final main site - gen input report.pdf
PDF 311 KB Posted
- Attached to
- 36-Month Electrical Distribution Testing
- Solicitation number
- 36C24727Q0044
About this file
Summary
This document is a DAPPER Fault Analysis Input Report for the VA Atlanta SKM Model Final project, detailing electrical system fault contribution data for a Veterans Affairs facility's electrical distribution network. The report contains comprehensive technical specifications for utility contributions, generator parameters, motor characteristics, and an extensive cable inventory across multiple electrical buses and distribution systems. The utility contributions are documented from Georgia Power at two ring configurations (480V), with detailed single-line-to-ground and three-phase fault current data in amperes and MVA. Generator contributions include five units designated A-GEN1 through A-GEN5 (each 2,500 kVA at 480V with 20% transient reactance), plus B-GENB (750 kVA) and D-GEN-D (562.5 kVA), all operating at 480V with varying impedance ratios.
The motor section documents over 40 individual motors distributed across bus configurations A through F, plus parking and other specialized areas, ranging from 10 kVA to 869 kVA capacity at various voltage levels (208V, 220V, and 480V), with applications including chillers, elevators, pumps, and fire protection systems. The extensive cable schedule comprises hundreds of entries detailing interconnections between distribution buses, specifying cable gauges (ranging from 1 AWG to 4000 MCM busway), lengths in feet, insulation types (primarily PVC with some Epoxy), conductor materials (Copper and Busway), and per-unit impedance values for both positive and zero sequence components on a 100 MVA base. This technical data supports fault analysis modeling and coordination studies for the Atlanta VA medical facility's electrical infrastructure.
View the file
Other files
Show 40 more
Latest 50 of 53 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DAPPER Fault Analysis Input Report (English)
Project: VA_Atlanta_SKM_Model
Final - Generator
Utilities
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
-------- Contribution Data -------- PU (100 MVA Base)
X PUR PUX/RUnitsDuty
GEORGIA POWER -
UTILITY-RING-2
BUS-UTILITY-2-RING 480 Amps 6.39Out 83,119
SLG:
3P:
Amps 6.30 0.767 0.128
Pos:
Zero: 98,287
0.224 1.430
GEORGIA POWER
UTILITY-RING-1
C-BUS-UTILITY-1-RIN
G
480 Amps 6.39Out 83,119
SLG:
3P:
Amps 6.30 0.767 0.128
Pos:
Zero: 98,287
0.224 1.430
T13-UTIL T13-BUS-UTIL-PRI 13,800 MVA 9,999.00Out 1,000,000
SLG:
3P:
MVA 9,999.00 0.000 0.000
Pos:
Zero: 333,333
0.000 0.000
Generators
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
-------- Contribution Data --------
Base kVA X" X/R
PU (100 MVA Base)
R PU X PU
A-GEN1 480A-BUS-GEN1 2,500.00 20.00 0.30 6.00In
0.30
6.00 0.30
0.15
0.15
0.15
20.00
20.00 6.00
A-GEN2 480A-BUS-GEN2 2,500.00 20.00 0.30 6.00In
0.30
6.00 0.30
0.15
0.15
0.15
20.00
20.00 6.00
A-GEN3 480A-BUS-GEN3 2,500.00 20.00 0.30 6.00In
0.30
6.00 0.30
0.15
0.15
0.15
20.00
20.00 6.00
A-GEN4 480A-BUS-GEN4 2,500.00 20.00 0.30 6.00In
0.30
6.00 0.30
0.15
0.15
0.15
20.00
20.00 6.00
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
-------- Contribution Data --------
Base kVA X" X/R
PU (100 MVA Base)
R PU X PU
A-GEN5 480A-BUS-GEN5 2,500.00 20.00 0.30 6.00In
0.30
6.00 0.30
0.15
0.15
0.15
20.00
20.00 6.00
B-GENB 480B-BUS-GENB 750.00 20.00 1.00 20.00In
1.00
20.00 1.00
0.15
0.15
0.15
20.00
20.00 20.00
D-GEN-D 480D-BUS-GEN-D 562.50 20.00 1.33 26.67In
1.33
26.67 1.33
0.15
0.15
0.15
20.00
20.00 26.67
Motors
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
--------- Contribution Data --------
Base kVA Xd" X/R
PU (100 MVA Base)
R PU X PU
# of
Motors
A-MTR-CHILLER-OR1 A-BUS-CHILLER-OR1 480 401.08 0.1507 4.90 7.672 37.583In 1
A-MTR-CHILLER-OR2 A-BUS-CHILLER-OR2 480 401.08 0.1507 4.90 7.672 37.583In 1
A-MTR-ELEV-P21 ELEV P21 480 25.07 0.1507 4.90 122.746 601.335In 1
A-MTR-ELEV-S1 A-BUS-ELEV-S1 480 50.13 0.1507 4.90 61.373 300.667In 1
A-MTR-ELEV-S2 A-BUS-ELEV-S2 480 50.13 0.1507 4.90 61.373 300.667In 1
A-MTR-P10 A-BUS-P10-MTR 480 40.11 0.1507 4.90 76.717 375.834In 1
A-MTR-P11 A-BUS-P11-MTR 480 40.11 0.1507 4.90 76.717 375.834In 1
A-MTR-P12 A-BUS-P12-MTR 480 40.11 0.1507 4.90 76.717 375.834In 1
B-MTR-CHILLER-PED B-BUS-CHILLER-PED 480 100.27 0.1507 4.90 30.687 150.334In 1
B-MTR-ELEV-P17 B-BUS-ELEV-P17 480 30.08 0.1507 4.90 102.289 501.112In 1
Bus
Name
In/Out
Service
Nominal
Voltage
--------- Contribution Data --------
Base kVA Xd" X/R
PU (100 MVA Base)
R PU X PU
# of
Motors
B-MTR-ELEV-P18 B-BUS-ELEV P18 480 30.08 0.1507 4.90 102.289 501.112In 1
B-MTR-ELEV-P8 B-BUS-ELEV-P8 480 50.13 0.1507 4.90 61.373 300.667In 1
B-MTR-ELEV-P9 B-BUS-ELEV-P9 480 50.13 0.1507 4.90 61.373 300.667In 1
C-MTR-CHILLER1 C-BUS-CHILLER1-MTR 480 745.00 0.1507 4.90 0.000 0.000In 1
C-MTR-CHILLER2 C-BUS-CHILLER2-MTR 480 741.94 0.1507 4.90 0.000 0.000In 1
C-MTR-CHILLER4 C-BUS-CHILLER4-MTR 480 869.33 0.1507 4.90 0.000 0.000In 1
C-MTR-ELEV13 C-BUS-ELEV13 480 40.11 0.1507 4.90 76.717 375.834In 1
C-MTR-ELEV14 C-BUS-ELEV14 480 40.11 0.1507 4.90 76.717 375.834In 1
C-MTR-ELEV2 C-BUS-ELEV2 480 25.07 0.1507 4.90 122.746 601.335In 1
C-MTR-ELEVS5 C-BUS-ELEVS5 220 55.15 0.1507 4.90 265.597 1,301.161In 1
C-MTR-ELEVS6 C-BUS-ELEVS6 220 55.15 0.1507 4.90 265.597 1,301.161In 1
C-MTR-FIRE-PUMP C-BUS-FIRE-PUMP 480 23.59 0.1507 4.90 130.418 638.918In 1
C-MTR-NPE-1-DISC C-BUS-NPE-1-DISC-(1) 480 10.03 0.1507 4.90 0.000 0.000In 1
C-MTR-P1-ELEV C-BUS-P1-ELEV 208 40.11 0.1507 4.90 76.717 375.834In 1
C-MTR-P2-ELEV C-BUS-P2-ELEV 208 40.11 0.1507 4.90 76.717 375.834In 1
C-MTR-P3-ELEV C-BUS-P3-ELEV 208 40.11 0.1507 4.90 76.717 375.834In 1
Bus
Name
In/Out
Service
Nominal
Voltage
--------- Contribution Data --------
Base kVA Xd" X/R
PU (100 MVA Base)
R PU X PU
# of
Motors
C-MTR-P4-ELEV C-BUS-P4-ELEV 208 40.11 0.1507 4.90 76.717 375.834In 1
D-MTR-ELEV-5 D-BUS-ELEV-5 480 60.16 0.1507 4.90 51.144 250.556In 1
D-MTR-ELEV-6 D-BUS-ELEV-6 480 60.16 0.1507 4.90 51.144 250.556In 1
D-MTR-ELEV-7 D-BUS-ELEV-7 480 60.16 0.1507 4.90 51.144 250.556In 1
E-MTR-ELEV-P19 E-BUS-ELEV-P19 480 50.13 0.1507 4.90 61.373 300.667In 1
E-MTR-ELEV-P20 E-BUS-ELEV-P20 480 40.11 0.1507 4.90 76.717 375.834In 1
F-MTR-ELEV1 F-BUS-ELEV1 480 35.09 0.1507 4.90 87.676 429.525In 1
F-MTR-ELEV2 F-BUS-ELEV2 480 35.09 0.1507 4.90 87.676 429.525In 1
F-MTR-ELEV-F F-BUS-ELEV-F 480 50.13 0.1507 4.90 0.000 0.000In 1
PK-MTR-ELEV-1 PK-BUS-ELEV-1 480 35.09 0.1507 4.90 0.000 0.000In 1
