final main site - gen input report.pdf

PDF 311 KB Posted

Attached to
36-Month Electrical Distribution Testing
Solicitation number
36C24727Q0044
Issued by

About this file

Summary

This document is a DAPPER Fault Analysis Input Report for the VA Atlanta SKM Model Final project, detailing electrical system fault contribution data for a Veterans Affairs facility's electrical distribution network. The report contains comprehensive technical specifications for utility contributions, generator parameters, motor characteristics, and an extensive cable inventory across multiple electrical buses and distribution systems. The utility contributions are documented from Georgia Power at two ring configurations (480V), with detailed single-line-to-ground and three-phase fault current data in amperes and MVA. Generator contributions include five units designated A-GEN1 through A-GEN5 (each 2,500 kVA at 480V with 20% transient reactance), plus B-GENB (750 kVA) and D-GEN-D (562.5 kVA), all operating at 480V with varying impedance ratios.

The motor section documents over 40 individual motors distributed across bus configurations A through F, plus parking and other specialized areas, ranging from 10 kVA to 869 kVA capacity at various voltage levels (208V, 220V, and 480V), with applications including chillers, elevators, pumps, and fire protection systems. The extensive cable schedule comprises hundreds of entries detailing interconnections between distribution buses, specifying cable gauges (ranging from 1 AWG to 4000 MCM busway), lengths in feet, insulation types (primarily PVC with some Epoxy), conductor materials (Copper and Busway), and per-unit impedance values for both positive and zero sequence components on a 100 MVA base. This technical data supports fault analysis modeling and coordination studies for the Atlanta VA medical facility's electrical infrastructure.

View the file

Other files

File Type Posted
Final - AF Label List.xlsx XLSX spreadsheet
final remote - gen device eval.pdf PDF
Attachment B - Fort McPherson Equipment Schedule - REV19.1.xlsx XLSX spreadsheet
Drawing List.pdf PDF
GHTA-AG-1.pdf PDF
final main site - util input report.pdf PDF
NHSB-BG-1.pdf PDF
20200603 - Final Combined pdfs.pdf PDF
final main site - util device eval.pdf PDF
final main site - util bus eval.pdf PDF
Existing-Recommended Breaker Settings - Final.xlsx XLSX spreadsheet
GHSB-C3-1.pdf PDF
final remote - gen results report.pdf PDF
NHSB-CB-1.pdf PDF
final main site - gen bus eval.pdf PDF
Equipment Condition Assessment Sheets.xlsx XLSX spreadsheet
GHTA-CB-1.pdf PDF
final remote - gen input report.pdf PDF
final remote - util results report.pdf PDF
Questions and Answers.docx DOCX document
Attachment C - Trinka-Davis Equipment Schedule - REV19.1.xlsx XLSX spreadsheet
Switchboard C.pdf PDF
Attachment D - Equipment and Test Matrix - REV19.1.docx DOCX document
Electrical Distribution Testing SOW final.docx DOCX document
final remote - util bus eval.pdf PDF
7.6 Facility Condition Assessment - Final Submission.xlsx XLSX spreadsheet
NHSB-C3-2.pdf PDF
final main site - gen device eval.pdf PDF
GHSB-AG-1.pdf PDF
Electrical Directive 1028 D 2020-02-24.pdf PDF
GHTA-CB-2.pdf PDF
final remote - util device eval.pdf PDF
ArcFlash - Atlanta Main Site Final.xls XLS spreadsheet
Attachment A - Main Campus Equipment Schedule - REV19.1.xlsx XLSX spreadsheet
ArcFlash - Atlanta Remote Sites Final.xls XLS spreadsheet
final remote - gen bus eval.pdf PDF
NSHB-CB-2.pdf PDF
NHSB-C3-1 Fast Transfer.pdf PDF
36C24727Q0044 0002.pdf PDF
7.7 Building System Assessment_Atlanta.xlsx XLSX spreadsheet
NHSB-C3-1.pdf PDF
Wage Determination 2015-4471.docx DOCX document
Switchgear ED.pdf PDF
final main site - gen results report.pdf PDF
final remote - util input report.pdf PDF
Atlanta VA Main Campus 2022 IR Report.pdf PDF
final main site - util results report.pdf PDF
36C24727Q0044 0001.pdf PDF
36C24727Q0044_1 36-Month Electrical Distribution Testing.docx DOCX document
Attachment D - Equipment and Test Matrix - REV19.docx DOCX document
Show 40 more

Latest 50 of 53 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DAPPER Fault Analysis Input Report (English)

Project: VA_Atlanta_SKM_Model

Final - Generator

Utilities

Contribution

From Name

Bus

Name

In/Out

Service

Nominal

Voltage

-------- Contribution Data -------- PU (100 MVA Base)

X PUR PUX/RUnitsDuty

GEORGIA POWER -

UTILITY-RING-2

BUS-UTILITY-2-RING 480 Amps 6.39Out 83,119

SLG:

3P:

Amps 6.30 0.767 0.128

Pos:

Zero: 98,287

0.224 1.430

GEORGIA POWER

UTILITY-RING-1

C-BUS-UTILITY-1-RIN

G

480 Amps 6.39Out 83,119

SLG:

3P:

Amps 6.30 0.767 0.128

Pos:

Zero: 98,287

0.224 1.430

T13-UTIL T13-BUS-UTIL-PRI 13,800 MVA 9,999.00Out 1,000,000

SLG:

3P:

MVA 9,999.00 0.000 0.000

Pos:

Zero: 333,333

0.000 0.000

Generators

Contribution

From Name

Bus

Name

In/Out

Service

Nominal

Voltage

-------- Contribution Data --------

Base kVA X" X/R

PU (100 MVA Base)

R PU X PU

A-GEN1 480A-BUS-GEN1 2,500.00 20.00 0.30 6.00In

0.30

6.00 0.30

0.15

0.15

0.15

20.00

20.00 6.00

A-GEN2 480A-BUS-GEN2 2,500.00 20.00 0.30 6.00In

0.30

6.00 0.30

0.15

0.15

0.15

20.00

20.00 6.00

A-GEN3 480A-BUS-GEN3 2,500.00 20.00 0.30 6.00In

0.30

6.00 0.30

0.15

0.15

0.15

20.00

20.00 6.00

A-GEN4 480A-BUS-GEN4 2,500.00 20.00 0.30 6.00In

0.30

6.00 0.30

0.15

0.15

0.15

20.00

20.00 6.00

Contribution

From Name

Bus

Name

In/Out

Service

Nominal

Voltage

-------- Contribution Data --------

Base kVA X" X/R

PU (100 MVA Base)

R PU X PU

A-GEN5 480A-BUS-GEN5 2,500.00 20.00 0.30 6.00In

0.30

6.00 0.30

0.15

0.15

0.15

20.00

20.00 6.00

B-GENB 480B-BUS-GENB 750.00 20.00 1.00 20.00In

1.00

20.00 1.00

0.15

0.15

0.15

20.00

20.00 20.00

D-GEN-D 480D-BUS-GEN-D 562.50 20.00 1.33 26.67In

1.33

26.67 1.33

0.15

0.15

0.15

20.00

20.00 26.67

Motors

Contribution

From Name

Bus

Name

In/Out

Service

Nominal

Voltage

--------- Contribution Data --------

Base kVA Xd" X/R

PU (100 MVA Base)

R PU X PU

# of

Motors

A-MTR-CHILLER-OR1 A-BUS-CHILLER-OR1 480 401.08 0.1507 4.90 7.672 37.583In 1

A-MTR-CHILLER-OR2 A-BUS-CHILLER-OR2 480 401.08 0.1507 4.90 7.672 37.583In 1

A-MTR-ELEV-P21 ELEV P21 480 25.07 0.1507 4.90 122.746 601.335In 1

A-MTR-ELEV-S1 A-BUS-ELEV-S1 480 50.13 0.1507 4.90 61.373 300.667In 1

A-MTR-ELEV-S2 A-BUS-ELEV-S2 480 50.13 0.1507 4.90 61.373 300.667In 1

A-MTR-P10 A-BUS-P10-MTR 480 40.11 0.1507 4.90 76.717 375.834In 1

A-MTR-P11 A-BUS-P11-MTR 480 40.11 0.1507 4.90 76.717 375.834In 1

A-MTR-P12 A-BUS-P12-MTR 480 40.11 0.1507 4.90 76.717 375.834In 1

B-MTR-CHILLER-PED B-BUS-CHILLER-PED 480 100.27 0.1507 4.90 30.687 150.334In 1

B-MTR-ELEV-P17 B-BUS-ELEV-P17 480 30.08 0.1507 4.90 102.289 501.112In 1

Bus

Name

In/Out

Service

Nominal

Voltage

--------- Contribution Data --------

Base kVA Xd" X/R

PU (100 MVA Base)

R PU X PU

# of

Motors

B-MTR-ELEV-P18 B-BUS-ELEV P18 480 30.08 0.1507 4.90 102.289 501.112In 1

B-MTR-ELEV-P8 B-BUS-ELEV-P8 480 50.13 0.1507 4.90 61.373 300.667In 1

B-MTR-ELEV-P9 B-BUS-ELEV-P9 480 50.13 0.1507 4.90 61.373 300.667In 1

C-MTR-CHILLER1 C-BUS-CHILLER1-MTR 480 745.00 0.1507 4.90 0.000 0.000In 1

C-MTR-CHILLER2 C-BUS-CHILLER2-MTR 480 741.94 0.1507 4.90 0.000 0.000In 1

C-MTR-CHILLER4 C-BUS-CHILLER4-MTR 480 869.33 0.1507 4.90 0.000 0.000In 1

C-MTR-ELEV13 C-BUS-ELEV13 480 40.11 0.1507 4.90 76.717 375.834In 1

C-MTR-ELEV14 C-BUS-ELEV14 480 40.11 0.1507 4.90 76.717 375.834In 1

C-MTR-ELEV2 C-BUS-ELEV2 480 25.07 0.1507 4.90 122.746 601.335In 1

C-MTR-ELEVS5 C-BUS-ELEVS5 220 55.15 0.1507 4.90 265.597 1,301.161In 1

C-MTR-ELEVS6 C-BUS-ELEVS6 220 55.15 0.1507 4.90 265.597 1,301.161In 1

C-MTR-FIRE-PUMP C-BUS-FIRE-PUMP 480 23.59 0.1507 4.90 130.418 638.918In 1

C-MTR-NPE-1-DISC C-BUS-NPE-1-DISC-(1) 480 10.03 0.1507 4.90 0.000 0.000In 1

C-MTR-P1-ELEV C-BUS-P1-ELEV 208 40.11 0.1507 4.90 76.717 375.834In 1

C-MTR-P2-ELEV C-BUS-P2-ELEV 208 40.11 0.1507 4.90 76.717 375.834In 1

C-MTR-P3-ELEV C-BUS-P3-ELEV 208 40.11 0.1507 4.90 76.717 375.834In 1

Bus

Name

In/Out

Service

Nominal

Voltage

--------- Contribution Data --------

Base kVA Xd" X/R

PU (100 MVA Base)

R PU X PU

# of

Motors

C-MTR-P4-ELEV C-BUS-P4-ELEV 208 40.11 0.1507 4.90 76.717 375.834In 1

D-MTR-ELEV-5 D-BUS-ELEV-5 480 60.16 0.1507 4.90 51.144 250.556In 1

D-MTR-ELEV-6 D-BUS-ELEV-6 480 60.16 0.1507 4.90 51.144 250.556In 1

D-MTR-ELEV-7 D-BUS-ELEV-7 480 60.16 0.1507 4.90 51.144 250.556In 1

E-MTR-ELEV-P19 E-BUS-ELEV-P19 480 50.13 0.1507 4.90 61.373 300.667In 1

E-MTR-ELEV-P20 E-BUS-ELEV-P20 480 40.11 0.1507 4.90 76.717 375.834In 1

F-MTR-ELEV1 F-BUS-ELEV1 480 35.09 0.1507 4.90 87.676 429.525In 1

F-MTR-ELEV2 F-BUS-ELEV2 480 35.09 0.1507 4.90 87.676 429.525In 1

F-MTR-ELEV-F F-BUS-ELEV-F 480 50.13 0.1507 4.90 0.000 0.000In 1

PK-MTR-ELEV-1 PK-BUS-ELEV-1 480 35.09 0.1507 4.90 0.000 0.000In 1

PK-MTR-ELEV-2 PK-BUS-ELEV-2 480 35.09 0.1507 4.90 0.000 0.000In 1

PK-MTR-ELEV-3 PK-BUS-ELEV-3 480 35.09 0.1507 4.90 0.000 0.000In 1

Cables

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-ATS-E-(L)

