CLIN 03 Bldg 34- Quarterly Sprinkler 12-22-25 FAIL.pdf
PDF 64 KB Posted
- Solicitation number
- 36C25926Q0519
About this file
This is a Semi-Annual Inspection Report for fire protection systems at VA Grand Junction Building 34, completed on December 15, 2025. The inspection was conducted by James Trudeau of Platinum Fire Protection (PO Box 607, Mead, CO 80542) in accordance with NFPA 25 2011 standards for the inspection, testing, and maintenance of water-based fire protection systems.
The inspection identified three deficiencies. Deficiency #1 (Section 13.3.2.2) involves missing identification signs for control valves, including valves on backflow preventers that have locks or electrical supervision. Deficiency #2 (Section 13.2.5) relates to the wet sprinkler system's inability to observe flow, with notes indicating no main drain pipes are available for testing because the system is fed from Building 1's basement standpipe. Deficiency #3 concerns a butterball valve (size 1) located above the clean agent room door in Building 34, identified as a tamper valve, which lacks required ceiling signage. The inspector certified that all equipment tested was left in operational condition except as noted, signing the report on December 15, 2025.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Semi Annual Inspection Report
Completed on: 12-15-2025 for
VA Grand Junction Building 34 2121 North Ave
Grand Junction, CO
Conducted By:
James Trudeau
Platinum Fire Protection PO Box 607
Mead, CO 80542
This Joint Commission inspection was performed in accordance with the following codes and regulations:
• NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems
Deficiencies - General Questions
Deficiency #1
Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified? - 13.3.2.2: No
Notes: Missing signs
Deficiencies - General Wet System Questions
None
Deficiencies - Wet
Deficiency #2
Sprinkler Type: Wet Is flow observed? - 13.2.5: No
Notes: No main drain pipes anywhere to test. System is fed from bldg 1 stair 1 basement standpipe. It may be called another building number, but it's 100% a part of building 1.
Deficiencies - Inspectors Test Connection
None
Deficiencies - Valves
Deficiency #3
Location: B34 above clean agent room door Valve Type: Butterball Size: 1 Description: B34 tamper Signs: No
Notes: No sign on ceiling
Report of Inspection / Test Semi-Annual NFPA 25
12-15-2025 Property VA Grand Junction Building 34 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Copyright 2025 Inspect Point
Inspector Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Inspector Name Signature Date Completed
James Trudeau 2025-12-15
Report of Inspection / Test Semi-Annual NFPA 25
12-15-2025 Property VA Grand Junction Building 34 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Copyright 2025 Inspect Point
File details come from the government source that posted it. Updated .