PK-MTR-ELEV-2 PK-BUS-ELEV-2 480 35.09 0.1507 4.90 0.000 0.000In 1
PK-MTR-ELEV-3 PK-BUS-ELEV-3 480 35.09 0.1507 4.90 0.000 0.000In 1
Cables
Cable
Name
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-ATS-E-(L)
A-BUS-CHD-AG-1
2 40 600 PVC Pos:
Zero:
0.2231 0.4019
0.9896
A-CBL-ATS-E-(1) In
0.7023
MagneticCopper
Cable
Name
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-ATS-L-(L)
A-BUS-SHD-AG-1
1 20 3/0 PVC Pos:
Zero:
0.6988 0.4505
1.1094
A-CBL-ATS-L-(1) In
2.2023
MagneticCopper
A-BUS-ATS-MTS-
(L)
A-BUS-EHD-A3-1
1 310 4/0 PVC Pos:
Zero:
8.6111 6.6871
16.4688
A-CBL-ATS-MTS-
(1)
In
27.1385
MagneticCopper
A-BUS-ATS-Q1-
(L)
A-BUS-EHD-AG-1
2 30 500 PVC Pos:
Zero:
0.1914 0.3034
0.7467
A-CBL-ATS-Q1-(1) In
0.6029
A-BUS-ATS-Q2-
(L)
A-BUS-EHD-AG-2
3 180 300 PVC Pos:
Zero:
1.2083 1.2839
3.1615
A-CBL-ATS-Q2-(1) In
3.8073
MagneticCopper
A-BUS-ATS-Q3-
(L)
A-BUS-EHD-AG-3
2 10 500 PVC Pos:
Zero:
0.0638 0.1011
0.2489
A-CBL-ATS-Q3-(1) In
0.2010
MagneticCopper
A-BUS-CHD-AG-1
A-BUS-CHD-AG-1
-(1)-TAP
1 240 4/0 PVC Pos:
Zero:
6.6667 5.1771
12.7500
A-CBL-CHD-AG-1
-(1)
In
21.0104
MagneticCopper
A-BUS-CHD-AG-1
A-BUS-SW-CX-A1
-1-DISC
1 90 1/0 PVC Pos:
Zero:
5.0000 2.1094
5.1914
A-CBL-CHD-AG-1
-(10)
In
15.7578
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-CHD-AG-1
A-BUS-CHD-AG-2
1 240 2 PVC Pos:
Zero:
21.0417 6.0938
15.0000
A-CBL-CHD-AG-1
-(11)
In
66.3125
MagneticCopper
A-BUS-CHD-AG-1
-(1)-TAP
A-BUS-CHL-A4-1
1 3 4/0 PVC Pos:
Zero:
0.0833 0.0647
0.1594
A-CBL-CHD-AG-1
-(1-1)
In
0.2626
MagneticCopper
A-BUS-CHD-AG-1
A-BUS-CX-A3-1-D
ISC
1 240 2 PVC Pos:
Zero:
21.0417 6.0938
15.0000
A-CBL-CHD-AG-1
-(12)
In
66.3125
MagneticCopper
A-BUS-CHD-AG-1
-(1)-TAP
A-BUS-CHL-A5-1
1 15 4/0 PVC Pos:
Zero:
0.4167 0.3236
0.7969
A-CBL-CHD-AG-1
-(1-2)
1.3132
A-BUS-CHD-AG-1
A-BUS-CX-AG-2-
DISC
1 230 6 PVC Pos:
Zero:
50.9115 6.8381
16.8407
A-CBL-CHD-AG-1
-(13)
In
160.4410
MagneticCopper
A-BUS-CHD-AG-1
A-BUS-CHMCC-A
R-1
1 315 4/0 PVC Pos:
Zero:
8.7500 6.7949
16.7344
A-CBL-CHD-AG-1
-(2)
In
27.5762
MagneticCopper
A-BUS-CHD-AG-1
A-BUS-CATHLAB
1 100 3/0 PVC Pos:
Zero:
3.4939 2.2526
5.5469
A-CBL-CHD-AG-1
-(3)
In
11.0113
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-CHD-AG-1
A-BUS-CX-A3-2-D
ISC-1
1 150 1/0 PVC Pos:
Zero:
8.3333 3.5156
8.6523
A-CBL-CHD-AG-1
-(4)
26.2630
A-BUS-CX-A2-1-D
ISC
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
A-CBL-CHD-AG-1
-(5)
In
1.6578
MagneticCopper
A-BUS-CHD-AG-1
A-BUS-CX-A4-2-D
ISC
1 160 2 PVC Pos:
Zero:
14.0278 4.0625
10.0000
A-CBL-CHD-AG-1
-(6)
In
44.2083
MagneticCopper
A-BUS-CHD-AG-1
A-BUS-CX-AG-1-
DISC
1 50 10 PVC Pos:
Zero:
25.6076 1.8533
4.5638
A-CBL-CHD-AG-1
-(7)
In
80.7031
MagneticCopper
A-BUS-CHD-AG-1
A-BUS-CHL-A2-1
1 210 4/0 PVC Pos:
Zero:
5.8333 4.5299
11.1563
A-CBL-CHD-AG-1
-(8)
18.3841
A-BUS-HL-5A-277
1 245 3/0 PVC Pos:
Zero:
8.5601 5.5189
13.5898
A-CBL-CHD-AG-1
-(9)
In
26.9776
MagneticCopper
A-BUS-CHD-AG-2
A-BUS-CHL-A1-1
1 70 6 PVC Pos:
Zero:
15.4948 2.0812
5.1254
A-CBL-CHD-AG-2
-(1)
In
48.8299
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-CHD-AG-2
A-BUS-CX-AG-3-P
RI
1 6 6 PVC Pos:
Zero:
1.3281 0.1784
0.4393
A-CBL-CHD-AG-2
-(2)
In
4.1854
MagneticCopper
A-BUS-CHL-A2-1
A-BUS-CHL-A2-1-
(1)-TAP
1 60 2 PVC Pos:
Zero:
5.2604 1.5234
3.7500
A-CBL-CHL-A2-1-
(1)
16.5781
A-BUS-CHL-A2-1-
(1)-TAP
A-BUS-SW-CX-A2
-2-DISC
1 3 2 PVC Pos:
Zero:
0.2630 0.0762
0.1875
A-CBL-CHL-A2-1-
TAP-(1)
In
0.8289
MagneticCopper
A-BUS-CHL-A2-1-
(1)-TAP
A-BUS-CHL-A3-1
1 75 6 PVC Pos:
Zero:
16.6016 2.2298
5.4915
A-CBL-CHL-A2-1-
TAP-(2)
In
52.3177
MagneticCopper
A-BUS-CHL-A4-1
A-BUS-CX-A4-1-P
RI
1 6 6 PVC Pos:
Zero:
1.3281 0.1784
0.4393
A-CBL-CHL-A4-1-
(1)
In
4.1854
MagneticCopper
A-BUS-CHL-A5-1
A-BUS-CX-A5-1-P
RI
1 6 6 PVC Pos:
Zero:
1.3281 0.1784
0.4393
A-CBL-CHL-A5-1-
(1)
4.1854
A-BUS-CHL-A5-1
A-BUS-CX-A5-2-D
ISC
1 60 1/0 PVC Pos:
Zero:
3.3333 1.4063
3.4609
A-CBL-CHL-A5-1-
(2)
In
10.5052
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-CLD-A1-1
A-BUS-CLP-A5-1
1 80 1/0 PVC Pos:
Zero:
23.6686 9.9852
24.5747
A-CBL-CLD-A1-1-
(1)
In
74.5932
MagneticCopper
A-BUS-CLD-A1-1
A-BUS-CLP-A1-1
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
A-CBL-CLD-A1-1-
(2)
In
22.2892
MagneticCopper
A-BUS-CLD-A1-1
A-BUS-CLP-A4-1
1 80 2 PVC Pos:
Zero:
37.3521 10.8173
26.6272
A-CBL-CLD-A1-1-
(3)
117.7145
A-BUS-CLD-A3-1
A-BUS-CLP-A4-6
1 20 2 PVC Pos:
Zero:
9.3380 2.7043
6.6568
A-CBL-CLD-A3-1-
(1)
In
29.4286
MagneticCopper
A-BUS-CLD-A3-1
A-BUS-CLP-A5-7
1 30 2 PVC Pos:
Zero:
14.0070 4.0565
9.9852
A-CBL-CLD-A3-1-
(2)
In
44.1429
MagneticCopper
A-BUS-CLD-A3-2
A-BUS-CLP-A4-3
1 130 2/0 PVC Pos:
Zero:
30.6490 16.0156
39.4231
A-CBL-CLD-A3-2-
(1)
In
96.5745
MagneticCopper
A-BUS-CLD-A3-2
A-BUS-CLP-A5-4
1 150 1/0 PVC Pos:
Zero:
44.3787 18.7223
46.0776
A-CBL-CLD-A3-2-
(2)
139.8622
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-CLP-A2-1
A-BUS-CLP-A2-1-
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-CLP-A2-1-
(1)
In
2.7972
MagneticCopper
A-BUS-CLP-A2-2
A-BUS-CLP-A2-2-
1 3 4/0 PVC Pos:
Zero:
0.4438 0.3446
0.8487
A-CBL-CLP-A2-2-
(1)
In
1.3986
MagneticCopper
A-BUS-CLP-A2-2-
C-BUS-CLP-C2-5-
(2)
1 3 4/0 PVC Pos:
Zero:
0.4438 0.3446
0.8487
A-CBL-CLP-A2-2-
2-(1)
In
1.3986
MagneticCopper
A-BUS-CLP-A4-2
A-BUS-CLP-A5-3-
1 15 1/0 PVC Pos:
Zero:
4.4379 1.8722
4.6078
A-CBL-CLP-A4-2-
(1)
13.9862
A-BUS-CLP-A4-3
A-BUS-CLP-A4-3-
1 3 2/0 PVC Pos:
Zero:
0.7073 0.3696
0.9098
A-CBL-CLP-A4-3-
(1)
In
2.2286
MagneticCopper
A-BUS-CLP-A4-4
A-BUS-CLP-A4-5
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
A-CBL-CLP-A4-4-
(1)
In
22.2892
MagneticCopper
A-BUS-CLP-A5-1
A-BUS-CLP-A5-2
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
A-CBL-CLP-A5-1-
(1)
In
22.2892
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-CLP-A5-3-
A-BUS-CLP-A5-3
1 3 1/0 PVC Pos:
Zero:
0.8876 0.3744
0.9216
A-CBL-CLP-A5-3-
2-(1)
2.7972
A-BUS-CLP-A5-4
A-BUS-CLP-A5-5
1 10 6 PVC Pos:
Zero:
11.7881 1.5833
3.8993
A-CBL-CLP-A5-4-
(1)
In
37.1487
MagneticCopper
A-BUS-CLP-AG-2
A-BUS-CLP-A1-2
1 100 6 PVC Pos:
Zero:
117.8809 15.8330
38.9932
A-CBL-CLP-AG-2-
(1)
In
371.4867
MagneticCopper
A-BUS-CLP-AG-3
A-BUS-CLP-AG-3-
1 5 3/0 PVC Pos:
Zero:
0.9303 0.5998
1.4770
A-CBL-CLP-AG-3-
(1)
In
2.9320
MagneticCopper
A-BUS-CX-A1-1-S
EC
A-BUS-CLD-A1-1
1 6 500 PVC Pos:
Zero:
0.4077 0.6463
1.5907
A-CBL-CX-A1-1-
(1)
1.2842
A-BUS-SW-CX-A1
-1-DISC
A-BUS-CX-A1-1-P
RI
1 3 1/0 PVC Pos:
Zero:
0.1667 0.0703
0.1730
A-CBL-CX-A1-1-D
ISC-(1)
In
0.5253
MagneticCopper
A-BUS-CX-A2-1-S
EC
A-BUS-CLP-A2-1
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-CX-A2-1-
(1)
In
2.7972
