LG, Series G | 600.0 | 600.0 | - | - | - | - | 5 | - | - | - | - | - | - | 5 | - | - |
| MAIN CAMPUS - BUILDING E | |||||||||||||||||||
| EXISTING SETTINGS | RECOMMENDED SETTINGS | ||||||||||||||||||
| BREAKER | MANUFACTURER | MODEL | FRAME SIZE (AMPS) | TRIP (AMPS) | LTPU | LTD | STPU | STD | INST | GFPU | GFD | LTPU | LTD | STPU | STD | INST | GFPU | GFD | |
| EHL-L1-1 | EHL-L1-1-(1) | CUTLER-HAMMER | FD | 100.0 | 100.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
| EHL-L1-1-(2) | CUTLER-HAMMER | FD | 100.0 | 100.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| EHL-L1-1-(3) | CHALLENGER | CF | 100.0 | 100.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| EHL-L1-1-(4) | CHALLENGER | CF | 100.0 | 100.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| EHL-L1-1-(5) | CHALLENGER | CF | 40.0 | 40.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| EHL-L1-1-(6) | CUTLER-HAMMER | FD | 100.0 | 100.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| EHL-L1-1-(7) | CHALLENGER | CF | 60.0 | 60.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| EHL-L1-1-MAIN | CHALLENGER | CKS/CK | 400.0 | 350.0 | - | - | - | - | 5 | - | - | - | - | - | - | 5 | - | - | |
| NLD-LB-1 | NLD-LB-1-(1) | CUTLER-HAMMER | HFD | 200.0 | 200.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
| NLD-LB-1-(2) | CUTLER-HAMMER | HFD | 200.0 | 200.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NLD-LB-1-(3) | CUTLER-HAMMER | HFD | 150.0 | 150.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NLD-LB-1-(4) | CUTLER-HAMMER | HKD, RMS 310 | 400.0 | 400.0 | Fixed | Fixed | 8 | Fixed (I^s T On) | Fixed | - | - | Fixed | Fixed | 8 | Fixed (I^s T On) | Fixed | - | - | |
| NLD-LB-1-(5) | CUTLER-HAMMER | HKD, RMS 310 | 400.0 | 400.0 | Fixed | Fixed | 8 | Fixed (I^s T On) | Fixed | - | - | Fixed | Fixed | 8 | Fixed (I^s T On) | Fixed | - | - | |
| NLD-LB-1-MAIN | CUTLER-HAMMER | HMDL, RMS 310 (06/07) | 800.0 | 800.0 | Fixed | Fixed | 4 | Fixed (I^s T On) | Fixed | - | - | Fixed | Fixed | 4 | Fixed (I^s T On) | Fixed | - | - |
| MAIN CAMPUS - BUILDING F | |||||||||||||||||||
| EXISTING SETTINGS | RECOMMENDED SETTINGS | ||||||||||||||||||
| BREAKER | MANUFACTURER | MODEL | FRAME SIZE (AMPS) | TRIP (AMPS) | LTPU | LTD | STPU | STD | INST | GFPU | GFD | LTPU | LTD | STPU | STD | INST | GFPU | GFD | |
| NHDP-LG-1 | NHDP-LG-1-(1) | CHALLENGER | CFH | 100.0 | 100.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
| NHDP-LG-1-(2) | CUTLER-HAMMER | FD | 125.0 | 125.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHDP-LG-1-(3) | CHALLENGER | CKS/CK | 400.0 | 350.0 | - | - | - | - | 5 | - | - | - | - | - | - | 5 | - | - | |
