16200 Electrical.pdf

PDF 139 KB Posted

Attached to
Renovate 20 Apartments in Parkridge - Phase 2
Solicitation number
US.245854
Issued by
Northampton County, Pennsylvania

About this file

This is an electrical specification document for the Bethlehem Housing Authority's apartment renovation project at the Parkridge family development in Pennsylvania. The project involves renovating 20 apartments and requires electrical work as detailed in the specifications. Bids are due electronically through the PennBid site by Thursday, October 22, 2026 at 11:00 AM, at which time bids will be electronically opened. A bid bond equal to 10% of the bid amount, secured by a surety company listed in the Department of Treasury Circular #570, must accompany each bid submission. The successful bidder will be required to furnish and pay for satisfactory Performance and Payment Bonds. Contract documents, including specifications and drawings, are available on the PennBid website. Prospective bidders with questions should contact Scott Speshok at 610-483-0322, and additional information is available at www.Bethlehemhousing.org. The Bethlehem Housing Authority reserves the right to reject any or all bids or waive any informalities or irregularities in the bidding process.

The electrical specifications provide detailed requirements for the work scope, materials, and installation standards required for the renovation project. Pricing terms and payment structures are to be determined through the competitive bid process. No specific set-asides, incumbent information, or contract renewal options are identified in the available documentation. Funding sources and amounts are not specified in the file provided.

View the file

Other files

File Type Posted
02900 Landscaping.pdf PDF
2-Parkridge PH 2 wage rates.pdf PDF
09670 Vinyl Composition Tile.pdf PDF
01010 General Work Requirements.pdf PDF
7-Parkridge PH 2 Addendum.pdf PDF
9-Bid table for Parkridge Phase 2.pdf PDF
06100 Rough Carpentry.pdf PDF
02210 Selective Demolition.pdf PDF
5-Parkridge PH2 IFB.pdf PDF
1-Parkridge documents to be submitted.pdf PDF
06650 Solid Polymer Fabrication.pdf PDF
15400 Plumbing.pdf PDF
05500 Metal Fabrications.pdf PDF
06240 Plastic Laminate.pdf PDF
08110 Storm Doors.pdf PDF
08200 Flush Wood Doors and Frames.pdf PDF
07920 Sealants and Caulking.pdf PDF
01700 Project Close-out.pdf PDF
10300 Vinyl Coated Shelves.pdf PDF
3-Parkridge Ren. PH 2 Admin. Specs.pdf PDF
01545 Contractor Use of Premesis.pdf PDF
01500 Construction Facilities.pdf PDF
08100 Metal Doors and Frames.pdf PDF
6-Parkridge PH 2 Ren. Drawings.pdf PDF
09260 Gypsum Wallboard.pdf PDF
09650 Resilient Sheet Flooring.pdf PDF
8-Parkridge PH 2 Addendum 2.pdf PDF
09900 Painting.pdf PDF
0 Table of Contents.pdf PDF
01710 Cleaning.pdf PDF
01620 Storage and Protection.pdf PDF
12390 Kitchen Cabinetry.pdf PDF
06200 Finish Carpentry.pdf PDF
16000 Basic Electrical Requirements.pdf PDF
08541 Vinyl Windows.pdf PDF
10260 Fiberglass Wall Panels.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION 16200

ELECTRICAL

SUMMARY:

Work of this Section includes, but may not be limited to, all electrical work necessary to properly complete the work as indicated on the Drawings and in these specifications.

1. Removal and replacement of all existing switches, outlets and light fixtures.

2. Provide new branch circuits and light fixtures in the living room and bedrooms so the light switches operate the new fixtures. Currently the switches control switched outlets. See Electrical drawings.

3. Installation of new coax cable and CAT5 cable as shown on the Electrical drawings.

Documents affecting work of this Section include, cut are not necessarily limited to, General Conditions, Supplementary Conditions, Drawings, and these specifications.

QUALITY ASSURANCE:

For actual fabrication, installation and testing of the work of this Section, use only thoroughly trained and experienced workmen completely familiar with the items required and with the manufacturer’s recommended methods of installation. In acceptance or rejection of installed work, no allowance will be made for lack of skill on the part of the workmen.

In addition to complying with all pertinent codes and regulations also comply with:

1. National Electrical Code, latest edition.

2. Local utility company regulations.

3. All Local, State and Federal Agencies having jurisdiction.

16200-1

SUBMITTALS:

Comply with pertinent provisions of the General Requirements.

Submit the following information and product data within 15 days of award of contract to the Contractor.

1. Complete materials list of all items proposed to be furnished and installed under this Section.

2. Manufacturer’s Specifications and catalog cuts as required to demonstrate compliance with specified requirements.

3. Manufacturer’s recommended installation procedures which, when approved by the Owner, will become one of the means for inspecting and accepting or rejecting mutual installation procedures used on the work.

RECORD OF DRAWINGS:

During progress of work and as a condition of acceptance, compile a manual of all work completed. Upon completion of the project, deliver to the Owner, maintenance manuals and operating instructions for all equipment installed. Provide as-built drawings for any field changes authorized during the performance of work under this section.

PRODUCT HANDLING:

Protection: Use all means necessary to properly protect the materials of this Section before, during, and after installation and to protect the work and materials of other trades.

Replacement: In the event of damage, immediately make all repairs and replacements at no additional cost to the Owner and to the approval of the Owner.

UTILITY COSTS:

Any additional charges for installation of the new electrical service by the local utility company shall be the responsibility of the Contractor.

16200-2

Identification of components: Identify all components by means of a neatly stenciled label or etched micra labels.

Properly identify all circuits on inside of new panel box door.

Wiring devices: All duplex receptacles shall be 3-pole grounding type, with the third pole wired to the grounding system and shall be as follows:

20 amp – Bryant No. 5362-I or approved equal.

Cover plates shall be metal plates: color: ivory, or as approved by the owner in advance.

All tumbler switches shall be 15 amp, Type 120/277VAC, and shall be the following:

Single Pole: 3-way Bryant or approved equal 841-I 843-I

All ground fault receptacles shall be duplex type, 20 amp, 125 Volt AC, Bryant #GRF53, FTI or approved equal. Cover plate color: as approved by the Owner in advance.

RACEWAYS AND FITTINGS:

All outlets, junction boxes and switch boxes shall be galvanized, code-gauge metal or plastic boxes or as required by local codes.

Pull boxes shall be plastic, of sizes and shape to accommodate wires without crowding and to suit the location.

Provide sleeves and chases where conduits pass through floors and walls.

CONDUCTORS:

Wire and cable shall be 600V insulated NEC standard TW, RHW or XHHW or as local codes otherwise require. Use 12 gauge wire.

Branch circuit conductors within 3” of a ballast within the ballast compartment shall have 90 degree C. (194 degrees F.) insulation or better.

16200-3

LIGHTING FIXTURES:

General: All lighting fixtures shall be complete with all required accessories, canopies, casing, sockets, holders, reflector and other items required for complete and proper installation and shall be complete wired and assembled.

Ballasts: Ballasts for all fluorescent light fixtures (if required), unless otherwise specified, shall be one of the high-power-factor class P type and their design and construction shall conform to CBM-ETL label. Ballasts shall be equipped with a dual protection system consisting of non-resetting protector in the power capacitor and a UL approved protector adjacent to the coil.

Lighting fixtures shall be installed as shown on the Drawings and be of the type and quality listed on the Electrical Fixture Schedule or Owner approved equal.

EXECUTION:

Examine the areas and conditions under which work of this Section will be installed.

Correct detrimental conditions to ensure the proper and timely completion of the work involved. Do not proceed with work until all unsatisfactory conditions have been corrected.

All electrical work installed underground within the contract limits on site and inside all buildings shall be inspected and approved in writing, prior to cover-up, and at its final completion by an “I.A.E.I.” certified electric inspector. Inspectors must provide proof of certification.