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-CX-A2-1-D
ISC
A-BUS-CX-A2-1-P
RI
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
A-CBL-CX-A2-1-D
ISC-(1)
In
1.6578
MagneticCopper
A-BUS-CX-A2-2-S
EC
A-BUS-CLP-A2-2
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-CX-A2-2-
(1)
A-BUS-SW-CX-A2
-2-DISC
A-BUS-CX-A2-2-P
RI
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
A-CBL-CX-A2-2-D
ISC-(1)
In
1.6578
MagneticCopper
A-BUS-CX-A3-1-S
EC
A-BUS-CLD-A3-1
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-CX-A3-1-
(1)
In
2.7972
MagneticCopper
A-BUS-CX-A3-1-D
ISC
A-BUS-CX-A3-1-P
RI
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
A-CBL-CX-A3-1-D
ISC-(1)
In
1.6578
MagneticCopper
A-BUS-CX-A3-2-S
EC
A-BUS-CLD-A3-2
1 6 500 PVC Pos:
Zero:
0.4077 0.6463
1.5907
A-CBL-CX-A3-2-
(1)
A-BUS-CX-A3-2-D
ISC-1
A-BUS-CX-A3-2-P
RI
1 6 1/0 PVC Pos:
Zero:
0.3333 0.1406
0.3461
A-CBL-CX-A3-2-D
ISC
In
1.0505
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-CX-A4-1-S
EC
A-BUS-CLP-A4-4
1 6 3/0 PVC Pos:
Zero:
1.1164 0.7198
1.7724
A-CBL-CX-A4-1-
(1)
In
3.5184
MagneticCopper
A-BUS-CX-A4-2-S
EC
A-BUS-CLP-A4-2
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-CX-A4-2-
(1)
In
2.7972
MagneticCopper
A-BUS-CX-A4-2-D
ISC
A-BUS-CX-A4-2-P
RI
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
A-CBL-CX-A4-2-D
ISC
1.6578
A-BUS-CX-A5-1-S
EC
A-BUS-CLP-A5-6
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-CX-A5-1-
(1)
In
2.7972
MagneticCopper
A-BUS-CX-A5-2-S
EC
A-BUS-CLP-A5-8
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-CX-A5-2-
(1)
In
2.7972
MagneticCopper
A-BUS-CX-A5-2-D
ISC
A-BUS-CX-A5-2-P
RI
1 8 1/0 PVC Pos:
Zero:
0.4444 0.1875
0.4615
A-CBL-CX-A5-2-D
ISC-(1)
In
1.4007
MagneticCopper
A-BUS-CX-AG-1-S
EC
A-BUS-CLP-AG-1
1 5 6 PVC Pos:
Zero:
5.8940 0.7917
1.9497
A-CBL-CX-AG-1-
(1)
18.5743
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-CX-AG-1-
DISC
A-BUS-CX-AG-1-P
RI
1 5 10 PVC Pos:
Zero:
2.5608 0.1853
0.4564
A-CBL-CX-AG-1-
DISC-(1)
In
8.0703
MagneticCopper
A-BUS-CX-AG-2-S
EC
A-BUS-CLP-AG-2
1 5 2 PVC Pos:
Zero:
2.3345 0.6761
1.6642
A-CBL-CX-AG-2-
(1)
In
7.3572
MagneticCopper
A-BUS-CX-AG-2-
DISC
A-BUS-CX-AG-2-P
RI
1 5 6 PVC Pos:
Zero:
1.1068 0.1487
0.3661
A-CBL-CX-AG-2-
DISC-(1)
In
3.4878
MagneticCopper
A-BUS-CX-AG-3-S
EC
A-BUS-CLP-AG-3
1 6 3/0 PVC Pos:
Zero:
1.1164 0.7198
1.7724
A-CBL-CX-AG-3-
(1)
3.5184
A-BUS-ED
A-BUS-GHATS-A
G-1-(N)
1 20 2/0 PVC Pos:
Zero:
0.8854 0.4627
1.1389
A-CBL-ED-(1) In
2.7899
MagneticCopper
A-BUS-ED
A-BUS-ATS-L-(N)
1 35 3/0 PVC Pos:
Zero:
1.2229 0.7884
1.9414
A-CBL-ED-(2) In
3.8539
MagneticCopper
A-BUS-ED
A-BUS-ATS-MTS-
(N)
1 35 4/0 PVC Pos:
Zero:
0.9722 0.7550
1.8594
A-CBL-ED-(3) In
3.0640
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-ED
A-BUS-ATS-Q2-
(N)
2 35 500 PVC Pos:
Zero:
0.2233 0.3539
0.8712
A-CBL-ED-(4) In
0.7033
A-BUS-ED
A-BUS-ATS-E-(N)
2 35 500 PVC Pos:
Zero:
0.2233 0.3539
0.8712
A-CBL-ED-(5) In
0.7033
MagneticCopper
A-BUS-ED
A-BUS-ATS-Q1-
(N)
3 35 300 PVC Pos:
Zero:
0.2350 0.2496
0.6147
A-CBL-ED-(6) In
0.7403
MagneticCopper
A-BUS-ED
A-BUS-ATS-Q3-
(N)
2 35 500 PVC Pos:
Zero:
0.2233 0.3539
0.8712
A-CBL-ED-(7) In
0.7033
MagneticCopper
A-BUS-EHD-A3-1
A-BUS-UPS-COM
PR-IN
1 10 1/0 PVC Pos:
Zero:
0.5556 0.2344
0.5768
A-CBL-EHD-A3-1-
(1)
1.7509
A-BUS-EHD-A3-1
A-BUS-XF-EX-A3-
2-PRI
1 10 1/0 PVC Pos:
Zero:
0.5556 0.2344
0.5768
A-CBL-EHD-A3-1-
(2)
In
1.7509
MagneticCopper
A-BUS-EHD-A4-1
A-BUS-EX-A4-1-D
ISC
1 20 6 PVC Pos:
Zero:
4.4271 0.5946
1.4644
A-CBL-EHD-A4-1(
1)
In
13.9514
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-EHD-A4-1
A-BUS-EX-A5-1-D
ISC
1 50 10 PVC Pos:
Zero:
25.6076 1.8533
4.5638
A-CBL-EHD-A4-1(
2)
In
80.7031
MagneticCopper
A-BUS-EHD-A4-1
A-BUS-EHPP-A5-1
1 50 4/0 PVC Pos:
Zero:
1.3889 1.0786
2.6563
A-CBL-EHD-A4-1(
3)
4.3772
A-BUS-EHD-A4-2
A-BUS-EX-A3-1-D
ISC
1 95 8 PVC Pos:
Zero:
33.4397 3.1089
7.6528
A-CBL-EHD-A4-2-
(1)
In
105.3865
MagneticCopper
A-BUS-EHD-AG-1
A-BUS-EHP-A2-1
1 130 350 PVC Pos:
Zero:
2.1328 2.7704
6.8216
A-CBL-EHD-AG-1
-(1)
In
6.7201
MagneticCopper
A-BUS-EHD-AG-1
A-BUS-EHP-AR-1
1 150 350 PVC Pos:
Zero:
2.4609 3.1966
7.8711
A-CBL-EHD-AG-1
-(3)
In
7.7539
MagneticCopper
A-BUS-EHD-AG-1
A-BUS-EX-A1-2-D
ISC
1 70 6 PVC Pos:
Zero:
15.4948 2.0812
5.1254
A-CBL-EHD-AG-1
-(4)
48.8299
A-BUS-EHD-AG-2
A-BUS-EHP-AR-2
1 125 500 PVC Pos:
Zero:
1.5951 2.5282
6.2229
A-CBL-EHD-AG-2
-(1)
In
5.0239
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-EHD-AG-2
A-BUS-EHD-A4-2
1 140 500 PVC Pos:
Zero:
1.7865 2.8316
6.9696
A-CBL-EHD-AG-2
-(2)
In
5.6267
MagneticCopper
A-BUS-EHD-AG-2
A-BUS-EHL-A1-1
1 6 4 PVC Pos:
Zero:
0.8359 0.1646
0.4052
A-CBL-EHD-AG-2
-(3)
In
2.6344
MagneticCopper
A-BUS-EHD-AG-3
A-BUS-EHD-A4-1
2 140 250 PVC Pos:
Zero:
1.6771 1.5039
3.7036
A-CBL-EHD-AG-3
-(1)
5.2834
A-BUS-EHD-AG-3
A-BUS-EHDP-AB-
1 45 4/0 PVC Pos:
Zero:
1.2500 0.9707
2.3906
A-CBL-EHD-AG-3
-(2)
In
3.9395
MagneticCopper
A-BUS-EHDP-AB-
A-BUS-EX-AB-1-P
RI
1 5 8 PVC Pos:
Zero:
1.7600 0.1636
0.4028
A-CBL-EHDP-AB-
1-(1)
In
5.5467
MagneticCopper
A-BUS-EHL-A1-1
A-BUS-EX-A1-1-P
RI
1 3 8 PVC Pos:
Zero:
1.0560 0.0982
0.2417
A-CBL-EHL-A1-1-
(1)
In
3.3280
MagneticCopper
A-BUS-EHP-A2-1
A-BUS-EHP-A2-1-
1 3 350 PVC Pos:
Zero:
0.0492 0.0639
0.1574
A-CBL-EHP-A2-1-
(1)
0.1551
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-EHP-AR-1
A-BUS-EX-AR-1-P
RI
1 150 6 PVC Pos:
Zero:
33.2031 4.4596
10.9831
A-CBL-EHP-AR-1-
(1)
In
104.6354
MagneticCopper
A-BUS-EHP-AR-1
A-BUS-S2-DISC-1
1 20 2 PVC Pos:
Zero:
1.7535 0.5078
1.2500
A-CBL-EHP-AR-1-
(2)
In
5.5260
MagneticCopper
A-BUS-EHP-AR-1
A-BUS-S1-DISC-1
1 20 2 PVC Pos:
Zero:
1.7535 0.5078
1.2500
A-CBL-EHP-AR-1-
(3)
In
5.5260
MagneticCopper
A-BUS-EHP-AR-2
A-BUS-EHP-AR-2-
1 3 500 PVC Pos:
Zero:
0.0383 0.0607
0.1493
A-CBL-EHP-AR-2-
(1)
0.1206
A-BUS-EHP-AR-2
A-BUS-P10-DISC-
1 50 2 PVC Pos:
Zero:
4.3837 1.2695
3.1250
A-CBL-EHP-AR-2-
(2)
In
13.8151
MagneticCopper
A-BUS-EHP-AR-2-
A-BUS-P11-DISC-
1 50 2 PVC Pos:
Zero:
4.3837 1.2695
3.1250
A-CBL-EHP-AR-2-
2-(1)
In
13.8151
MagneticCopper
A-BUS-EHP-AR-2-
A-BUS-P12-DISC-
1 50 2 PVC Pos:
Zero:
4.3837 1.2695
3.1250
A-CBL-EHP-AR-2-
2-(2)
In
13.8151
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-EHP-AR-2-
A-BUS-EX-AR-2-P
RI
1 6 8 PVC Pos:
Zero:
2.1120 0.1964
0.4833
A-CBL-EHP-AR-2-
2-(3)
6.6560
A-BUS-ELR-A3-1
A-BUS-ELR-A3-2
1 6 250 PVC Pos:
Zero:
0.7655 0.6865
1.6906
A-CBL-ELR-A3-1-
(1)
In
2.4117
MagneticCopper
A-BUS-ELR-A3-2
A-BUS-ELR-A3-3
1 6 250 PVC Pos:
Zero:
0.7655 0.6865
1.6906
A-CBL-ELR-A3-1-
(2)
In
2.4117
MagneticCopper
A-BUS-EX-A1-1-S
EC
A-BUS-ELP-A1-1
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
A-CBL-EX-A1-1-
(1)
In
22.2892
MagneticCopper
A-BUS-EX-A1-2-S
EC
A-BUS-ELP-A1-2
1 6 3/0 PVC Pos:
Zero:
1.1164 0.7198
1.7724
A-CBL-EX-A1-2-
(1)
3.5184
A-BUS-EX-A1-2-D
ISC
A-BUS-EX-A1-2-P
RI
1 4 6 PVC Pos:
Zero:
0.8854 0.1189
0.2929
A-CBL-EX-A1-2-D
ISC-(1)
In
2.7903
MagneticCopper
A-BUS-EX-A3-1-S
EC
A-BUS-ELP-A3-1
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
A-CBL-EX-A3-1-
(1)
In
8.8286
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-EX-A3-1-D
ISC
A-BUS-EX-A3-1-P
RI
1 5 8 PVC Pos:
Zero:
1.7600 0.1636
0.4028
A-CBL-EX-A3-1-D
ISC-(1)
In
5.5467
MagneticCopper
A-BUS-EX-A3-2-S
EC
A-BUS-ELR-A3-1
1 70 250 PVC Pos:
Zero:
8.9312 8.0090
19.7231
A-CBL-EX-A3-2-
(1)
28.1366
A-BUS-EX-A4-1-S
EC
A-BUS-ELP-A4-1
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-EX-A4-1-
(1)
In
2.7972
MagneticCopper
A-BUS-EX-A4-1-D
ISC
A-BUS-EX-A4-1-P
RI
1 6 6 PVC Pos:
Zero:
1.3281 0.1784
0.4393
A-CBL-EX-A4-1-D
ISC
In
4.1854
MagneticCopper
A-BUS-EX-A5-1-S
EC
A-BUS-ELP-A5-1
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
A-CBL-EX-A5-1-
(1)
In
22.2892
MagneticCopper
A-BUS-EX-A5-1-D
ISC
A-BUS-EX-A5-1-P
RI
1 6 10 PVC Pos:
Zero:
3.0729 0.2224
0.5477
A-CBL-EX-A5-1-D
ISC
9.6844
A-BUS-EX-AB-1-S
EC
A-BUS-ELP-AB-1
1 5 2 PVC Pos:
Zero:
2.3345 0.6761
1.6642
A-CBL-EX-AB-1-
(1)
In
7.3572
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-EX-AR-1-S
EC
A-BUS-ELP-AR-1
1 6 10 PVC Pos:
Zero:
16.3646 1.1844
2.9165
A-CBL-EX-AR-1-
(1)
In
51.5736
MagneticCopper
A-BUS-EX-AR-2-S
EC
A-BUS-ELP-AR-2
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
A-CBL-EX-AR-2-
(1)
In
22.2892
MagneticCopper
A-BUS-GEN1
A-BUS-GHSB-CB-
7 320 600 PVC Pos:
Zero:
0.5099 0.9187
2.2619
A-CBL-GEN1 In
1.6052
A-BUS-GEN2
A-BUS-GHSB-CB-
7 340 600 PVC Pos:
Zero:
0.5418 0.9761
2.4033
A-CBL-GEN2 In
1.7055
MagneticCopper
A-BUS-GEN3
A-BUS-GHSB-AG-
10 110 600 PVC Pos:
Zero:
0.1227 0.2211
0.5443
A-CBL-GEN3 In
0.3862
MagneticCopper
A-BUS-GEN4
A-BUS-GHSB-AG-
10 90 600 PVC Pos:
Zero:
0.1004 0.1809
0.4453
A-CBL-GEN4 In
0.3160
MagneticCopper
A-BUS-GEN5
A-BUS-GHSB-AG-
10 70 600 PVC Pos:
Zero:
0.0781 0.1407
0.3464
A-CBL-GEN5 In
0.2458
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-GHATS-A
G-1-(L)
A-BUS-GHECB-A
G-1
1 6 2/0 PVC Pos:
Zero:
0.2656 0.1388
0.3417
A-CBL-GHATS-A
G-1-(1)
In
0.8370
MagneticCopper
A-BUS-GHECB-A
G-1
A-BUS-GLX-AG-1-
PRI
1 6 2/0 PVC Pos:
Zero:
0.2656 0.1388
0.3417
A-CBL-GHECB-A
G-1-(1)
In
0.8370
MagneticCopper
A-BUS-GHSB-AG-
A-BUS-GHTA-AG-
8 15 600 PVC Pos:
Zero:
0.0209 0.0377
0.0928
A-CBL-GHSB-AG-
1-(1)
In
0.0658
MagneticCopper
A-BUS-GHSB-AG-
A-BUS-GHSB-CB-
10 3 600 PVC Pos:
Zero:
0.0033 0.0060
0.0148
A-CBL-GHSB-AG-
1-(10)
0.0105
A-BUS-GHSB-AG-
C-BUS-GHTA-CB-
4 200 600 PVC Pos:
Zero:
0.5577 1.0048
2.4740
A-CBL-GHSB-AG-
1-(2)
In
1.7556
MagneticCopper
A-BUS-GHSB-AG-
C-BUS-GHTA-CB-
4 100 600 PVC Pos:
Zero:
0.2789 0.5024
1.2370
A-CBL-GHSB-AG-
1(4)
In
0.8778
MagneticCopper
A-BUS-GHSB-AG-
A-BUS-GHATS-A
G-1-(E)
1 35 2/0 PVC Pos:
Zero:
1.5495 0.8097
1.9931
A-CBL-GHSB-AG-
1(5)
In
4.8824
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-GHSB-AG-
A-BUS-GHSB-AG-
1-DUCT-(1)
10 10 600 PVC Pos:
Zero:
0.0112 0.0201
0.0495
A-CBL-GHSB-AG-
1-(6)
0.0351
A-BUS-GHSB-AG-
1-DUCT-(2)
10 15 600 PVC Pos:
Zero:
0.0167 0.0301
0.0742
A-CBL-GHSB-AG-
1-(7)
In
0.0527
MagneticCopper
A-BUS-GHSB-AG-
A-BUS-GHSB-AG-
6 10 600 PVC Pos:
Zero:
0.0186 0.0335
0.0825
A-CBL-GHSB-AG-
1-(9)
In
0.0585
MagneticCopper
A-BUS-GHSB-AG-
1-DUCT-(1)
A-BUS-NHSB-C3-
2-DUCT
1 280 4000 Epoxy Pos:
Zero:
0.4010 0.2309
1.2274
A-CBL-GHSB-AG-
1-DUCT-(1)
In
2.3819
BuswayCopper
A-BUS-GHSB-AG-
1-DUCT-(2)
C-BUS-NHSB-C3-
1-DUCT
1 265 4000 Epoxy Pos:
Zero:
0.3796 0.2185
1.1617
A-CBL-GHSB-AG-
1-DUCT-(2)
2.2543
BuswayCopper
A-BUS-ATS-Q1-
(E)
2 30 600 PVC Pos:
Zero:
0.1673 0.3014
0.7422
A-CBL-GHSB-AG-
2-(1)
In
0.5267
MagneticCopper
A-BUS-GHSB-AG-
A-BUS-ATS-E-(E)
2 20 600 PVC Pos:
Zero:
0.1115 0.2010
0.4948
A-CBL-GHSB-AG-
2-(2)
In
0.3511
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-GHSB-AG-
A-BUS-ATS-Q3-
(E)
2 40 600 PVC Pos:
Zero:
0.2231 0.4019
0.9896
A-CBL-GHSB-AG-
2-(3)
In
0.7023
MagneticCopper
A-BUS-GHSB-AG-
A-BUS-ATS-Q2-
(E)
3 40 300 PVC Pos:
Zero:
0.2685 0.2853
0.7025
A-CBL-GHSB-AG-
2-(4)
0.8461
A-BUS-ATS-MTS-
(E)
1 40 4/0 PVC Pos:
Zero:
1.1111 0.8628
2.1250
A-CBL-GHSB-AG-
2-(5)
In
3.5017
MagneticCopper
A-BUS-GHSB-AG-
A-BUS-ATS-L-(E)
1 50 3/0 PVC Pos:
Zero:
1.7470 1.1263
2.7734
A-CBL-GHSB-AG-
2-(6)
In
5.5056
MagneticCopper
A-BUS-GHSB-CB-
A-BUS-SHATS-CB
-1-(E)
1 20 350 PVC Pos:
Zero:
0.3281 0.4262
1.0495
A-CBL-GHSB-CB-
1-(2)
In
1.0339
MagneticCopper
A-BUS-GHSB-CB-
C-BUS-SHD-C3-2
2 260 600 PVC Pos:
Zero:
1.4501 2.6124
6.4323
A-CBL-GHSB-CB-
1-(3)
4.5647
A-BUS-GHSB-CB-
A-BUS-GHSB-CB-
1-DUCT-(1)
12 260 600 PVC Pos:
Zero:
0.2417 0.4354
1.0720
A-CBL-GHSB-CB-
1-(4)
In
0.7608
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-GHSB-CB-
C-BUS-ATS-F-(E)
1 95 2 PVC Pos:
Zero:
8.3290 2.4121
5.9375
A-CBL-GHSB-CB-
1-(5)
In
26.2487
MagneticCopper
A-BUS-GHSB-CB-
F-BUS-ATS-PG-(E)
1 275 500 PVC Pos:
Zero:
3.5091 5.5621
13.6903
A-CBL-GHSB-CB-
1-(6)
In
11.0525
MagneticCopper
A-BUS-GHSB-CB-
C-BUS-ATS-2-(E)
1 675 600 PVC Pos:
Zero:
7.5293 13.5645
33.3984
A-CBL-GHSB-CB-
1-(7)
23.7012
A-BUS-GHSB-CB-
C-BUS-EHATS-CB
-1-(E)
5 85 600 PVC Pos:
Zero:
0.1896 0.3416
0.8411
A-CBL-GHSB-CB-
1-(8)
In
0.5969
MagneticCopper
A-BUS-GHSB-CB-
1-DUCT-(1)
C-BUS-GHSB-C3-
1 5 4000 Epoxy Pos:
Zero:
0.0072 0.0041
0.0219
A-CBL-GHSB-CB-
1-DUCT-(1)
In
0.0425
BuswayCopper
A-BUS-GHTA-AG-
A-BUS-SWBD-C
8 35 600 PVC Pos:
Zero:
0.0488 0.0879
0.2165
A-CBL-GHTA-AG-
1-(1)
In
0.1536
MagneticCopper
A-BUS-GLD-AG-1
A-BUS-GEN3PNL
1 110 1 PVC Pos:
Zero:
40.6805 14.4924
35.6717
A-CBL-GLD-AG-1-
(1)
128.1943
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-GLD-AG-1
A-BUS-GEN4PNL
1 90 1 PVC Pos:
Zero:
33.2840 11.8574
29.1859
A-CBL-GLD-AG-1-
(2)
In
104.8863
MagneticCopper
A-BUS-GLD-AG-1
A-BUS-GEN5PNL
1 70 1 PVC Pos:
Zero:
25.8876 9.2224
22.7002
A-CBL-GLD-AG-1-
(3)
In
81.5782
MagneticCopper
A-BUS-GLX-AG-1-
SEC
A-BUS-GLD-AG-1
1 15 500 PVC Pos:
Zero:
1.0193 1.6157
3.9767
A-CBL-GLX-AG-1-
(1)
In
3.2105
MagneticCopper
A-BUS-HL-5A-277
A-BUS-HL-5A-277
-2
1 3 1/0 PVC Pos:
Zero:
0.1667 0.0703
0.1730
A-CBL-HL-5A-277
-(1)
0.5253
A-BUS-HL-5A-277
-2
A-BUS-UPS-NEUR
O-PRI
1 6 10 PVC Pos:
Zero:
3.0729 0.2224
0.5477
A-CBL-HL-5A-277
-2-(1)
In
9.6844
MagneticCopper
A-BUS-NHD-A1-1
A-BUS-NX-A4-5-D
ISC
1 6 1/0 PVC Pos:
Zero:
0.3333 0.1406
0.3461
A-CBL-NHD-A1-1-
(1)
In
1.0505
MagneticCopper
A-BUS-NHD-A1-1
A-BUS-NX-A2-5-D
ISC
1 60 2 PVC Pos:
Zero:
5.2604 1.5234
3.7500
A-CBL-NHD-A1-1-
(3)
In
16.5781
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NHD-A1-1
A-BUS-NX-A3-5-D
ISC
1 75 8 PVC Pos:
Zero:
26.3997 2.4544
6.0417
A-CBL-NHD-A1-1-
(4)
83.1999
A-BUS-NHD-A1-1
A-BUS-T1A5A-PRI
1 6 1 PVC Pos:
Zero:
0.4167 0.1484
0.3654
A-CBL-NHD-A1-1-
(5)
In
1.3130
MagneticCopper
A-BUS-NHD-A1-1
A-BUS-NX-A5-5-D
ISC
1 105 1/0 PVC Pos:
Zero:
5.8333 2.4609
6.0566
A-CBL-NHD-A1-1-
(6)
In
18.3841
MagneticCopper
A-BUS-NHD-A1-1
A-BUS-NX-A5-6-D
ISC
1 170 6 PVC Pos:
Zero:
37.6302 5.0543
12.4475
A-CBL-NHD-A1-1-
(7)
In
118.5868
MagneticCopper
A-BUS-NHD-A1-1
A-BUS-NX-A1-5-D
ISC
1 6 10 PVC Pos:
Zero:
3.0729 0.2224
0.5477
A-CBL-NHD-A1-1-
(8)
A-BUS-NHL-A5-2
A-BUS-NX-A5-2-P
RI
1 6 1/0 PVC Pos:
Zero:
0.3333 0.1406
0.3461
A-CBL-NHD-A5-2-
(1)
In
1.0505
MagneticCopper
A-BUS-NHD-AG-1
A-BUS-NHD-AG-1
-TAP
1 45 350 PVC Pos:
Zero:
0.7383 0.9590
2.3613
A-CBL-NHD-AG-1
-(1)
In
2.3262
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NHD-AG-1
A-BUS-NHD-AG-1
-2-TAP
1 60 1/0 PVC Pos:
Zero:
3.3333 1.4063
3.4609
A-CBL-NHD-AG-1
-(2)
In
10.5052
MagneticCopper
A-BUS-NHD-AG-1
A-BUS-NHL-A5-1
1 75 1/0 PVC Pos:
Zero:
4.1667 1.7578
4.3262
A-CBL-NHD-AG-1
-(3)
13.1315
A-BUS-NHD-AG-1
A-BUS-NHL-AG-1
1 12 3 PVC Pos:
Zero:
1.3177 0.3151
0.7755
A-CBL-NHD-AG-1
-(4)
In
4.1526
MagneticCopper
A-BUS-NHD-AG-1
-2-TAP
A-BUS-NHL-A1-1
1 3 2 PVC Pos:
Zero:
0.2630 0.0762
0.1875
A-CBL-NHD-AG-1
-2-TAP-(1)
In
0.8289
MagneticCopper
A-BUS-NHD-AG-1
-2-TAP
A-BUS-NHL-A2-1
1 15 1/0 PVC Pos:
Zero:
0.8333 0.3516
0.8652
A-CBL-NHD-AG-1
-2-TAP-(2)
In
2.6263
MagneticCopper
A-BUS-NHD-AG-1
-TAP
A-BUS-NHL-A3-1
1 3 2 PVC Pos:
Zero:
0.2630 0.0762
0.1875
A-CBL-NHD-AG-1
-TAP-(1)
0.8289
A-BUS-NHD-AG-1
-TAP
A-BUS-NHL-A4-1
1 15 350 PVC Pos:
Zero:
0.2461 0.3197
0.7871
A-CBL-NHD-AG-1
-TAP-(2)
In
0.7754
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NHD-AG-2
A-BUS-NHL-A5-2
1 135 3/0 PVC Pos:
Zero:
4.7168 3.0410
7.4883
A-CBL-NHD-AG-2
(1)
In
14.8652
MagneticCopper
A-BUS-NHD-AG-2
A-BUS-NHD-AG-2
-(2)-TAP
1 105 1/0 PVC Pos:
Zero:
5.8333 2.4609
6.0566
A-CBL-NHD-AG-2
(2)
In
18.3841
MagneticCopper
A-BUS-NHD-AG-2
-(2)-TAP
A-BUS-NHL-A3-2
1 6 6 PVC Pos:
Zero:
1.3281 0.1784
0.4393
A-CBL-NHD-AG-2
-(2)-TAP-(1)
A-BUS-NHD-AG-2
-(2)-TAP
A-BUS-NHL-A4-2
1 15 1/0 PVC Pos:
Zero:
0.8333 0.3516
0.8652
A-CBL-NHD-AG-2
-(2)-TAP-(2)
In
2.6263
MagneticCopper
A-BUS-NHD-AG-2
A-BUS-NHD-AG-2
-(3)-TAP
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
A-CBL-NHD-AG-2
(3)
In
8.7543
MagneticCopper
A-BUS-NHD-AG-2
-(3)-TAP
A-BUS-NHL-A1-2
1 3 2 PVC Pos:
Zero:
0.2630 0.0762
0.1875
A-CBL-NHD-AG-2
-(3)-TAP-(1)
In
0.8289
MagneticCopper
A-BUS-NHD-AG-2
-(3)-TAP
A-BUS-NHL-A2-2
1 55 1/0 PVC Pos:
Zero:
3.0556 1.2891
3.1725
A-CBL-NHD-AG-2
-(3)-TAP-(2)
9.6298
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NHD-AG-2
A-BUS-NHL-AG-2
1 5 2 PVC Pos:
Zero:
0.4384 0.1270
0.3125
A-CBL-NHD-AG-2
(4)
In
1.3815
MagneticCopper
A-BUS-NHD-AG-3
A-BUS-NX-A4-3-D
ISC
1 130 1/0 PVC Pos:
Zero:
7.2222 3.0469
7.4987
A-CBL-NHD-AG-3
-(1)
In
22.7613
MagneticCopper
A-BUS-NHD-AG-3
A-BUS-NX-A5-3-D
ISC
1 150 1/0 PVC Pos:
Zero:
8.3333 3.5156
8.6523
A-CBL-NHD-AG-3
-(2)
In
26.2630
MagneticCopper
A-BUS-NHD-AG-3
A-BUS-NX-A5-7-D
ISC
1 195 2 PVC Pos:
Zero:
17.0964 4.9512
12.1875
A-CBL-NHD-AG-3
-(3)
53.8789
A-BUS-NHD-AG-4
A-BUS-NHL-A1-3
1 50 4/0 PVC Pos:
Zero:
1.3889 1.0786
2.6563
A-CBL-NHD-AG-4
-(1)
In
4.3772
MagneticCopper
A-BUS-NHD-AG-4
A-BUS-NHL-A2-3
1 105 2 PVC Pos:
Zero:
9.2057 2.6660
6.5625
A-CBL-NHD-AG-4
-(2)
In
29.0117
MagneticCopper
A-BUS-NHD-AG-4
A-BUS-NX-AG-5-
DISC
1 140 1 PVC Pos:
Zero:
9.7222 3.4635
8.5252
A-CBL-NHD-AG-4
-(3)
In
30.6372
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NHD-AG-4
A-BUS-NX-AG-3-P
RI
1 8 2 PVC Pos:
Zero:
0.7014 0.2031
0.5000
A-CBL-NHD-AG-4
-(4)
2.2104
A-BUS-NHD-AG-4
A-BUS-NX-A3-3-D
ISC
1 120 8 PVC Pos:
Zero:
42.2396 3.9271
9.6667
A-CBL-NHD-AG-4
-(5)
In
133.1198
MagneticCopper
A-BUS-NHD-AG-5
A-BUS-NHL-A1-5
1 110 250 PVC Pos:
Zero:
2.6354 2.3633
5.8199
A-CBL-NHD-AG-5
-(1)
In
8.3025
MagneticCopper
A-BUS-NHD-AG-5
A-BUS-NHD-AG-5
-(3)-TAP
1 50 4/0 PVC Pos:
Zero:
1.3889 1.0786
2.6563
A-CBL-NHD-AG-5
-(3)
In
4.3772
MagneticCopper
A-BUS-NHD-AG-5
-(3)-TAP
A-BUS-NHL-A1-4
1 10 1/0 PVC Pos:
Zero:
0.5556 0.2344
0.5768
A-CBL-NHD-AG-5
-(3)-TAP-(1)
1.7509
A-BUS-NHD-AG-5
-(3)-TAP
A-BUS-NHL-A2-4
1 55 4/0 PVC Pos:
Zero:
1.5278 1.1864
2.9219
A-CBL-NHD-AG-5
-(3)-TAP-(2)
In
4.8149
MagneticCopper
A-BUS-NHD-AG-5
A-BUS-NHD-AG-5
-(4)-TAP
1 45 4/0 PVC Pos:
Zero:
1.2500 0.9707
2.3906
A-CBL-NHD-AG-5
-(4)
In
3.9395
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NHD-AG-5
A-BUS-NHL-A5-3
1 75 1/0 PVC Pos:
Zero:
4.1667 1.7578
4.3262
A-CBL-NHD-AG-5
-(5)
In
13.1315
MagneticCopper
A-BUS-NHD-AG-5
A-BUS-NHL-AG-3
1 12 1 PVC Pos:
Zero:
0.8333 0.2969
0.7307
A-CBL-NHD-AG-5
-(6)
2.6260
A-BUS-NHL-A1-1
A-BUS-NX-A1-1-P
RI
1 6 6 PVC Pos:
Zero:
1.3281 0.1784
0.4393
A-CBL-NHL-A1-1-
(1)
In
4.1854
MagneticCopper
A-BUS-NHL-A1-2
A-BUS-NX-A1-2-P
RI
1 3 10 PVC Pos:
Zero:
1.5365 0.1112
0.2738
A-CBL-NHL-A1-2-
(1)
In
4.8422
MagneticCopper
A-BUS-NHL-A1-3
A-BUS-NX-A1-3-P
RI
1 6 2/0 PVC Pos:
Zero:
0.2656 0.1388
0.3417
A-CBL-NHL-A1-3-
(1)
In
0.8370
MagneticCopper
A-BUS-NHL-A1-4
A-BUS-NX-A1-4-P
RI
1 6 4 PVC Pos:
Zero:
0.8359 0.1646
0.4052
A-CBL-NHL-A1-4-
(2)
2.6344
A-BUS-NHL-A1-5
A-BUS-NX-A1-6-P
RI
1 6 1/0 PVC Pos:
Zero:
0.3333 0.1406
0.3461
A-CBL-NHL-A1-5-
(1)
In
1.0505
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NHL-A2-1
A-BUS-NX-A2-1-P
RI
1 6 8 PVC Pos:
Zero:
2.1120 0.1964
0.4833
A-CBL-NHL-A2-1-
(1)
In
6.6560
MagneticCopper
A-BUS-NHL-A2-2
A-BUS-NX-A2-2-P
RI
1 6 8 PVC Pos:
Zero:
2.1120 0.1964
0.4833
A-CBL-NHL-A2-2-
(1)
In
6.6560
MagneticCopper
A-BUS-NHL-A2-3
A-BUS-NX-A2-3-P
RI
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
A-CBL-NHL-A2-3-
(1)
A-BUS-NHL-A2-4
A-BUS-NX-A2-4-P
RI
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
A-CBL-NHL-A2-4-
(1)
In
1.6578
MagneticCopper
A-BUS-NHL-A3-1
A-BUS-NX-A3-1-P
RI
1 6 6 PVC Pos:
Zero:
1.3281 0.1784
0.4393
A-CBL-NHL-A3-1-
(1)
In
4.1854
MagneticCopper
A-BUS-NHL-A3-2
A-BUS-NX-A3-2-P
RI
1 6 10 PVC Pos:
Zero:
3.0729 0.2224
0.5477
A-CBL-NHL-A3-2-
(1)
In
9.6844
MagneticCopper
A-BUS-NHD-AG-5
-(4)-TAP
A-BUS-NHL-A3-3
1 10 2/0 PVC Pos:
Zero:
0.4427 0.2313
0.5694
A-CBL-NHL-A3-3 In
1.3950
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NHL-A3-3
A-BUS-NX-A3-4-P
RI
1 6 8 PVC Pos:
Zero:
2.1120 0.1964
0.4833
A-CBL-NHL-A3-3-
(1)
In
6.6560
MagneticCopper
A-BUS-NHL-A4-1
A-BUS-NX-A4-1-P
RI
