CLIN 03 Bldg 6- Quarterly Sprinkler 12-22-25 FAIL.pdf

PDF 81 KB Posted

Attached to
J012--575 Fire System Inspection & Repairs - one year only
Solicitation number
36C25926Q0519
Issued by

About this file

This is a Semi-Annual Inspection Report for water-based fire protection systems conducted on December 16, 2025, at VA Grand Junction Building 6 located at 2121 North Ave, Grand Junction, Colorado. The inspection was performed by James Trudeau of Platinum Fire Protection (PO Box 607, Mead, CO 80542) in accordance with NFPA 25 2011 standards for inspection, testing, and maintenance of water-based fire protection systems.

The report identifies six deficiencies requiring corrective action: (1) two missing control valve signs on backflow preventers per NFPA 13.3.2.2; (2) two gauges requiring replacement due to poor condition per NFPA 5.2.4.1; (3) electrical waterflow alarm devices failing test due to malfunctioning inspector's test valves that will not properly close after opening per NFPA 5.3.3.3; (4) the basement inspector's test connection experiencing manual-only operation due to the test valve being extremely difficult to close once opened; (5) basement Backflow #2 (3-inch butterfly valve) lacking required signage; and (6) basement Backflow #1 (3-inch butterfly valve) lacking required signage. No deficiencies were identified in the wet system category. The inspector certified that all equipment was left in operational condition except as noted, with the report signed and dated December 16, 2025.

View the file

Other files

File Type Posted
36C25926Q0519 0003.docx DOCX document
Life Safety and Environment of Care Document List and Review Tool 10-2023.pdf PDF
VHA-Joint Commission Clarification Document effective 1-October-2023.pdf PDF
36C25926Q0519 0002.docx DOCX document
Attachment 2 - Revised Price Schedule.docx DOCX document
CLIN 03 Bldg 7- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 1- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 33- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 8- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 01 VA -Grnd Junc CLC Kitchen Hood 2121 N Ave FAIL.pdf PDF
CLIN 03 Bldg 22 Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 37- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 02 VA B37 Audible Deficiencies.pdf PDF
CLIN 03 Bldg 5- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 36- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 35- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 02 VA Hosp - Grand Junction Battery List 2025.pdf PDF
CLIN 03 Bldg 13- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 20- Quarterly Sprinkler 12-22-25 Fail.pdf PDF
CLIN 01 VA- NFS-Kitchen Hood 2121- N Ave-FAIL.pdf PDF
CLIN 03 Bldg 45- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 12- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
CLIN 03 Bldg 34- Quarterly Sprinkler 12-22-25 FAIL.pdf PDF
36C25926Q0519 0001.docx DOCX document
36C25926Q0519.docx DOCX document
Attachment 2 - Price Schedule.docx DOCX document
Attachment 1 - SOW.docx DOCX document
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Semi Annual Inspection Report

Completed on: 12-16-2025 for

VA Grand Junction Building 6 2121 North Ave

Grand Junction, CO

Conducted By:

James Trudeau

Platinum Fire Protection PO Box 607

Mead, CO 80542

This Joint Commission inspection was performed in accordance with the following codes and regulations:

• NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems

Deficiencies - General Questions

Deficiency #1

Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified? - 13.3.2.2: No

Notes: 2 control valve signs missing

Deficiency #2

Are the gauges on system in good condition and showing normal water supply pressure? - 5.2.4.1: No

Notes: 2 gauges due for replacement

Deficiency #3

The electrical waterflow alarm devices passed test by opening inspector's test connection/bypass connection with alarms actuating and flow observed? - 5.3.3.3:

No

Notes: Manual trip only due to bad inspectors test valves it will open but does not want to shut after testing.

Deficiency #3 - Photo #1

Date Taken: December 16, 2025

Deficiencies - General Wet System Questions

None

Deficiencies - Wet

Report of Inspection / Test Semi-Annual NFPA 25

12-16-2025 Property VA Grand Junction Building 6 2121 North Ave Grand Junction CO

Print Date: 12-22-2025

Conducted by: James Trudeau

Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com

Copyright 2025 Inspect Point

None

Deficiencies - Inspectors Test Connection

Deficiency #4

Location: Basement Description: Inspectors test Pass?: No

Notes: Manual trip only. Inspectors test valve so bad it is almost impossible to close once it's open.

Deficiencies - Valves

Deficiency #5

Location: Basement Valve Type: Butterfly Size: 3 Description: Backflow #2 Signs: No

Notes: No sign

Deficiency #6

Location: Basement Valve Type: Butterfly Size: 3 Description: Backflow #1 Signs: No

Notes: No sign

Report of Inspection / Test Semi-Annual NFPA 25

12-16-2025 Property VA Grand Junction Building 6 2121 North Ave Grand Junction CO

Print Date: 12-22-2025

Conducted by: James Trudeau

Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com

Inspector Signature

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Inspector Name Signature Date Completed

James Trudeau 2025-12-16

Report of Inspection / Test Semi-Annual NFPA 25

12-16-2025 Property VA Grand Junction Building 6 2121 North Ave Grand Junction CO

Print Date: 12-22-2025

Conducted by: James Trudeau

Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com