CLIN 03 Bldg 22 Quarterly Sprinkler 12-22-25 FAIL.pdf

PDF 62 KB Posted

Attached to
J012--575 Fire System Inspection & Repairs - one year only
Solicitation number
36C25926Q0519
Issued by

About this file

This is a Semi-Annual Inspection Report for water-based fire protection systems conducted on December 16, 2025, for VA Grand Junction Building 22 located at 2121 North Avenue, Grand Junction, Colorado. The inspection was performed by James Trudeau of Platinum Fire Protection (PO Box 607, Mead, CO 80542) in accordance with NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems, as required by Joint Commission regulations.

The inspection identified two deficiencies. Deficiency #1 concerns the wet sprinkler system, which showed no observed flow at the inspector's test connection; notes indicate that water is fed from Building 7 and reference should be made to that facility's report for results. Deficiency #2 pertains to the Building 22 inspector's test connection located in secure pharmacy storage, which failed the test due to a flow switch that requires replacement with no delay noted. All other general questions and general wet system questions resulted in no deficiencies. The inspector certified that all equipment tested was left in operational condition upon completion of the inspection except as noted in the deficiency findings. The report was signed and dated December 16, 2025, with a print date of December 22, 2025.

View the file

Other files

File Type Posted
36C25926Q0519 0003.docx DOCX document
Life Safety and Environment of Care Document List and Review Tool 10-2023.pdf PDF
VHA-Joint Commission Clarification Document effective 1-October-2023.pdf PDF
36C25926Q0519 0002.docx DOCX document
Attachment 2 - Revised Price Schedule.docx DOCX document
CLIN 03 Bldg 7- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 1- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 33- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 8- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 01 VA -Grnd Junc CLC Kitchen Hood 2121 N Ave FAIL.pdf PDF
CLIN 03 Bldg 6- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 37- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 02 VA B37 Audible Deficiencies.pdf PDF
CLIN 03 Bldg 5- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 36- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 35- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 02 VA Hosp - Grand Junction Battery List 2025.pdf PDF
CLIN 03 Bldg 13- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 20- Quarterly Sprinkler 12-22-25 Fail.pdf PDF
CLIN 01 VA- NFS-Kitchen Hood 2121- N Ave-FAIL.pdf PDF
CLIN 03 Bldg 45- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 12- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 34- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
36C25926Q0519 0001.docx DOCX document
36C25926Q0519.docx DOCX document
Attachment 2 - Price Schedule.docx DOCX document
Attachment 1 - SOW.docx DOCX document
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Semi Annual Inspection Report

Completed on: 12-16-2025 for

VA Grand Junction Building 22 2121 North Ave

Grand Junction, CO

Conducted By:

James Trudeau

Platinum Fire Protection PO Box 607

Mead, CO 80542

This Joint Commission inspection was performed in accordance with the following codes and regulations:

• NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems

Deficiencies - General Questions

None

Deficiencies - General Wet System Questions

None

Deficiencies - Wet

Deficiency #1

Sprinkler Type: Wet Is flow observed? - 13.2.5: No

Notes: Water fed from bldg 7. See that report for results.

Deficiencies - Inspectors Test Connection

Deficiency #2

Location: Secure pharmacy storage Description: Bldg 22 inspectors test Pass?: No

Notes: No delay. Flow switch Needs to be replaced

Report of Inspection / Test Semi-Annual NFPA 25

12-16-2025 Property VA Grand Junction Building 22 2121 North Ave Grand Junction CO

Print Date: 12-22-2025

Conducted by: James Trudeau

Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com

Copyright 2025 Inspect Point

Inspector Signature

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Inspector Name Signature Date Completed

James Trudeau 2025-12-16

Report of Inspection / Test Semi-Annual NFPA 25

12-16-2025 Property VA Grand Junction Building 22 2121 North Ave Grand Junction CO

Print Date: 12-22-2025

Conducted by: James Trudeau

Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com

Copyright 2025 Inspect Point

File details come from the government source that posted it. Updated .