This document is a battery and panel status report prepared by ALARMSpecialists, Inc. for the VA Hospital in Grand Junction, Colorado, dated August 22, 2025.

The report provides comprehensive inventory and condition assessments of backup power supply (BPS) batteries and electrical panels across five hospital buildings and the parking garage. For each location, the document lists battery group designations, physical locations, panel voltages (ranging from 118.7 to 121.0 VAC), charging voltages (26.1 to 27.8 VDC), individual battery voltages, and ampere-hour (AH) ratings. Battery sizes range from 9.0Ah to 55.0Ah. Each battery entry is marked as either "OK" or "FAIL" based on performance criteria. Specific failures are documented across multiple locations: Parking Garage Building has two failed 12.6 VDC 0 AH batteries; Building 5 has two failed 12.7-12.8 VDC batteries with 2.7 AH ratings; Building 6 has two failed 12.6-12.7 VDC 0 AH batteries; Building 33 has two failed 13.5 VAC batteries with 5 AH and 7.5 AH ratings; and Building 37 has two failed 13.0-12.8 VDC batteries with 1.9 AH ratings. Test dates range from February 25, 2025 to March 23, 2025, with Building 33 including a December 22 test date. The report serves as a facility maintenance and compliance document identifying which battery systems require replacement or repair.

View the file

Other files

File Type Posted
36C25926Q0519 0003.docx DOCX document
Life Safety and Environment of Care Document List and Review Tool 10-2023.pdf PDF
VHA-Joint Commission Clarification Document effective 1-October-2023.pdf PDF
36C25926Q0519 0002.docx DOCX document
Attachment 2 - Revised Price Schedule.docx DOCX document
CLIN 03 Bldg 7- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 1- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 33- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 8- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 01 VA -Grnd Junc CLC Kitchen Hood 2121 N Ave FAIL.pdf PDF
CLIN 03 Bldg 6- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 22 Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 37- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 02 VA B37 Audible Deficiencies.pdf PDF
CLIN 03 Bldg 5- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 36- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 35- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 13- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 20- Quarterly Sprinkler 12-22-25 Fail.pdf PDF
CLIN 01 VA- NFS-Kitchen Hood 2121- N Ave-FAIL.pdf PDF
CLIN 03 Bldg 45- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 12- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 34- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
36C25926Q0519 0001.docx DOCX document
36C25926Q0519.docx DOCX document
Attachment 2 - Price Schedule.docx DOCX document
Attachment 1 - SOW.docx DOCX document
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Prepared by

ALARMSpecialists, Inc

Battery

Group Location

Panel

Voltage

Charging

Voltage Voltage

AH

Rating OK FAIL Size Comments

13.6 VDC 17 AH X 55.0Ah

13.6 VDC 17 AH X 55.0Ah

12.6 VDC 0 AH X 9.0Ah

12.6 VDC 0 AH X 9.0Ah

VA Hospital - Grand Junction - Parking Garage - Battery and Panel List - August 22, 2025

1 Electrical Room 104 Panel 119.0 VAC 27.7 VDC 23-Mar

2 Electrical Room 104 BPS 1 119.0 VAC 26.1 VDC 23-Mar

6786 S Revere Pkwy Ste 100 Centennial, CO 80112

Battery

Group Location

Panel

Voltage

Charging

Voltage Voltage

AH

Rating OK FAIL Size Comments

13.5 VDC 39 AH X 55.0Ah

13.6 VDC 40 AH X 55.0Ah

12.8 VDC 2.7 AH X 12.0Ah

12.7 VDC 2.7 AH X 12.0Ah

VA Hospital - Grand Junction - Bldg 5 - Battery and Panel List - August 22, 2025

1 Basement Panel 118.7 VAC 27.7 VDC 25-Feb

2 Basement BPS (ACPS) - Lower CAB of FACP 118.7 VAC 27.8 VDC

Battery

Group Location

Panel

Voltage

Charging

Voltage Voltage

AH

Rating OK FAIL Size Comments

13.5 VDC 38 AH X 55.0Ah

13.1 VDC 32 AH X 55.0Ah

12.6 VDC 0 AH X 12.0Ah

12.7 VDC 0 AH X 12.0Ah

VA Hospital - Grand Junction - Bldg 6 - Battery and Panel List - August 22, 2025

1 Basement Panel 121.0 VAC 27.7 VDC 25-Feb

2 Basement BPS (bottom of FACP cabinet) 121.0 VAC 27.4 VDC

\ Location Panel

Voltage

Charging

Voltage Voltage

AH

Rating OK FAIL Size Comments

13.5 VAC 5 AH X 50 AH

13.5 VAC 7.5 AH X 50 AH

13.1 VDC 7.8 AH X 12 AH

13.0 VDC 7.6 AH X 12 AH

VA Hospital - Grand Junction - Bldg 33 - Battery and Panel List - August 22, 2025

1 Panel 119.0 VAC 27.7 VDC 23-Mar

2 BPS 119.1 VAC 27.8 VDC

22-Dec

Battery

Group Location

Panel

Voltage

Charging

Voltage Voltage AH Rating OK FAIL Size Comments

13.0 VDC 1.9 AH X 12 AH

12.8 VDC 1.9 AH X 12 AH

VA Hospital - Grand Junction - Bldg 37 - Battery and Panel List - August 22, 2025

1 Room 122 BPS 119.5 VAC 27.6 VDC 23-Jan

File details come from the government source that posted it. Updated .