All costs for the service provided by the electrical inspector shall be the responsibility of the General Contractor.

Coordinate installation of all electrical work with all other ongoing or proposed work for this contract.

Where lighting fixtures, and/or other electrical system components or equipment, are shown in conflict with locations of structural members and mechanical or other equipment, provide all required supports and wiring to clear the encroachment.

16200-4

The data indicated on the drawings are for diagrammatic purposed only, the absolute accuracy is not guaranteed. Exact locations, distances, levels and other conditions will be governed by the building and Owner direction. Use the drawings and these specifications for guidance and secure the Owner’s approval of all changes in location.

Field verify all measurements, locations, and/or elevations at the site. No extra compensation will be made to the contractor because of the differences between locations shown on the drawings and measurements at the building.

Run branch circuits and/or home runs for maximum economy consistent with the sizes for voltage drop and other considerations.

Install conduit, if required, for all wiring and where indicated on the drawings. Keep conduit at least 6’ away from the covering on hot water pipes.

Keep ends of conduit closed with approved conduit seals during the construction of the building. Use conduit unions where union joints are required. Do not use running threads.

Where conduit is installed in concrete slabs, on the ground, underground, or exposed to the weather, make all joints liquid tight and gas tight. Bury all underground conduit to a depth of 2’ – 0” below finish grade unless otherwise shown on the drawings.

Provide all final connections to power equipment, kitchen equipment, motors, HVAC equipment, light fixtures, switches, equipment control wiring, and/or all other equipment involved with this contract or being provided by others.

Unless otherwise indicated on the drawings, all wires for branch circuits shall be number 12, TW, protected by 20 amp circuit breakers. Install larger wires, as indicated on the drawings, or as necessary to limit voltage drop.

Where size of wire is not indicated on the drawing, install No. 12 wire unless individual circumstances require different size wiring and upon approval of the Electrical Inspector of the City of Bethlehem and the Owner.

16200-5

Where holes for wiring or conduit are bored into wood framing members, the edge of the hole shall be a minimum of 1 ¼” from the nearest edge of the framing member.

Where this is not possible, steel plates shall be installed to protect the wiring or conduit from penetration by nails or screws. Steel plates shall be a minimum of 1/16” thick and of adequate length and width to totally cover the wiring or conduit.

Use identified (white) neutrals and color-coded insulated phase wires for all branch circuit wiring.

Make all splices electrically and mechanically secure with pressure type connectors or soldering. Insulate and tape all splices in accordance with governing codes.

The drawings indicate the general direction of home runs. Continue all such home runs to the panel box as though the routes were completely indicated.

Install all lighting fixtures complete and ready for services, in accordance with the drawings and Owner direction.

Wire all fixtures with fixture wiring at least 150 degrees C-rating. Conductors in wiring channels of fixtures mounted in tows shall be the same size as circuit wiring supplying the rows.

Install all fluorescent fixtures straight, square, and true with reference to adjacent walls.

Install all lighting fixtures, including those mounted in continuous rows, so that the weight of the fixture is supported either directly or indirectly by a sound and safe structural member of the building, using adequate number and type of fasteners to ensure safe installation. Screwed fastenings and toggles through ceiling or wall material are not acceptable.

Provide all lamps as required for each lighting fixture installed.

Label panel directory with permanent ink on the inside of each panel door. On the director, show the circuit number and a complete description of all outlets on each circuit.

16200-6

TESTING:

Upon completion of work of this Section, test all parts of the electrical system in the presence of the Owner. Demonstrate that all equipment furnished, installed, and/or connected under this Section of these Specifications functions electrically and as required by the National Electrical Code.

All systems shall test free from short circuits and grounds, shall be free from mechanical and electric defects, and shall show an insulation resistance between phase conductors and ground of not less than that required by the National Electric Code.

Test all circuits for proper neutral connections.

END OF SECTION

16200-7