This is a DAPPER Fault Contribution Complete Report for the Atlanta-Remote-Sites project, presenting a comprehensive short circuit study analysis with final generator configuration data.

The report documents initial symmetrical and asymmetrical fault current calculations across multiple bus locations and cable connections within the electrical system. The study evaluated three-phase faults and single line-to-ground (SLG) faults at 0.50 cycles, incorporating motor contributions, transformer tap settings, and transformer phase shift parameters. Key fault current data is presented in amperes across various bus nodes, including 125-BUS-CP, 125-BUS-GEN, 125-BUS-SBDPCH, 128-BUS-EML, 129-BUS-SB1, 129-BUS-SB2, 130-BUS-OAH-1, 130-BUS-SB1, 130-BUS-SB2, 131-BUS-KP, and numerous subsidiary buses designated for power distribution branches (SB1, SB2, SBM, SBDP configurations) and transmission distribution (TD-BUS) locations including remote sites identified as HE, HN, HP, HW, LE, LN, and LP. The asymmetrical fault current data includes DC offset and decay calculations. Initial symmetrical SLG faults ranged from 286 amps at 131-CBL-SBDP2-1 to 10,229 amps at 131-BUS-SBDP2, while asymmetrical SLG values ranged from 286 amps to 11,525 amps at the same locations. The report includes neutral amperage contributions for SLG and line-to-line-to-ground (LLG) fault scenarios, with no contributions recorded for line-to-line faults across the analyzed system.

View the file

Other files

File Type Posted
Final - AF Label List.xlsx XLSX spreadsheet
final remote - gen device eval.pdf PDF
Attachment B - Fort McPherson Equipment Schedule - REV19.1.xlsx XLSX spreadsheet
Drawing List.pdf PDF
GHTA-AG-1.pdf PDF
final main site - util input report.pdf PDF
NHSB-BG-1.pdf PDF
20200603 - Final Combined pdfs.pdf PDF
final main site - util device eval.pdf PDF
final main site - util bus eval.pdf PDF
Existing-Recommended Breaker Settings - Final.xlsx XLSX spreadsheet
GHSB-C3-1.pdf PDF
NHSB-CB-1.pdf PDF
final main site - gen bus eval.pdf PDF
Equipment Condition Assessment Sheets.xlsx XLSX spreadsheet
GHTA-CB-1.pdf PDF
final remote - gen input report.pdf PDF
final remote - util results report.pdf PDF
Questions and Answers.docx DOCX document
Attachment C - Trinka-Davis Equipment Schedule - REV19.1.xlsx XLSX spreadsheet
Switchboard C.pdf PDF
Attachment D - Equipment and Test Matrix - REV19.1.docx DOCX document
Electrical Distribution Testing SOW final.docx DOCX document
final remote - util bus eval.pdf PDF
7.6 Facility Condition Assessment - Final Submission.xlsx XLSX spreadsheet
NHSB-C3-2.pdf PDF
final main site - gen device eval.pdf PDF
GHSB-AG-1.pdf PDF
Electrical Directive 1028 D 2020-02-24.pdf PDF
GHTA-CB-2.pdf PDF
final remote - util device eval.pdf PDF
ArcFlash - Atlanta Main Site Final.xls XLS spreadsheet
Attachment A - Main Campus Equipment Schedule - REV19.1.xlsx XLSX spreadsheet
ArcFlash - Atlanta Remote Sites Final.xls XLS spreadsheet
final remote - gen bus eval.pdf PDF
NSHB-CB-2.pdf PDF
NHSB-C3-1 Fast Transfer.pdf PDF
36C24727Q0044 0002.pdf PDF
7.7 Building System Assessment_Atlanta.xlsx XLSX spreadsheet
NHSB-C3-1.pdf PDF
Wage Determination 2015-4471.docx DOCX document
final main site - gen input report.pdf PDF
Switchgear ED.pdf PDF
final main site - gen results report.pdf PDF
final remote - util input report.pdf PDF
Atlanta VA Main Campus 2022 IR Report.pdf PDF
final main site - util results report.pdf PDF
36C24727Q0044 0001.pdf PDF
36C24727Q0044_1 36-Month Electrical Distribution Testing.docx DOCX document
Attachment D - Equipment and Test Matrix - REV19.docx DOCX document
Show 40 more

Latest 50 of 53 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DAPPER Fault Contribution Complete Report

Comprehensive Short Circuit Study Settings

Three Phase Fault

Single Line to Ground

Line to Line Fault

Line to Line to Ground

All BusesFaulted Bus

Yes

Yes

Yes

No

No

Motor Contribution

Transformer Tap

Xformer Phase Shift

Yes

Yes

Bus Voltages

Branch Currents

Phase or Sequence

Fault Current Calculation

Asym Fault Current at Time 0.50

First Bus From Fault

First Branch From Fault

Report phase quantities

Asymmetrical RMS (with DC offset and Decay)

Cycles

Project: Atlanta-Remote-Sites

Final - Generator

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

125-BUS-CP 2 0 0 0 3 0 0 0

InCABLE125-CBL-UPS-2 3 0 0 0 2 0 0 0

125-BUS-GEN 396 0 0 394 606 0 0 592

InCABLE125-CBL-GEN 606 0 0 592 396 0 0 394 394

125-BUS-SBDPCH 976 0 0 964 1,456 0 0 1,390

InCABLE125-CBL-UPS-1 0 0 0 0 0 0 0 0

InCABLE125-CBL-DP1-2 1,456 0 0 1,390 976 0 0 964 964

128-BUS-EML 1,735 0 0 1,065 1,736 0 0 1,065

InCABLE128-CBL-ATS-SB1-L-1 1,736 0 0 1,065 1,735 0 0 1,065 1,065

129-BUS-SB1 1,730 0 0 1,050 1,730 0 0 1,050

InCABLE129-CBL-ATS-SB1-L-1 1,730 0 0 1,050 1,730 0 0 1,050 1,050

129-BUS-SB2 5,050 0 0 3,427 5,115 0 0 3,441

InCABLE129-CBL-SB2-1 0 0 0 0 0 0 0 0

InCABLE129-CBL-ATS-SB2-L-1 5,115 0 0 3,441 5,050 0 0 3,427 3,427

Bus Name

-------------Initial Symmetrical Amps-----------

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

129-BUS-SB22 5,005 0 0 3,393 5,068 0 0 3,407

InCABLE129-CBL-SB2-1 5,068 0 0 3,407 5,005 0 0 3,393 3,393

130-BUS-OAH-1 4,501 0 0 2,844 4,502 0 0 2,844

InCABLE130-CBL-SB2-1 4,502 0 0 2,844 4,501 0 0 2,844 2,844

130-BUS-SB1 2,687 0 0 1,679 2,687 0 0 1,679

InCABLE130-CBL-ATS-SB1-L-1 2,687 0 0 1,679 2,687 0 0 1,679 1,679

130-BUS-SB2 7,881 0 0 5,840 8,621 0 0 6,117

InCABLE130-CBL-SB2-1 0 0 0 0 0 0 0 0

InCABLE130-CBL-ATS-SB2-L-2 0 0 0 0 0 0 0 0

InCABLE130-CBL-ATS-SB2-L-1 8,621 0 0 6,117 7,881 0 0 5,840 5,840

130-BUS-SB22 7,717 0 0 5,699 8,420 0 0 5,961

InCABLE130-CBL-ATS-SB2-L-2 8,420 0 0 5,961 7,717 0 0 5,699 5,699

131-BUS-KP 9,197 0 0 6,897 9,833 0 0 7,095