| NHDP-LG-1-(4) | CHALLENGER | CFH | 100.0 | 100.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHDP-LG-1-(5) | CUTLER-HAMMER | FD | 125.0 | 125.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| NHDP-LG-1-MAIN | CHALLENGER | CLS/CL | 600.0 | 500.0 | - | - | - | - | 5 | - | - | - | - | - | - | 5 | - | - |
| MAIN CAMPUS - BUILDING T13 | |||||||||||||||||||
| EXISTING SETTINGS | RECOMMENDED SETTINGS | ||||||||||||||||||
| BREAKER | MANUFACTURER | MODEL | FRAME SIZE (AMPS) | TRIP (AMPS) | LTPU | LTD | STPU | STD | INST | GFPU | GFD | LTPU | LTD | STPU | STD | INST | GFPU | GFD | |
| MK | MK-(1) | SQUARE D | FH | 70.0 | 70.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
| MK-(2) | SQUARE D | KA | 250.0 | 200.0 | - | - | - | - | HI | - | - | - | - | - | - | HI | - | - | |
| MK-(3) | SQUARE D | FH | 70.0 | 70.0 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MK-(4) | SQUARE D | KA | 250.0 | 200.0 | - | - | - | - | HI | - | - | - | - | - | - | HI | - | - |
| MCPHERSON - BUILDING 125 | |||||||||||||||||||
| EXISTING SETTINGS | RECOMMENDED SETTINGS | ||||||||||||||||||
| BREAKER | MANUFACTURER | MODEL | FRAME SIZE (AMPS) | TRIP (AMPS) | LTPU | LTD | STPU | STD | INST | GFPU | GFD | LTPU | LTD | STPU | STD | INST | GFPU | GFD | |
| MAIN SWBD | MAIN-SWBD-1 | CUTLER-HAMMER | KD | 100 | 100 | - | - | - | - | 8 | - | - | - | - | - | - | 8 | - | - |
| MAIN-SWBD-10 | CUTLER-HAMMER | MDL | 800 | 800 | - | - | - | - | 4 | - | - | - | - | - | - | 4 | - | - | |
| MAIN-SWBD-2 | CUTLER-HAMMER | KD | 250 | 250 | - | - | - | - | 8 | - | - | - | - | - | - | 8 | - | - | |
| MAIN-SWBD-3 | CUTLER-HAMMER | KD | 300 | 300 | - | - | - | - | 8 | - | - | - | - | - | - | 8 | - | - | |
| MAIN-SWBD-4 | CUTLER-HAMMER | LD | 600 | 350 | - | - | - | - | 6 | - | - | - | - | - | - | 6 | - | - | |
| MAIN-SWBD-5 | EATON | NG-Frame, 310+ | 800 | 800 | G | 2 | 5 | Inst. | Fixed | - | - | G | 2 | 5 | Inst. | Fixed | - | - | |
| MAIN-SWBD-6 | CUTLER-HAMMER | KD | 400 | 400 | - | - | - | - | 8 | - | - | - | - | - | - | 8 | - | - | |
| MAIN-SWBD-7 | CUTLER-HAMMER | KD | 400 | 400 | - | - | - | - | 8 | - | - | - | - | - | - | 8 | - | - | |
| MAIN-SWBD-8 | CUTLER-HAMMER | KD | 100 | 100 | - | - | - | - | 8 | - | - | - | - | - | - | 8 | - | - | |
| MAIN-SWBD-9 | CUTLER-HAMMER | JD | 200 | 200 | - | - | - | - | 10 | - | - | - | - | - | - | 10 | - | - | |
| MAIN-SWBD-MAIN | CUTLER-HAMMER | DS, RMS 510/610/810/910 | 2000 | 2000 | 1 | 4 | 3 | 0.3 Sec. (I^s T Off) | M2(12) | - | - | 1 | 12 | 3 | 0.3 Sec. (I^s T Off) | M2(12) | - | - | |
| MAIN-SWBD-MAIN-GF | CUTLER-HAMMER | DS, RMS 510/610/810/910 | 2000 | 2000 | - | - | - | - | - | D (800A) | 0.1 Sec. (I^s T Off) | - | - | - | - | - | D (800A) | 0.1 Sec. (I^s T Off) |
