CLIN 03 Bldg 22 Quarterly Sprinkler 12-22-25 FAIL.pdf
PDF 62 KB Posted
- Solicitation number
- 36C25926Q0519
About this file
This is a Semi-Annual Inspection Report for water-based fire protection systems conducted on December 16, 2025, for VA Grand Junction Building 22 located at 2121 North Avenue, Grand Junction, Colorado. The inspection was performed by James Trudeau of Platinum Fire Protection (PO Box 607, Mead, CO 80542) in accordance with NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems, as required by Joint Commission regulations.
The inspection identified two deficiencies. Deficiency #1 concerns the wet sprinkler system, which showed no observed flow at the inspector's test connection; notes indicate that water is fed from Building 7 and reference should be made to that facility's report for results. Deficiency #2 pertains to the Building 22 inspector's test connection located in secure pharmacy storage, which failed the test due to a flow switch that requires replacement with no delay noted. All other general questions and general wet system questions resulted in no deficiencies. The inspector certified that all equipment tested was left in operational condition upon completion of the inspection except as noted in the deficiency findings. The report was signed and dated December 16, 2025, with a print date of December 22, 2025.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Semi Annual Inspection Report
Completed on: 12-16-2025 for
VA Grand Junction Building 22 2121 North Ave
Grand Junction, CO
Conducted By:
James Trudeau
Platinum Fire Protection PO Box 607
Mead, CO 80542
This Joint Commission inspection was performed in accordance with the following codes and regulations:
• NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems
Deficiencies - General Questions
None
Deficiencies - General Wet System Questions
None
Deficiencies - Wet
Deficiency #1
Sprinkler Type: Wet Is flow observed? - 13.2.5: No
Notes: Water fed from bldg 7. See that report for results.
Deficiencies - Inspectors Test Connection
Deficiency #2
Location: Secure pharmacy storage Description: Bldg 22 inspectors test Pass?: No
Notes: No delay. Flow switch Needs to be replaced
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 22 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Copyright 2025 Inspect Point
Inspector Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Inspector Name Signature Date Completed
James Trudeau 2025-12-16
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 22 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Copyright 2025 Inspect Point