36C25926Q0519 0001.docx
DOCX document 28 KB Posted
- Solicitation number
- 36C25926Q0519
About this file
This file is a Questions and Answers document from a previous solicitation (36C25926Q0408) provided as an amendment to the current fire system inspection and repairs solicitation. The document clarifies that this is a new one-year-only contract requirement with no incumbent contractor, and the primary objective is to correct previously identified fire system deficiencies and document repairs for Joint Commission audit compliance, rather than perform ongoing annual testing. Current service providers include Vulcan Fire for monitoring services and Citrine, LLC for backflow preventor services.
The Q&A addresses specific technical details about the VA West Los Angeles Healthcare System fire suppression infrastructure, including confirmation of antifreeze/glycol loops in Buildings 6 and 36, the absence of sprinkler systems in the parking garage (Building 44), and OS&Y valve sizes ranging from 2.5 to 8 inches. Key work requirements include five-year internal piping inspections with photographic documentation, removal of flushing connections and sprinklers at branch line ends, and resolution of network issues in Building 34. The solicitation (36C25926Q0519) requires all offers to be submitted via email to heather.chase2@va.gov no later than 5:00 p.m. MT on June 22, 2026, with attached inspection reports provided to support the bidding process.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Amendment to a Previous Combined Solicitation
Amendment to a Previous Combined Solicitation
| SUBJECT* |
| 575 Fire System Inspection & Repairs - one year only |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 80111 |
| SOLICITATION NUMBER* |
| 36C25926Q0519 |
| RESPONSE DATE/TIME/ZONE |
| 06-22-2026 5:00 PM MOUNTAIN TIME, DENVER, USA |
| ARCHIVE |
| 30 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
| SET-ASIDE |
| SBA |
| PRODUCT SERVICE CODE* |
| J012 |
| NAICS CODE* |
| 561621 |
| CONTRACTING OFFICE ADDRESS |
| Department of Veterans Affairs |
Network Contracting Office
NCO 19
6162 South Willow Drive, Suite 300 Greenwood Village CO 80111
POINT OF CONTACT*
Contracting Officer Heather Chase heather.chase2@va.gov
PLACE OF PERFORMANCE
ADDRESS
Department of Veterans Affairs
VA Western Colorado Healthcare System
2121 North Ave.
Grand Junction CO
| POSTAL CODE |
| 81501 |
COUNTRY
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
AGENCY CONTACT’S EMAIL ADDRESS
EMAIL DESCRIPTION
DESCRIPTION
The purpose of this amendment is to:
1. Provide questions, answers and reports provided under previous solicitation (36C25926Q0408).
All offers are to be emailed to heather.chase2@va.gov and received no later than 5:00pm MT on June 22, 2026.
Questions and Answers below were provided under previous RFQ 36C25926Q0408:
Q. Is this a new or follow-on requirement? If a follow-on, who is the incumbent and what is the contract number?
A. This is a new one-year only requirement. This requirement has not previously been awarded and therefore there is no incumbent.
Q. Is the intent of the contract to perform annual testing, identify, and correct deficiencies?
A. No, the intent is to correct the deficiencies that have previously been identified and to document the repairs for the Joint Commission audit.
Q. Who is currently performing the monitoring service for the VA WCHCS?
A. Vulcan Fire.
Q. Who is currently performing the backflow preventor service for VA WCHCS?
A. Citrine, LLC Q. Can we be provided a copy of the reports? The in-person tags refer to this report.
A. Yes. See attached reports.
Q. Does the VA WCHCS have any antifreeze or glycol loops within their fire suppression system?
A. Yes, those are located in Building 6 and Building 36.
Q. Does the parking garage (Building 44) contain sprinkler systems?
A. No, but there are alarm systems.
Q. Building 34 has an open deficiency tag for network issues. Has this been resolved?
A. This deficiency correction is currently in progress.
Q. For the 5-year internal inspections, is it just the internal piping 5-year you are needing?
A. Yes, it is the internal piping to include the removal of a flushing connections and sprinkler near the end of a branch line. Will also require photographic evidence of the state of the pipe to fulfill the 5-year requirement.
Q. For the OS&Y valves, would you know what size the valves are?
A. OS&Y valves on station are 8inch, 3inch, 2.5inch and 6 inch.
Q. Do you know what size the inspectors’ test valves are?
A. There are currently no sizing listed in the report. It will be the Contractors responsibility to verify prior to beginning work.
Q. Do you know what size the flow switch is in building 22?
A. There is currently no size listed in the report. It will be the Contractors responsibility to verify prior to beginning work.
See attached document: CLIN 01 VA -Grnd Junc CLC Kitchen Hood 2121 N Ave FAIL.
See attached document: CLIN 01 VA- NFS-Kitchen Hood 2121- N Ave-FAIL.
See attached document: CLIN 02 VA B37 Audible Deficiencies.
See attached document: CLIN 02 VA Hosp - Grand Junction Battery List 2025.
See attached document: CLIN 03 Bldg 1- Quarterly Sprinkler 12-22-25 FAIL.
See attached document: CLIN 03 Bldg 5- Quarterly Sprinkler 12-22-25 FAIL.
See attached document: CLIN 03 Bldg 6- Quarterly Sprinkler 12-22-25 FAIL.
See attached document: CLIN 03 Bldg 7- Quarterly Sprinkler 12-22-25 FAIL.
See attached document: CLIN 03 Bldg 8- Quarterly Sprinkler 12-22-25 FAIL.
See attached document: CLIN 03 Bldg 12- Quarterly Sprinkler 12-22-25 FAIL.
See attached document: CLIN 03 Bldg 13- Quarterly Sprinkler 12-22-25 FAIL.
See attached document: CLIN 03 Bldg 20- Quarterly Sprinkler 12-22-25 Fail.
See attached document: CLIN 03 Bldg 22 Quarterly Sprinkler 12-22-25 FAIL.
See attached document: CLIN 03 Bldg 33- Quarterly Sprinkler 12-22-25 FAIL.
See attached document: CLIN 03 Bldg 34- Quarterly Sprinkler 12-22-25 FAIL.
See attached document: CLIN 03 Bldg 35- Quarterly Sprinkler 12-22-25 FAIL.
See attached document: CLIN 03 Bldg 36- Quarterly Sprinkler 12-22-25 FAIL.
See attached document: CLIN 03 Bldg 37- Quarterly Sprinkler 12-22-25 FAIL.
See attached document: CLIN 03 Bldg 45- Quarterly Sprinkler 12-22-25 FAIL.