| MCPHERSON - BUILDING 128 | |||||||||||||||||||
| EXISTING SETTINGS | RECOMMENDED SETTINGS | ||||||||||||||||||
| BREAKER | MANUFACTURER | MODEL | FRAME SIZE (AMPS) | TRIP (AMPS) | LTPU | LTD | STPU | STD | INST | GFPU | GFD | LTPU | LTD | STPU | STD | INST | GFPU | GFD | |
| MDP | MDP-1 | SQUARE D | HG | 150 | 150 | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
| MDP-2 | SQUARE D | HG | 100 | 100 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MDP-3 | SQUARE D | HG | 100 | 100 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MDP-4 | SQUARE D | HG | 70 | 70 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MDP-5 | SQUARE D | QG | 175 | 175 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MDP-6 | SQUARE D | HG | 100 | 100 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MDP-7 | SQUARE D | J-Frame, Powerpact | 250 | 225 | - | - | - | - | High | - | - | - | - | - | - | High | - | - |
| MCPHERSON - BUILDING 129 | |||||||||||||||||||
| EXISTING SETTINGS | RECOMMENDED SETTINGS | ||||||||||||||||||
| BREAKER | MANUFACTURER | MODEL | FRAME SIZE (AMPS) | TRIP (AMPS) | LTPU | LTD | STPU | STD | INST | GFPU | GFD | LTPU | LTD | STPU | STD | INST | GFPU | GFD | |
| MDP | MDP-1 | CUTLER-HAMMER | ED | 175 | 175 | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
| MDP-2 | CUTLER-HAMMER | ED | 175 | 175 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MDP-3 | CUTLER-HAMMER | FD | 70 | 70 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MDP-4 | CUTLER-HAMMER | FD | 100 | 100 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MDP-5 | CUTLER-HAMMER | JD | 250 | 250 | - | - | - | - | 10 | - | - | - | - | - | - | 10 | - | - | |
| MDP-6 | CUTLER-HAMMER | DK | 300 | 300 | - | - | - | - | 10 | - | - | - | - | - | - | 10 | - | - |
| MCPHERSON - BUILDING 130 | |||||||||||||||||||
| EXISTING SETTINGS | RECOMMENDED SETTINGS | ||||||||||||||||||
| BREAKER | MANUFACTURER | MODEL | FRAME SIZE (AMPS) | TRIP (AMPS) | LTPU | LTD | STPU | STD | INST | GFPU | GFD | LTPU | LTD | STPU | STD | INST | GFPU | GFD | |
| MDP | MDP-1 | SQUARE D | J-Frame, Powerpact | 250 | 250 | - | - | - | - | High | - | - | - | - | - | - | High | - | - |
| MDP-2 | SQUARE D | FH | 70 | 70 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MDP-3 | SQUARE D | J-Frame, Powerpact | 250 | 250 | - | - | - | - | High | - | - | - | - | - | - | High | - | - | |
| MDP-4 | SQUARE D | FH | 100 | 100 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MDP-5 | SQUARE D | J-Frame, Powerpact | 250 | 250 | - | - | - | - | High | - | - | - | - | - | - | High | - | - | |