A-BUS-CHD-AG-1

2 40 600 PVC Pos:

Zero:

0.2231 0.4019

0.9896

A-CBL-ATS-E-(1) In

0.7023

MagneticCopper

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-ATS-L-(L)

A-BUS-SHD-AG-1

1 20 3/0 PVC Pos:

Zero:

0.6988 0.4505

1.1094

A-CBL-ATS-L-(1) In

2.2023

MagneticCopper

A-BUS-ATS-MTS-

(L)

A-BUS-EHD-A3-1

1 310 4/0 PVC Pos:

Zero:

8.6111 6.6871

16.4688

A-CBL-ATS-MTS-

(1)

In

27.1385

MagneticCopper

A-BUS-ATS-Q1-

(L)

A-BUS-EHD-AG-1

2 30 500 PVC Pos:

Zero:

0.1914 0.3034

0.7467

A-CBL-ATS-Q1-(1) In

0.6029

A-BUS-ATS-Q2-

(L)

A-BUS-EHD-AG-2

3 180 300 PVC Pos:

Zero:

1.2083 1.2839

3.1615

A-CBL-ATS-Q2-(1) In

3.8073

MagneticCopper

A-BUS-ATS-Q3-

(L)

A-BUS-EHD-AG-3

2 10 500 PVC Pos:

Zero:

0.0638 0.1011

0.2489

A-CBL-ATS-Q3-(1) In

0.2010

MagneticCopper

A-BUS-CHD-AG-1

A-BUS-CHD-AG-1

-(1)-TAP

1 240 4/0 PVC Pos:

Zero:

6.6667 5.1771

12.7500

A-CBL-CHD-AG-1

-(1)

In

21.0104

MagneticCopper

A-BUS-CHD-AG-1

A-BUS-SW-CX-A1

-1-DISC

1 90 1/0 PVC Pos:

Zero:

5.0000 2.1094

5.1914

A-CBL-CHD-AG-1

-(10)

In

15.7578

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-CHD-AG-1

A-BUS-CHD-AG-2

1 240 2 PVC Pos:

Zero:

21.0417 6.0938

15.0000

A-CBL-CHD-AG-1

-(11)

In

66.3125

MagneticCopper

A-BUS-CHD-AG-1

-(1)-TAP

A-BUS-CHL-A4-1

1 3 4/0 PVC Pos:

Zero:

0.0833 0.0647

0.1594

A-CBL-CHD-AG-1

-(1-1)

In

0.2626

MagneticCopper

A-BUS-CHD-AG-1

A-BUS-CX-A3-1-D

ISC

1 240 2 PVC Pos:

Zero:

21.0417 6.0938

15.0000

A-CBL-CHD-AG-1

-(12)

In

66.3125

MagneticCopper

A-BUS-CHD-AG-1

-(1)-TAP

A-BUS-CHL-A5-1

1 15 4/0 PVC Pos:

Zero:

0.4167 0.3236

0.7969

A-CBL-CHD-AG-1

-(1-2)

1.3132

A-BUS-CHD-AG-1

A-BUS-CX-AG-2-

DISC

1 230 6 PVC Pos:

Zero:

50.9115 6.8381

16.8407

A-CBL-CHD-AG-1

-(13)

In

160.4410

MagneticCopper

A-BUS-CHD-AG-1

A-BUS-CHMCC-A

R-1

1 315 4/0 PVC Pos:

Zero:

8.7500 6.7949

16.7344

A-CBL-CHD-AG-1

-(2)

In

27.5762

MagneticCopper

A-BUS-CHD-AG-1

A-BUS-CATHLAB

1 100 3/0 PVC Pos:

Zero:

3.4939 2.2526

5.5469

A-CBL-CHD-AG-1

-(3)

In

11.0113

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-CHD-AG-1

A-BUS-CX-A3-2-D

ISC-1

1 150 1/0 PVC Pos:

Zero:

8.3333 3.5156

8.6523

A-CBL-CHD-AG-1

-(4)

26.2630

A-BUS-CX-A2-1-D

ISC

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

A-CBL-CHD-AG-1

-(5)

In

1.6578

MagneticCopper

A-BUS-CHD-AG-1

A-BUS-CX-A4-2-D

ISC

1 160 2 PVC Pos:

Zero:

14.0278 4.0625

10.0000

A-CBL-CHD-AG-1

-(6)

In

44.2083

MagneticCopper

A-BUS-CHD-AG-1

A-BUS-CX-AG-1-

DISC

1 50 10 PVC Pos:

Zero:

25.6076 1.8533

4.5638

A-CBL-CHD-AG-1

-(7)

In

80.7031

MagneticCopper

A-BUS-CHD-AG-1

A-BUS-CHL-A2-1

1 210 4/0 PVC Pos:

Zero:

5.8333 4.5299

11.1563

A-CBL-CHD-AG-1

-(8)

18.3841

A-BUS-HL-5A-277

1 245 3/0 PVC Pos:

Zero:

8.5601 5.5189

13.5898

A-CBL-CHD-AG-1

-(9)

In

26.9776

MagneticCopper

A-BUS-CHD-AG-2

A-BUS-CHL-A1-1

1 70 6 PVC Pos:

Zero:

15.4948 2.0812

5.1254

A-CBL-CHD-AG-2

-(1)

In

48.8299

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-CHD-AG-2

A-BUS-CX-AG-3-P

RI

1 6 6 PVC Pos:

Zero:

1.3281 0.1784

0.4393

A-CBL-CHD-AG-2

-(2)

In

4.1854

MagneticCopper

A-BUS-CHL-A2-1

A-BUS-CHL-A2-1-

(1)-TAP

1 60 2 PVC Pos:

Zero:

5.2604 1.5234

3.7500

A-CBL-CHL-A2-1-

(1)

16.5781

A-BUS-CHL-A2-1-

(1)-TAP

A-BUS-SW-CX-A2

-2-DISC

1 3 2 PVC Pos:

Zero:

0.2630 0.0762

0.1875

A-CBL-CHL-A2-1-

TAP-(1)

In

0.8289

MagneticCopper

A-BUS-CHL-A2-1-

(1)-TAP

A-BUS-CHL-A3-1

1 75 6 PVC Pos:

Zero:

16.6016 2.2298

5.4915

A-CBL-CHL-A2-1-

TAP-(2)

In

52.3177

MagneticCopper

A-BUS-CHL-A4-1

A-BUS-CX-A4-1-P

RI

1 6 6 PVC Pos:

Zero:

1.3281 0.1784

0.4393

A-CBL-CHL-A4-1-

(1)

In

4.1854

MagneticCopper

A-BUS-CHL-A5-1

A-BUS-CX-A5-1-P

RI

1 6 6 PVC Pos:

Zero:

1.3281 0.1784

0.4393

A-CBL-CHL-A5-1-

(1)

4.1854

A-BUS-CHL-A5-1

A-BUS-CX-A5-2-D

ISC

1 60 1/0 PVC Pos:

Zero:

3.3333 1.4063

3.4609

A-CBL-CHL-A5-1-

(2)

In

10.5052

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-CLD-A1-1

A-BUS-CLP-A5-1

1 80 1/0 PVC Pos:

Zero:

23.6686 9.9852

24.5747

A-CBL-CLD-A1-1-

(1)

In

74.5932

MagneticCopper

A-BUS-CLD-A1-1

A-BUS-CLP-A1-1

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

A-CBL-CLD-A1-1-

(2)

In

22.2892

MagneticCopper

A-BUS-CLD-A1-1

A-BUS-CLP-A4-1

1 80 2 PVC Pos:

Zero:

37.3521 10.8173

26.6272

A-CBL-CLD-A1-1-

(3)

117.7145

A-BUS-CLD-A3-1

A-BUS-CLP-A4-6

1 20 2 PVC Pos:

Zero:

9.3380 2.7043

6.6568

A-CBL-CLD-A3-1-

(1)

In

29.4286

MagneticCopper

A-BUS-CLD-A3-1

A-BUS-CLP-A5-7

1 30 2 PVC Pos:

Zero:

14.0070 4.0565

9.9852

A-CBL-CLD-A3-1-

(2)

In

44.1429

MagneticCopper

A-BUS-CLD-A3-2

A-BUS-CLP-A4-3

1 130 2/0 PVC Pos:

Zero:

30.6490 16.0156

39.4231

A-CBL-CLD-A3-2-

(1)

In

96.5745

MagneticCopper

A-BUS-CLD-A3-2

A-BUS-CLP-A5-4

1 150 1/0 PVC Pos:

Zero:

44.3787 18.7223

46.0776

A-CBL-CLD-A3-2-

(2)

139.8622

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-CLP-A2-1

A-BUS-CLP-A2-1-

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-CLP-A2-1-

(1)

In

2.7972

MagneticCopper

A-BUS-CLP-A2-2

A-BUS-CLP-A2-2-

1 3 4/0 PVC Pos:

Zero:

0.4438 0.3446

0.8487

A-CBL-CLP-A2-2-

(1)

In

1.3986

MagneticCopper

A-BUS-CLP-A2-2-

C-BUS-CLP-C2-5-

(2)

1 3 4/0 PVC Pos:

Zero:

0.4438 0.3446

0.8487

A-CBL-CLP-A2-2-

2-(1)

In

1.3986

MagneticCopper

A-BUS-CLP-A4-2

A-BUS-CLP-A5-3-

1 15 1/0 PVC Pos:

Zero:

4.4379 1.8722

4.6078

A-CBL-CLP-A4-2-

(1)

13.9862

A-BUS-CLP-A4-3

A-BUS-CLP-A4-3-

1 3 2/0 PVC Pos:

Zero:

0.7073 0.3696

0.9098

A-CBL-CLP-A4-3-

(1)

In

2.2286

MagneticCopper

A-BUS-CLP-A4-4

A-BUS-CLP-A4-5

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

A-CBL-CLP-A4-4-

(1)

In

22.2892

MagneticCopper

A-BUS-CLP-A5-1

A-BUS-CLP-A5-2

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

A-CBL-CLP-A5-1-

(1)

In

22.2892

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-CLP-A5-3-

A-BUS-CLP-A5-3

1 3 1/0 PVC Pos:

Zero:

0.8876 0.3744

0.9216

A-CBL-CLP-A5-3-

2-(1)

2.7972

A-BUS-CLP-A5-4

A-BUS-CLP-A5-5

1 10 6 PVC Pos:

Zero:

11.7881 1.5833

3.8993

A-CBL-CLP-A5-4-

(1)

In

37.1487

MagneticCopper

A-BUS-CLP-AG-2

A-BUS-CLP-A1-2

1 100 6 PVC Pos:

Zero:

117.8809 15.8330

38.9932

A-CBL-CLP-AG-2-

(1)

In

371.4867

MagneticCopper

A-BUS-CLP-AG-3

A-BUS-CLP-AG-3-

1 5 3/0 PVC Pos:

Zero:

0.9303 0.5998

1.4770

A-CBL-CLP-AG-3-

(1)

In

2.9320

MagneticCopper

A-BUS-CX-A1-1-S

EC

A-BUS-CLD-A1-1

1 6 500 PVC Pos:

Zero:

0.4077 0.6463

1.5907

A-CBL-CX-A1-1-

(1)

1.2842

A-BUS-SW-CX-A1

-1-DISC

A-BUS-CX-A1-1-P

RI

1 3 1/0 PVC Pos:

Zero:

0.1667 0.0703

0.1730

A-CBL-CX-A1-1-D

ISC-(1)

In

0.5253

MagneticCopper

A-BUS-CX-A2-1-S

EC

A-BUS-CLP-A2-1

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-CX-A2-1-

(1)

In

2.7972

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-CX-A2-1-D

ISC

A-BUS-CX-A2-1-P

RI

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

A-CBL-CX-A2-1-D

ISC-(1)

In

1.6578

MagneticCopper

A-BUS-CX-A2-2-S

EC

A-BUS-CLP-A2-2

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-CX-A2-2-

(1)

A-BUS-SW-CX-A2

-2-DISC

A-BUS-CX-A2-2-P

RI

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

A-CBL-CX-A2-2-D

ISC-(1)

In

1.6578

MagneticCopper

A-BUS-CX-A3-1-S

EC

A-BUS-CLD-A3-1

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-CX-A3-1-

(1)

In

2.7972

MagneticCopper

A-BUS-CX-A3-1-D

ISC

A-BUS-CX-A3-1-P

RI

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

A-CBL-CX-A3-1-D

ISC-(1)

In

1.6578

MagneticCopper

A-BUS-CX-A3-2-S

EC

A-BUS-CLD-A3-2

1 6 500 PVC Pos:

Zero:

0.4077 0.6463

1.5907

A-CBL-CX-A3-2-

(1)

A-BUS-CX-A3-2-D

ISC-1

A-BUS-CX-A3-2-P

RI

1 6 1/0 PVC Pos:

Zero:

0.3333 0.1406

0.3461

A-CBL-CX-A3-2-D

ISC

In

1.0505

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-CX-A4-1-S

EC

A-BUS-CLP-A4-4

1 6 3/0 PVC Pos:

Zero:

1.1164 0.7198

1.7724

A-CBL-CX-A4-1-

(1)

In

3.5184

MagneticCopper

A-BUS-CX-A4-2-S

EC

A-BUS-CLP-A4-2

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-CX-A4-2-

(1)

In

2.7972

MagneticCopper

A-BUS-CX-A4-2-D

ISC

A-BUS-CX-A4-2-P

RI

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

A-CBL-CX-A4-2-D

ISC

1.6578

A-BUS-CX-A5-1-S

EC

A-BUS-CLP-A5-6

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-CX-A5-1-

(1)

In

2.7972

MagneticCopper

A-BUS-CX-A5-2-S

EC

A-BUS-CLP-A5-8

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-CX-A5-2-

(1)

In

2.7972

MagneticCopper

A-BUS-CX-A5-2-D

ISC

A-BUS-CX-A5-2-P

RI

1 8 1/0 PVC Pos:

Zero:

0.4444 0.1875

0.4615

A-CBL-CX-A5-2-D

ISC-(1)

In

1.4007

MagneticCopper

A-BUS-CX-AG-1-S

EC

A-BUS-CLP-AG-1

1 5 6 PVC Pos:

Zero:

5.8940 0.7917

1.9497

A-CBL-CX-AG-1-

(1)

18.5743

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-CX-AG-1-

DISC

A-BUS-CX-AG-1-P

RI

1 5 10 PVC Pos:

Zero:

2.5608 0.1853

0.4564

A-CBL-CX-AG-1-

DISC-(1)

In

8.0703

MagneticCopper

A-BUS-CX-AG-2-S

EC

A-BUS-CLP-AG-2

1 5 2 PVC Pos:

Zero:

2.3345 0.6761

1.6642

A-CBL-CX-AG-2-

(1)

In

7.3572

MagneticCopper

A-BUS-CX-AG-2-

DISC

A-BUS-CX-AG-2-P

RI

1 5 6 PVC Pos:

Zero:

1.1068 0.1487

0.3661

A-CBL-CX-AG-2-

DISC-(1)

In

3.4878

MagneticCopper

A-BUS-CX-AG-3-S

EC

A-BUS-CLP-AG-3

1 6 3/0 PVC Pos:

Zero:

1.1164 0.7198

1.7724

A-CBL-CX-AG-3-

(1)

3.5184

A-BUS-ED

A-BUS-GHATS-A

G-1-(N)

1 20 2/0 PVC Pos:

Zero:

0.8854 0.4627

1.1389

A-CBL-ED-(1) In

2.7899

MagneticCopper

A-BUS-ED

A-BUS-ATS-L-(N)

1 35 3/0 PVC Pos:

Zero:

1.2229 0.7884

1.9414

A-CBL-ED-(2) In

3.8539

MagneticCopper

A-BUS-ED

A-BUS-ATS-MTS-

(N)

1 35 4/0 PVC Pos:

Zero:

0.9722 0.7550

1.8594

A-CBL-ED-(3) In

3.0640

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-ED

A-BUS-ATS-Q2-

(N)

2 35 500 PVC Pos:

Zero:

0.2233 0.3539

0.8712

A-CBL-ED-(4) In

0.7033

A-BUS-ED

A-BUS-ATS-E-(N)

2 35 500 PVC Pos:

Zero:

0.2233 0.3539

0.8712

A-CBL-ED-(5) In

0.7033

MagneticCopper

A-BUS-ED

A-BUS-ATS-Q1-

(N)

3 35 300 PVC Pos:

Zero:

0.2350 0.2496

0.6147

A-CBL-ED-(6) In

0.7403

MagneticCopper

A-BUS-ED

A-BUS-ATS-Q3-

(N)

2 35 500 PVC Pos:

Zero:

0.2233 0.3539

0.8712

A-CBL-ED-(7) In

0.7033

MagneticCopper

A-BUS-EHD-A3-1

A-BUS-UPS-COM

PR-IN

1 10 1/0 PVC Pos:

Zero:

0.5556 0.2344

0.5768

A-CBL-EHD-A3-1-

(1)

1.7509

A-BUS-EHD-A3-1

A-BUS-XF-EX-A3-

2-PRI

1 10 1/0 PVC Pos:

Zero:

0.5556 0.2344

0.5768

A-CBL-EHD-A3-1-

(2)

In

1.7509

MagneticCopper

A-BUS-EHD-A4-1

A-BUS-EX-A4-1-D

ISC

1 20 6 PVC Pos:

Zero:

4.4271 0.5946

1.4644

A-CBL-EHD-A4-1(

1)

In

13.9514

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-EHD-A4-1

A-BUS-EX-A5-1-D

ISC

1 50 10 PVC Pos:

Zero:

25.6076 1.8533

4.5638

A-CBL-EHD-A4-1(

2)

In

80.7031

MagneticCopper

A-BUS-EHD-A4-1

A-BUS-EHPP-A5-1

1 50 4/0 PVC Pos:

Zero:

1.3889 1.0786

2.6563

A-CBL-EHD-A4-1(

3)

4.3772

A-BUS-EHD-A4-2

A-BUS-EX-A3-1-D

ISC

1 95 8 PVC Pos:

Zero:

33.4397 3.1089

7.6528

A-CBL-EHD-A4-2-

(1)

In

105.3865

MagneticCopper

A-BUS-EHD-AG-1

A-BUS-EHP-A2-1

1 130 350 PVC Pos:

Zero:

2.1328 2.7704

6.8216

A-CBL-EHD-AG-1

-(1)

In

6.7201

MagneticCopper

A-BUS-EHD-AG-1

A-BUS-EHP-AR-1

1 150 350 PVC Pos:

Zero:

2.4609 3.1966

7.8711

A-CBL-EHD-AG-1

-(3)

In

7.7539

MagneticCopper

A-BUS-EHD-AG-1

A-BUS-EX-A1-2-D

ISC

1 70 6 PVC Pos:

Zero:

15.4948 2.0812

5.1254

A-CBL-EHD-AG-1

-(4)

48.8299

A-BUS-EHD-AG-2

A-BUS-EHP-AR-2

1 125 500 PVC Pos:

Zero:

1.5951 2.5282

6.2229

A-CBL-EHD-AG-2

-(1)

In

5.0239

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-EHD-AG-2

A-BUS-EHD-A4-2

1 140 500 PVC Pos:

Zero:

1.7865 2.8316

6.9696

A-CBL-EHD-AG-2

-(2)

In

5.6267

MagneticCopper

A-BUS-EHD-AG-2

A-BUS-EHL-A1-1

1 6 4 PVC Pos:

Zero:

0.8359 0.1646

0.4052

A-CBL-EHD-AG-2

-(3)

In

2.6344

MagneticCopper

A-BUS-EHD-AG-3

A-BUS-EHD-A4-1

2 140 250 PVC Pos:

Zero:

1.6771 1.5039

3.7036

A-CBL-EHD-AG-3

-(1)

5.2834

A-BUS-EHD-AG-3

A-BUS-EHDP-AB-

1 45 4/0 PVC Pos:

Zero:

1.2500 0.9707

2.3906

A-CBL-EHD-AG-3

-(2)

In

3.9395

MagneticCopper

A-BUS-EHDP-AB-

A-BUS-EX-AB-1-P

RI

1 5 8 PVC Pos:

Zero:

1.7600 0.1636

0.4028

A-CBL-EHDP-AB-

1-(1)

In

5.5467

MagneticCopper

A-BUS-EHL-A1-1

A-BUS-EX-A1-1-P

RI

1 3 8 PVC Pos:

Zero:

1.0560 0.0982

0.2417

A-CBL-EHL-A1-1-

(1)

In

3.3280

MagneticCopper

A-BUS-EHP-A2-1

A-BUS-EHP-A2-1-

1 3 350 PVC Pos:

Zero:

0.0492 0.0639

0.1574

A-CBL-EHP-A2-1-

(1)

0.1551

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-EHP-AR-1

A-BUS-EX-AR-1-P

RI

1 150 6 PVC Pos:

Zero:

33.2031 4.4596

10.9831

A-CBL-EHP-AR-1-

(1)

In

104.6354

MagneticCopper

A-BUS-EHP-AR-1

A-BUS-S2-DISC-1

1 20 2 PVC Pos:

Zero:

1.7535 0.5078

1.2500

A-CBL-EHP-AR-1-

(2)

In

5.5260

MagneticCopper

A-BUS-EHP-AR-1

A-BUS-S1-DISC-1

1 20 2 PVC Pos:

Zero:

1.7535 0.5078

1.2500

A-CBL-EHP-AR-1-

(3)

In

5.5260

MagneticCopper

A-BUS-EHP-AR-2

A-BUS-EHP-AR-2-

1 3 500 PVC Pos:

Zero:

0.0383 0.0607

0.1493

A-CBL-EHP-AR-2-

(1)

0.1206

A-BUS-EHP-AR-2

A-BUS-P10-DISC-

1 50 2 PVC Pos:

Zero:

4.3837 1.2695

3.1250

A-CBL-EHP-AR-2-

(2)

In

13.8151

MagneticCopper

A-BUS-EHP-AR-2-

A-BUS-P11-DISC-

1 50 2 PVC Pos:

Zero:

4.3837 1.2695

3.1250

A-CBL-EHP-AR-2-

2-(1)

In

13.8151

MagneticCopper

A-BUS-EHP-AR-2-

A-BUS-P12-DISC-

1 50 2 PVC Pos:

Zero:

4.3837 1.2695

3.1250

A-CBL-EHP-AR-2-

2-(2)

In

13.8151

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-EHP-AR-2-

A-BUS-EX-AR-2-P

RI

1 6 8 PVC Pos:

Zero:

2.1120 0.1964

0.4833

A-CBL-EHP-AR-2-

2-(3)

6.6560

A-BUS-ELR-A3-1

A-BUS-ELR-A3-2

1 6 250 PVC Pos:

Zero:

0.7655 0.6865

1.6906

A-CBL-ELR-A3-1-

(1)

In

2.4117

MagneticCopper

A-BUS-ELR-A3-2

A-BUS-ELR-A3-3

1 6 250 PVC Pos:

Zero:

0.7655 0.6865

1.6906

A-CBL-ELR-A3-1-

(2)

In

2.4117

MagneticCopper

A-BUS-EX-A1-1-S

EC

A-BUS-ELP-A1-1

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

A-CBL-EX-A1-1-

(1)

In

22.2892

MagneticCopper

A-BUS-EX-A1-2-S

EC

A-BUS-ELP-A1-2

1 6 3/0 PVC Pos:

Zero:

1.1164 0.7198

1.7724

A-CBL-EX-A1-2-

(1)

3.5184

A-BUS-EX-A1-2-D

ISC

A-BUS-EX-A1-2-P

RI

1 4 6 PVC Pos:

Zero:

0.8854 0.1189

0.2929

A-CBL-EX-A1-2-D

ISC-(1)

In

2.7903

MagneticCopper

A-BUS-EX-A3-1-S

EC

A-BUS-ELP-A3-1

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

A-CBL-EX-A3-1-

(1)

In

8.8286

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-EX-A3-1-D

ISC

A-BUS-EX-A3-1-P

RI

1 5 8 PVC Pos:

Zero:

1.7600 0.1636

0.4028

A-CBL-EX-A3-1-D

ISC-(1)

In

5.5467

MagneticCopper

A-BUS-EX-A3-2-S

EC

A-BUS-ELR-A3-1

1 70 250 PVC Pos:

Zero:

8.9312 8.0090

19.7231

A-CBL-EX-A3-2-

(1)

28.1366

A-BUS-EX-A4-1-S

EC

A-BUS-ELP-A4-1

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-EX-A4-1-

(1)

In

2.7972

MagneticCopper

A-BUS-EX-A4-1-D

ISC

A-BUS-EX-A4-1-P

RI

1 6 6 PVC Pos:

Zero:

1.3281 0.1784

0.4393

A-CBL-EX-A4-1-D

ISC

In

4.1854

MagneticCopper

A-BUS-EX-A5-1-S

EC

A-BUS-ELP-A5-1

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

A-CBL-EX-A5-1-

(1)

In

22.2892

MagneticCopper

A-BUS-EX-A5-1-D

ISC

A-BUS-EX-A5-1-P

RI

1 6 10 PVC Pos:

Zero:

3.0729 0.2224

0.5477

A-CBL-EX-A5-1-D

ISC

9.6844

A-BUS-EX-AB-1-S

EC

A-BUS-ELP-AB-1

1 5 2 PVC Pos:

Zero:

2.3345 0.6761

1.6642

A-CBL-EX-AB-1-

(1)

In

7.3572

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-EX-AR-1-S

EC

A-BUS-ELP-AR-1

1 6 10 PVC Pos:

Zero:

16.3646 1.1844

2.9165

A-CBL-EX-AR-1-

(1)

In

51.5736

MagneticCopper

A-BUS-EX-AR-2-S

EC

A-BUS-ELP-AR-2

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

A-CBL-EX-AR-2-

(1)

In

22.2892

MagneticCopper

A-BUS-GEN1

A-BUS-GHSB-CB-

7 320 600 PVC Pos:

Zero:

0.5099 0.9187

2.2619

A-CBL-GEN1 In

1.6052

A-BUS-GEN2

A-BUS-GHSB-CB-

7 340 600 PVC Pos:

Zero:

0.5418 0.9761

2.4033

A-CBL-GEN2 In

1.7055

MagneticCopper

A-BUS-GEN3

A-BUS-GHSB-AG-

10 110 600 PVC Pos:

Zero:

0.1227 0.2211

0.5443

A-CBL-GEN3 In

0.3862

MagneticCopper

A-BUS-GEN4

A-BUS-GHSB-AG-

10 90 600 PVC Pos:

Zero:

0.1004 0.1809

0.4453

A-CBL-GEN4 In

0.3160

MagneticCopper

A-BUS-GEN5

A-BUS-GHSB-AG-

10 70 600 PVC Pos:

Zero:

0.0781 0.1407

0.3464

A-CBL-GEN5 In

0.2458

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-GHATS-A

G-1-(L)

A-BUS-GHECB-A

G-1

1 6 2/0 PVC Pos:

Zero:

0.2656 0.1388

0.3417

A-CBL-GHATS-A

G-1-(1)

In

0.8370

MagneticCopper

A-BUS-GHECB-A

G-1

A-BUS-GLX-AG-1-

PRI

1 6 2/0 PVC Pos:

Zero:

0.2656 0.1388

0.3417

A-CBL-GHECB-A

G-1-(1)

In

0.8370

MagneticCopper

A-BUS-GHSB-AG-

A-BUS-GHTA-AG-

8 15 600 PVC Pos:

Zero:

0.0209 0.0377

0.0928

A-CBL-GHSB-AG-

1-(1)

In

0.0658

MagneticCopper

A-BUS-GHSB-AG-

A-BUS-GHSB-CB-

10 3 600 PVC Pos:

Zero:

0.0033 0.0060

0.0148

A-CBL-GHSB-AG-

1-(10)

0.0105

A-BUS-GHSB-AG-

C-BUS-GHTA-CB-

4 200 600 PVC Pos:

Zero:

0.5577 1.0048

2.4740

A-CBL-GHSB-AG-

1-(2)

In

1.7556

MagneticCopper

A-BUS-GHSB-AG-

C-BUS-GHTA-CB-

4 100 600 PVC Pos:

Zero:

0.2789 0.5024

1.2370

A-CBL-GHSB-AG-

1(4)

In

0.8778

MagneticCopper

A-BUS-GHSB-AG-

A-BUS-GHATS-A

G-1-(E)

1 35 2/0 PVC Pos:

Zero:

1.5495 0.8097

1.9931

A-CBL-GHSB-AG-

1(5)

In

4.8824

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-GHSB-AG-

A-BUS-GHSB-AG-

1-DUCT-(1)

10 10 600 PVC Pos:

Zero:

0.0112 0.0201

0.0495

A-CBL-GHSB-AG-

1-(6)

0.0351

A-BUS-GHSB-AG-

1-DUCT-(2)

10 15 600 PVC Pos:

Zero:

0.0167 0.0301

0.0742

A-CBL-GHSB-AG-

1-(7)

In

0.0527

MagneticCopper

A-BUS-GHSB-AG-

A-BUS-GHSB-AG-

6 10 600 PVC Pos:

Zero:

0.0186 0.0335

0.0825

A-CBL-GHSB-AG-

1-(9)

In

0.0585

MagneticCopper

A-BUS-GHSB-AG-

1-DUCT-(1)

A-BUS-NHSB-C3-

2-DUCT

1 280 4000 Epoxy Pos:

Zero:

0.4010 0.2309

1.2274

A-CBL-GHSB-AG-

1-DUCT-(1)

In

2.3819

BuswayCopper

A-BUS-GHSB-AG-

1-DUCT-(2)

C-BUS-NHSB-C3-

1-DUCT

1 265 4000 Epoxy Pos:

Zero:

0.3796 0.2185

1.1617

A-CBL-GHSB-AG-

1-DUCT-(2)

2.2543

BuswayCopper

A-BUS-ATS-Q1-

(E)

2 30 600 PVC Pos:

Zero:

0.1673 0.3014

0.7422

A-CBL-GHSB-AG-

2-(1)

In

0.5267

MagneticCopper

A-BUS-GHSB-AG-

A-BUS-ATS-E-(E)

2 20 600 PVC Pos:

Zero:

0.1115 0.2010

0.4948

A-CBL-GHSB-AG-

2-(2)

In

0.3511

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-GHSB-AG-

A-BUS-ATS-Q3-

(E)

2 40 600 PVC Pos:

Zero:

0.2231 0.4019

0.9896

A-CBL-GHSB-AG-

2-(3)

In

0.7023

MagneticCopper

A-BUS-GHSB-AG-

A-BUS-ATS-Q2-

(E)

3 40 300 PVC Pos:

Zero:

0.2685 0.2853

0.7025

A-CBL-GHSB-AG-

2-(4)

0.8461

A-BUS-ATS-MTS-

(E)

1 40 4/0 PVC Pos:

Zero:

1.1111 0.8628

2.1250

A-CBL-GHSB-AG-

2-(5)

In

3.5017

MagneticCopper

A-BUS-GHSB-AG-

A-BUS-ATS-L-(E)

1 50 3/0 PVC Pos:

Zero:

1.7470 1.1263

2.7734

A-CBL-GHSB-AG-

2-(6)

In

5.5056

MagneticCopper

A-BUS-GHSB-CB-

A-BUS-SHATS-CB

-1-(E)

1 20 350 PVC Pos:

Zero:

0.3281 0.4262

1.0495

A-CBL-GHSB-CB-

1-(2)

In

1.0339

MagneticCopper

A-BUS-GHSB-CB-

C-BUS-SHD-C3-2

2 260 600 PVC Pos:

Zero:

1.4501 2.6124

6.4323

A-CBL-GHSB-CB-

1-(3)

4.5647

A-BUS-GHSB-CB-

A-BUS-GHSB-CB-

1-DUCT-(1)

12 260 600 PVC Pos:

Zero:

0.2417 0.4354

1.0720

A-CBL-GHSB-CB-

1-(4)

In

0.7608

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-GHSB-CB-

C-BUS-ATS-F-(E)

1 95 2 PVC Pos:

Zero:

8.3290 2.4121

5.9375

A-CBL-GHSB-CB-

1-(5)

In

26.2487

MagneticCopper

A-BUS-GHSB-CB-

F-BUS-ATS-PG-(E)

1 275 500 PVC Pos:

Zero:

3.5091 5.5621

13.6903

A-CBL-GHSB-CB-

1-(6)

In

11.0525

MagneticCopper

A-BUS-GHSB-CB-

C-BUS-ATS-2-(E)

1 675 600 PVC Pos:

Zero:

7.5293 13.5645

33.3984

A-CBL-GHSB-CB-

1-(7)

23.7012

A-BUS-GHSB-CB-

C-BUS-EHATS-CB

-1-(E)

5 85 600 PVC Pos:

Zero:

0.1896 0.3416

0.8411

A-CBL-GHSB-CB-

1-(8)

In

0.5969

MagneticCopper

A-BUS-GHSB-CB-

1-DUCT-(1)

C-BUS-GHSB-C3-

1 5 4000 Epoxy Pos:

Zero:

0.0072 0.0041

0.0219

A-CBL-GHSB-CB-

1-DUCT-(1)

In

0.0425

BuswayCopper

A-BUS-GHTA-AG-

A-BUS-SWBD-C

8 35 600 PVC Pos:

Zero:

0.0488 0.0879

0.2165

A-CBL-GHTA-AG-

1-(1)

In

0.1536

MagneticCopper

A-BUS-GLD-AG-1

A-BUS-GEN3PNL

1 110 1 PVC Pos:

Zero:

40.6805 14.4924

35.6717

A-CBL-GLD-AG-1-

(1)

128.1943

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-GLD-AG-1

A-BUS-GEN4PNL

1 90 1 PVC Pos:

Zero:

33.2840 11.8574

29.1859

A-CBL-GLD-AG-1-

(2)

In

104.8863

MagneticCopper

A-BUS-GLD-AG-1

A-BUS-GEN5PNL

1 70 1 PVC Pos:

Zero:

25.8876 9.2224

22.7002

A-CBL-GLD-AG-1-

(3)

In

81.5782

MagneticCopper

A-BUS-GLX-AG-1-

SEC

A-BUS-GLD-AG-1

1 15 500 PVC Pos:

Zero:

1.0193 1.6157

3.9767

A-CBL-GLX-AG-1-

(1)

In

3.2105

MagneticCopper

A-BUS-HL-5A-277

A-BUS-HL-5A-277

-2

1 3 1/0 PVC Pos:

Zero:

0.1667 0.0703

0.1730

A-CBL-HL-5A-277

-(1)

0.5253

A-BUS-HL-5A-277

-2

A-BUS-UPS-NEUR

O-PRI

1 6 10 PVC Pos:

Zero:

3.0729 0.2224

0.5477

A-CBL-HL-5A-277

-2-(1)

In

9.6844

MagneticCopper

A-BUS-NHD-A1-1

A-BUS-NX-A4-5-D

ISC

1 6 1/0 PVC Pos:

Zero:

0.3333 0.1406

0.3461

A-CBL-NHD-A1-1-

(1)

In

1.0505

MagneticCopper

A-BUS-NHD-A1-1

A-BUS-NX-A2-5-D

ISC

1 60 2 PVC Pos:

Zero:

5.2604 1.5234

3.7500

A-CBL-NHD-A1-1-

(3)

In

16.5781

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NHD-A1-1

A-BUS-NX-A3-5-D

ISC

1 75 8 PVC Pos:

Zero:

26.3997 2.4544

6.0417

A-CBL-NHD-A1-1-

(4)

83.1999

A-BUS-NHD-A1-1

A-BUS-T1A5A-PRI

1 6 1 PVC Pos:

Zero:

0.4167 0.1484

0.3654

A-CBL-NHD-A1-1-

(5)

In

1.3130

MagneticCopper

A-BUS-NHD-A1-1

A-BUS-NX-A5-5-D

ISC

1 105 1/0 PVC Pos:

Zero:

5.8333 2.4609

6.0566

A-CBL-NHD-A1-1-

(6)

In

18.3841

MagneticCopper

A-BUS-NHD-A1-1

A-BUS-NX-A5-6-D

ISC

1 170 6 PVC Pos:

Zero:

37.6302 5.0543

12.4475

A-CBL-NHD-A1-1-

(7)

In

118.5868

MagneticCopper

A-BUS-NHD-A1-1

A-BUS-NX-A1-5-D

ISC

1 6 10 PVC Pos:

Zero:

3.0729 0.2224

0.5477

A-CBL-NHD-A1-1-

(8)

A-BUS-NHL-A5-2

A-BUS-NX-A5-2-P

RI

1 6 1/0 PVC Pos:

Zero:

0.3333 0.1406

0.3461

A-CBL-NHD-A5-2-

(1)

In

1.0505

MagneticCopper

A-BUS-NHD-AG-1

A-BUS-NHD-AG-1

-TAP

1 45 350 PVC Pos:

Zero:

0.7383 0.9590

2.3613

A-CBL-NHD-AG-1

-(1)

In

2.3262

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NHD-AG-1

A-BUS-NHD-AG-1

-2-TAP

1 60 1/0 PVC Pos:

Zero:

3.3333 1.4063

3.4609

A-CBL-NHD-AG-1

-(2)

In

10.5052

MagneticCopper

A-BUS-NHD-AG-1

A-BUS-NHL-A5-1

1 75 1/0 PVC Pos:

Zero:

4.1667 1.7578

4.3262

A-CBL-NHD-AG-1

-(3)

13.1315

A-BUS-NHD-AG-1

A-BUS-NHL-AG-1

1 12 3 PVC Pos:

Zero:

1.3177 0.3151

0.7755

A-CBL-NHD-AG-1

-(4)

In

4.1526

MagneticCopper

A-BUS-NHD-AG-1

-2-TAP

A-BUS-NHL-A1-1

1 3 2 PVC Pos:

Zero:

0.2630 0.0762

0.1875

A-CBL-NHD-AG-1

-2-TAP-(1)

In

0.8289

MagneticCopper

A-BUS-NHD-AG-1

-2-TAP

A-BUS-NHL-A2-1

1 15 1/0 PVC Pos:

Zero:

0.8333 0.3516

0.8652

A-CBL-NHD-AG-1

-2-TAP-(2)

In

2.6263

MagneticCopper

A-BUS-NHD-AG-1

-TAP

A-BUS-NHL-A3-1

1 3 2 PVC Pos:

Zero:

0.2630 0.0762

0.1875

A-CBL-NHD-AG-1

-TAP-(1)

0.8289

A-BUS-NHD-AG-1

-TAP

A-BUS-NHL-A4-1

1 15 350 PVC Pos:

Zero:

0.2461 0.3197

0.7871

A-CBL-NHD-AG-1

-TAP-(2)

In

0.7754

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NHD-AG-2

A-BUS-NHL-A5-2

1 135 3/0 PVC Pos:

Zero:

4.7168 3.0410

7.4883

A-CBL-NHD-AG-2

(1)

In

14.8652

MagneticCopper

A-BUS-NHD-AG-2

A-BUS-NHD-AG-2

-(2)-TAP

1 105 1/0 PVC Pos:

Zero:

5.8333 2.4609

6.0566

A-CBL-NHD-AG-2

(2)

In

18.3841

MagneticCopper

A-BUS-NHD-AG-2

-(2)-TAP

A-BUS-NHL-A3-2

1 6 6 PVC Pos:

Zero:

1.3281 0.1784

0.4393

A-CBL-NHD-AG-2

-(2)-TAP-(1)

A-BUS-NHD-AG-2

-(2)-TAP

A-BUS-NHL-A4-2

1 15 1/0 PVC Pos:

Zero:

0.8333 0.3516

0.8652

A-CBL-NHD-AG-2

-(2)-TAP-(2)

In

2.6263

MagneticCopper

A-BUS-NHD-AG-2

A-BUS-NHD-AG-2

-(3)-TAP

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

A-CBL-NHD-AG-2

(3)

In

8.7543

MagneticCopper

A-BUS-NHD-AG-2

-(3)-TAP

A-BUS-NHL-A1-2

1 3 2 PVC Pos:

Zero:

0.2630 0.0762

0.1875

A-CBL-NHD-AG-2

-(3)-TAP-(1)

In

0.8289

MagneticCopper

A-BUS-NHD-AG-2

-(3)-TAP

A-BUS-NHL-A2-2

1 55 1/0 PVC Pos:

Zero:

3.0556 1.2891

3.1725

A-CBL-NHD-AG-2

-(3)-TAP-(2)

9.6298

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NHD-AG-2

A-BUS-NHL-AG-2

1 5 2 PVC Pos:

Zero:

0.4384 0.1270

0.3125

A-CBL-NHD-AG-2

(4)

In

1.3815

MagneticCopper

A-BUS-NHD-AG-3

A-BUS-NX-A4-3-D

ISC

1 130 1/0 PVC Pos:

Zero:

7.2222 3.0469

7.4987

A-CBL-NHD-AG-3

-(1)

In

22.7613

MagneticCopper

A-BUS-NHD-AG-3

A-BUS-NX-A5-3-D

ISC

1 150 1/0 PVC Pos:

Zero:

8.3333 3.5156

8.6523

A-CBL-NHD-AG-3

-(2)

In

26.2630

MagneticCopper

A-BUS-NHD-AG-3

A-BUS-NX-A5-7-D

ISC

1 195 2 PVC Pos:

Zero:

17.0964 4.9512

12.1875

A-CBL-NHD-AG-3

-(3)

53.8789

A-BUS-NHD-AG-4

A-BUS-NHL-A1-3

1 50 4/0 PVC Pos:

Zero:

1.3889 1.0786

2.6563

A-CBL-NHD-AG-4

-(1)

In

4.3772

MagneticCopper

A-BUS-NHD-AG-4

A-BUS-NHL-A2-3

1 105 2 PVC Pos:

Zero:

9.2057 2.6660

6.5625

A-CBL-NHD-AG-4

-(2)

In

29.0117

MagneticCopper

A-BUS-NHD-AG-4

A-BUS-NX-AG-5-

DISC

1 140 1 PVC Pos:

Zero:

9.7222 3.4635

8.5252

A-CBL-NHD-AG-4

-(3)

In

30.6372

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NHD-AG-4

A-BUS-NX-AG-3-P

RI

1 8 2 PVC Pos:

Zero:

0.7014 0.2031

0.5000

A-CBL-NHD-AG-4

-(4)

2.2104

A-BUS-NHD-AG-4

A-BUS-NX-A3-3-D

ISC

1 120 8 PVC Pos:

Zero:

42.2396 3.9271

9.6667

A-CBL-NHD-AG-4

-(5)

In

133.1198

MagneticCopper

A-BUS-NHD-AG-5

A-BUS-NHL-A1-5

1 110 250 PVC Pos:

Zero:

2.6354 2.3633

5.8199

A-CBL-NHD-AG-5

-(1)

In

8.3025

MagneticCopper

A-BUS-NHD-AG-5

A-BUS-NHD-AG-5

-(3)-TAP

1 50 4/0 PVC Pos:

Zero:

1.3889 1.0786

2.6563

A-CBL-NHD-AG-5

-(3)

In

4.3772

MagneticCopper

A-BUS-NHD-AG-5

-(3)-TAP

A-BUS-NHL-A1-4

1 10 1/0 PVC Pos:

Zero:

0.5556 0.2344

0.5768

A-CBL-NHD-AG-5

-(3)-TAP-(1)

1.7509

A-BUS-NHD-AG-5

-(3)-TAP

A-BUS-NHL-A2-4

1 55 4/0 PVC Pos:

Zero:

1.5278 1.1864

2.9219

A-CBL-NHD-AG-5

-(3)-TAP-(2)

In

4.8149

MagneticCopper

A-BUS-NHD-AG-5

A-BUS-NHD-AG-5

-(4)-TAP

1 45 4/0 PVC Pos:

Zero:

1.2500 0.9707

2.3906

A-CBL-NHD-AG-5

-(4)

In

3.9395

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NHD-AG-5

A-BUS-NHL-A5-3

1 75 1/0 PVC Pos:

Zero:

4.1667 1.7578

4.3262

A-CBL-NHD-AG-5

-(5)

In

13.1315

MagneticCopper

A-BUS-NHD-AG-5

A-BUS-NHL-AG-3

1 12 1 PVC Pos:

Zero:

0.8333 0.2969

0.7307

A-CBL-NHD-AG-5

-(6)

2.6260

A-BUS-NHL-A1-1

A-BUS-NX-A1-1-P

RI

1 6 6 PVC Pos:

Zero:

1.3281 0.1784

0.4393

A-CBL-NHL-A1-1-

(1)

In

4.1854

MagneticCopper

A-BUS-NHL-A1-2

A-BUS-NX-A1-2-P

RI

1 3 10 PVC Pos:

Zero:

1.5365 0.1112

0.2738

A-CBL-NHL-A1-2-

(1)

In

4.8422

MagneticCopper

A-BUS-NHL-A1-3

A-BUS-NX-A1-3-P

RI

1 6 2/0 PVC Pos:

Zero:

0.2656 0.1388

0.3417

A-CBL-NHL-A1-3-

(1)

In

0.8370

MagneticCopper

A-BUS-NHL-A1-4

A-BUS-NX-A1-4-P

RI

1 6 4 PVC Pos:

Zero:

0.8359 0.1646

0.4052

A-CBL-NHL-A1-4-

(2)

2.6344

A-BUS-NHL-A1-5

A-BUS-NX-A1-6-P

RI

1 6 1/0 PVC Pos:

Zero:

0.3333 0.1406

0.3461

A-CBL-NHL-A1-5-

(1)

In

1.0505

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NHL-A2-1

A-BUS-NX-A2-1-P

RI

1 6 8 PVC Pos:

Zero:

2.1120 0.1964

0.4833

A-CBL-NHL-A2-1-

(1)

In

6.6560

MagneticCopper

A-BUS-NHL-A2-2

A-BUS-NX-A2-2-P

RI

1 6 8 PVC Pos:

Zero:

2.1120 0.1964

0.4833

A-CBL-NHL-A2-2-

(1)

In

6.6560

MagneticCopper

A-BUS-NHL-A2-3

A-BUS-NX-A2-3-P

RI

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

A-CBL-NHL-A2-3-

(1)

A-BUS-NHL-A2-4

A-BUS-NX-A2-4-P

RI

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

A-CBL-NHL-A2-4-

(1)

In

1.6578

MagneticCopper

A-BUS-NHL-A3-1

A-BUS-NX-A3-1-P

RI

1 6 6 PVC Pos:

Zero:

1.3281 0.1784

0.4393

A-CBL-NHL-A3-1-

(1)

In

4.1854

MagneticCopper

A-BUS-NHL-A3-2

A-BUS-NX-A3-2-P

RI

1 6 10 PVC Pos:

Zero:

3.0729 0.2224

0.5477

A-CBL-NHL-A3-2-

(1)

In

9.6844

MagneticCopper

A-BUS-NHD-AG-5

-(4)-TAP

A-BUS-NHL-A3-3

1 10 2/0 PVC Pos:

Zero:

0.4427 0.2313

0.5694

A-CBL-NHL-A3-3 In

1.3950

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NHL-A3-3

A-BUS-NX-A3-4-P

RI

1 6 8 PVC Pos:

Zero:

2.1120 0.1964

0.4833

A-CBL-NHL-A3-3-

(1)

In

6.6560

MagneticCopper

A-BUS-NHL-A4-1

A-BUS-NX-A4-1-P

RI

1 6 1/0 PVC Pos:

Zero:

0.3333 0.1406

0.3461

A-CBL-NHL-A4-1-

(1)

In

1.0505

MagneticCopper

A-BUS-NHL-A4-2

A-BUS-NX-A4-2-P

RI

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

A-CBL-NHL-A4-2-

(1)

In

1.6578

MagneticCopper

A-BUS-NHD-AG-5

-(4)-TAP

A-BUS-NHL-A4-3

1 3 4/0 PVC Pos:

Zero:

0.0833 0.0647

0.1594

A-CBL-NHL-A4-3 In

0.2626

A-BUS-NHL-A4-3

A-BUS-NX-A4-4-P

RI

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

A-CBL-NHL-A4-3-

(1)

In

1.6578

MagneticCopper

A-BUS-NHL-A5-1

A-BUS-NX-A5-1-P

RI

1 6 6 PVC Pos:

Zero:

1.3281 0.1784

0.4393

A-CBL-NHL-A5-1-

(1)

In

4.1854

MagneticCopper

A-BUS-NHL-A5-3

A-BUS-NX-A5-4-P

RI

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

A-CBL-NHL-A5-3-

(1)

In

1.6578

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NHL-AG-1

A-BUS-NX-AG-1-P

RI

1 6 10 PVC Pos:

Zero:

3.0729 0.2224

0.5477

A-CBL-NHL-AG-1-

(1)

A-BUS-NHL-AG-2

A-BUS-NX-AG-2-P

RI

1 5 2 PVC Pos:

Zero:

0.4384 0.1270

0.3125

A-CBL-NHL-AG-2-

(1)

In

1.3815

MagneticCopper

A-BUS-NHL-AG-3

A-BUS-NX-AG-4-P

RI

1 8 8 PVC Pos:

Zero:

2.8160 0.2618

0.6444

A-CBL-NHL-AG-3-

(1)

In

8.8747

MagneticCopper

A-BUS-NHLP-AB-

A-BUS-NX-AB-1-P

RI

1 6 10 PVC Pos:

Zero:

3.0729 0.2224

0.5477

A-CBL-NHLP-AB-

1-(1)

In

9.6844

MagneticCopper

A-BUS-NHSB-C3-

2-DUCT

C-BUS-NHSB-C3-

2-(B)

10 6 600 PVC Pos:

Zero:

0.0067 0.0121

0.0297

A-CBL-NHSB-C3-

2-MAIN-(E)

0.0211

C-BUS-NHSB-CB-

C-BUS-EHATS-CB

-1-(N)

1 30 2000 Epoxy Pos:

Zero:

0.0859 0.0456

0.2435

A-CBL-NHSB-CB-

3-(1)

In

0.5104

BuswayCopper

A-BUS-NLD-AG-1

A-BUS-NLP-AG-7

1 5 350 PVC Pos:

Zero:

0.4369 0.5674

1.3972

A-CBL-NLD-AG-1-

(1)

In

1.3764

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NLD-AG-1-

DISC

A-BUS-NLD-AG-1

3 5 350 PVC Pos:

Zero:

0.1456 0.1891

0.4657

A-CBL-NLD-AG-1-

DISC-(1)

In

0.4588

MagneticCopper

A-BUS-NLP-AG-7

A-BUS-NLP-AG-7-

1 5 350 PVC Pos:

Zero:

0.4369 0.5674

1.3972

A-CBL-NLD-AG-7-

(1)

1.3764

A-BUS-NLP-A1-3

A-BUS-NLP-A1-3-

1 3 250 PVC Pos:

Zero:

0.3828 0.3432

0.8453

A-CBL-NLP-A1-3-

(1)

In

1.2059

MagneticCopper

A-BUS-NLP-A1-8

A-BUS-NLP-A1-8-

1 8 250 PVC Pos:

Zero:

1.0207 0.9153

2.2541

A-CBL-NLP-A1-8-

(1)

In

3.2156

MagneticCopper

A-BUS-NLP-A4-1

A-BUS-NLP-A4-1-

1 3 500 PVC Pos:

Zero:

0.2039 0.3231

0.7953

A-CBL-NLP-A4-1-

(1)

In

0.6421

MagneticCopper

A-BUS-NLP-A4-2

A-BUS-NLP-A4-2-

1 3 4/0 PVC Pos:

Zero:

0.4438 0.3446

0.8487

A-CBL-NLP-A4-2-

(1)

1.3986

A-BUS-NLP-A4-3

A-BUS-NLP-A4-3-

1 3 500 PVC Pos:

Zero:

0.2039 0.3231

0.7953

A-CBL-NLP-A4-3-

(1)

In

0.6421

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NLP-A4-5

A-BUS-NLP-A4-5-

1 3 500 PVC Pos:

Zero:

0.2039 0.3231

0.7953

A-CBL-NLP-A4-5-

(1)

In

0.6421

MagneticCopper

A-BUS-NLP-A5-2

A-BUS-NLP-A5-2-

1 3 4/0 PVC Pos:

Zero:

0.4438 0.3446

0.8487

A-CBL-NLP-A5-2-

(1)

In

1.3986

MagneticCopper

A-BUS-NLP-A5-3

A-BUS-NLP-A5-3-

1 3 4/0 PVC Pos:

Zero:

0.4438 0.3446

0.8487

A-CBL-NLP-A5-3-

(1)

1.3986

A-BUS-NLP-AG-2

A-BUS-NLP-AG-2-

1 5 2/0 PVC Pos:

Zero:

1.1788 0.6160

1.5163

A-CBL-NLP-AG-2-

(1)

In

3.7144

MagneticCopper

A-BUS-NLP-AG-2

A-BUS-NLP-AG-2-

1 5 2 PVC Pos:

Zero:

2.3345 0.6761

1.6642

A-CBL-NLP-AG-2-

(2)

In

7.3572

MagneticCopper

A-BUS-NLP-AG-3

A-BUS-NLP-AG-3-

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-NLP-AG-3-

(1)

In

2.7972

MagneticCopper

A-BUS-NLP-AG-5

A-BUS-NLP-AG-5-

1 5 1/0 PVC Pos:

Zero:

1.4793 0.6241

1.5359

A-CBL-NLP-AG-5-

(1)

4.6621

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

C-BUS-NPE-1-DIS

C

C-BUS-NPE-1-DIS

C-(1)

1 10 10 PVC Pos:

Zero:

5.1215 0.3707

0.9128

A-CBL-NPE-1-DIS

C-(1)

In

16.1406

MagneticCopper

A-BUS-NX-A1-1-S

EC

A-BUS-NLP-A1-1

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

A-CBL-NX-A1-1-

(1)

In

8.8286

MagneticCopper

A-BUS-NX-A1-2-S

EC

A-BUS-NLP-A1-2

1 3 6 PVC Pos:

Zero:

3.5364 0.4750

1.1698

A-CBL-NX-A1-2-

(1)

In

11.1446

MagneticCopper

A-BUS-NX-A1-3-S

EC

A-BUS-NLP-A1-7

1 6 2/0 PVC Pos:

Zero:

1.4146 0.7392

1.8195

A-CBL-NX-A1-3-

(1)

4.4573

A-BUS-NX-A1-3-S

EC

A-BUS-NLP-A1-3

1 6 250 PVC Pos:

Zero:

0.7655 0.6865

1.6906

A-CBL-NX-A1-3-

(2)

In

2.4117

MagneticCopper

A-BUS-NX-A1-4-S

EC

A-BUS-NHP-A1-4

1 6 3/0 PVC Pos:

Zero:

1.1164 0.7198

1.7724

A-CBL-NX-A1-4-

(1)

In

3.5184

MagneticCopper

A-BUS-NX-A1-5-S

EC

A-BUS-NLD-A1-5

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

A-CBL-NX-A1-5-

(1)

In

22.2892

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NX-A1-5-D

ISC

A-BUS-NX-A1-5-P

RI

1 3 10 PVC Pos:

Zero:

1.5365 0.1112

0.2738

A-CBL-NX-A1-5-D

ISC-(1)

4.8422

A-BUS-NX-A1-6-S

EC

A-BUS-NX-A1-6-T

AP

1 3 250 PVC Pos:

Zero:

0.3828 0.3432

0.8453

A-CBL-NX-A1-6-

(1)

In

1.2059

MagneticCopper

A-BUS-NX-A1-6-T

AP

A-BUS-NLP-A1-9

1 8 2 PVC Pos:

Zero:

3.7352 1.0817

2.6627

A-CBL-NX-A1-6-T

AP-(1)

In

11.7715

MagneticCopper

A-BUS-NX-A1-6-T

AP

A-BUS-NLP-A1-8

1 8 250 PVC Pos:

Zero:

1.0207 0.9153

2.2541

A-CBL-NX-A1-6-T

AP-(2)

In

3.2156

MagneticCopper

A-BUS-NX-A2-1-S

EC

A-BUS-NLP-A2-1

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

A-CBL-NX-A2-1-

(1)

8.8286

A-BUS-NX-A2-2-S

EC

A-BUS-NLP-A2-2

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

A-CBL-NX-A2-2-

(1)

In

8.8286

MagneticCopper

A-BUS-NX-A2-3-S

EC

A-BUS-NLP-A2-3-

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-NX-A2-3-

(1)

In

2.7972

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NLP-A2-3-

A-BUS-NLP-A2-3

1 3 4/0 PVC Pos:

Zero:

0.4438 0.3446

0.8487

A-CBL-NX-A2-3-2

-(1)

In

1.3986

MagneticCopper

A-BUS-NX-A2-4-S

EC

A-BUS-NLP-A2-4

1 10 4/0 PVC Pos:

Zero:

1.4793 1.1488

2.8291

A-CBL-NX-A2-4-

(1)

A-BUS-NX-A2-5-S

EC

A-BUS-NLP-A2-5

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-NX-A2-5-

(1)

In

2.7972

MagneticCopper

A-BUS-NX-A2-5-D

ISC

A-BUS-NX-A2-5-P

RI

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

A-CBL-NX-A2-5-D

ISC-(1)

In

1.6578

MagneticCopper

A-BUS-NX-A3-1-S

EC

A-BUS-NLP-A3-1

1 6 3/0 PVC Pos:

Zero:

1.1164 0.7198

1.7724

A-CBL-NX-A3-1-S

EC

In

3.5184

MagneticCopper

A-BUS-NX-A3-2-S

EC

A-BUS-NLP-A3-2

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

A-CBL-NX-A3-2-

(1)

22.2892

A-BUS-NX-A3-3-S

EC

A-BUS-NLP-A3-3

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

A-CBL-NX-A3-3-

(1)

In

8.8286

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NX-A3-3-D

ISC

A-BUS-NX-A3-3-P

RI

1 6 8 PVC Pos:

Zero:

2.1120 0.1964

0.4833

A-CBL-NX-A3-3-D

ISC-(1)

In

6.6560

MagneticCopper

A-BUS-NX-A3-4-S

EC

A-BUS-NLP-A3-4

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

A-CBL-NX-A3-4-

(1)

In

8.8286

MagneticCopper

A-BUS-NX-A3-5-S

EC

A-BUS-NLP-A3-5

1 6 1 PVC Pos:

Zero:

2.2189 0.7905

1.9457

A-CBL-NX-A3-5-

(1)

6.9924

A-BUS-NX-A3-5-D

ISC

A-BUS-NX-A3-5-P

RI

1 6 8 PVC Pos:

Zero:

2.1120 0.1964

0.4833

A-CBL-NX-A3-5-D

ISC-(1)

In

6.6560

MagneticCopper

A-BUS-NX-A4-1-S

EC

A-BUS-NLP-A4-1

1 6 500 PVC Pos:

Zero:

0.4077 0.6463

1.5907

A-CBL-NX-A4-1-S

EC

In

1.2842

MagneticCopper

A-BUS-NX-A4-2-S

EC

A-BUS-NLP-A4-2

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-NX-A4-2-

(1)

In

2.7972

MagneticCopper

A-BUS-NX-A4-3-S

EC

A-BUS-NLP-A4-3

1 6 500 PVC Pos:

Zero:

0.4077 0.6463

1.5907

A-CBL-NX-A4-3-

(1)

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NX-A4-3-D

ISC

A-BUS-NX-A4-3-P

RI

1 6 1/0 PVC Pos:

Zero:

0.3333 0.1406

0.3461

A-CBL-NX-A4-3-D

ISC-(1)

In

1.0505

MagneticCopper

A-BUS-NX-A4-4-S

EC

A-BUS-NLP-A4-4

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-NX-A4-4-

(1)

In

2.7972

MagneticCopper

A-BUS-NX-A4-5-S

EC

A-BUS-NLP-A4-5

1 6 500 PVC Pos:

Zero:

0.4077 0.6463

1.5907

A-CBL-NX-A4-5-

(1)

In

1.2842

MagneticCopper

A-BUS-NX-A4-5-D

ISC

A-BUS-NX-A4-5-P

RI

1 6 1/0 PVC Pos:

Zero:

0.3333 0.1406

0.3461

A-CBL-NX-A4-5-D

ISC-(1)

1.0505

A-BUS-NX-A5-1-S

EC

A-BUS-NLP-A5-1

1 6 1/0 PVC Pos:

Zero:

1.7751 0.7489

1.8431

A-CBL-NX-A5-1-

(1)

In

5.5945

MagneticCopper

A-BUS-NX-A5-2-S

EC

A-BUS-NX-A5-2-T

AP

1 3 4/0 PVC Pos:

Zero:

0.4438 0.3446

0.8487

A-CBL-NX-A5-2-

(1)

In

1.3986

MagneticCopper

A-BUS-NX-A5-2-T

AP

A-BUS-NLP-A5-7

1 6 1/0 PVC Pos:

Zero:

1.7751 0.7489

1.8431

A-CBL-NX-A5-2-T

AP-(1)

In

5.5945

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NX-A5-2-T

AP

A-BUS-NLP-A5-2

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-NX-A5-2-T

AP-(2)

A-BUS-NX-A5-3-S

EC

A-BUS-NLP-A5-3

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-NX-A5-3-

(1)

In

2.7972

MagneticCopper

A-BUS-NX-A5-3-S

EC

A-BUS-NLP-A5-8

1 6 1/0 PVC Pos:

Zero:

1.7751 0.7489

1.8431

A-CBL-NX-A5-3-

(2)

In

5.5945

MagneticCopper

A-BUS-NX-A5-3-D

ISC

A-BUS-NX-A5-3-P

RI

1 6 1/0 PVC Pos:

Zero:

0.3333 0.1406

0.3461

A-CBL-NX-A5-3-D

ISC-(1)

In

1.0505

MagneticCopper

A-BUS-NX-A5-4-S

EC

A-BUS-NLP-A5-4

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-NX-A5-4-

(1)

A-BUS-NX-A5-5-S

EC

A-BUS-NLP-A5-5

1 6 1/0 PVC Pos:

Zero:

1.7751 0.7489

1.8431

A-CBL-NX-A5-5-

(1)

In

5.5945

MagneticCopper

A-BUS-NX-A5-5-S

EC

A-BUS-NLP-A5-10

1 6 3/0 PVC Pos:

Zero:

1.1164 0.7198

1.7724

A-CBL-NX-A5-5-

(2)

In

3.5184

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NX-A5-5-D

ISC

A-BUS-NX-A5-5-P

RI

1 6 1/0 PVC Pos:

Zero:

0.3333 0.1406

0.3461

A-CBL-NX-A5-5-D

ISC-(1)

In

1.0505

MagneticCopper

A-BUS-NX-A5-6-S

EC

A-BUS-NLP-A5-6

1 6 4/0 PVC Pos:

Zero:

0.8876 0.6893

1.6975

A-CBL-NX-A5-6-

(1)

A-BUS-NX-A5-6-D

ISC

A-BUS-NX-A5-6-P

RI

1 6 6 PVC Pos:

Zero:

1.3281 0.1784

0.4393

A-CBL-NX-A5-6-D

ISC-(1)

In

4.1854

MagneticCopper

A-BUS-NX-A5-7-S

EC

A-BUS-NLP-A5-9

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

A-CBL-NX-A5-7-

(1)

In

8.8286

MagneticCopper

A-BUS-NX-A5-7-S

EC

A-BUS-NLP-A5-11

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

A-CBL-NX-A5-7-

(2)

In

8.8286

MagneticCopper

A-BUS-NX-A5-7-D

ISC

A-BUS-NX-A5-7-P

RI

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

A-CBL-NX-A5-7-D

ISC-(1)

A-BUS-NX-AB-1-S

EC

A-BUS-NLPP-AB-

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

A-CBL-NX-AB-1-

(1)

In

22.2892

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NX-AG-1-S

EC

A-BUS-NLP-AG-1

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

A-CBL-NX-AG-1-

(1)

In

22.2892

MagneticCopper

A-BUS-NX-AG-2-S

EC

A-BUS-NLP-AG-2

1 5 4/0 PVC Pos:

Zero:

0.7396 0.5744

1.4146

A-CBL-NX-AG-2-

(1)

In

2.3310

MagneticCopper

A-BUS-NX-AG-3-S

EC

A-BUS-NLP-AG-3

1 8 4/0 PVC Pos:

Zero:

1.1834 0.9190

2.2633

A-CBL-NX-AG-3-

(1)

3.7297

A-BUS-NX-AG-4-S

EC

A-BUS-NLP-AG-4

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

A-CBL-NX-AG-4-

(1)

In

8.8286

MagneticCopper

A-BUS-NX-AG-5-S

EC

A-BUS-NLP-AG-5

1 10 1/0 PVC Pos:

Zero:

2.9586 1.2482

3.0718

A-CBL-NX-AG-5-

(1)

In

9.3242

MagneticCopper

A-BUS-NX-AG-5-S

EC

A-BUS-NLP-AG-6

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

A-CBL-NX-AG-5-

(2)

In

22.2892

MagneticCopper

A-BUS-NX-AG-5-

DISC

A-BUS-NX-AG-5-P

RI

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

A-CBL-NX-AG-5-

DISC-(1)

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-NX-AG-6-S

EC

A-BUS-NLD-AG-1-

DISC

3 205 350 PVC Pos:

Zero:

5.9703 7.7551

19.0956

A-CBL-NX-AG-6-

(1)

In

18.8113

MagneticCopper

A-BUS-P10-DISC-

A-BUS-P10-DISC-

1 15 2 PVC Pos:

Zero:

1.3151 0.3809

0.9375

A-CBL-P10-DISC-

1-(1)

In

4.1445

MagneticCopper

A-BUS-P10-DISC-

A-BUS-P10-MTR

1 15 2 PVC Pos:

Zero:

1.3151 0.3809

0.9375

A-CBL-P10-DISC-

2-(1)

In

4.1445

MagneticCopper

A-BUS-P11-DISC-

A-BUS-P11-DISC-

1 15 2 PVC Pos:

Zero:

1.3151 0.3809

0.9375

A-CBL-P11-DISC-

1-(1)

4.1445

A-BUS-P11-DISC-

A-BUS-P11-MTR

1 15 2 PVC Pos:

Zero:

1.3151 0.3809

0.9375

A-CBL-P11-DISC-

2-(1)

In

4.1445

MagneticCopper

A-BUS-P12-DISC-

A-BUS-P12-DISC-

1 15 2 PVC Pos:

Zero:

1.3151 0.3809

0.9375

A-CBL-P12-DISC-

1-(1)

In

4.1445

MagneticCopper

A-BUS-P12-DISC-

A-BUS-P12-MTR

1 15 2 PVC Pos:

Zero:

1.3151 0.3809

0.9375

A-CBL-P12-DISC-

2-(1)

In

4.1445

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-S1-DISC-1

A-BUS-S1-DISC-2

1 20 2 PVC Pos:

Zero:

1.7535 0.5078

1.2500

A-CBL-S1-DISC-1-

(1)

5.5260

A-BUS-S1-DISC-2

A-BUS-ELEV-S1

1 20 2 PVC Pos:

Zero:

1.7535 0.5078

1.2500

A-CBL-S1-DISC-2-

(1)

In

5.5260

MagneticCopper

A-BUS-S2-DISC-1

A-BUS-S2-DISC-2

1 20 2 PVC Pos:

Zero:

1.7535 0.5078

1.2500

A-CBL-S2-DISC-1-

(1)

In

5.5260

MagneticCopper

A-BUS-S2-DISC-2

A-BUS-ELEV-S2

1 20 2 PVC Pos:

Zero:

1.7535 0.5078

1.2500

A-CBL-S2-DISC-2-

(1)

In

5.5260

MagneticCopper

A-BUS-SDC-(1)

A-BUS-GHTA-AG-

8 95 600 PVC Pos:

Zero:

0.1325 0.2386

0.5876

A-CBL-SDC-(1) In

0.4170

A-BUS-SDED

A-BUS-ED

1 100 4000 Epoxy Pos:

Zero:

0.1432 0.0825

0.4384

A-CBL-SDED-(1) In

0.8507

BuswayCopper

A-BUS-SHATS-CB

-1-(L)

A-BUS-T-SLP-CB-

1-PRI

1 30 350 PVC Pos:

Zero:

0.4922 0.6393

1.5742

A-CBL-SHATS-CB

-1-(1)

In

1.5508

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-SHD-AG-1

A-BUS-SHD-1-(1)

-TAP

1 3 4 PVC Pos:

Zero:

0.4180 0.0823

0.2026

A-CBL-SHD-AG-1-

(1)

In

1.3172

MagneticCopper

A-BUS-SHD-1-(1)

-TAP

A-BUS-SHL-A3-1

1 205 4 PVC Pos:

Zero:

28.5612 5.6233

13.8446

A-CBL-SHD-AG-1-

(1)-TAP-(1)

90.0078

A-BUS-SHD-1-(1)

-TAP

A-BUS-SHL-A4-1

1 220 8 PVC Pos:

Zero:

77.4392 7.1997

17.7222

A-CBL-SHD-AG-1-

(1)-TAP-(2)

In

244.0530

MagneticCopper

A-BUS-SHD-AG-1

A-BUS-SX-A2-1-D

ISC

1 85 10 PVC Pos:

Zero:

43.5330 3.1506

7.7585

A-CBL-SHD-AG-1-

(2)

In

137.1953

MagneticCopper

A-BUS-SHD-AG-1

A-BUS-SHL-A5-1

1 255 6 PVC Pos:

Zero:

56.4453 7.5814

18.6712

A-CBL-SHD-AG-1-

(3)

In

177.8802

MagneticCopper

A-BUS-SHD-AG-1

A-BUS-SHD-AG-1-

(4)-TAP

1 160 2 PVC Pos:

Zero:

14.0278 4.0625

10.0000

A-CBL-SHD-AG-1-

(4)

44.2083

A-BUS-SHD-AG-1

A-BUS-AX-AG-1-P

RI

1 70 6 PVC Pos:

Zero:

15.4948 2.0812

5.1254

A-CBL-SHD-AG-1-

(5)

In

48.8299

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-SHD-AG-1

A-BUS-SHL-AG-1

1 5 6 PVC Pos:

Zero:

1.1068 0.1487

0.3661

A-CBL-SHD-AG-1-

(7)

