J012--575 Fire System Inspection & Repairs - one year only

Closed Solicitation Posted

Solicitation number
36C25926Q0519
Agency
Responses due
Set-aside
Total Small Business

Opportunity facts

Place of performance
Department of Veterans Affairs Grand Junction CO 81501

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19 seeks labor and equipment to repair fire suppression and alarm system deficiencies at VA Western Colorado Healthcare System in Grand Junction, Colorado, with proposals due June 29, 2026, at 12:00 PM Mountain Time. This is a Total Small Business set-aside. The one-year period of performance runs July 15, 2026, through July 14, 2027.

Place of performance is Grand Junction, Colorado. The scope spans three distinct work categories: kitchen hood fire system repairs at three locations (NFS, Canteen, and CLC) under CLIN 0001; battery replacement and fire alarm sensor-strobe upgrades at the parking garage and Buildings 5, 6, 33, and 37 under CLIN 0002; and correction of quarterly sprinkler system deficiencies across 13 buildings (1, 5, 6, 7, 8, 12, 13, 20, 22, 33, 34, 36, and 45) under CLIN 0003. The work is limited to correcting previously identified deficiencies documented in inspection reports and preparing repair documentation to support Joint Commission audit compliance. CLIN 0003 work includes five-year internal piping inspections with photographic evidence, removal of flushing connections and sprinklers at branch line ends, and OS&Y valve inspections in 2.5-inch, 3-inch, 6-inch, and 8-inch sizes. Buildings 6 and 36 contain antifreeze or glycol loops requiring specialized attention. The scope explicitly excludes dry systems, pre-action systems, deluge systems, backflow preventers, fire pumps, and pressure regulating valves.

This is a new requirement with no incumbent contractor. Current fire suppression monitoring is performed by Vulcan Fire, and backflow preventor services are provided by Citrine, LLC. The NAICS code is 561621, Security Systems Services (except Locksmiths), and the PSC code is J012, Maint/Repair/Rebuild of Equipment—Fire Control Equipment. Offers must be emailed to Contracting Officer Heather Chase at heather.chase2@va.gov. The price schedule contains three line items with quantity measured in job orders; offerors submit unit pricing per job order. Previous inspection reports and deficiency documentation are attached.

Notice text

2 versions

Update #2 · Latest ·

Q&A

Solicitation # 36C25926Q0519

The purpose of this amendment is to:

Provide answers to questions received under solicitation 36C25926Q0519.

To provide the Joint Commission review tool and clarification document to add awareness for prospective contractors regarding the standards for completing repairs and inspections (see attached).

All offers are to be emailed to heather.chase2@va.gov and received no later than 12:00pm (noon) MT on June 29, 2026.

Questions and Answers below are referencing RFQ 36C25926Q0519:

Q. Will the Government please provide the number of Wet Systems per building?

B1: 1

B5: 1

B6: 1

B7: 1

B8: 1

B12: 1

B13: 1

B20: 1

B22: 1

B33: 1

B34: 1

B36: 1

B45: 1

.

Q. What is the total number of Dry Systems per building?

A. Not in scope of the required repairs.

Q. What is the total number of Pre-Action Systems?

A. None, station is wet-piped.

Q. What is the total number of Deluge Systems?

A. Not in scope of required repairs.

Q. What is the total number of Backflow Preventers?.

A. Not in scope of required repairs.Â

Q. What is the total number of Fire Pumps?

A. Not in scope of required repairs.

Q. What is the total number of Control Valves?

A. Please see CLIN 3 (page 5 & 6) of Attachment 1 - SOW.

Q. What is the total number of Flow Switches?

A. Please see CLIN 3 (page 5 & 6) of Attachment 1 - SOW.

Q. What is the total number of Pressure Regulating Valves PRV?

A. Not in scope of required repairs.

Update #1 ·

The purpose of this amendment is to:

Provide questions, answers and reports provided under previous solicitation (36C25926Q0408).

All offers are to be emailed to heather.chase2@va.gov and received no later than 5:00pm MT on June 22, 2026.

Questions and Answers below were provided under previous RFQ 36C25926Q0408:

Q. Is this a new or follow-on requirement? If a follow-on, who is the incumbent and what isÂ

the contract number?

A. This is a new one-year only requirement. This requirement has not previously been awarded and therefore there is no incumbent.

Q. Is the intent of the contract to perform annual testing, identify, and correct deficiencies?

A. No, the intent is to correct the deficiencies that have previously been identified and to document the repairs for the Joint Commission audit.

Q. Who is currently performing the monitoring service for the VA WCHCS?

A. Vulcan Fire.

Q. Who is currently performing the backflow preventor service for VA WCHCS?

A. Citrine, LLC

Q. Can we be provided a copy of the reports? The in-person tags refer to this report.

A. Yes. See attached reports.Â

Q. Does the VA WCHCS have any antifreeze or glycol loops within their fire suppression system?

A. Yes, those are located in Building 6 and Building 36.

Q. Does the parking garage (Building 44) contain sprinkler systems?

A. No, but there are alarm systems.

Q. Building 34 has an open deficiency tag for network issues. Has this been resolved?

A. This deficiency correction is currently in progress.

Q. For the 5-year internal inspections, is it just the internal piping 5-year you are needing?

A. Yes, it is the internal piping to include the removal of a flushing connections and sprinkler near the end of a branch line. Will also require photographic evidence of the state of the pipe to fulfill the 5-year requirement.

Q. For the OS&Y valves, would you know what size the valves are?

A. OS&Y valves on station are 8inch, 3inch, 2.5inch and 6 inch.

Q. Do you know what size the inspectors test valves are?

A. There are currently no sizing listed in the report. It will be the Contractors responsibility to verify prior to beginning work.

Q. Do you know what size the flow switch is in building 22?

A. There is currently no size listed in the report. It will be the Contractors responsibility to verify prior to beginning work.

Files

File Type Posted
VHA-Joint Commission Clarification Document effective 1-October-2023.pdf PDF
Life Safety and Environment of Care Document List and Review Tool 10-2023.pdf PDF
36C25926Q0519 0003.docx DOCX document
36C25926Q0519 0002.docx DOCX document
Attachment 2 - Revised Price Schedule.docx DOCX document
CLIN 03 Bldg 36- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 35- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 5- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 02 VA Hosp - Grand Junction Battery List 2025.pdf PDF
CLIN 02 VA B37 Audible Deficiencies.pdf PDF
CLIN 03 Bldg 37- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 13- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 7- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 1- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 22 Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 8- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 6- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 01 VA -Grnd Junc CLC Kitchen Hood 2121 N Ave FAIL.pdf PDF
CLIN 03 Bldg 45- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 34- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 33- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 20- Quarterly Sprinkler 12-22-25 Fail.pdf PDF
CLIN 03 Bldg 12- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 01 VA- NFS-Kitchen Hood 2121- N Ave-FAIL.pdf PDF
36C25926Q0519 0001.docx DOCX document
Attachment 2 - Price Schedule.docx DOCX document
36C25926Q0519.docx DOCX document
Attachment 1 - SOW.docx DOCX document
Show all 28

Similar open opportunities

Opportunity Agency Set-aside Responses due
S222--Hazardous & Universal Waste Disposal Service Department of Veterans Affairs Grand Junction CO 81501 · NAICS 562112 Veterans Integrated Service Network 19 Service-Disabled Veteran-Owned Small Business
J042--Fire Alarm, Suppression Systems, and Hood Testing, Inspection, and Certification Services - SAVAHCS Department of Veterans Affairs Southern Arizona VA Health Care System Tucson, Arizona 85723, United States · NAICS 541350 Veterans Integrated Service Network 22 Service-Disabled Veteran-Owned Small Business
Z1DA--Upgrade Fire Alarm System Construction 676-22-110 Tomah, Wisconsin 54660, United States · NAICS 238210 Veterans Integrated Service Network 12 Service-Disabled Veteran-Owned Small Business
J012--Fire Suppression Testing Remains the same 32608, United States · NAICS 811310 Veterans Integrated Service Network 8 Service-Disabled Veteran-Owned Small Business
H112--Secutron Fire Alarm testing and Maintenance at the VA Northern California Health Care System (VANCHCS) NAICS 238210 Veterans Integrated Service Network 21 No set-aside

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity