This is a Questions and Answers amendment to a federal solicitation for fire system inspection and repairs services. Solicitation 36C25926Q0519, issued by the Department of Veterans Affairs Network Contracting Office 19 (serving VA Western Colorado Healthcare System in Grand Junction, Colorado), seeks contractors to perform fire system inspections and repairs on a one-year-only basis. The work involves correcting previously identified deficiencies and documenting repairs for Joint Commission audit compliance. The facility operates 13 wet-piped fire suppression systems across various buildings (B1, B5, B6, B7, B8, B12, B13, B20, B22, B33, B34, B36, and B45), with antifreeze or glycol loops located in Buildings 6 and 36. The Product Service Code is J012 (Maintenance and Repair Services), with NAICS Code 561621. All offers must be submitted via email to Contracting Officer Heather Chase (heather.chase2@va.gov) by June 29, 2026 at 12:00 PM Mountain Time.
The amendment addresses questions regarding the scope of work and provides two attached reference documents: the Life Safety and Environment of Care Document List and Review Tool (10-2023) and the VHA-Joint Commission Clarification Document (effective January 1, 2023) to establish standards for inspections and repairs. Work items outside the scope include dry systems, deluge systems, backflow preventers, fire pumps, and pressure regulating valves. Additional details regarding control valves and flow switches are referenced in CLIN 3 of the Statement of Work. The solicitation represents a new requirement with no incumbent contractor, as this is distinct from previous monitoring services performed by Vulcan Fire and backflow services performed by Citrine, LLC.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Q&A Solicitation # 36C25926Q0519
| SUBJECT* |
| 575 Fire System Inspection & Repairs - one year only |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 80111 |
| SOLICITATION NUMBER* |
| 36C25926Q0519 |
| RESPONSE DATE/TIME/ZONE |
| 06-29-2026 12:00 PM MOUNTAIN TIME, DENVER, USA |
| ARCHIVE |
| 30 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
| SET-ASIDE |
| SBA |
| PRODUCT SERVICE CODE* |
| J012 |
| NAICS CODE* |
| 561621 |
| CONTRACTING OFFICE ADDRESS |
| Department of Veterans Affairs |
Network Contracting Office
NCO 19
6162 South Willow Drive, Suite 300 Greenwood Village CO 80111
POINT OF CONTACT*
Contracting Officer Heather Chase heather.chase2@va.gov 303-712-5772
PLACE OF PERFORMANCE
ADDRESS
Department of Veterans Affairs
VA Western Colorado Healthcare System
2121 North ave
Grand Junction CO
| POSTAL CODE |
| 81501 |
COUNTRY
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
AGENCY CONTACT’S EMAIL ADDRESS
EMAIL DESCRIPTION
Amendment to a Previous Combined Solicitation
Amendment to a Previous Combined Solicitation
DESCRIPTION
| *= Required Field |
| Amendment to a Previous Combined Solicitation |
Page 1 of
Amendment to a Previous Combined Solicitation
The purpose of this amendment is to:
1. Provide answers to questions received under solicitation 36C25926Q0519.
2. To provide the Joint Commission review tool and clarification document to add awareness for prospective contractors regarding the standards for completing repairs and inspections (see attached).
All offers are to be emailed to heather.chase2@va.gov and received no later than 12:00pm (noon) MT on June 29, 2026.
Questions and Answers below are referencing RFQ 36C25926Q0519:
Q. Will the Government please provide the number of Wet Systems per building?
· B1: 1
· B5: 1
· B6: 1
· B7: 1
· B8: 1
· B12: 1
· B13: 1
· B20: 1
· B22: 1
· B33: 1
· B34: 1
· B36: 1
· B45: 1 Q. What is the total number of Dry Systems per building?
A. Not in scope of the required repairs.
Q. What is the total number of Pre-Action Systems?
A. None, station is wet-piped.
Q. What is the total number of Deluge Systems?
A. Not in scope of required repairs.
Q. What is the total number of Backflow Preventers?.
A. Not in scope of required repairs.
Q. What is the total number of Fire Pumps?
A. Not in scope of required repairs.
Q. What is the total number of Control Valves?
A. Please see CLIN 3 (page 5 & 6) of Attachment 1 - SOW.
Q. What is the total number of Flow Switches?
A. Please see CLIN 3 (page 5 & 6) of Attachment 1 - SOW.
Q. What is the total number of Pressure Regulating Valves PRV?
A. Not in scope of required repairs.
See attached document: Life Safety and Environment of Care Document List and Review Tool 10-2023.
See attached document: VHA-Joint Commission Clarification Document effective 1-October-2023.