In

3.4878

MagneticCopper

A-BUS-SHD-AG-1-

(4)-TAP

A-BUS-SHL-A1-1

1 6 8 PVC Pos:

Zero:

2.1120 0.1964

0.4833

A-CBL-SHL-A1-1 In

6.6560

MagneticCopper

A-BUS-SHD-AG-1-

(4)-TAP

A-BUS-SHL-A2-1

1 15 2 PVC Pos:

Zero:

1.3151 0.3809

0.9375

A-CBL-SHL-A1-2 In

4.1445

A-BUS-SHL-A5-1

A-BUS-SX-A5-1-P

RI

1 6 10 PVC Pos:

Zero:

3.0729 0.2224

0.5477

A-CBL-SHL-A5-1-

(1)

In

9.6844

MagneticCopper

A-BUS-SHL-AG-1

A-BUS-SX-AG-2-P

RI

1 5 10 PVC Pos:

Zero:

2.5608 0.1853

0.4564

A-CBL-SHL-AG-1-

(1)

In

8.0703

MagneticCopper

A-BUS-SX-A5-1-S

EC

A-BUS-SLP-A5-1

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

A-CBL-SLP-A5-1-

(1)

In

22.2892

MagneticCopper

A-BUS-SLP-AG-1

A-BUS-SLP-AG-1-

1 5 1/0 PVC Pos:

Zero:

1.4793 0.6241

1.5359

A-CBL-SLP-AG-1-

(1)

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-SLP-CB-1

GEN-BUS-GEN-C-

1 300 2/0 PVC Pos:

Zero:

70.7286 36.9591

90.9763

A-CBL-SLP-CB-1-

(1)

In

222.8643

MagneticCopper

A-BUS-SLP-CB-1

GEN-BUS-GEN-C-

1 300 2/0 PVC Pos:

Zero:

70.7286 36.9591

90.9763

A-CBL-SLP-CB-1-

(2)

In

222.8643

MagneticCopper

A-BUS-SWBD-C

A-BUS-NHMCC-A

B-1

2 25 500 PVC Pos:

Zero:

0.1595 0.2528

0.6223

A-CBL-SWBD-C-

(1)

In

0.5024

MagneticCopper

A-BUS-SWBD-C

A-BUS-NX-AG-6-P

RI

2 35 4/0 PVC Pos:

Zero:

0.4861 0.3775

0.9297

A-CBL-SWBD-C-

(10)

1.5320

A-BUS-SWBD-C

A-BUS-NHP-A1-1

2 130 350 PVC Pos:

Zero:

1.0664 1.3852

3.4108

A-CBL-SWBD-C-

(11)

In

3.3600

MagneticCopper

A-BUS-SWBD-C

A-BUS-NHP-A1-2

2 130 350 PVC Pos:

Zero:

1.0664 1.3852

3.4108

A-CBL-SWBD-C-

(12)

In

3.3600

MagneticCopper

A-BUS-SWBD-C

A-BUS-NHLP-AB-

1 25 500 PVC Pos:

Zero:

0.3190 0.5056

1.2446

A-CBL-SWBD-C-

(2)

In

1.0048

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-SWBD-C

A-BUS-NHD-AG-1

2 30 250 PVC Pos:

Zero:

0.3594 0.3223

0.7936

A-CBL-SWBD-C-

(4)

1.1322

A-BUS-NHD-AG-2

2 30 250 PVC Pos:

Zero:

0.3594 0.3223

0.7936

A-CBL-SWBD-C-

(5)

In

1.1322

MagneticCopper

A-BUS-SWBD-C

A-BUS-NHD-AG-5

2 155 500 PVC Pos:

Zero:

0.9889 1.5675

3.8582

A-CBL-SWBD-C-

(6)

In

3.1148

MagneticCopper

A-BUS-SWBD-C

A-BUS-NHD-AG-3

1 10 500 PVC Pos:

Zero:

0.1276 0.2023

0.4978

A-CBL-SWBD-C-

(7)

In

0.4019

MagneticCopper

A-BUS-SWBD-C

A-BUS-NHD-AG-4

2 10 3/0 PVC Pos:

Zero:

0.1747 0.1126

0.2773

A-CBL-SWBD-C-

(8)

0.5506

A-BUS-NHD-A1-1

2 125 500 PVC Pos:

Zero:

0.7975 1.2641

3.1114

A-CBL-SWBD-C-

(9)

In

2.5119

MagneticCopper

A-BUS-SX-A2-1-S

EC

A-BUS-SLP-A2-1

1 8 8 PVC Pos:

Zero:

14.9963 1.3942

3.4320

A-CBL-SX-A2-1-

(1)

In

47.2615

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-SX-A2-1-D

ISC

A-BUS-SX-A2-1-P

RI

1 4 10 PVC Pos:

Zero:

2.0486 0.1483

0.3651

A-CBL-SX-A2-1-D

ISC

In

6.4563

MagneticCopper

A-BUS-SX-AG-1-S

EC

A-BUS-SLP-AG-1

1 10 1/0 PVC Pos:

Zero:

2.9586 1.2482

3.0718

A-CBL-SX-AG-1-

(1)

9.3242

A-BUS-SX-AG-2-S

EC

A-BUS-SLP-AG-2

1 5 8 PVC Pos:

Zero:

9.3727 0.8714

2.1450

A-CBL-SX-AG-2-

(1)

In

29.5384

MagneticCopper

A-BUS-T1A5A-SE

C

A-BUS-NLP-A1-6

1 6 3/0 PVC Pos:

Zero:

1.1164 0.7198

1.7724

A-CBL-T1A5A-(1) In

3.5184

MagneticCopper

A-BUS-T-SLP-CB-

1-SEC

A-BUS-SLP-CB-1

1 5 350 PVC Pos:

Zero:

0.4369 0.5674

1.3972

A-CBL-T-SLP-CB-

1-(1)

In

1.3764

MagneticCopper

A-BUS-UPS-COM

PR-OUT

A-BUS-XF-EX-A3-

2-PRI

1 20 1/0 PVC Pos:

Zero:

1.1111 0.4688

1.1536

A-CBL-UPS-COM

PR-(1)

3.5017

A-BUS-UPS-NEUR

O-SEC

A-BUS-UPS-NEUR

O

1 6 10 PVC Pos:

Zero:

16.3646 1.1844

2.9165

A-CBL-UPS-NEUR

O-(1)

In

51.5736

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

A-BUS-UTIL-1-RI

NG-(1)

A-BUS-SDC-(1)

1 25 4000 Epoxy Pos:

Zero:

0.0358 0.0206

0.1096

A-CBL-UTIL-1-RI

NG-(1)-2

In

0.2127

BuswayCopper

B-BUS-ATS-1-(L)

B-BUS-SHL-BG-1

1 12 1/0 PVC Pos:

Zero:

0.6667 0.2813

0.6922

B-CBL-ATS-1-(1) In

2.1010

MagneticCopper

B-BUS-ATS-3-(L)

B-BUS-EHD-CG-3

1 25 1/0 PVC Pos:

Zero:

1.3889 0.5859

1.4421

B-CBL-ATS-3-(1) In

4.3772

B-BUS-ATS-5-(L)

B-BUS-EHD-BG-1

2 8 500 PVC Pos:

Zero:

0.0510 0.0809

0.1991

B-CBL-ATS-5-(1) In

0.1608

MagneticCopper

B-BUS-ATS-6-(L)

B-BUS-CHD-BG-1

1 8 500 PVC Pos:

Zero:

0.1021 0.1618

0.3983

B-CBL-ATS-6-(1) In

0.3215

MagneticCopper

B-BUS-CHD-BG-1

B-BUS-CHL-B2-2

1 100 2 PVC Pos:

Zero:

8.7674 2.5391

6.2500

B-CBL-CHD-BG-1

-(1)

In

27.6302

MagneticCopper

B-BUS-CHD-BG-1

B-BUS-CHL-B2-1

1 190 1 PVC Pos:

Zero:

13.1944 4.7005

11.5699

B-CBL-CHD-BG-1

-(2)

41.5790

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

B-BUS-CHD-BG-1

B-BUS-SX-B3-2-D

ISC

1 100 10 PVC Pos:

Zero:

51.2153 3.7066

9.1276

B-CBL-CHD-BG-1

-(3)

In

161.4063

MagneticCopper

B-BUS-CHD-BG-1

C-BUS-CHL-C1-3

1 230 2/0 PVC Pos:

Zero:

10.1823 5.3207

13.0972

B-CBL-CHD-BG-1

-(4)

In

32.0842

MagneticCopper

B-BUS-CHD-BG-1

B-BUS-XC-1B-2-P

RI

1 125 4 PVC Pos:

Zero:

17.4154 3.4288

8.4418

B-CBL-CHD-BG-1

-(5)

In

54.8828

MagneticCopper

B-BUS-CHD-BG-1

B-BUS-CX-BG-2-P

RI

1 125 8 PVC Pos:

Zero:

43.9996 4.0907

10.0694

B-CBL-CHD-BG-1

-(6)

138.6665

B-BUS-CHD-BG-1

B-BUS-CX-BG-1-P

RI

1 20 4 PVC Pos:

Zero:

2.7865 0.5486

1.3507

B-CBL-CHD-BG-1

-(7)

In

8.7813

MagneticCopper

B-BUS-CHL-B2-1

B-BUS-CX-B2-1-P

RI

1 8 2 PVC Pos:

Zero:

0.7014 0.2031

0.5000

B-CBL-CHL-B2-1-

(1)

In

2.2104

MagneticCopper

B-BUS-CHL-B2-2

B-BUS-CX-B2-2-P

RI

1 50 2 PVC Pos:

Zero:

4.3837 1.2695

3.1250

B-CBL-CHL-B2-2-

(1)

In

13.8151

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

B-BUS-CHL-B2-2

B-BUS-CX-B2-4-P

RI

1 100 10 PVC Pos:

Zero:

51.2153 3.7066

9.1276

B-CBL-CHL-B2-2-

(2)

161.4063

B-BUS-CHL-B2-2

B-BUS-CX-B2-3-P

RI

1 5 6 PVC Pos:

Zero:

1.1068 0.1487

0.3661

B-CBL-CHL-B2-2-

(3)

In

3.4878

MagneticCopper

C-BUS-CHL-C1-3

C-BUS-CX-C1-3-P

RI

1 6 4 PVC Pos:

Zero:

0.8359 0.1646

0.4052

B-CBL-CHL-C1-3-

(1)

In

2.6344

MagneticCopper

B-BUS-CLP-B2-1

B-BUS-CLP-B2-1-

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

B-CBL-CLP-B2-1-

(1)

In

8.8286

MagneticCopper

B-BUS-CLP-B2-2

B-BUS-CLP-B2-2-

1 20 3/0 PVC Pos:

Zero:

3.7213 2.3992

5.9079

B-CBL-CLP-B2-2-

(1)

11.7280

B-BUS-CLP-B2-2

B-BUS-CLP-B2-2-

1 20 6 PVC Pos:

Zero:

23.5762 3.1666

7.7986

B-CBL-CLP-B2-2-

(2)

In

74.2973

MagneticCopper

B-BUS-CLP-BG-1

B-BUS-CLP-BG-1-

1 5 3/0 PVC Pos:

Zero:

0.9303 0.5998

1.4770

B-CBL-CLP-BG-1-

(1)

In

2.9320

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

B-BUS-CLP-BG-1

C-BUS-CLP-C1-2

1 5 3 PVC Pos:

Zero:

2.9239 0.6992

1.7208

B-CBL-CLP-BG-1-

(2)

In

9.2144

MagneticCopper

B-BUS-CLP-BG-1-

B-BUS-CLP-BG-2

1 135 2 PVC Pos:

Zero:

63.0316 18.2542

44.9334

B-CBL-CLP-BG-1-

2-(2)

198.6432

C-BUS-CLP-C1-3

C-BUS-CLP-C1-4

1 8 3 PVC Pos:

Zero:

4.6783 1.1187

2.7533

B-CBL-CLP-C1-3-

(1)

In

14.7430

MagneticCopper

B-BUS-CX…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .