CLIN 03 Bldg 34- Quarterly Sprinkler 12-22-25 FAIL.pdf

PDF 64 KB Posted

Attached to
J012--575 Fire System Inspection & Repairs - one year only
Solicitation number
36C25926Q0519
Issued by

About this file

This is a Semi-Annual Inspection Report for fire protection systems at VA Grand Junction Building 34, completed on December 15, 2025. The inspection was conducted by James Trudeau of Platinum Fire Protection (PO Box 607, Mead, CO 80542) in accordance with NFPA 25 2011 standards for the inspection, testing, and maintenance of water-based fire protection systems.

The inspection identified three deficiencies. Deficiency #1 (Section 13.3.2.2) involves missing identification signs for control valves, including valves on backflow preventers that have locks or electrical supervision. Deficiency #2 (Section 13.2.5) relates to the wet sprinkler system's inability to observe flow, with notes indicating no main drain pipes are available for testing because the system is fed from Building 1's basement standpipe. Deficiency #3 concerns a butterball valve (size 1) located above the clean agent room door in Building 34, identified as a tamper valve, which lacks required ceiling signage. The inspector certified that all equipment tested was left in operational condition except as noted, signing the report on December 15, 2025.

View the file

Other files

File Type Posted
36C25926Q0519 0003.docx DOCX document
Life Safety and Environment of Care Document List and Review Tool 10-2023.pdf PDF
VHA-Joint Commission Clarification Document effective 1-October-2023.pdf PDF
36C25926Q0519 0002.docx DOCX document
Attachment 2 - Revised Price Schedule.docx DOCX document
CLIN 03 Bldg 7- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 1- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 33- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 8- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 01 VA -Grnd Junc CLC Kitchen Hood 2121 N Ave FAIL.pdf PDF
CLIN 03 Bldg 6- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 22 Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 37- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 02 VA B37 Audible Deficiencies.pdf PDF
CLIN 03 Bldg 5- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 36- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 35- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 02 VA Hosp - Grand Junction Battery List 2025.pdf PDF
CLIN 03 Bldg 13- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 20- Quarterly Sprinkler 12-22-25 Fail.pdf PDF
CLIN 01 VA- NFS-Kitchen Hood 2121- N Ave-FAIL.pdf PDF
CLIN 03 Bldg 45- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 12- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
36C25926Q0519 0001.docx DOCX document
36C25926Q0519.docx DOCX document
Attachment 2 - Price Schedule.docx DOCX document
Attachment 1 - SOW.docx DOCX document
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Semi Annual Inspection Report

Completed on: 12-15-2025 for

VA Grand Junction Building 34 2121 North Ave

Grand Junction, CO

Conducted By:

James Trudeau

Platinum Fire Protection PO Box 607

Mead, CO 80542

This Joint Commission inspection was performed in accordance with the following codes and regulations:

• NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems

Deficiencies - General Questions

Deficiency #1

Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified? - 13.3.2.2: No

Notes: Missing signs

Deficiencies - General Wet System Questions

None

Deficiencies - Wet

Deficiency #2

Sprinkler Type: Wet Is flow observed? - 13.2.5: No

Notes: No main drain pipes anywhere to test. System is fed from bldg 1 stair 1 basement standpipe. It may be called another building number, but it's 100% a part of building 1.

Deficiencies - Inspectors Test Connection

None

Deficiencies - Valves

Deficiency #3

Location: B34 above clean agent room door Valve Type: Butterball Size: 1 Description: B34 tamper Signs: No

Notes: No sign on ceiling

Report of Inspection / Test Semi-Annual NFPA 25

12-15-2025 Property VA Grand Junction Building 34 2121 North Ave Grand Junction CO

Print Date: 12-22-2025

Conducted by: James Trudeau

Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com

Copyright 2025 Inspect Point

Inspector Signature

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Inspector Name Signature Date Completed

James Trudeau 2025-12-15

Report of Inspection / Test Semi-Annual NFPA 25

12-15-2025 Property VA Grand Junction Building 34 2121 North Ave Grand Junction CO

Print Date: 12-22-2025

Conducted by: James Trudeau

Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com

Copyright 2025 Inspect Point