CLIN 01 VA -Grnd Junc CLC Kitchen Hood 2121 N Ave FAIL.pdf

PDF 551 KB Posted

Attached to
J012--575 Fire System Inspection & Repairs - one year only
Solicitation number
36C25926Q0519
Issued by

About this file

This is a Kitchen Hood Fire Inspection Report for the VA Medical Center (CLC Hood) located at 2121 North Ave, Grand Junction, CO 81501, conducted by Integrity Fire Safety Services on March 17, 2026. The inspection was performed by technicians JJ/CR under job number 42102653 for the Grand Junction Fire jurisdiction, with primary contact Tia Clemmer, Healthcare Engineer, at 970-852-7243.

The inspection covered a wet chemical ANSUL R-102 fire suppression system installed in 2010 with a 6-year hydro test due date that is past due and requires replacement. The system includes a 1½ gallon CO2 cylinder (2008 model year) and a 35½ oz cartridge. The hood configuration consists of a 40'x36" plenum, 8x8 duct size, and three nozzles (1N/Plenum/1W) at 42 inches height covering a 36"x24" appliance area with 260-degree coverage. All major system components passed inspection including fusible link testing, manual pull station activation, electrical shutdown operation, exhaust fan functionality, and filter replacement. However, two deficiencies were identified: a minor deficiency regarding the past-due hydro test on the CO2 tank, and a critical deficiency for a Class K kitchen fire extinguisher that is non-compliant and requires a 6-year hydro test. The system is otherwise fully functional and compliant with NFPA 96 2017 Edition standards. The semi-annual inspection interval applies, with monitoring services provided through account #2615QB via 1.800.631.2299.

View the file

Other files

File Type Posted
36C25926Q0519 0003.docx DOCX document
Life Safety and Environment of Care Document List and Review Tool 10-2023.pdf PDF
VHA-Joint Commission Clarification Document effective 1-October-2023.pdf PDF
36C25926Q0519 0002.docx DOCX document
Attachment 2 - Revised Price Schedule.docx DOCX document
CLIN 03 Bldg 7- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 1- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 33- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 8- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 6- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 22 Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 37- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 02 VA B37 Audible Deficiencies.pdf PDF
CLIN 03 Bldg 5- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 36- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 35- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 02 VA Hosp - Grand Junction Battery List 2025.pdf PDF
CLIN 03 Bldg 13- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 20- Quarterly Sprinkler 12-22-25 Fail.pdf PDF
CLIN 01 VA- NFS-Kitchen Hood 2121- N Ave-FAIL.pdf PDF
CLIN 03 Bldg 45- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 12- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 34- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
36C25926Q0519 0001.docx DOCX document
36C25926Q0519.docx DOCX document
Attachment 2 - Price Schedule.docx DOCX document
Attachment 1 - SOW.docx DOCX document
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

JURISDICTION GRAND JUNCTION FIRE

BUILDING/PROPERTY NAME VA MEDICAL CENTER (CLC HOOD)

STREET, CITY,STATE, ZIP CODE 2121 NORTH AVE GRAND JUNCTION CO 81501

KITCHEN HOOD FIRE INSPECTION REPORT

JOB NUMBER

PO NUMBER (IF ANY) NA

DATE PERFORMED 3/17/2026

INSPECTOR(S) INITIALS JJ/CR

42102653

TITLE HEALTHCARE ENGINEER TITLE

PHONE NUMBER 970-852-7243 PHONE NUMBER

TIA CLEMMER NAME NANAME

NFPA REFERENCES AND PROCEDURE

YOUR KITCHEN HOOD EXTINGUISHING SYSTEM(S) ARE REQUIRED TO BE THOROUGHLY INSPECTED, TESTED AND MAINTAINED EVERY 6 MONTHS BY AN APPROVED SERVICING

COMPANY IN ACCORDANCE WITH THE FOLLOWING NFPA CHAPTER REFERENCES:

NFPA 96 2017 EDITION

TESTING MUST INCLUDE CONTROL EQUIPMENT, INITIATING DEVICES, HVAC/ ELECTRICAL/GAS SHUTDOWN, LINKAGE REPLACEMENT (ANNUALLY) AND ALARM NOTIFICATION

APPLIANCES. SEE THE BELOW LIST OF VARIOUS TESTING DEVICES:

✓ VISUAL AND FUNCTIONAL TESTING OF THE INITIATING COMPONENTS.

✓ VISUAL INSPECTION TO VERIFY PROPER SUPPRESSION APPLICATION.

✓ VISUAL INSPECTION & VERIFICATION OF CYLINDER SERVICE DATES.

✓ REPLACEMENT OF COMPONENTS PER CODE REQUIREMENTS (SEMI-ANNUALLY).

✓ VISUAL AND FUNCTIONAL TESTING OF ALL SHUNT OPERATIONS AND SHUTDOWN.

✓ ALARM SIGNAL TRANSMISSION TO CENTRAL STATION VERIFICATION (IF APPLICABLE)

✓ VISUAL AND FUCNTIONAL VERIFICATION OF ALARM SIGNALS SENT TO THE FIRE ALARM PANEL.

✓ VISUAL INSPECTION OF PORTABLE EXTINGUISHER UNITS AND VERIFICATION OF PROPER CLASS RATING FOR APPLICATION.

MONITORING

PHONE NUMBER 1.800.631.2299

MONITORING

ACCOUNT NUMBER #2615QB

SITE CONTACT INFORMATION

PRIMARY CONTACT SECONDARY CONTACT

EMAIL TIA.CLEMMER@VA.GOV EMAIL

X

YES X NO

Y N N/A

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

YES YES YES

NOTE #:GREASE ACCUMULATION

TEMPCOUNT

VERIFIED OPERATIONS NOTE #:

LOW MODERATE EXCESSIVE

36" X 24"

DUCT SIZE NOZZLE TYPE 1N/PLENUM/1W DUCT8 X 8

DIMESIONS

NOZZLE #

NOZZLE HEIGHT

FLAT TOP

42"INCH

40'X36"

PROPER HAND HELD PORTABLE EXTINGUISHER(S)

PROPERLY SERVICED? (CLASS K IN KITCHEN?)

3 TOTAL

SYSTEM DIMENSIONS

PLENUM SIZE

ALARM ELEC./LIGHTS APPLIANCES

360°

APPLIANCE

NOZZLE #

NOTE #

EACH HAZARD PROPERLY COVERED WITH CORRECT NOZZLES

K

ITC

H

EN

H O

O D

FIR

E IN

SP

EC

TIO

N

R

EP

O R

T

INTERNAL INSPECTION & CHEMICAL WEIGHT VERIFIED (ANSUL)

ACTUATION HOSE INSPECTED FOR DAMAGE

VERIFIED EXHAUST FAN IS OPERATIONAL

VERIFIED MAKE-UP AIR IS OPERATION (PAINT BOOTH)

ELECTRIC SHUTDOWN OPERATIONAL

INSPECTION & SERVICE TAG ON SYSTEM CYLINDER/MANUAL PULL

SYSTEM RESET TO NORMAL OPERATION

NO DEFICIENCES WITH OPERATION OR COVERAGE

PROPER OPERATION OF WORKING GAS VALVE(S)

FAN WARNING SIGN ON HOOD

ALL FILTERS ARE REPLACED

ALL NOZZLE CAPS/SEALS ARE REPLACED & CLEAR OF BLOCKAGE

CHECKED PRESSURE GAUGE INDICATOR FOR OPERABLE RANCE

MANUAL PULL STATION OPERATION & SUCESSFULLY ACTIVATED SYSTEM

CONFIRMED ALL CONDUIT & PIPING IS SECURED

PROPER BLOWN DOWN PERFORMED

INSPECTION INTERVAL

ANNUAL SEMI-ANNUAL

SYSTEM INFORMATION

SYSTEM TYPE WET CHEMICAL CARTRIDGE DATE 2010

H O

O D

C H

EC

K

LIST A

N

D

IN

FO

R

M A

TIO

N

BUILDING NAME VA MEDICAL CENTER (CLC HOOD) DATE 3/17/2026 TECH(S) JJ/CR JOB #

SYSTEM SHOWS NO VISIBLE SIGNS THAT IT HAS FIRED OR BEEN TAMPERED WITH

SYSTEM DESIGN HAS NOT BEEN CHANGED

FUSIBLE LINK TESTED & SYSTEM ACTIVATED UPON TEST

TEST DATE/LAST HYDRO

SYSTEM IS COMPLIANT

42102653

MANUFACTURER

ELECTRICAL SHUNT LOCATION ROOM 147 / ELECTRICAL PANEL

REPLACE FUSIBLE LINKS ( SEMI-ANNUAL INSPECTION)

DATE:LINEAR ACTUATOR MANUFACTURER DATE:

DATE:DATES ON MODULAR BATTERY

ANSUL CARTRIDGE WEIGHT 35 1/2 OZ

MODEL ANSUL R-102 6 YR/HYDRO DUE DATE PAST DUE/NEEDS NEW CARTRIDGE

PAST DUE / 1 1/2 GAL. CYLINDER 2008 YR U.L. 300 COMPLIANT

HOOD INSPECTION CHECKLIST

QUESTION

Integral to your Safety. Because it Matters.

303.557.1820 www.integrityfiresafetyservices.com

1.

2.

1.

D

EFIC

IEN

C

IES A

N

D O

B

SER

V A

TIO

N

S

SEVERITY

JJ/CR JOB # 42102653

Minor

Critical

DEFICIENCY LIST & PROPOSED SOLUTIONS MAKE/MODEL

HYDRO PAST DUE ON CO2 TANK

CLC KITCHEN FIRE EXTINGUISHER NOT COMPLAINT( 6YR. HYDRO TEST NEEDED ) K/CLASS 6LT

BUILDING NAME VA MEDICAL CENTER (CLC HOOD) DATE 3/17/2026 TECH(S)

K

ITC

H

EN

H O

O D

FIR

E IN

SP

EC

TIO

N

R

EP

O R

T

GENERAL NOTES & SITE OBSERVATIONS SEVERITY

ANSUL HOOD SYSTEM IS FULLY FUNCTIONAL BLANK

Listed above are any General Notes to report. This section also contains any issues that were found during inspections and either require a substantial investment to correct