InCABLE131-CBL-SB2-3 9,833 0 0 7,095 9,197 0 0 6,897 6,897

131-BUS-SB1 5,175 0 0 3,640 5,394 0 0 3,709

InCABLE131-CBL-SB1-1 0 0 0 0 0 0 0 0

InCABLE131-CBL-SB1-2 0 0 0 0 0 0 0 0

InCABLE131-CBL-SB1-L-1 5,394 0 0 3,709 5,175 0 0 3,640 3,640

131-BUS-SB1A 2,180 0 0 1,326 2,180 0 0 1,326

InCABLE131-CBL-SB1-1 2,180 0 0 1,326 2,180 0 0 1,326 1,326

131-BUS-SB1B 1,925 0 0 1,163 1,925 0 0 1,163

InCABLE131-CBL-SB1-2 1,925 0 0 1,163 1,925 0 0 1,163 1,163

131-BUS-SB2 12,210 0 0 9,919 14,667 0 0 11,095

InCABLE131-CBL-SB2-1 0 0 0 0 0 0 0 0

InCABLE131-CBL-SB2-3 0 0 0 0 0 0 0 0

InCABLE131-CBL-SB2-2 0 0 0 0 0 0 0 0

InCABLE131-CBL-SB2-4 0 0 0 0 0 0 0 0

InCABLE131-CBL-SB2-L-1 14,667 0 0 11,095 12,210 0 0 9,919 9,919

131-BUS-SB2A 7,131 0 0 4,877 7,174 0 0 4,882

InCABLE131-CBL-SB2-1 7,174 0 0 4,882 7,131 0 0 4,877 4,877

131-BUS-SB2B 6,420 0 0 4,305 6,442 0 0 4,307

InCABLE131-CBL-SB2-2 6,442 0 0 4,307 6,420 0 0 4,305 4,305

131-BUS-SBDP1 5,434 0 0 3,862 5,736 0 0 3,965

InCABLE131-CBL-SBP1-1 0 0 0 0 0 0 0 0

InCABLE131-CBL-SBP1-2 0 0 0 0 0 0 0 0

InCABLE131-CBL-SBP1-3 0 0 0 0 0 0 0 0

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

InCABLE131-CBL-SBP1-4 0 0 0 0 0 0 0 0

InCABLE131-CBL-GEN-1-2 5,736 0 0 3,965 5,434 0 0 3,862 3,862

131-BUS-SBDP2 12,508 0 0 10,229 15,156 0 0 11,525

InCABLE131-CBL-SBDP2-2 0 0 0 0 0 0 0 0

InCABLE131-CBL-SBDP2-6 0 0 0 0 0 0 0 0

InCABLE131-CBL-SBDP2-3 0 0 0 0 0 0 0 0

InCABLE131-CBL-SBDP2-5 0 0 0 0 0 0 0 0

InCABLE131-CBL-SBDP2-1 636 0 0 322 525 0 0 286

InCABLE131-CBL-GEN-1-1 14,520 0 0 11,203 11,984 0 0 9,943 10,229

131-BUS-SBM 12,114 0 0 9,820 14,512 0 0 10,960

InCABLE131-CBL-SBM-1 0 0 0 0 0 0 0 0

InCABLE131-CBL-SB2-4 14,512 0 0 10,960 12,114 0 0 9,820 9,820

131-BUS-SBMA 11,429 0 0 9,024 12,781 0 0 9,525

InCABLE131-CBL-SBM-1 12,781 0 0 9,525 11,429 0 0 9,024 9,024

TD-BUS-HE 1,254 0 0 1,228 1,819 0 0 1,696

InCABLETD-CBL-HE-1 0 0 0 0 0 0 0 0

InCABLETD-CBL-ATS1-L-1 1,819 0 0 1,696 1,254 0 0 1,228 1,228

TD-BUS-HN1 1,134 0 0 1,052 1,431 0 0 1,215

InCABLETD-CBL-HN1-1 0 0 0 0 0 0 0 0

InCABLETD-CBL-ATS2-L-1 1,431 0 0 1,215 1,134 0 0 1,052 1,052

TD-BUS-HN2 1,193 0 0 1,136 1,599 0 0 1,407

InCABLETD-CBL-HN2-1 0 0 0 0 0 0 0 0