| MDP-6 | SQUARE D | PowerPact L-Frame, 3.3S | 400 | 400 | 400 | Fixed | 1.5 | Fixed | 1.5 | - | - | 400 | Fixed | 1.5 | Fixed | 1.5 | - | - |
| MCPHERSON - BUILDING 131 | |||||||||||||||||||
| EXISTING SETTINGS | RECOMMENDED SETTINGS | ||||||||||||||||||
| BREAKER | MANUFACTURER | MODEL | FRAME SIZE (AMPS) | TRIP (AMPS) | LTPU | LTD | STPU | STD | INST | GFPU | GFD | LTPU | LTD | STPU | STD | INST | GFPU | GFD | |
| MDP | MDP-1 | CUTLER-HAMMER | FDE/FDCE/HFDE, 310+ | 225 | 225 | A (100) | 15 | 7 | 120ms (M,N,O) | Fixed | - | - | A (100) | 15 | 7 | 120ms (M,N,O) | Fixed | - | - |
| MDP-2 | CUTLER-HAMMER | FDE/FDCE/HFDE, 310+ | 225 | 225 | C (125) | 24 | 10 | 300ms (P,Q,R) | Fixed | - | - | C (125) | 24 | 10 | 300ms (P,Q,R) | Fixed | - | - | |
| MDP-3 | CUTLER-HAMMER | FDE/FDCE/HFDE, 310+ | 225 | 225 | H (225) | 2 | 2 | Inst (J,K,L) | Fixed | - | - | H (225) | 2 | 2 | Inst (J,K,L) | Fixed | - | - | |
| MDP-4 | CUTLER-HAMMER | MDL, RMS 310 (06/07) | 800 | 800 | Fixed | Fixed | 8 | Inst (I^s T Off) | Fixed | - | - | Fixed | Fixed | 8 | Inst (I^s T Off) | Fixed | - | - | |
| MDP-5 | CUTLER-HAMMER | FDE/FDCE/HFDE, 310+ | 225 | 225 | A (100) | 2 | 2 | Inst (J,K,L) | Fixed | - | - | A (100) | 2 | 2 | Inst (J,K,L) | Fixed | - | - | |
| MDP-6 | CUTLER-HAMMER | FDE/FDCE/HFDE, 310+ | 225 | 225 | A (100) | 2 | 2 | Inst (J,K,L) | Fixed | - | - | A (100) | 2 | 2 | Inst (J,K,L) | Fixed | - | - | |
| MDP-7 | CUTLER-HAMMER | FDE/FDCE/HFDE, 310+ | 225 | 225 | D (150) | 2 | 2 | Inst (J,K,L) | Fixed | - | - | D (150) | 2 | 2 | Inst (J,K,L) | Fixed | - | - | |
| MDP-8 | CUTLER-HAMMER | FDE/FDCE/HFDE, 310+ | 225 | 160 | E (100) | 2 | 2 | Inst (J,K,L) | Fixed | - | - | E (100) | 2 | 2 | Inst (J,K,L) | Fixed | - | - | |
| MDP-MAIN | CUTLER-HAMMER | CRD, RMS 510/610/810/910 | 1600 | 1600 | 0.5 | 24 | 4 | 0.3 Sec. (I^s T Off) | 6 | - | - | 0.7 | 24 | S2(8) | 0.3 Sec. (I^s T Off) | 6 | - | - | |
| SBDP1 | SBDP1-1 | CUTLER-HAMMER | QBHW, 3-Pole | 70 | 70 | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
| SBDP1-2 | CUTLER-HAMMER | QBHW, 3-Pole | 30 | 30 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| SBDP1-3 | CUTLER-HAMMER | QBHW, 3-Pole | 70 | 70 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| SBDP1-4 | CUTLER-HAMMER | QBHW, 3-Pole | 100 | 100 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| SBDP2 | SBDP2-1 | CUTLER-HAMMER | FD | 125 | 125 | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
| SBDP2-2 | CUTLER-HAMMER | JD | 250 | 250 | - | - | - | - | 10 | - | - | - | - | - | - | 10 | - | - | |
| SBDP2-3 | CUTLER-HAMMER | DK | 400 | 400 | - | - | - | - | 10 | - | - | - | - | - | - | 10 | - | - | |
| SBDP2-4 | CUTLER-HAMMER | JD | 250 | 250 | - | - | - | - | 10 | - | - | - | - | - | - | 10 | - | - | |
