CLIN 03 Bldg 37- Quarterly Sprinkler 12-22-25 FAIL.pdf
PDF 63 KB Posted
- Solicitation number
- 36C25926Q0519
About this file
This document is a Semi-Annual Inspection Report for fire protection systems at VA Grand Junction Building 37, conducted on December 16, 2025, by James Trudeau of Platinum Fire Protection. The inspection was performed in accordance with NFPA 25 2011 standards for the inspection, testing, and maintenance of water-based fire protection systems.
The report identifies five deficiencies requiring corrective action: (1) several control valves, including those on backflow preventers, lack proper identification signs per standard 13.3.2.2; (2) three gauges measuring water supply pressure are in poor condition and require replacement per standard 5.2.4.1; (3) three gauges on systems with low pressure alarms require replacement per standard 13.4.4.1.2.4; (4) the inspector's test connection at the southwest corner of the building lacks a required alarm test sign; and (5) a 4-inch butterfly dry valve control valve on the riser lacks a required identification sign. All equipment was confirmed to be in operational condition upon completion of the inspection except as noted. The inspector certified the accuracy of the report as of the inspection date and location.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Semi Annual Inspection Report
Completed on: 12-16-2025 for
VA Grand Junction Building 37 2121 North Ave
Grand Junction, CO
Conducted By:
James Trudeau
Platinum Fire Protection PO Box 607
Mead, CO 80542
This Joint Commission inspection was performed in accordance with the following codes and regulations:
• NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems
Deficiencies - General Questions
Deficiency #1
Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified? - 13.3.2.2: No
Notes: Several valves missing signs
Deficiency #2
Are the gauges on system in good condition and showing normal water supply pressure? - 5.2.4.1: No
Notes: 3 gauges due for replacement
Deficiencies - General Dry System Questions
Deficiency #3
Are the gauges on systems with low pressure alarms in good condition and showing normal air and water pressure? - 13.4.4.1.2.4: No
Notes: 3 gauges due for replacement
Deficiencies - Dry
None
Deficiencies - Inspectors Test Connection
Deficiency #4
Location: S/W corner of building Description: Inspectors test Signs: No
Notes: Alarm test missing sign
Deficiencies - Valves
Deficiency #5
Location: Riser Valve Type: Butterfly Size: 4 Description: Dry valve control Signs: No
Notes: No sign on dry control valve
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 37 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Copyright 2025 Inspect Point
Inspector Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Inspector Name Signature Date Completed
James Trudeau 2025-12-16
Report of Inspection / Test Semi-Annual NFPA 25
12-16-2025 Property VA Grand Junction Building 37 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Copyright 2025 Inspect Point
File details come from the government source that posted it. Updated .