CLIN 03 Bldg 8- Quarterly Sprinkler 12-22-25 FAIL.pdf
PDF 85 KB Posted
- Solicitation number
- 36C25926Q0519
About this file
This is a Semi-Annual Inspection Report for water-based fire protection systems at VA Grand Junction Building 8, completed on December 15, 2025, by James Trudeau of Platinum Fire Protection. The inspection was conducted in accordance with NFPA 25 2011 standards for the inspection, testing, and maintenance of water-based fire protection systems.
The report identifies six deficiencies requiring corrective action: (1) control valves and backflow preventer valves lack proper identification signs; (2) two system gauges require replacement due to condition issues; (3) the lowest backflow valve requires a new tamper switch as the supervisory switch does not indicate movement properly; (4) the inspector's test connection on the riser lacks a required sign; (5) Backflow #2 OS&Y valve (2-1/2 size) on the riser lacks signage; and (6) Backflow #1 OS&Y valve (2-1/2 size) requires a new OS&Y tamper switch because the existing micro switch sticks when activated and will not return to normal position without manual manipulation. No deficiencies were identified in the general wet system questions or wet system categories. The inspector certified that all equipment tested was left in operational condition upon completion of the inspection except as noted in the deficiency findings.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Semi Annual Inspection Report
Completed on: 12-15-2025 for
VA Grand Junction Building 8 2121 North Ave
Grand Junction, CO
Conducted By:
James Trudeau
Platinum Fire Protection PO Box 607
Mead, CO 80542
This Joint Commission inspection was performed in accordance with the following codes and regulations:
• NFPA 25 2011 - Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems
Deficiencies - General Questions
Deficiency #1
Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified? - 13.3.2.2: No
Notes: No signs
Deficiency #2
Are the gauges on system in good condition and showing normal water supply pressure? - 5.2.4.1: No
Notes: 2 gauges due for replacement
Deficiency #3
Do valve supervisory switches indicate movement? - 13.3.3.5.2: No
Notes: Lowest backflow valve needs a new tamper switch
Deficiency #3 - Photo #1
Date Taken: December 15, 2025
Deficiencies - General Wet System Questions
None
Deficiencies - Wet
None
Report of Inspection / Test Semi-Annual NFPA 25
12-15-2025 Property VA Grand Junction Building 8 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Copyright 2025 Inspect Point
Deficiencies - Inspectors Test Connection
Deficiency #4
Location: Riser Description: Inspectors test Signs: No
Notes: No sign
Deficiencies - Valves
Deficiency #5
Location: Riser Valve Type: OS&Y Size: 2-1/2 Description: Backflow #2 Signs: No
Notes:
Deficiency #6
Location: Riser Valve Type: OS&Y Size: 2-1/2 Description: Backflow #1 Signs: No Exercised?: No
Notes: Tamper switch wouldn't clear again after testing. Found micro switch inside sticks when activated and won't return to normal without removing cover and manipulating the micro switch. Needs new OS&Y tamper switch.
Report of Inspection / Test Semi-Annual NFPA 25
12-15-2025 Property VA Grand Junction Building 8 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
Inspector Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Inspector Name Signature Date Completed
James Trudeau 2025-12-15
Report of Inspection / Test Semi-Annual NFPA 25
12-15-2025 Property VA Grand Junction Building 8 2121 North Ave Grand Junction CO
Print Date: 12-22-2025
Conducted by: James Trudeau
Platinum Fire Protection PO Box 607 Mead CO 80542 3036880177 rachel@platfire.com
File details come from the government source that posted it. Updated .