| SBDP2-5 | CUTLER-HAMMER | DK | 400 | 400 | - | - | - | - | 10 | - | - | - | - | - | - | 10 | - | - | |
| SBDP2-6 | CUTLER-HAMMER | CMDL, RMS 310 (06/07) | 800 | 800 | Fixed | Fixed | 8 | Fixed (I^s T On) | Fixed | - | - | Fixed | Fixed | 8 | Fixed (I^s T On) | Fixed | - | - |
| TRINKA DAVIS | |||||||||||||||||||
| EXISTING SETTINGS | RECOMMENDED SETTINGS | ||||||||||||||||||
| BREAKER | MANUFACTURER | MODEL | FRAME SIZE (AMPS) | TRIP (AMPS) | LTPU | LTD | STPU | STD | INST | GFPU | GFD | LTPU | LTD | STPU | STD | INST | GFPU | GFD | |
| MAIN SWBD | MAIN-SWBD-1 | GE | SGLA, Spectra RMS | 400 | 400 | - | - | - | - | 5 | - | - | - | - | - | - | MAX | - | - |
| MAIN-SWBD-2 | GE | SELA, Spectra RMS | 100 | 100 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MAIN-SWBD-3 | GE | SFLA, Spectra RMS | 250 | 225 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MAIN-SWBD-4 | GE | SGLA, Spectra RMS | 400 | 400 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MAIN-SWBD-5 | GE | SFLA, Spectra RMS | 250 | 225 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MAIN-SWBD-6 | GE | SELA, Spectra RMS | 100 | 100 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MAIN-SWBD-7 | GE | SFLA, Spectra RMS | 250 | 225 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MAIN-SWBD-8 | GE | SFLA, Spectra RMS | 250 | 225 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
| MAIN-SWBD-MAIN | GE | SS, SH PowerBreak II, EGTU, ZSI | 1600 | 1600 | 0.50X | C-2 | 1.5X | ST01-Min (I^s T Off) | 2X | - | - | 0.60X | C-6 | 6.5X | ST01-Min (I^s T Off) | 4X | - | - | |
| MAIN-SWBD-MAIN-GF | GE | SS, SH PowerBreak I & II, EGTU | 1600 | 1600 | - | - | - | - | - | 0.2 | GFD01 (I^s T Off) | - | - | - | - | - | 0.2 | GFD01 (I^s T Off) |
&9Atlanta VAMC - Existing/Recommended Circuit Breaker Settings - Final Submission
Page &P of &N
OTHER CHANGES
| OTHER RECOMMENDED CHANGES | |||||||||||||||||||
| EXISTING SETTINGS | RECOMMENDED SETTINGS | ||||||||||||||||||
| BLDG | BREAKER | MANUFACTURER | MODEL | FRAME SIZE (AMPS) | TRIP (AMPS) | LTPU | LTD | STPU | STD | INST | GFPU | GFD | LTPU | LTD | STPU | STD | INST | GFPU | GFD |
| A | EHD-AG-2-(1) | GE | SGHA, Spectra RMS | 400 | 350 | - | - | - | - | MAX | - | - | - | - | - | - | 3 | - | - |
| A | EHD-AG-2-(2) | GE | SGHA, Spectra RMS | 400 | 350 | - | - | - | - | MAX | - | - | - | - | - | - | 3 | - | - |
| A | GHECB-AG-1-MAIN | CUTLER-HAMMER | FDE/FDCE/HFDE, 310+ | 225 | 225 | G (200) | 2 | 2 | Inst (J,K,L) | Fixed | - | - | G (200) | 10 | 7 | Inst (J,K,L) | Fixed | - | - |
| A | GHTA-AG-1-MAIN-(2)-GF | CUTLER-HAMMER | Magnum DS, RMS 520 | 3200 | 3200 | - | - | - | - | - | 0.35 | 0.1 (I^s T Off) | - | - | - | - | - | 0.4 | 0.5 (I^s T Off) |
| A | GHTA-AG-1-MAIN-GF-(1) | CUTLER-HAMMER | Magnum DS, RMS 520 | 3200 | 3200 | - | - | - | - | - | 0.35 | 0.1 (I^s T Off) | - | - | - | - | - | 0.4 | 0.5 (I^s T Off) |
| A | NHD-A1-1-(1) | GE | SELA, Spectra RMS | 150 | 150 | - | - | - | - | MAX | - | - | - | - | - | - | MIN | - | - |
| A | NHD-A1-1-(3) | GE | SELA, Spectra RMS | 100 | 100 | - | - | - | - | MAX | - | - | - | - | - | - | MIN | - | - |
| A | NHD-A1-1-(4) | GE | SELA, Spectra RMS | 60 | 60 | - | - | - | - | MAX | - | - | - | - | - | - | MIN | - | - |
| A | NHD-AG-1-(2) | GE | SEPA, Spectra RMS | 150 | 150 | - | - | - | - | MIN | - | - | - | - | - | - | MAX | - | - |
| A | NHD-AG-1-(3) | GE | SEPA, Spectra RMS | 150 | 150 | - | - | - | - | MIN | - | - | - | - | - | - | MAX | - | - |
| A | NHP-A1-1-MAIN | GE | SGHA, Spectra RMS | 600 | 600 | - | - | - | - | MAX | - | - | - | - | - | - | MIN | - | - |
| A | NHP-A1-2-MAIN | GE | SGHA, Spectra RMS | 600 | 600 | - | - | - | - | MAX | - | - | - | - | - | - | MIN | - | - |
| B | EHD-BG-1-(5) | CUTLER-HAMMER | HKD | 400.0 | 400.0 | - | - | - | - | 10 | - | - | - | - | - | - | 5 | - | - |
| C | CHD-C2-2-(1) | SQUARE D | KA | 250.0 | 200.0 | - | - | - | - | HI | - | - | - | - | - | - | LO | - | - |
| C | CHD-C3-1-MAIN | CUTLER-HAMMER | NDC, RMS 310 | 800.0 | 800.0 | Fixed | Fixed | 2 | Fixed (I^s T On) | Fixed | - | - | Fixed | Fixed | 5 | Fixed (I^s T On) | Fixed | - | - |
| C | EHD-C3-1-MAIN | CUTLER-HAMMER | NDC, RMS 310 | 800.0 | 800.0 | Fixed | Fixed | 2 | Fixed (I^s T On) | Fixed | - | - | Fixed | Fixed | 4 | Fixed (I^s T On) | Fixed | - | - |
| C | EHD-C3-2-(2) | CUTLER-HAMMER | ND, RMS 310 | 800.0 | 800.0 | 800A | Fixed | 5 | Fixed (I^s T On) | Fixed | - | - | 800A | Fixed | 2 | Fixed (I^s T On) | Fixed | - | - |
| C | EHD-C3-2-MAIN | CUTLER-HAMMER | NDC, RMS 310 | 800.0 | 800.0 | 800A | Fixed | 2 | Fixed (I^s T On) | Fixed | - | - | 800A | Fixed | 4 | Fixed (I^s T On) | Fixed | - | - |
| C | NHD-C1-2-(5) | SQUARE D | KH | 250.0 | 200.0 | - | - | - | - | LO | - | - | - | - | - | - | HI | - | - |
| C | NHD-C13-1-MAIN | CUTLER-HAMMER | RDC, RMS 510/610/810/910 | 2000.0 | 2000.0 | 0.6 | 2 | 4 | 0.4 (I^s T Off) | 2.5 | - | - | 0.6 | 2 | 2.5 | 0.1 (I^s T Off) | 2.5 | - | - |
| C | NHD-C2-1-(3) | SQUARE D | KA | 250.0 | 200.0 | - | - | - | - | HI | - | - | - | - | - | - | LO | - | - |
| C | NHD-CG-1-(1) | SQUARE D | LA | 400.0 | 300.0 | - | - | - | - | LO | - | - | - | - | - | - | HI | - | - |
| C | NHL-C1-6-(2) | SQUARE D | LA | 400.0 | 300.0 | - | - | - | - | HI | - | - | - | - | - | - | LO | - | - |