InCABLETD-CBL-ATS3-L-1 1,599 0 0 1,407 1,193 0 0 1,136 1,136

TD-BUS-HP 1,299 0 0 1,296 2,016 0 0 1,996

InCABLETD-CBL-HP-1 0 0 0 0 0 0 0 0

InCABLETD-CBL-HP-2 0 0 0 0 0 0 0 0

InCABLETD-CBL-ATS4-L-1 2,016 0 0 1,996 1,299 0 0 1,296 1,296

TD-BUS-HW 1,296 0 0 1,292 2,004 0 0 1,976

InCABLETD-CBL-HW-1 0 0 0 0 0 0 0 0

InCABLETD-CBL-HP-2 2,004 0 0 1,976 1,296 0 0 1,292 1,292

TD-BUS-LE1 1,542 0 0 1,868 1,927 0 0 2,267

InCABLETD-CBL-LE1-1 0 0 0 0 0 0 0 0

InCABLETD-CBL-TLE-1 1,927 0 0 2,267 1,542 0 0 1,868 1,868

TD-BUS-LE2 1,539 0 0 1,859 1,917 0 0 2,247

InCABLETD-CBL-LE2-1 0 0 0 0 0 0 0 0

InCABLETD-CBL-LE1-1 1,917 0 0 2,247 1,539 0 0 1,859 1,859

3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG

----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---

---------Contributions---------

TD-BUS-LE3 1,535 0 0 1,851 1,908 0 0 2,228

InCABLETD-CBL-LE2-1 1,908 0 0 2,228 1,535 0 0 1,851 1,851

TD-BUS-LN11 1,454 0 0 1,779 1,726 0 0 2,081

InCABLETD-CBL-LN11-1 0 0 0 0 0 0 0 0

InCABLETD-CBL-TLN1-1 1,726 0 0 2,081 1,454 0 0 1,779 1,779

TD-BUS-LN12 1,451 0 0 1,772 1,719 0 0 2,065

InCABLETD-CBL-LN12-1 0 0 0 0 0 0 0 0

InCABLETD-CBL-LN11-1 1,719 0 0 2,065 1,451 0 0 1,772 1,772

TD-BUS-LN13 1,448 0 0 1,764 1,712 0 0 2,049

InCABLETD-CBL-LN12-1 1,712 0 0 2,049 1,448 0 0 1,764 1,764

TD-BUS-LN21 1,497 0 0 1,823 1,819 0 0 2,169

InCABLETD-CBL-LN21-1 0 0 0 0 0 0 0 0

InCABLETD-CBL-TLN2-1 1,819 0 0 2,169 1,497 0 0 1,823 1,823

TD-BUS-LN22 1,494 0 0 1,815 1,811 0 0 2,151

InCABLETD-CBL-LN22-1 0 0 0 0 0 0 0 0

InCABLETD-CBL-LN21-1 1,811 0 0 2,151 1,494 0 0 1,815 1,815

TD-BUS-LN23 1,490 0 0 1,807 1,804 0 0 2,133

InCABLETD-CBL-LN22-1 1,804 0 0 2,133 1,490 0 0 1,807 1,807

TD-BUS-LP 1,163 0 0 1,329 1,398 0 0 1,551

InCABLETD-CBL-TLP-1 1,398 0 0 1,551 1,163 0 0 1,329 1,329

TD-BUS-P1 1,573 0 0 1,898 2,006 0 0 2,338

InCABLETD-CBL-P1-1 0 0 0 0 0 0 0 0

InCABLETD-CBL-TP1-1 2,006 0 0 2,338 1,573 0 0 1,898 1,898

TD-BUS-P2 1,569 0 0 1,890 1,996 0 0 2,317

InCABLETD-CBL-P2-1 0 0 0 0 0 0 0 0

InCABLETD-CBL-P1-1 1,996 0 0 2,317 1,569 0 0 1,890 1,890

TD-BUS-P3 1,565 0 0 1,881 1,986 0 0 2,295

InCABLETD-CBL-P2-1 1,986 0 0 2,295 1,565 0 0 1,881 1,881