CLIN 03 Bldg 36- Quarterly Sprinkler 12-22-25 FAIL.pdf
PDF 63 KB Posted
- Solicitation number
- 36C25926Q0519
About this file
This is a Semi-Annual Inspection Report for water-based fire protection systems at VA Grand Junction Building 36 located at 2121 North Ave, Grand Junction, Colorado, completed on December 16, 2025.
The inspection was conducted by James Trudeau of Platinum Fire Protection (PO Box 607, Mead, CO 80542) in accordance with NFPA 25 2011 standards for water-based fire protection systems. The report identifies five deficiencies requiring corrective action: (1) control valves including backflow preventer valves lack proper identification signage per section 13.3.2.2; (2) two system gauges require replacement as they are not in good condition and not showing normal water supply pressure per section 5.2.4.1; (3) the test and drain connection at the riser lacks required signage; (4) a 4-inch butterfly backflow preventer valve (#2) at the riser lacks proper signage; and (5) a 4-inch butterfly backflow preventer valve (#1) at the riser lacks proper signage. No deficiencies were identified in the general wet system questions or wet system categories. The inspector certified that all equipment tested was left in operational condition upon completion of the inspection except as noted in the deficiency findings.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Semi Annual Inspection Report
Completed on: 12-16-2025 for
VA Grand Junction Building 36 2121 North Ave
Grand Junction, CO
Conducted By:
James Trudeau
Platinum Fire Protection PO Box 607
Mead, CO 80542
This Joint Commission inspection was performed in accordance with the following codes and regulations:
• NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems
Deficiencies - General Questions
Deficiency #1
Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified? - 13.3.2.2: No
Notes: No control or inspectors test signs
Deficiency #2
Are the gauges on system in good condition and showing normal water supply pressure? - 5.2.4.1: No
Notes: 2 gauges due for replacement
Deficiencies - General Wet System Questions
None
Deficiencies - Wet
None
Deficiencies - Inspectors Test Connection
Deficiency #3
Location: Riser Description: Test and drain Signs: No
Notes:
Deficiencies - Valves
Deficiency #4
Location: Riser Valve Type: Butterfly Size: 4 Description: Backflow #2 Signs: No
Notes:
Deficiency #5
Location: Riser Valve Type: Butterfly Size: 4 Description: Backflow #1 Signs: No
Notes:
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 36 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Copyright 2025 Inspect Point
Inspector Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Inspector Name Signature Date Completed
James Trudeau 2025-12-16
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 36 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com