The report provides comprehensive inventory and condition assessments of backup power supply (BPS) batteries and electrical panels across five hospital buildings and the parking garage. For each location, the document lists battery group designations, physical locations, panel voltages (ranging from 118.7 to 121.0 VAC), charging voltages (26.1 to 27.8 VDC), individual battery voltages, and ampere-hour (AH) ratings. Battery sizes range from 9.0Ah to 55.0Ah. Each battery entry is marked as either "OK" or "FAIL" based on performance criteria. Specific failures are documented across multiple locations: Parking Garage Building has two failed 12.6 VDC 0 AH batteries; Building 5 has two failed 12.7-12.8 VDC batteries with 2.7 AH ratings; Building 6 has two failed 12.6-12.7 VDC 0 AH batteries; Building 33 has two failed 13.5 VAC batteries with 5 AH and 7.5 AH ratings; and Building 37 has two failed 13.0-12.8 VDC batteries with 1.9 AH ratings. Test dates range from February 25, 2025 to March 23, 2025, with Building 33 including a December 22 test date. The report serves as a facility maintenance and compliance document identifying which battery systems require replacement or repair.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared by
ALARMSpecialists, Inc
Battery
Group Location
Panel
Voltage
Charging
Voltage Voltage
AH
Rating OK FAIL Size Comments
13.6 VDC 17 AH X 55.0Ah
13.6 VDC 17 AH X 55.0Ah
12.6 VDC 0 AH X 9.0Ah
12.6 VDC 0 AH X 9.0Ah
VA Hospital - Grand Junction - Parking Garage - Battery and Panel List - August 22, 2025
1 Electrical Room 104 Panel 119.0 VAC 27.7 VDC 23-Mar
2 Electrical Room 104 BPS 1 119.0 VAC 26.1 VDC 23-Mar
6786 S Revere Pkwy Ste 100 Centennial, CO 80112
Battery
Group Location
Panel
Voltage
Charging
Voltage Voltage
AH
Rating OK FAIL Size Comments
13.5 VDC 39 AH X 55.0Ah
13.6 VDC 40 AH X 55.0Ah
12.8 VDC 2.7 AH X 12.0Ah
12.7 VDC 2.7 AH X 12.0Ah
VA Hospital - Grand Junction - Bldg 5 - Battery and Panel List - August 22, 2025
1 Basement Panel 118.7 VAC 27.7 VDC 25-Feb
2 Basement BPS (ACPS) - Lower CAB of FACP 118.7 VAC 27.8 VDC
Battery
Group Location
Panel
Voltage
Charging
Voltage Voltage
AH
Rating OK FAIL Size Comments
13.5 VDC 38 AH X 55.0Ah
13.1 VDC 32 AH X 55.0Ah
12.6 VDC 0 AH X 12.0Ah
12.7 VDC 0 AH X 12.0Ah
VA Hospital - Grand Junction - Bldg 6 - Battery and Panel List - August 22, 2025
1 Basement Panel 121.0 VAC 27.7 VDC 25-Feb
2 Basement BPS (bottom of FACP cabinet) 121.0 VAC 27.4 VDC
\ Location Panel
Voltage
Charging
Voltage Voltage
AH
Rating OK FAIL Size Comments
13.5 VAC 5 AH X 50 AH
13.5 VAC 7.5 AH X 50 AH
13.1 VDC 7.8 AH X 12 AH
13.0 VDC 7.6 AH X 12 AH
VA Hospital - Grand Junction - Bldg 33 - Battery and Panel List - August 22, 2025
1 Panel 119.0 VAC 27.7 VDC 23-Mar
2 BPS 119.1 VAC 27.8 VDC
22-Dec
Battery
Group Location
Panel
Voltage
Charging
Voltage Voltage AH Rating OK FAIL Size Comments
13.0 VDC 1.9 AH X 12 AH
12.8 VDC 1.9 AH X 12 AH
VA Hospital - Grand Junction - Bldg 37 - Battery and Panel List - August 22, 2025
1 Room 122 BPS 119.5 VAC 27.6 VDC 23-Jan