| C | NHL-C1-6-MAIN | SQUARE D | LC | 300.0 | 300.0 | - | - | - | - | LO | - | - | - | - | - | - | HI | - | - |
| C | NHL-C1-8-(1) | SQUARE D | KA | 250.0 | 200.0 | - | - | - | - | HI | - | - | - | - | - | - | LO | - | - |
| C | NHL-C7-1-MAIN | SQUARE D | LA | 400.0 | 300.0 | - | - | - | - | HI | - | - | - | - | - | - | LO | - | - |
| C | NHL-C7-2-(1) | SQUARE D | KA | 150.0 | 150.0 | - | - | - | - | HI | - | - | - | - | - | - | 3 | - | - |
| C | NHL-CG-2-(1) | SQUARE D | KA | 150.0 | 150.0 | - | - | - | - | HI | - | - | - | - | - | - | 4 | - | - |
| C | NHSB-CB-1-(1)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 0.5 | 0.1 (I^s T Off) |
| C | NHSB-CB-1-(2) | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | 0.8 | 2 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 0.8 | 13 | 8 | 0.5 (I^s T Off) | 10 | - | - |
| C | NHSB-CB-1-(2)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 600.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 0.5 | 0.1 (I^s T Off) |
| C | NHSB-CB-1-(3)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 800.0 | 800.0 | - | - | - | - | - | 1 | 0.5 (I^s T Off) | - | - | - | - | - | 0.35 | 0.1 (I^s T Off) |
| C | NHSB-CB-1-MAIN | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 2000.0 | 2000.0 | 0.8 | 2 | 5 | 0.1 (I^s T Off) | 6 | - | - | 0.6 | 2 | 4 | 0.1 (I^s T Off) | 6 | - | - |
| C | NHSB-CB-1-MAIN-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 2000.0 | 2000.0 | - | - | - | - | - | 0.6 | 0.5 (I^s T Off) | - | - | - | - | - | 0.25 | 0.5 (I^s T Off) |
| C | NHSB-CB-2-(1)-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 2000.0 | 2000.0 | - | - | - | - | - | 0.6 | 0.5 (I^s T Off) | - | - | - | - | - | 0.4 | 0.4 (I^s T Off) |
| C | NHSB-CB-2-MAIN | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 2000.0 | 2000.0 | 1 | 2 | 2 | 0.1 (I^s T Off) | 5 | - | - | 1 | 24 | M1(14x) | 0.5 (I^s T Off) | M1(14x) | - | - |
| C | NHSB-CB-2-MAIN-GF | CUTLER-HAMMER | Magnum DS-L, DT 1150/1150i | 2000.0 | 2000.0 | - | - | - | - | - | 0.6 | 0.5 (I^s T Off) | - | - | - | - | - | 1 | 0.5 (I^s T Off) |
| C | NHSB-CB-3-(1)GF | CUTLER-HAMMER | DSLII, RMS 510/610/810/910 | 2000.0 | 2000.0 | - | - | - | - | - | D | 0.5 Sec. (I^s T Off) | - | - | - | - | - | E | 0.5 Sec. (I^s T Off) |
| C | NLP-C1-9-MAIN | SQUARE D | LA | 400.0 | 350.0 | - | - | - | - | LO | - | - | - | - | - | - | HI | - | - |
| C | SHL-C1-1-MAIN | CUTLER-HAMMER | KA | 225.0 | 100.0 | - | - | - | - | 5 | - | - | - | - | - | - | 10 | - | - |
| D | GHD-DB-1-MAIN | CUTLER-HAMMER | HMDL | 800.0 | 700.0 | - | - | - | - | 4 | - | - | - | - | - | - | 8 | - | - |
| F | NHDS-LG-1-MAIN | SQUARE D | J-Frame, Powerpact | 250.0 | 225.0 | - | - | - | - | High | - | - | - | - | - | - | Low | - | - |
| PK | EGHA-MAIN | SIEMENS | FXD6 Sentron | 200.0 | 200.0 | - | - | - | - | LO | - | - | - | - | - | - | HI | - | - |
| 125 | MCC2-1 | CUTLER-HAMMER | HJD | 200 | 200 | - | - | - | - | 10 | - | - | - | - | - | - | 5 | - | - |
| 129 | CH-1 | CUTLER-HAMMER | LG, Series G | 630 | 630 | H | 2 | 2 | Inst | 12 x In | - | - | H | 2 | 4 | Inst | 12 x In | - | - |
| 129 | CH-DISC | CUTLER-HAMMER | CMDL, RMS 310 (06/07) | 800 | 800 | Fixed | Fixed | 2 | Inst (I^s T Off) | Fixed | - | - | Fixed | Fixed | 4 | Inst (I^s T Off) | Fixed | - | - |
| 129 | SERV-DISC-MAIN | CUTLER-HAMMER | MDL, RMS 310 (06/07) | 800 | 800 | 400A | Fixed | 2 | Inst (I^s T Off) | Fixed | - | - | 800A | Fixed | 6 | Inst (I^s T Off) | Fixed | - | - |
| 130 | SERV-DISC-MAIN | SQUARE D | Powerpact P-Frame, 6.0A/P/H | 1200 | 800 | 1 | 0.5 | 1.5 | 0.2 (I^s T On) | 2 | - | - | 1 | 12 | 5 | 0.2 (I^s T On) | 6 | - | - |
| 131 | GEN-1-1 | SQUARE D | Powerpact R-Frame, 6.0A/P/H | 2500 | 1600 | 0.8 | 0.5 | 1.5 | 0.1 (I^s T Off) | 2 | - | - | 0.8 | 8 | 8 | 0.1 (I^s T Off) | 6 | - | - |
| 131 | GEN-1-2 | SQUARE D | PowerPact D-Frame, STR23SP | 400 | 400 | 1,1 | Fixed | 2 | - | - | - | - | 1,1 | Fixed | 4 | - | - | - | - |
&9Atlanta VAMC - Existing/Recommended Circuit Breaker Settings - Final Submission
Page &P of &N
REPLACEMENTS
| Circuit Breaker Replacements | ||||
| BUILDING | PANEL | FEEDING | EXISTING | RECOMMENDED |
| A | CHD-AG-1 | CHL-A4-1, CHL-A5-1 | 225A CH TYPE FDC | 250A CH TYPE JD |
| A | HL-5A-277-2 | UPS-NEURO XF | 30A SQD TYPE EG | 50A SQD TYPE EG |
| B | NHL-B2-1 | MAIN | 100A GE TYPE FD | 150A GE TYPE FD |
| C | EHL-CB-1 | EHL-CG-4 | 30A CH TYPE GHB | 50A CH TYPE GHB |
| C | NHD-C13-1 | NX-C13-1 | 60A CH TYPE FDC | 100A CH TYPE FDC |
| C | NHL-C11-3 | NX-C11-1 | 225A WESTINGHOUSE TYPE JA | 100A WESTINGHOUSE TYPE JA |
| C | NHL-C5-3 | NX-C5-3 | 150A WESTINGHOUSE TYPE LAB | 100A CH TYPE FD |
| C | NLP-C7-3 | MAIN | 225A SIEMENS TYPE QJH | 125A SIEMENS TYPE QJH |
| 125 | L2B | MAIN | 200A CH TYPE HJD | 250A CH TYPE HJD |
| 128 | LP2 | MAIN | 100A SQD TYPE QO | 70A SQD TYPE QD |
| 128 | MDP | LP2 | 100A SQD TYPE HG | 100A SQD TYPE QD |
| TD | EGHA | EGLA | 30A CH TYPE GHB | 60A CH TYPE GHB |
| TD | EGLA | MAIN | 60A CH TYPE GHB | 30A CH TYPE EHD |
| Cable Replacements | ||||
| BUILDING | FROM | TO | EXISTING | RECOMMENDED |
| A | CHD-AG-1 | CHL-A4-1, CHL-A5-1 | 4/0 AWG | 250 KCMIL |
| A | HL-5A-277-2 | UPS NEURO XF | 10 AWG | 8 AWG |
| C | EHD-CG-2 | EHL-CG-1 | 3/0 AWG | 500 KCMIL |
| C | EHL-CB-1 | EHL-CG-4 | 10 AWG | 8 AWG |
Atlanta VAMC - Final Submission
File details come from the government source that posted it. Updated .