1 6 1/0 PVC Pos:
Zero:
0.3333 0.1406
0.3461
A-CBL-NHL-A4-1-
(1)
In
1.0505
MagneticCopper
A-BUS-NHL-A4-2
A-BUS-NX-A4-2-P
RI
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
A-CBL-NHL-A4-2-
(1)
In
1.6578
MagneticCopper
A-BUS-NHD-AG-5
-(4)-TAP
A-BUS-NHL-A4-3
1 3 4/0 PVC Pos:
Zero:
0.0833 0.0647
0.1594
A-CBL-NHL-A4-3 In
0.2626
A-BUS-NHL-A4-3
A-BUS-NX-A4-4-P
RI
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
A-CBL-NHL-A4-3-
(1)
In
1.6578
MagneticCopper
A-BUS-NHL-A5-1
A-BUS-NX-A5-1-P
RI
1 6 6 PVC Pos:
Zero:
1.3281 0.1784
0.4393
A-CBL-NHL-A5-1-
(1)
In
4.1854
MagneticCopper
A-BUS-NHL-A5-3
A-BUS-NX-A5-4-P
RI
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
A-CBL-NHL-A5-3-
(1)
In
1.6578
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NHL-AG-1
A-BUS-NX-AG-1-P
RI
1 6 10 PVC Pos:
Zero:
3.0729 0.2224
0.5477
A-CBL-NHL-AG-1-
(1)
A-BUS-NHL-AG-2
A-BUS-NX-AG-2-P
RI
1 5 2 PVC Pos:
Zero:
0.4384 0.1270
0.3125
A-CBL-NHL-AG-2-
(1)
In
1.3815
MagneticCopper
A-BUS-NHL-AG-3
A-BUS-NX-AG-4-P
RI
1 8 8 PVC Pos:
Zero:
2.8160 0.2618
0.6444
A-CBL-NHL-AG-3-
(1)
In
8.8747
MagneticCopper
A-BUS-NHLP-AB-
A-BUS-NX-AB-1-P
RI
1 6 10 PVC Pos:
Zero:
3.0729 0.2224
0.5477
A-CBL-NHLP-AB-
1-(1)
In
9.6844
MagneticCopper
A-BUS-NHSB-C3-
2-DUCT
C-BUS-NHSB-C3-
2-(B)
10 6 600 PVC Pos:
Zero:
0.0067 0.0121
0.0297
A-CBL-NHSB-C3-
2-MAIN-(E)
0.0211
C-BUS-NHSB-CB-
C-BUS-EHATS-CB
-1-(N)
1 30 2000 Epoxy Pos:
Zero:
0.0859 0.0456
0.2435
A-CBL-NHSB-CB-
3-(1)
In
0.5104
BuswayCopper
A-BUS-NLD-AG-1
A-BUS-NLP-AG-7
1 5 350 PVC Pos:
Zero:
0.4369 0.5674
1.3972
A-CBL-NLD-AG-1-
(1)
In
1.3764
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NLD-AG-1-
DISC
A-BUS-NLD-AG-1
3 5 350 PVC Pos:
Zero:
0.1456 0.1891
0.4657
A-CBL-NLD-AG-1-
DISC-(1)
In
0.4588
MagneticCopper
A-BUS-NLP-AG-7
A-BUS-NLP-AG-7-
1 5 350 PVC Pos:
Zero:
0.4369 0.5674
1.3972
A-CBL-NLD-AG-7-
(1)
1.3764
A-BUS-NLP-A1-3
A-BUS-NLP-A1-3-
1 3 250 PVC Pos:
Zero:
0.3828 0.3432
0.8453
A-CBL-NLP-A1-3-
(1)
In
1.2059
MagneticCopper
A-BUS-NLP-A1-8
A-BUS-NLP-A1-8-
1 8 250 PVC Pos:
Zero:
1.0207 0.9153
2.2541
A-CBL-NLP-A1-8-
(1)
In
3.2156
MagneticCopper
A-BUS-NLP-A4-1
A-BUS-NLP-A4-1-
1 3 500 PVC Pos:
Zero:
0.2039 0.3231
0.7953
A-CBL-NLP-A4-1-
(1)
In
0.6421
MagneticCopper
A-BUS-NLP-A4-2
A-BUS-NLP-A4-2-
1 3 4/0 PVC Pos:
Zero:
0.4438 0.3446
0.8487
A-CBL-NLP-A4-2-
(1)
1.3986
A-BUS-NLP-A4-3
A-BUS-NLP-A4-3-
1 3 500 PVC Pos:
Zero:
0.2039 0.3231
0.7953
A-CBL-NLP-A4-3-
(1)
In
0.6421
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NLP-A4-5
A-BUS-NLP-A4-5-
1 3 500 PVC Pos:
Zero:
0.2039 0.3231
0.7953
A-CBL-NLP-A4-5-
(1)
In
0.6421
MagneticCopper
A-BUS-NLP-A5-2
A-BUS-NLP-A5-2-
1 3 4/0 PVC Pos:
Zero:
0.4438 0.3446
0.8487
A-CBL-NLP-A5-2-
(1)
In
1.3986
MagneticCopper
A-BUS-NLP-A5-3
A-BUS-NLP-A5-3-
1 3 4/0 PVC Pos:
Zero:
0.4438 0.3446
0.8487
A-CBL-NLP-A5-3-
(1)
1.3986
A-BUS-NLP-AG-2
A-BUS-NLP-AG-2-
1 5 2/0 PVC Pos:
Zero:
1.1788 0.6160
1.5163
A-CBL-NLP-AG-2-
(1)
In
3.7144
MagneticCopper
A-BUS-NLP-AG-2
A-BUS-NLP-AG-2-
1 5 2 PVC Pos:
Zero:
2.3345 0.6761
1.6642
A-CBL-NLP-AG-2-
(2)
In
7.3572
MagneticCopper
A-BUS-NLP-AG-3
A-BUS-NLP-AG-3-
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-NLP-AG-3-
(1)
In
2.7972
MagneticCopper
A-BUS-NLP-AG-5
A-BUS-NLP-AG-5-
1 5 1/0 PVC Pos:
Zero:
1.4793 0.6241
1.5359
A-CBL-NLP-AG-5-
(1)
4.6621
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
C-BUS-NPE-1-DIS
C
C-BUS-NPE-1-DIS
C-(1)
1 10 10 PVC Pos:
Zero:
5.1215 0.3707
0.9128
A-CBL-NPE-1-DIS
C-(1)
In
16.1406
MagneticCopper
A-BUS-NX-A1-1-S
EC
A-BUS-NLP-A1-1
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
A-CBL-NX-A1-1-
(1)
In
8.8286
MagneticCopper
A-BUS-NX-A1-2-S
EC
A-BUS-NLP-A1-2
1 3 6 PVC Pos:
Zero:
3.5364 0.4750
1.1698
A-CBL-NX-A1-2-
(1)
In
11.1446
MagneticCopper
A-BUS-NX-A1-3-S
EC
A-BUS-NLP-A1-7
1 6 2/0 PVC Pos:
Zero:
1.4146 0.7392
1.8195
A-CBL-NX-A1-3-
(1)
4.4573
A-BUS-NX-A1-3-S
EC
A-BUS-NLP-A1-3
1 6 250 PVC Pos:
Zero:
0.7655 0.6865
1.6906
A-CBL-NX-A1-3-
(2)
In
2.4117
MagneticCopper
A-BUS-NX-A1-4-S
EC
A-BUS-NHP-A1-4
1 6 3/0 PVC Pos:
Zero:
1.1164 0.7198
1.7724
A-CBL-NX-A1-4-
(1)
In
3.5184
MagneticCopper
A-BUS-NX-A1-5-S
EC
A-BUS-NLD-A1-5
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
A-CBL-NX-A1-5-
(1)
In
22.2892
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NX-A1-5-D
ISC
A-BUS-NX-A1-5-P
RI
1 3 10 PVC Pos:
Zero:
1.5365 0.1112
0.2738
A-CBL-NX-A1-5-D
ISC-(1)
4.8422
A-BUS-NX-A1-6-S
EC
A-BUS-NX-A1-6-T
AP
1 3 250 PVC Pos:
Zero:
0.3828 0.3432
0.8453
A-CBL-NX-A1-6-
(1)
In
1.2059
MagneticCopper
A-BUS-NX-A1-6-T
AP
A-BUS-NLP-A1-9
1 8 2 PVC Pos:
Zero:
3.7352 1.0817
2.6627
A-CBL-NX-A1-6-T
AP-(1)
In
11.7715
MagneticCopper
A-BUS-NX-A1-6-T
AP
A-BUS-NLP-A1-8
1 8 250 PVC Pos:
Zero:
1.0207 0.9153
2.2541
A-CBL-NX-A1-6-T
AP-(2)
In
3.2156
MagneticCopper
A-BUS-NX-A2-1-S
EC
A-BUS-NLP-A2-1
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
A-CBL-NX-A2-1-
(1)
8.8286
A-BUS-NX-A2-2-S
EC
A-BUS-NLP-A2-2
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
A-CBL-NX-A2-2-
(1)
In
8.8286
MagneticCopper
A-BUS-NX-A2-3-S
EC
A-BUS-NLP-A2-3-
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-NX-A2-3-
(1)
In
2.7972
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NLP-A2-3-
A-BUS-NLP-A2-3
1 3 4/0 PVC Pos:
Zero:
0.4438 0.3446
0.8487
A-CBL-NX-A2-3-2
-(1)
In
1.3986
MagneticCopper
A-BUS-NX-A2-4-S
EC
A-BUS-NLP-A2-4
1 10 4/0 PVC Pos:
Zero:
1.4793 1.1488
2.8291
A-CBL-NX-A2-4-
(1)
A-BUS-NX-A2-5-S
EC
A-BUS-NLP-A2-5
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-NX-A2-5-
(1)
In
2.7972
MagneticCopper
A-BUS-NX-A2-5-D
ISC
A-BUS-NX-A2-5-P
RI
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
A-CBL-NX-A2-5-D
ISC-(1)
In
1.6578
MagneticCopper
A-BUS-NX-A3-1-S
EC
A-BUS-NLP-A3-1
1 6 3/0 PVC Pos:
Zero:
1.1164 0.7198
1.7724
A-CBL-NX-A3-1-S
EC
In
3.5184
MagneticCopper
A-BUS-NX-A3-2-S
EC
A-BUS-NLP-A3-2
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
A-CBL-NX-A3-2-
(1)
22.2892
A-BUS-NX-A3-3-S
EC
A-BUS-NLP-A3-3
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
A-CBL-NX-A3-3-
(1)
In
8.8286
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NX-A3-3-D
ISC
A-BUS-NX-A3-3-P
RI
1 6 8 PVC Pos:
Zero:
2.1120 0.1964
0.4833
A-CBL-NX-A3-3-D
ISC-(1)
In
6.6560
MagneticCopper
A-BUS-NX-A3-4-S
EC
A-BUS-NLP-A3-4
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
A-CBL-NX-A3-4-
(1)
In
8.8286
MagneticCopper
A-BUS-NX-A3-5-S
EC
A-BUS-NLP-A3-5
1 6 1 PVC Pos:
Zero:
2.2189 0.7905
1.9457
A-CBL-NX-A3-5-
(1)
6.9924
A-BUS-NX-A3-5-D
ISC
A-BUS-NX-A3-5-P
RI
1 6 8 PVC Pos:
Zero:
2.1120 0.1964
0.4833
A-CBL-NX-A3-5-D
ISC-(1)
In
6.6560
MagneticCopper
A-BUS-NX-A4-1-S
EC
A-BUS-NLP-A4-1
1 6 500 PVC Pos:
Zero:
0.4077 0.6463
1.5907
A-CBL-NX-A4-1-S
EC
In
1.2842
MagneticCopper
A-BUS-NX-A4-2-S
EC
A-BUS-NLP-A4-2
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-NX-A4-2-
(1)
In
2.7972
MagneticCopper
A-BUS-NX-A4-3-S
EC
A-BUS-NLP-A4-3
1 6 500 PVC Pos:
Zero:
0.4077 0.6463
1.5907
A-CBL-NX-A4-3-
(1)
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NX-A4-3-D
ISC
A-BUS-NX-A4-3-P
RI
1 6 1/0 PVC Pos:
Zero:
0.3333 0.1406
0.3461
A-CBL-NX-A4-3-D
ISC-(1)
In
1.0505
MagneticCopper
A-BUS-NX-A4-4-S
EC
A-BUS-NLP-A4-4
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-NX-A4-4-
(1)
In
2.7972
MagneticCopper
A-BUS-NX-A4-5-S
EC
A-BUS-NLP-A4-5
1 6 500 PVC Pos:
Zero:
0.4077 0.6463
1.5907
A-CBL-NX-A4-5-
(1)
In
1.2842
MagneticCopper
A-BUS-NX-A4-5-D
ISC
A-BUS-NX-A4-5-P
RI
1 6 1/0 PVC Pos:
Zero:
0.3333 0.1406
0.3461
A-CBL-NX-A4-5-D
ISC-(1)
1.0505
A-BUS-NX-A5-1-S
EC
A-BUS-NLP-A5-1
1 6 1/0 PVC Pos:
Zero:
1.7751 0.7489
1.8431
A-CBL-NX-A5-1-
(1)
In
5.5945
MagneticCopper
A-BUS-NX-A5-2-S
EC
A-BUS-NX-A5-2-T
AP
1 3 4/0 PVC Pos:
Zero:
0.4438 0.3446
0.8487
A-CBL-NX-A5-2-
(1)
In
1.3986
MagneticCopper
A-BUS-NX-A5-2-T
AP
A-BUS-NLP-A5-7
1 6 1/0 PVC Pos:
Zero:
1.7751 0.7489
1.8431
A-CBL-NX-A5-2-T
AP-(1)
In
5.5945
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NX-A5-2-T
AP
A-BUS-NLP-A5-2
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-NX-A5-2-T
AP-(2)
A-BUS-NX-A5-3-S
EC
A-BUS-NLP-A5-3
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-NX-A5-3-
(1)
In
2.7972
MagneticCopper
A-BUS-NX-A5-3-S
EC
A-BUS-NLP-A5-8
1 6 1/0 PVC Pos:
Zero:
1.7751 0.7489
1.8431
A-CBL-NX-A5-3-
(2)
In
5.5945
MagneticCopper
A-BUS-NX-A5-3-D
ISC
A-BUS-NX-A5-3-P
RI
1 6 1/0 PVC Pos:
Zero:
0.3333 0.1406
0.3461
A-CBL-NX-A5-3-D
ISC-(1)
In
1.0505
MagneticCopper
A-BUS-NX-A5-4-S
EC
A-BUS-NLP-A5-4
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-NX-A5-4-
(1)
A-BUS-NX-A5-5-S
EC
A-BUS-NLP-A5-5
1 6 1/0 PVC Pos:
Zero:
1.7751 0.7489
1.8431
A-CBL-NX-A5-5-
(1)
In
5.5945
MagneticCopper
A-BUS-NX-A5-5-S
EC
A-BUS-NLP-A5-10
1 6 3/0 PVC Pos:
Zero:
1.1164 0.7198
1.7724
A-CBL-NX-A5-5-
(2)
In
3.5184
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NX-A5-5-D
ISC
A-BUS-NX-A5-5-P
RI
1 6 1/0 PVC Pos:
Zero:
0.3333 0.1406
0.3461
A-CBL-NX-A5-5-D
ISC-(1)
In
1.0505
MagneticCopper
A-BUS-NX-A5-6-S
EC
A-BUS-NLP-A5-6
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
A-CBL-NX-A5-6-
(1)
A-BUS-NX-A5-6-D
ISC
A-BUS-NX-A5-6-P
RI
1 6 6 PVC Pos:
Zero:
1.3281 0.1784
0.4393
A-CBL-NX-A5-6-D
ISC-(1)
In
4.1854
MagneticCopper
A-BUS-NX-A5-7-S
EC
A-BUS-NLP-A5-9
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
A-CBL-NX-A5-7-
(1)
In
8.8286
MagneticCopper
A-BUS-NX-A5-7-S
EC
A-BUS-NLP-A5-11
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
A-CBL-NX-A5-7-
(2)
In
8.8286
MagneticCopper
A-BUS-NX-A5-7-D
ISC
A-BUS-NX-A5-7-P
RI
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
A-CBL-NX-A5-7-D
ISC-(1)
A-BUS-NX-AB-1-S
EC
A-BUS-NLPP-AB-
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
A-CBL-NX-AB-1-
(1)
In
22.2892
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NX-AG-1-S
EC
A-BUS-NLP-AG-1
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
A-CBL-NX-AG-1-
(1)
In
22.2892
MagneticCopper
A-BUS-NX-AG-2-S
EC
A-BUS-NLP-AG-2
1 5 4/0 PVC Pos:
Zero:
0.7396 0.5744
1.4146
A-CBL-NX-AG-2-
(1)
In
2.3310
MagneticCopper
A-BUS-NX-AG-3-S
EC
A-BUS-NLP-AG-3
1 8 4/0 PVC Pos:
Zero:
1.1834 0.9190
2.2633
A-CBL-NX-AG-3-
(1)
3.7297
A-BUS-NX-AG-4-S
EC
A-BUS-NLP-AG-4
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
A-CBL-NX-AG-4-
(1)
In
8.8286
MagneticCopper
A-BUS-NX-AG-5-S
EC
A-BUS-NLP-AG-5
1 10 1/0 PVC Pos:
Zero:
2.9586 1.2482
3.0718
A-CBL-NX-AG-5-
(1)
In
9.3242
MagneticCopper
A-BUS-NX-AG-5-S
EC
A-BUS-NLP-AG-6
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
A-CBL-NX-AG-5-
(2)
In
22.2892
MagneticCopper
A-BUS-NX-AG-5-
DISC
A-BUS-NX-AG-5-P
RI
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
A-CBL-NX-AG-5-
DISC-(1)
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-NX-AG-6-S
EC
A-BUS-NLD-AG-1-
DISC
3 205 350 PVC Pos:
Zero:
5.9703 7.7551
19.0956
A-CBL-NX-AG-6-
(1)
In
18.8113
MagneticCopper
A-BUS-P10-DISC-
A-BUS-P10-DISC-
1 15 2 PVC Pos:
Zero:
1.3151 0.3809
0.9375
A-CBL-P10-DISC-
1-(1)
In
4.1445
MagneticCopper
A-BUS-P10-DISC-
A-BUS-P10-MTR
1 15 2 PVC Pos:
Zero:
1.3151 0.3809
0.9375
A-CBL-P10-DISC-
2-(1)
In
4.1445
MagneticCopper
A-BUS-P11-DISC-
A-BUS-P11-DISC-
1 15 2 PVC Pos:
Zero:
1.3151 0.3809
0.9375
A-CBL-P11-DISC-
1-(1)
4.1445
A-BUS-P11-DISC-
A-BUS-P11-MTR
1 15 2 PVC Pos:
Zero:
1.3151 0.3809
0.9375
A-CBL-P11-DISC-
2-(1)
In
4.1445
MagneticCopper
A-BUS-P12-DISC-
A-BUS-P12-DISC-
1 15 2 PVC Pos:
Zero:
1.3151 0.3809
0.9375
A-CBL-P12-DISC-
1-(1)
In
4.1445
MagneticCopper
A-BUS-P12-DISC-
A-BUS-P12-MTR
1 15 2 PVC Pos:
Zero:
1.3151 0.3809
0.9375
A-CBL-P12-DISC-
2-(1)
In
4.1445
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-S1-DISC-1
A-BUS-S1-DISC-2
1 20 2 PVC Pos:
Zero:
1.7535 0.5078
1.2500
A-CBL-S1-DISC-1-
(1)
5.5260
A-BUS-S1-DISC-2
A-BUS-ELEV-S1
1 20 2 PVC Pos:
Zero:
1.7535 0.5078
1.2500
A-CBL-S1-DISC-2-
(1)
In
5.5260
MagneticCopper
A-BUS-S2-DISC-1
A-BUS-S2-DISC-2
1 20 2 PVC Pos:
Zero:
1.7535 0.5078
1.2500
A-CBL-S2-DISC-1-
(1)
In
5.5260
MagneticCopper
A-BUS-S2-DISC-2
A-BUS-ELEV-S2
1 20 2 PVC Pos:
Zero:
1.7535 0.5078
1.2500
A-CBL-S2-DISC-2-
(1)
In
5.5260
MagneticCopper
A-BUS-SDC-(1)
A-BUS-GHTA-AG-
8 95 600 PVC Pos:
Zero:
0.1325 0.2386
0.5876
A-CBL-SDC-(1) In
0.4170
A-BUS-SDED
A-BUS-ED
1 100 4000 Epoxy Pos:
Zero:
0.1432 0.0825
0.4384
A-CBL-SDED-(1) In
0.8507
BuswayCopper
A-BUS-SHATS-CB
-1-(L)
A-BUS-T-SLP-CB-
1-PRI
1 30 350 PVC Pos:
Zero:
0.4922 0.6393
1.5742
A-CBL-SHATS-CB
-1-(1)
In
1.5508
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-SHD-AG-1
A-BUS-SHD-1-(1)
-TAP
1 3 4 PVC Pos:
Zero:
0.4180 0.0823
0.2026
A-CBL-SHD-AG-1-
(1)
In
1.3172
MagneticCopper
A-BUS-SHD-1-(1)
-TAP
A-BUS-SHL-A3-1
1 205 4 PVC Pos:
Zero:
28.5612 5.6233
13.8446
A-CBL-SHD-AG-1-
(1)-TAP-(1)
90.0078
A-BUS-SHD-1-(1)
-TAP
A-BUS-SHL-A4-1
1 220 8 PVC Pos:
Zero:
77.4392 7.1997
17.7222
A-CBL-SHD-AG-1-
(1)-TAP-(2)
In
244.0530
MagneticCopper
A-BUS-SHD-AG-1
A-BUS-SX-A2-1-D
ISC
1 85 10 PVC Pos:
Zero:
43.5330 3.1506
7.7585
A-CBL-SHD-AG-1-
(2)
In
137.1953
MagneticCopper
A-BUS-SHD-AG-1
A-BUS-SHL-A5-1
1 255 6 PVC Pos:
Zero:
56.4453 7.5814
18.6712
A-CBL-SHD-AG-1-
(3)
In
177.8802
MagneticCopper
A-BUS-SHD-AG-1
A-BUS-SHD-AG-1-
(4)-TAP
1 160 2 PVC Pos:
Zero:
14.0278 4.0625
10.0000
A-CBL-SHD-AG-1-
(4)
44.2083
A-BUS-SHD-AG-1
A-BUS-AX-AG-1-P
RI
1 70 6 PVC Pos:
Zero:
15.4948 2.0812
5.1254
A-CBL-SHD-AG-1-
(5)
In
48.8299
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-SHD-AG-1
A-BUS-SHL-AG-1
1 5 6 PVC Pos:
Zero:
1.1068 0.1487
0.3661
A-CBL-SHD-AG-1-
(7)
In
3.4878
MagneticCopper
A-BUS-SHD-AG-1-
(4)-TAP
A-BUS-SHL-A1-1
1 6 8 PVC Pos:
Zero:
2.1120 0.1964
0.4833
A-CBL-SHL-A1-1 In
6.6560
MagneticCopper
A-BUS-SHD-AG-1-
(4)-TAP
A-BUS-SHL-A2-1
1 15 2 PVC Pos:
Zero:
1.3151 0.3809
0.9375
A-CBL-SHL-A1-2 In
4.1445
A-BUS-SHL-A5-1
A-BUS-SX-A5-1-P
RI
1 6 10 PVC Pos:
Zero:
3.0729 0.2224
0.5477
A-CBL-SHL-A5-1-
(1)
In
9.6844
MagneticCopper
A-BUS-SHL-AG-1
A-BUS-SX-AG-2-P
RI
1 5 10 PVC Pos:
Zero:
2.5608 0.1853
0.4564
A-CBL-SHL-AG-1-
(1)
In
8.0703
MagneticCopper
A-BUS-SX-A5-1-S
EC
A-BUS-SLP-A5-1
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
A-CBL-SLP-A5-1-
(1)
In
22.2892
MagneticCopper
A-BUS-SLP-AG-1
A-BUS-SLP-AG-1-
1 5 1/0 PVC Pos:
Zero:
1.4793 0.6241
1.5359
A-CBL-SLP-AG-1-
(1)
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-SLP-CB-1
GEN-BUS-GEN-C-
1 300 2/0 PVC Pos:
Zero:
70.7286 36.9591
90.9763
A-CBL-SLP-CB-1-
(1)
In
222.8643
MagneticCopper
A-BUS-SLP-CB-1
GEN-BUS-GEN-C-
1 300 2/0 PVC Pos:
Zero:
70.7286 36.9591
90.9763
A-CBL-SLP-CB-1-
(2)
In
222.8643
MagneticCopper
A-BUS-SWBD-C
A-BUS-NHMCC-A
B-1
2 25 500 PVC Pos:
Zero:
0.1595 0.2528
0.6223
A-CBL-SWBD-C-
(1)
In
0.5024
MagneticCopper
A-BUS-SWBD-C
A-BUS-NX-AG-6-P
RI
2 35 4/0 PVC Pos:
Zero:
0.4861 0.3775
0.9297
A-CBL-SWBD-C-
(10)
1.5320
A-BUS-SWBD-C
A-BUS-NHP-A1-1
2 130 350 PVC Pos:
Zero:
1.0664 1.3852
3.4108
A-CBL-SWBD-C-
(11)
In
3.3600
MagneticCopper
A-BUS-SWBD-C
A-BUS-NHP-A1-2
2 130 350 PVC Pos:
Zero:
1.0664 1.3852
3.4108
A-CBL-SWBD-C-
(12)
In
3.3600
MagneticCopper
A-BUS-SWBD-C
A-BUS-NHLP-AB-
1 25 500 PVC Pos:
Zero:
0.3190 0.5056
1.2446
A-CBL-SWBD-C-
(2)
In
1.0048
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-SWBD-C
A-BUS-NHD-AG-1
2 30 250 PVC Pos:
Zero:
0.3594 0.3223
0.7936
A-CBL-SWBD-C-
(4)
1.1322
A-BUS-NHD-AG-2
2 30 250 PVC Pos:
Zero:
0.3594 0.3223
0.7936
A-CBL-SWBD-C-
(5)
In
1.1322
MagneticCopper
A-BUS-SWBD-C
A-BUS-NHD-AG-5
2 155 500 PVC Pos:
Zero:
0.9889 1.5675
3.8582
A-CBL-SWBD-C-
(6)
In
3.1148
MagneticCopper
A-BUS-SWBD-C
A-BUS-NHD-AG-3
1 10 500 PVC Pos:
Zero:
0.1276 0.2023
0.4978
A-CBL-SWBD-C-
(7)
In
0.4019
MagneticCopper
A-BUS-SWBD-C
A-BUS-NHD-AG-4
2 10 3/0 PVC Pos:
Zero:
0.1747 0.1126
0.2773
A-CBL-SWBD-C-
(8)
0.5506
A-BUS-NHD-A1-1
2 125 500 PVC Pos:
Zero:
0.7975 1.2641
3.1114
A-CBL-SWBD-C-
(9)
In
2.5119
MagneticCopper
A-BUS-SX-A2-1-S
EC
A-BUS-SLP-A2-1
1 8 8 PVC Pos:
Zero:
14.9963 1.3942
3.4320
A-CBL-SX-A2-1-
(1)
In
47.2615
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-SX-A2-1-D
ISC
A-BUS-SX-A2-1-P
RI
1 4 10 PVC Pos:
Zero:
2.0486 0.1483
0.3651
A-CBL-SX-A2-1-D
ISC
In
6.4563
MagneticCopper
A-BUS-SX-AG-1-S
EC
A-BUS-SLP-AG-1
1 10 1/0 PVC Pos:
Zero:
2.9586 1.2482
3.0718
A-CBL-SX-AG-1-
(1)
9.3242
A-BUS-SX-AG-2-S
EC
A-BUS-SLP-AG-2
1 5 8 PVC Pos:
Zero:
9.3727 0.8714
2.1450
A-CBL-SX-AG-2-
(1)
In
29.5384
MagneticCopper
A-BUS-T1A5A-SE
C
A-BUS-NLP-A1-6
1 6 3/0 PVC Pos:
Zero:
1.1164 0.7198
1.7724
A-CBL-T1A5A-(1) In
3.5184
MagneticCopper
A-BUS-T-SLP-CB-
1-SEC
A-BUS-SLP-CB-1
1 5 350 PVC Pos:
Zero:
0.4369 0.5674
1.3972
A-CBL-T-SLP-CB-
1-(1)
In
1.3764
MagneticCopper
A-BUS-UPS-COM
PR-OUT
A-BUS-XF-EX-A3-
2-PRI
1 20 1/0 PVC Pos:
Zero:
1.1111 0.4688
1.1536
A-CBL-UPS-COM
PR-(1)
3.5017
A-BUS-UPS-NEUR
O-SEC
A-BUS-UPS-NEUR
O
1 6 10 PVC Pos:
Zero:
16.3646 1.1844
2.9165
A-CBL-UPS-NEUR
O-(1)
In
51.5736
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
A-BUS-UTIL-1-RI
NG-(1)
A-BUS-SDC-(1)
1 25 4000 Epoxy Pos:
Zero:
0.0358 0.0206
0.1096
A-CBL-UTIL-1-RI
NG-(1)-2
In
0.2127
BuswayCopper
B-BUS-ATS-1-(L)
B-BUS-SHL-BG-1
1 12 1/0 PVC Pos:
Zero:
0.6667 0.2813
0.6922
B-CBL-ATS-1-(1) In
2.1010
MagneticCopper
B-BUS-ATS-3-(L)
B-BUS-EHD-CG-3
1 25 1/0 PVC Pos:
Zero:
1.3889 0.5859
1.4421
B-CBL-ATS-3-(1) In
4.3772
B-BUS-ATS-5-(L)
B-BUS-EHD-BG-1
2 8 500 PVC Pos:
Zero:
0.0510 0.0809
0.1991
B-CBL-ATS-5-(1) In
0.1608
MagneticCopper
B-BUS-ATS-6-(L)
B-BUS-CHD-BG-1
1 8 500 PVC Pos:
Zero:
0.1021 0.1618
0.3983
B-CBL-ATS-6-(1) In
0.3215
MagneticCopper
B-BUS-CHD-BG-1
B-BUS-CHL-B2-2
1 100 2 PVC Pos:
Zero:
8.7674 2.5391
6.2500
B-CBL-CHD-BG-1
-(1)
In
27.6302
MagneticCopper
B-BUS-CHD-BG-1
B-BUS-CHL-B2-1
1 190 1 PVC Pos:
Zero:
13.1944 4.7005
11.5699
B-CBL-CHD-BG-1
-(2)
41.5790
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
B-BUS-CHD-BG-1
B-BUS-SX-B3-2-D
ISC
1 100 10 PVC Pos:
Zero:
51.2153 3.7066
9.1276
B-CBL-CHD-BG-1
-(3)
In
161.4063
MagneticCopper
B-BUS-CHD-BG-1
C-BUS-CHL-C1-3
1 230 2/0 PVC Pos:
Zero:
10.1823 5.3207
13.0972
B-CBL-CHD-BG-1
-(4)
In
32.0842
MagneticCopper
B-BUS-CHD-BG-1
B-BUS-XC-1B-2-P
RI
1 125 4 PVC Pos:
Zero:
17.4154 3.4288
8.4418
B-CBL-CHD-BG-1
-(5)
In
54.8828
MagneticCopper
B-BUS-CHD-BG-1
B-BUS-CX-BG-2-P
RI
1 125 8 PVC Pos:
Zero:
43.9996 4.0907
10.0694
B-CBL-CHD-BG-1
-(6)
138.6665
B-BUS-CHD-BG-1
B-BUS-CX-BG-1-P
RI
1 20 4 PVC Pos:
Zero:
2.7865 0.5486
1.3507
B-CBL-CHD-BG-1
-(7)
In
8.7813
MagneticCopper
B-BUS-CHL-B2-1
B-BUS-CX-B2-1-P
RI
1 8 2 PVC Pos:
Zero:
0.7014 0.2031
0.5000
B-CBL-CHL-B2-1-
(1)
In
2.2104
MagneticCopper
B-BUS-CHL-B2-2
B-BUS-CX-B2-2-P
RI
1 50 2 PVC Pos:
Zero:
4.3837 1.2695
3.1250
B-CBL-CHL-B2-2-
(1)
In
13.8151
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
B-BUS-CHL-B2-2
B-BUS-CX-B2-4-P
RI
1 100 10 PVC Pos:
Zero:
51.2153 3.7066
9.1276
B-CBL-CHL-B2-2-
(2)
161.4063
B-BUS-CHL-B2-2
B-BUS-CX-B2-3-P
RI
1 5 6 PVC Pos:
Zero:
1.1068 0.1487
0.3661
B-CBL-CHL-B2-2-
(3)
In
3.4878
MagneticCopper
C-BUS-CHL-C1-3
C-BUS-CX-C1-3-P
RI
1 6 4 PVC Pos:
Zero:
0.8359 0.1646
0.4052
B-CBL-CHL-C1-3-
(1)
In
2.6344
MagneticCopper
B-BUS-CLP-B2-1
B-BUS-CLP-B2-1-
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
B-CBL-CLP-B2-1-
(1)
In
8.8286
MagneticCopper
B-BUS-CLP-B2-2
B-BUS-CLP-B2-2-
1 20 3/0 PVC Pos:
Zero:
3.7213 2.3992
5.9079
B-CBL-CLP-B2-2-
(1)
11.7280
B-BUS-CLP-B2-2
B-BUS-CLP-B2-2-
1 20 6 PVC Pos:
Zero:
23.5762 3.1666
7.7986
B-CBL-CLP-B2-2-
(2)
In
74.2973
MagneticCopper
B-BUS-CLP-BG-1
B-BUS-CLP-BG-1-
1 5 3/0 PVC Pos:
Zero:
0.9303 0.5998
1.4770
B-CBL-CLP-BG-1-
(1)
In
2.9320
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
B-BUS-CLP-BG-1
C-BUS-CLP-C1-2
1 5 3 PVC Pos:
Zero:
2.9239 0.6992
1.7208
B-CBL-CLP-BG-1-
(2)
In
9.2144
MagneticCopper
B-BUS-CLP-BG-1-
B-BUS-CLP-BG-2
1 135 2 PVC Pos:
Zero:
63.0316 18.2542
44.9334
B-CBL-CLP-BG-1-
2-(2)
198.6432
C-BUS-CLP-C1-3
C-BUS-CLP-C1-4
1 8 3 PVC Pos:
Zero:
4.6783 1.1187
2.7533
B-CBL-CLP-C1-3-
(1)
In
14.7430
MagneticCopper
B-BUS-CX…